HomeMy WebLinkAbout1401 W Seminole Blvd (a) (short stay revision) (rev)Sheet P4.2 — Plumbina Details
1. Edited Mechanical Room Equipment Detail to show one mater head unit on building water softener
system.
Sheet M1.0 — Mechanical Floor Plan
1. The 18x18 supply air devices in the main dining were revised to be tagged as Type V.
Sheet M1.1— Mechanical Roof Plan
1. The roof mounted refrigeration condensing units were revised per Florida requirements.
Sheet Mi.2 — Mechanical Roof Plan
1. The location of RTU-2 and associated dud drops were adjusted for structural coordination.
Feel free to contact our office should you have any questions or follow up for additional information.
Best Regards,
U�'—
Scott Windle, AIA, LEED AP
ID Studio 4, LLC
is
Cheddars Casual Cafe
Revision #2 Dated 01.09.2013
Page 4 of 4
r 1 #0
0.
CCD No. 1 Revision No. 1 Narrative
Project Name: CFRH - Short Stay Renovation
Project No.: H-12095.00
Document changes in CCD No. 1 Revision No. 1 include, but are not limited to, the following list of items:
SPECIFICATIONS
DRAWINGS
General Drawings
Dwg No
Description
Remar s
Re_ason for C«_hange
G110
Life Safety Plan
Added calculations for smoke
compartment 10 evacuation
capacity
Response to AHCA
comment
G110
Life Safety Plan
Added exit light
Response to AHCA
comment
Civil Drawings
Demolition Drawings
Dwg No
De.:sc«lption
Remarks
Reason for C«hange
D111
Demolition Plan
Removed phasing
Unit will be shut
down during
construction,
phasing not
required.
D112
Demolition Plan - Phase 2
Removed from set
See above
Architectural Drawings
800 North Mognolio Avenue ■ Suite 600 • Orlondo. Florida 32803 ■ 407.839.0886 ■ www.hunionbrady.com ■ #AACOOt744
CCD No. 1 Revision No. 1 Narrative
Project Name: CFRH - Short Stay Renovation
Project No.: H-12095.00
o �:,,�;
„Rema�ks�" � � "�'-"R►%`.:r
yReason for�;Cian e
A011
Door Schedule and I.G.O., Interior
Removed door at staff lounge
Response to AHCA
Partition Types
T1310, added glazing note to
comments.
glazing type.
A012
Specifications
Specify fire rated wood blocking
Response to AHCA
to wood blocking sec section.
comment.
A111
Floor Plan
Added equipment and notes to
Response to AHCA
plan, added exit clearance to
comments.
exterior door.
Al 12
Floor Plan - Existing Endoscopy
Indicate existing endoscopy suite
Response to AHCA
Suite
and location of temporary short
comment.
stay re /recove .
A411
Reflected Ceiling Plan
Added exit light
Response to AHCA
comment.
A601
Interior Elevations and Details
Added cubicle curtain track
Response to AHCA
mounting detail
comment
Structural Drawings
Plumbing Drawings
Dwg No
Description
Remarks
Reason for Change
P002
Schedules, Specifications, Legend
Indicate relocated/new medical
Response to AHCA
and Notes - Medical Gas
gas zone valve box (ZVB-1) to
comments.
corridor outside of suite.
P101
Demolition Plan - First Floor
Indicate relocated/new medical
Response to AHCA
Plumbing and Medical Gas
gas zone valve box (ZVB-1) to
comments.
corridor outside of suite.
P401
Renovation Plan - First Floor
Indicate relocated/new medical
Response to AHCA
Medical Gas
gas zone valve box (ZVB-1) to
comments.
corridor outside of suite.
Fire Protection Drawings
[,D,w',g;No;.; ,,Description '_� .R.,earn`.q�ks,;: :-': 1; :;. 'iReas.&ri;fo,� Change:
800 Norlh Magnolia Avenue n Suite 600 ■ Orlando. Florido 32803 ■ 407.839.0886 ■ www.huntonbrody.com ■ #AAC001744
v
CCD No. 1 Revision No. 1 Narrative
Project Name: CFRH - Short Stay Renovation
Project No.: H-12095.00
Mechanical Drawings
Dwg No
Description
a ar •s
Weaso or C« tinge
M401
Renovation Plan - First Floor -
Exhaust has been eliminated in
Response to AHCA
Mechanical
Room T1303 on revised Drawing
comments.
