Plans Review Sheet
Date: July 27, 2004 Business Address: 3940 Church Street
Occ. Industrial/Business Ch. 40
Business Name: Cox Lumber Ph. ()
Fax. O
Contractor: Wiginton Fire Protection & Engineering Ph (407) 831-3414
Fax. (407) 831-5740
Architect: Ph. ( )
Fax. ( )
Reewed[X..j Reviewed with comment I ] Rejected []
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner _P
Comment:
Application —New Industrial Occupancy
1.1 Fire Sprinkler Design: one (1) types of Design criteria
1.2 Industrial Area: Class commodities up to 12' ft- in height.
1.3 See N. F. PA. 13, (1999) Ed.
1.4 Densityfor this area— 0.2 GPAFSQ FT.
1.5 Operating area -1950
1.6 366 200 degree heads 8.0 K Factor %" Tread Tyco TY -B SSU -Chrome uprights
Two hour hydro required
o Provide fire sprinkler contractor at time of building finial
48 hour notice on all fire inspections
1
6
SANFORD FIRE DEPARTMEN-F
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, F1.32771 / P. O. Box 1788, Sanford, Fl. 32772
407302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
Plans Review Sheet
Date: June 1, 2004 Business Address: 3940 Church Street
Occ. Industrial/Business Ch. 40
Business Name: Cox Lumber
Contractor: Mc Kee Construction
Architect:
Ph. ()
Fax. ()
Ph (407) 323-1150
Fax. (407) 323-9304
Ph. ( )
Fax. ( )
R'evtewed[x3 Reviewed with comment [ ] Rejected []
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner —<_
Comment: Plans reviewed as right to require applicable code requirements if occupancy use
changes Fire Sprinkle ns toesubmitted dor reviewp emitting, ,and inspections', If separate
certified contractor does underground fireline, plans to be submitted for review, permitting, and
1.1 Application – New 36, 000 sq ft, type IV, unprotected, fire sprinklered protected
1.2 Mixed – Meets 6.1.14.2, mixed> safe guards viewed as.industrial
1.3 Special Definitions – None
1.4 Classification of Occupancy – Industrial
1.5 Classification of Hazard of Contents – Ordinary per 6-2.2.3
1.6 Minimum Construction – No requirements
2.2 Means of Egress Components –Two Exits per floor
2.3 Capacity of Egress –per table 7.3.1.2> 1 per 100 @(63, 000) =63 total occupancy load
1
R
r- w
SANFORD FIRE DEPARTMEN'C
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box :1788, Sanford, Fl. 32772
407302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
2.4 Number of Exits — Four (4) "exits" total
2.5 Arrangement of Egress — Found ready and accessible
2.6 Travel Distance All less than 200' ft
2.7 Discharge from Exits —This area shall be protected with fire sprinkler
2.8 Illumination of Means of Egress —Required
2.9 Emergency Lighting — Required
2.10 Marking of Means of Egress —all exits required with lighted exit signs
2.11 Special Features —Reserved
3.1 Protection of Vertical Openings — Protected with a automatic fire sprinkler sysytem
3.2 Protection from Hazards — Fire Sprinkler System will cover any hazardous areas
3.3 Interior Finish — No requirements
3.4 Detection, Alarm and Communications Systems:
3.5 Extinguishing Requirements — Four (4) 4A 60 B. C fire extinguishers required (see A. 01)
3.6 Corridors — N/A
4 Special Provisions
5 Building Services
5.1 Utilities — as per LSC 9-2
5.2 HVAC — as per LSC 9-2
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes — N/A
Sanford City Code — Chapter 9
Fire Sprinklers; ,Fire Sprinkler System required
Monitoring: required (SEE ABOVE)
Other: NFPA #1 >
3-5.1 Fire Lanes — Required.
SANFORD FIRE DEPARTMEN"I'
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. 0. Box t788, Sanford, Fl. 32772
407302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
3-6.1 Key Box — Required; will field verify (SEE APPLICATION)
3-7.1 Bldg. Address Number Posted and Legible — Required; will field verify (6") six
inch in size. See page A.3.0.