HomeMy WebLinkAbout159 Towne Center Cir 07-1665 (elec)TOwhe Q'IX'e- (2t .
L A R S 0 N B I N K L E Y
September 18, 2007
Dan Florian
City of Sanford
Building Official
300 N. Park Ave.
Sanford, FL 32771
Victoria's Secret -Seminole
San
1-131 Project No: 01200746.02
Mr. Florian:
Due to the distance between the mall electrical room and the store (over 200'), and the fact that the mail is
requiring that any new conduit be routed through adjacent tenant spaces (they will not allow the service to run in a
service corridor),we are asking for a variance to reuse a pair of existing 1-1/4" conduits wi0i new #3 conductors
for a single 2.00 amp service. The installed wire would be rated for 75 degrees which would provide for a full 100
amp capacity per feed resulting in a full 200 amp service. We do not feel that the smaller parallel feeds would be
a life safety issue or pose any other significant safety issues:
If you have any questions regarding the above, please contact this office.
Respectfully submitted,
John Coulter, P,E.
Vice President
CR Y:\,_ProjeclsWctive\2007\01200745,02101200745,02, GEN\O1200745,022007-09-18— Letter to City of5anford.doc
Larson Binkley, Inc. 6363 College Blvd., Suite 400 Overland Park, KS 66211-1542 T 913 383 2621 F 913 383 2831 larsonbinkley.com
OL A RS ON BINKLEY
TRANSMITTAL
Date: September 18, 2007 From: Greg McFarland
To: Dan Florian Sender's Phone: 913) 383-5863
Company: City of Sanford senders Fax 913) 383-2831
Address: 300 N. Park Avenue sent via: FedEx Priority
Sanford, FL 32771 Project Victoria's Secret -Seminole
Phone. 913-383-5841 1-81 No: 01200745.02
Subject Victoria's Secret -Seminole
F] urgent Per Your Request For Your Review For Your Approval
nX For Your Use F] Please Reply Approved as Noted F Reply ASAP
Attached: 1 Signed/Sealed Letter
Comments:
E9
CA / ca / Y:l„Pr*dsO4vet2007t01200745.02191200745.02.GENV01200745.02 2007-09.18 Tia to Dan Flarian.doc
Larson Binkley, Inc. 6363 College Blvd., Suite 400 Overland Park, KS 66211-1542 T 913 3832621 F 913 393 2831 larsonbinklsy.corn
I
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407 302-2516 /FAX (407) 302-2526
Fire Marshal Tim Robles
Plans Review Sheet
Date: April 6, 2007 Business Address: 159 Towne Center Circle
Victory's Secret
Occ. Ch. 36, Mercantile Class B Mercantile Occupancies (9,373 sqft)
Business Name: Victory's Secret
Contractor: Not Completed on Application Ph.
FAX. ( )
Architect: Gerald Schremshock Phone (614)545-4550
Fax (614) 545-4555
Reviewed by: Timothy Robles, Fire Marshal /) /Y --i
ll
Comment: The contractor must have all components of construction separatedfor the areasexposingthegeneralpublic.
N.F.M.-1 section 13.1.9 - When a fire
Protection system is out of service for
more than 4 hours in a 24 hour period,
mandatory fire watch required,
Plans reviewed as Mercantile Occupancy. FD reserves right to require applicable coderequirementsifoccupancyusechanges.
µ , w. 3 : 'ealed letter from Engineer of Record stating design criteriaforsprinklersystemneedstobesubmittedwithconstruction
plans. Separate permit required for Fire Alarm. Fire alarm system required in this buildingandnotificationineachtenantspace, but not limited to: Horn strobes in every unit, pull stationsineveryunit, kitchen suppression system tied into main fire alarm
panel. 1.1 Fire Alarm required for monitoringof sprinkler
system
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407 302-25161 FAX (407) 302-2526
Fire Marshal Tim Robles
1.2Application - New Building (9,373 s. q. ft.)
1.3 Mixed - N/A, mercantile
1.4Special Definitions —mercantile over 3,000
1.5 Classification of Occupancy — Mercantile Store Class "B"
1.6 Classification of Hazard of Contents — Ordinary in office areas, and storage area
classified as "High Hazard per L.S.C. 101
1.7 Minimum Construction - Shall comply with Florida Building Code 2004
mercantile occupancy Type IV, UNPROTECTED, with fire sprinkler system
1.8 2.2 Means of Egress Components — r,
2.3 Capacity of Egress — sales floor area based on one (])_person per 30 sq ft., storage area
based on one (1) person per 300 sq. ft.
2.4 Number of Exits — (Minimal ofTwo (2) required EXITS) two Provided, (2)
2.5 Arrangement of Egress: Travel distance increased up to 200' (ft) do to fire sprinkler system
2.6 Travel Distance" k4
a
2.7 Discharge from Exits — O.K., will field verify
2.8 Illumination of Means of Egress —additional EXIT SIGNS may be required (power shut
down test required at night only)
2.9 Emergency Lighting — (1) foot candle (101x & a minimum at any point of 0.1
foot-candle (1LX) measured along the path of egress at floor level. Therefore
additional emergency lights may be required, (power shut down test required at night
only)
Emergency Lighting required inside Main Electrical room and all rest rooms (*).
2.10 Marking of Means of Egress — O.K.; will field verify?
2.11 Special Features —Reserved
2
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407 302-25161 FAX (407) 302-2526
Fire Marshal Tim Robles
3.1 Protection of vertical Openings — Class Q) mercantile shall have an automatic fir
sprinkler system, design criteria SHALL SHOW storage maximum height in
storage area (*).
3.2 Protection from Hazards — (See exception 36-3.2.1 .LSC 101)
3.3 Interior Finish — Not required, building has an automatic fire sprinkler system
3.4 Detection, Alarm and Communications System: Provide additional horn
strobes in each individual unit,
3.5 Extinguishing Requirements — as per NEPA 10, Three (3)ire
extinguishers required per N.F.P.A... #10 See blueprints (Minimal 3A 40
B. C. Rated)(*).
5.1 Utilities — as per LSC 7-1
5.2 HVAC as per LSC 7-2
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
Sanford City Code — Chapter9:
Required; Fire Sprinklers. Fire Department will field verify sight glass at all inspectors
test.
Monitoring: Requiredforfire sprinkler system and all inside and outside fire sprinkler valves.
Other: NFPA 1
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box —
3-7.1 Bldg. Address Number Posted and Legible — Post address in 6" six inch numbers
contrasting in color.
3