Loading...
HomeMy WebLinkAbout159 Towne Center Cir (fire review) (a)TOwhe Q'IX'e- (2t . L A R S 0 N B I N K L E Y September 18, 2007 Dan Florian City of Sanford Building Official 300 N. Park Ave. Sanford, FL 32771 Victoria's Secret -Seminole San 1-131 Project No: 01200746.02 Mr. Florian: Due to the distance between the mall electrical room and the store (over 200'), and the fact that the mail is requiring that any new conduit be routed through adjacent tenant spaces (they will not allow the service to run in a service corridor),we are asking for a variance to reuse a pair of existing 1-1/4" conduits wi0i new #3 conductors for a single 2.00 amp service. The installed wire would be rated for 75 degrees which would provide for a full 100 amp capacity per feed resulting in a full 200 amp service. We do not feel that the smaller parallel feeds would be a life safety issue or pose any other significant safety issues: If you have any questions regarding the above, please contact this office. Respectfully submitted, John Coulter, P,E. Vice President CR Y:\,_ProjeclsWctive\2007\01200745,02101200745,02, GEN\O1200745,022007-09-18— Letter to City of5anford.doc Larson Binkley, Inc. 6363 College Blvd., Suite 400 Overland Park, KS 66211-1542 T 913 383 2621 F 913 383 2831 larsonbinkley.com OL A RS ON BINKLEY TRANSMITTAL Date: September 18, 2007 From: Greg McFarland To: Dan Florian Sender's Phone: 913) 383-5863 Company: City of Sanford senders Fax 913) 383-2831 Address: 300 N. Park Avenue sent via: FedEx Priority Sanford, FL 32771 Project Victoria's Secret -Seminole Phone. 913-383-5841 1-81 No: 01200745.02 Subject Victoria's Secret -Seminole F] urgent Per Your Request For Your Review For Your Approval nX For Your Use F] Please Reply Approved as Noted F Reply ASAP Attached: 1 Signed/Sealed Letter Comments: E9 CA / ca / Y:l„Pr*dsO4vet2007t01200745.02191200745.02.GENV01200745.02 2007-09.18 Tia to Dan Flarian.doc Larson Binkley, Inc. 6363 College Blvd., Suite 400 Overland Park, KS 66211-1542 T 913 3832621 F 913 393 2831 larsonbinklsy.corn I SANFORD FIRE DEPARTMENT FIRE PREVENTION DIVISION 300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772 407 302-2516 /FAX (407) 302-2526 Fire Marshal Tim Robles Plans Review Sheet Date: April 6, 2007 Business Address: 159 Towne Center Circle Victory's Secret Occ. Ch. 36, Mercantile Class B Mercantile Occupancies (9,373 sqft) Business Name: Victory's Secret Contractor: Not Completed on Application Ph. FAX. ( ) Architect: Gerald Schremshock Phone (614)545-4550 Fax (614) 545-4555 Reviewed by: Timothy Robles, Fire Marshal /) /Y --i ll Comment: The contractor must have all components of construction separatedfor the areasexposingthegeneralpublic. N.F.M.-1 section 13.1.9 - When a fire Protection system is out of service for more than 4 hours in a 24 hour period, mandatory fire watch required, Plans reviewed as Mercantile Occupancy. FD reserves right to require applicable coderequirementsifoccupancyusechanges. µ , w. 3 : 'ealed letter from Engineer of Record stating design criteriaforsprinklersystemneedstobesubmittedwithconstruction plans. Separate permit required for Fire Alarm. Fire alarm system required in this buildingandnotificationineachtenantspace, but not limited to: Horn strobes in every unit, pull stationsineveryunit, kitchen suppression system tied into main fire alarm panel. 1.1 Fire Alarm required for monitoringof sprinkler system SANFORD FIRE DEPARTMENT FIRE PREVENTION DIVISION 300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772 407 302-25161 FAX (407) 302-2526 Fire Marshal Tim Robles 1.2Application - New Building (9,373 s. q. ft.) 1.3 Mixed - N/A, mercantile 1.4Special Definitions —mercantile over 3,000 1.5 Classification of Occupancy — Mercantile Store Class "B" 1.6 Classification of Hazard of Contents — Ordinary in office areas, and storage area classified as "High Hazard per L.S.C. 101 1.7 Minimum Construction - Shall comply with Florida Building Code 2004 mercantile occupancy Type IV, UNPROTECTED, with fire sprinkler system 1.8 2.2 Means of Egress Components — r, 2.3 Capacity of Egress — sales floor area based on one (])_person per 30 sq ft., storage area based on one (1) person per 300 sq. ft. 2.4 Number of Exits — (Minimal ofTwo (2) required EXITS) two Provided, (2) 2.5 Arrangement of Egress: Travel distance increased up to 200' (ft) do to fire sprinkler system 2.6 Travel Distance" k4 a 2.7 Discharge from Exits — O.K., will field verify 2.8 Illumination of Means of Egress —additional EXIT SIGNS may be required (power shut down test required at night only) 2.9 Emergency Lighting — (1) foot candle (101x & a minimum at any point of 0.1 foot-candle (1LX) measured along the path of egress at floor level. Therefore additional emergency lights may be required, (power shut down test required at night only) Emergency Lighting required inside Main Electrical room and all rest rooms (*). 2.10 Marking of Means of Egress — O.K.; will field verify? 2.11 Special Features —Reserved 2 SANFORD FIRE DEPARTMENT FIRE PREVENTION DIVISION 300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772 407 302-25161 FAX (407) 302-2526 Fire Marshal Tim Robles 3.1 Protection of vertical Openings — Class Q) mercantile shall have an automatic fir sprinkler system, design criteria SHALL SHOW storage maximum height in storage area (*). 3.2 Protection from Hazards — (See exception 36-3.2.1 .LSC 101) 3.3 Interior Finish — Not required, building has an automatic fire sprinkler system 3.4 Detection, Alarm and Communications System: Provide additional horn strobes in each individual unit, 3.5 Extinguishing Requirements — as per NEPA 10, Three (3)ire extinguishers required per N.F.P.A... #10 See blueprints (Minimal 3A 40 B. C. Rated)(*). 5.1 Utilities — as per LSC 7-1 5.2 HVAC as per LSC 7-2 5.3 Elevators, Escalators, Conveyors (4A-47) — N/A Sanford City Code — Chapter9: Required; Fire Sprinklers. Fire Department will field verify sight glass at all inspectors test. Monitoring: Requiredforfire sprinkler system and all inside and outside fire sprinkler valves. Other: NFPA 1 3-5.1 Fire Lanes — Required if building is more than 150' from street; exception: building has fire sprinkler system. 3-6.1 Key Box — 3-7.1 Bldg. Address Number Posted and Legible — Post address in 6" six inch numbers contrasting in color. 3