M401.
Exhaust airflow has been revised
to increase negative pressure for
the room on revised Drawing
M401.
Supply airflow has been
increased for Nourishment Room
1409 on revised Drawing M401.
Note has been added to revised
Drawing M401 to verify access to
CV boxes and provide any
modifications necessary if existing
access is inadequate.
Revised Plumbing Sheets P002,
P101 and P401 to indicate
relocated/new medical gas zone
valve box (ZVB-1) to corridor
outside of suite.
Electrical Drawings
Dwg No
Description
e arks
�Rteaso_n o_ Change
E401
Renovation Plan - First Floor Power
Relocate the smoke detector to
Response to AHCA
and Systems
the new entry door T1301.
comments.
Specify metallic conduit for the
underground conduit for the
branch circuits to the nurse
station.
E501
Renovation Plan - First Floor
Coordinate the orientation of the
Response to AHCA
Lighting
exit sign with the life safety plan.
comments.
Provide a minimum of one foot
candle of life safety lighting to
the exits.
800 North Magnolia Avenue ■ Suite 600 . Orlando, Florida 32803 . 407.839.0886 ■ www.huntonbrody.com ■ #AAC001744
CCD No. 1 Revision No. 1 Narrative
Project Name: CFRH - Short Stay Renovation
Project No.: H-12095.00
Technology Drawings
END OF CCD NO. 1 NARRATIVE
Attachments: Specifications and drawings as listed above.
800 North Magnolia Avenue ■ Suite 600 ■ Orlando. Florida 32803 . 407.839,0886 ■ www.hvntonbrody.com ■ #AAC001744
11
;:N. ,:
FEB 1 1 2013
City of Sanford Building Department
REVISION BY: --=-- ---
PERMIT # 13-0315 DATE February 11, 2013
PROJECT ADDRESS - 1401 W. Seminole Boulevard, Sanford, FL 32771
CONTRACTOR H W Davis Construction, Inc.
PHONE # 407-849-1212 FAX # 407-839-4068
CONTACT PERSON Jim Peacock
DESCRIPTIO.��'ISION Attached'Narrative to explain the following revision areas:
1. R#-,onse to AHCA Comments
2. Demolition changes
3. Architectural
4. Plumbing - Medical Gas
5. Mechanical
6. Electrical
�MYDEPT
IRE PREVENTION As
PLANNING
ov`.
r- C C
N
40
lorD,I;Cl)
INTEGRATED DESIGN ENGINEERING ARCHITECTURE
January 09, 2013
Ryan Hatfield
Cheddar's Casual Cafe
2250 W. John Carpenter Fwy, Suite 560
Irving, Texas 75063
RE: Cheddar's Casual Cafe
Southgate Commons
1650 Rinehart Road
Sanford, FL 32771
Documented Revisions for Issuance of Construction Document Revision # 1 dated 11.26.2012
Mr. Hatfield,
The following is a sheet -by -sheet summary of the recently issued drawing revisions tagged with the above
description.
