HomeMy WebLinkAbout1121-1197 W Airport Blvd (fire review) (a)SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407 302-2520 / FAX (407) 302-2526
Plans Review Sheet
Date: September 16, 2005 Business Address: 1105-1117 W.Airport Blvd.
Occ. Ch. 40 Industrial -38 -Business
Business Name: BRIO CENTER
Architect: JRJJ & Associates
Contractor: Design Enterprise .
PH (407) 830-1414
Fax. (407) 830-8448
P H (407) 875-0115
Fax. (407) 875-0308
PH (407) 830-1414
Fax. (407) 830-8448
reo waet?oCt<>?wed'
hxi
1]
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner
Comment: Plans reviewed as Occ. Ch. 40 Industrial -38 -Business Type IVfire sprinkler
protected
20,160 sq ft type iv fire sprinkled building
Occupancy's FD reserves right to require applicable code requirements if occupancy use
changes. Sprinkler plans to be submitted for review, permitting, and inspections. Sealed
letter from Engineer of Record stating design criteria for sprinkler system needs to be submitted
with construction plans. F
Fire Alarm requirement: The fire sprinkler system shall be
monitoredfor the following: water flow fire sprinkler system.
Tamper valves will be required on all interior and exterior ofall
fore sprinkler valves
Fire Alarm notification: Each individual tenant space shall
have two (2) horn strobes, for individual tenant notification (one
in business office, and one in storage/industrial area).
1
a'-
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407302-2520 / FAX (407) 302-2526
Application — New Building (20,160 s. q. ft.)
1.1 Mixed — N/A,
Special Definitions — Ch. 40 Industrial -38 -Business
Classification of Occupancy — Ch. 40 Industrial -38 -Business Classification of Hazard of
Contents — Ordinary in office areas, and storage area classified as "High Hazard"
per L.S.C. 101
1.2 Minimum Construction — Shall comply with Florida Building Code 2004
mercantile occupancy
1. 3 22 Means of Egress Components . ets;LWT':;
ellaw art: .: r::ladan : tc:` :dace
2.3 Capacity of Egress— sales floor area based on one (])_person per 30 sqft., storage area
based on one (])person per 300 sq. ft.
2.4 Number of Exits — two for each individual tenant ok
2.5 Arrangement of Egress O.K. — two for each individual tenant ok 2.6 Travel Distance —
R. S B 1I 2 I2'I 44 ... ila u .. int Qn leadzr tri .clow.::::.iii..
2.7 Discharge from Exits — O.K., will field verify
2.8 Illumination of Means of Egress —additional EXIT SIGNS may be required (power shut
down test required at night only)
2.9 Emergency Lighting — (1) foot candle (10 lx & a minimum at any point of 0.1
foot-candle (I LX ) measured along the path of egress at floor level. Therfore
additional emergency lights may be required, (power shut down test required at night
only) EmergencyLLights required In all rest rooms & Main Electrical Room *).
2.10 Marking of Means of Egress — O.K.; will field verify
2.11 Special Features —Reserved
3.1 Protection of Vertical Openings — Ch. 40 Industrial -38 -Business shall have an
automatic -fire sprinkler system, design criteria
FA
r
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407302-2520 / FAX (407) 302-2526
shows rack storage maximum height in sto ae
area(rP
3.2 Protection from Hazards – (See exception 40-3.2.1 .LSC 101)
3.3 Interior Finish – Not required, building has an automatic fire sprinkler system
3.4 Detection, Alarm and Communications System: (as per N.F.PA.72- 3-8.3.1.2 (99)
Ed.
3.5 Extinguishing Requirements – as per NFPA 10, (10) ten 4A60 rated fire
extinguishers required per N.F.PA. #10 (see blueprints for locations).
5.1 Utilities – as per LSC 7-1
5.2 HVAC – as per LSC 7-2
5.3 Elevators, Escalators, Conveyors (4A-47) – N/A
Sanford City Code – Chapter9:
Required; Fire Sprinklers. Fire Department will field all inspectors test.
Monitoring: Required on allfire sprinkler valves (includes inside and out)
Other: NFPA 1
3-5.1 Fire Lanes – Required (see sight plan)
3-6.1 Key Box —One (1) required already
application attached)
3-7.1 Bldg. Address Number Posted and Legible –Post address in 6 " six inch
numbers contrasting in color (see blueprints).
3