Sheet AO.3 — Finish Schedule
1. S-2 stain revised.
2. WC-10 laminate added to schedule.
3. C-3 ceiling finish revised.
4. EF-3 exterior material revised.
5. SC-3 schluter trim revised.
6. Chesnut Stain Notes revised to Jacobean Stain Notes.
Sheet A1.0 — Dimensioned Floor Plan
1. Exterior wall dimension by entry revised.
Sheet A1.1— Noted Floor Plan
1. Two wall revisions in the dining area.
Sheet A1.2 — Furnishind Egress Plan
1. Table bases revised.
Sheet A1.3 — Floor Finish Plan
1. All F-6 Quarry Tile removed from plan and Floor Finish Legend.
Sheet A1.4 — Reflected Ceiling Plan
1. Section tag added in dining area.
2. Interior lights over booths revised.
Sheet A1.5 — Dimensioned Reflected Ceilin¢ Plan
1. Dimensions centered on exterior lights revised.
1431 GREENWAY DR SUITE 150 IRVING, TX 75038 972.870,1288 O##
Sheet A1.6 - Roof Plan
1. Compressor racks located and dimensioned.
2. Dimensions on dormers revised.
Sheet A1.7 - Enlarged Restroom Plan and Elevations
1. Dimensions revised and added in plan 1.
2. Scale corrected on detail 18.
3. Scale corrected on detail 24.
4. Toilet Accessory Schedule revised.
Sheet A1.8 - Enlarged Dumaster Plan and Details
1. Labeling
Sheet A1.9 - Enlarged Bar Plan and Details
1. Foundation revised on details 9 and 14.
Sheet A1.11- Enlarged Office, Mechanical and Receiving Area
1. Clear space to the cabinet revised in plan 13.
Sheet A2.1- Exterior Elevations
1. Cheddar's sign moved in elevation 1.
Sheet A2.2 - Interior Elevations
1. Added dimensions on elevation 6.
2. Added section tag on elevation 13.
3. Section tag Flipped on elevation 14.
Sheet A2.3 - Interior Elevations
1. Corrected elevation S.
2. Arch height revised on elevations 6, 7, and 8.
3. Materials specified and section tag added to elevation 8.
4. Chair rail added to elevations 9, 10, and 11.
Sheet A2.4 - Interior Elevations
1. Arch height revised on elevation 1.
Sheet A2.5 - Interior Elevations
1. Kitchen elevation 23 and tag on Key Plan added.
Sheet A3.0 - Building Sections
1. Revised soffit framing on section 1.
2. Added concrete curbs on section 2.
3. Key Notes revised.
Sheet A3.1- Wall Sections
1. Key Notes revised.
Sheet A3.2 - Wall Sections
1. Details 4 and 5 revised.
2. Added concrete curb on section 3.
3. Key Notes revised
Cheddars Casual Cafe
Revision #2 Dated 01.09.2013
Page 2 of 4
III
Sheet A3.3 - Wall Sections
1. Revised foundation on section 1, 2, and 3.
2. Revised soffit framing on section 1.
3. Detail 6 added.
4. Key Notes revised.
Sheet A3.5 - Exterior Details
1. Notes revised on details 1, 2, and 3.
2. Revised soffit framing on details 5 and 7.
Sheet A3.7 - Skylight Details
1. Framing by atrium notes added.
2. Detail 9 added.
Sheet A3.9 - Interior Details
1. Dimension on detail 2 revised.
Sheet A3.10 - Interior Details
1. Brick arch height revised on details 1 and 2.
2. Details 6, 8, and 21 revised.
Sheet A3.11- Millwork Details
1. Wood Paneling, Planks, Trim and Moulding Notes revised.
Sheet A4.0 - Door and Window Schedule
1. Notes added and hardware revised on all doors.
2. Notes added on Window Elevation C.
Sheet SO. 1-Typical Details
1. Shear wall anchor bolt embedment revised.
Sheet S2.0 - Roof Framin¢ Plan
1. Atrium window header strap note added.
Sheet S4.0 - Roof Framing Details
1. SIP panel revised per architectural specifications and general notes on details 1, 2, and 4.
Sheet S4.1- Roof Framing Details
1. SIP panel revised per architectural specifications and general notes on details 1, 2, and 4.
Sheet S4.2 - Roof Framing Details
1. SIP panel revised per architectural specifications and general notes on detail 2.
Sheet P1.2 - Plumbing Water Floor Plan
1. Added check and shut off valves above the ceiling in the kitchen area for various fixtures.
2. Rerouted hot water piping to run down in walls for restroom lavatories.
3. Rerouted hot water from dishwasher booster heater.
4. Resized cold water supply piping to water softener and hot water heater.
Sheet P2.2 - Water Isometric Riser Diagram
1. Rerouted hot water piping to run down in walls for restroom lavatories.
Sheet P3.1- Plumbine Schedules
1. Added lav-2.
Cheddar's Casual Cafe
Revision H2 Dated 01.09.2013
Page 3 of 4