SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI.32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 I FAX (407) 302-2526
Plans Review Sheet
Date: November 3, 2004 Business Address: 1401 W.P Ball Blvd.
Occ. Ch. 36, Mercantile Class `B'
Business Name: Movie Works @ 1401 W.P. Ball Blvd,
Contractor: Young Contracting Company Ph. (770) 522-9270
FAX. (770) 522-9273
Architect: Phillips Partnership Phone (770) 394-1616
Fax (770) 394-1314
Reviewed by: Timothy Robles Fire Protection Inspector/Plans ExaminerYY P
Comment: Plans reviewed as Mercantile Occupancy. FD reserves right to require
applicable code requirements if occupancy use changes. Sprinkler plans to be submitted for
review, permitting, and inspections. Sealed letter from Engineer of Record stating design
criteria for sprinkler system needs to be submitted with construction plans.
Separate permit required for Fire Alarm.
1.1 Fire Alarm requiredfor monitoring ofsprinkler system
1.2Application — New Building (5,200 s. + ft.)
1.3 Mixed — N/A, over 50 occupancy load
1.4Special Definitions — Class "B" Mercantile Store (Under 30,000 sq ft.)
1.5Classification of Occupancy — Mercantile Store Class "B"
1.6 Classification of Hazard of Contents — Ordinary in office areas, and storage area
classified as "High Hazard" per L.S.C. 101
1.7 Minimum Construction — Shall comply with Florida Building Code 2001
mercantile occupancy Type IV, UNPROTECTED
1.8 2.2 Means of Egress Components — Rear storage exits, E+XItT SIH, B = DIi i. i = ATrED
E01TIH 4_4' .elilow paint on floor leading to E+XItT door.
r
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 I FAX (407) 302-2526
2.3 Capacity of Egress — sales floor area based on one (])_person per 30 sq ft., storage area
based on one (1) person per 300 sq. ft.
2.4 Number of Exits — (Minimal of Two (2) required EXITS) Four Provided, (4)
2.5 Arrangement of Egress: Travel distance increased up to 200' (f) do tofire sprinkler system
2.6 Travel Distance —Rear=X INT SiHA iBE ,IiL1NIEATIE D W/IIIT . 4_4 yellow pain on oor
WO
leagnal
2.7 Discharge from Exits — O.K., will field verify
2.8 Illumination of Means of Egress —additional EXIT SIGNS may be required (power shut
down test required at night only)
2.9 Emergency Lighting — (1) foot candle (10 Ix & a minimum at any point of 0.1
foot-candle (1 LX) measured along the path of egress at floor level. Therefore
additional emergency lights may be required, (power shut down test required at night
only)
Emergency Lighting required inside Main Electrical room and all rest rooms 0).
2.10 Marking of Means of Egress — O.K.; will field verify?
2.11 Special Features —Reserved
3.1 Protection of Vertical Openings — Class (B) mercantile shall have an automatic, are
sprinkler system, design criteria SHALL SHOW storage maximum height in
storage area M.
3.2 Protection from Hazards — (See exception 36-3.2.1 .LSC 10 1)
3.3 Interior Finish — Not required, building has an automatic fire sprinkler system
3.4 Detection, Alarm and Communications System: (as per N.F.PA.72- 3-8.3.1.2 (99)
Ed.
3.5 Extinguishing Requirements — as per NFPA 10. FOUR (4) fire extinguishersshers
requiredper N.F.P.A... #10 See blue prints (Minimal 2A 10 B.0 Rated) M.
5.1 Utilities — as per LSC 7-1
5.2 HVAC — as per LSC 7-2
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
0)
0.
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 I FAX (407) 302-2526
Sanford City Code — Chapter9:
Required; Fire Sprinklers. Fire Department will field verify sight glass at all inspectors
test.
Monitoring: Requiredforfire sprinkler system and all inside and outside fire sprinkler valves.
Other: NFPA 1
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box — One (1 re uired see application attached
3-7.1 Bldg. Address Number Posted and Legible — Post address in 6" six inch numbers
contrasting in color.
r . SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISIO,* '• '
300'N. Park Ave., Sanford, FI.32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 I FAX (407) 302-2526
Plans Review Sheet
Date: June 17, 2004 Business Address: 2127-2191 W P Ball Blvd.
Occ. Ch. 36, Mercantile Class `B'
Business Name: Tennant "D"
Architect: Phillips Partnership
Ph. (770) 394-1616
FAX (770)394-1314
P H (770) 394-1616
Fax. (770) 394-1314
Contractor: T.B.A. (out to bid at time of submittal) Ph. ( )
evi -wed with comm InleaserplytocommentsMI ]
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner7/1 7
Comment: Plans reviewed as Mercantile Occupancy. FD reserves right to require
applicable code requirements if occupancy use changes. Sprinkler plans to be submitted for
review, permitting, and inspections. Sealed letter from Engineer of Record stating design
criteria for sprinkler system needs to be submitted with construction plans.
Separate permit required for Fire Alarm.
1.1 Fire Alarm requiredfor monitoring ofsprinkler system
1.2Application — New Building (9,624 s. q. ft.)
1.3 Mixed — N/A, all restaurants under 50 occupancy load
1.4Special Definitions — Class "B" Mercantile Store (Under 30,000 sq ft.)
1.50assification of Occupancy — Mercantile Store Class `B"
1.6 Classification of Hazard of Contents — Ordinary in office areas, and storage area
classified as "High Hazard" per L.S.C. 101
F
1.7 Minimum Construction — Shall comply with Florida Building Code 2001
mercantile occupancy Type IV, UNPROTECTED
1
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI.32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 / FAX (407) 302-2526 1.
8 2.2 Means of Egress Components — Rear storage exits, E X IITS+HAL B ' DIi i I =A ED NOT ,
4.4 ' vel1low pain on floor leading o E*XITdoor. 2.
3 Capacity of Egress — sales floor area based on one (])_person per 30 sq ft., storage area based
on one (1) person per 300 sq. ft. 2.
4 Number of Exits — (Minimal of Two (2) required EXITS 2.
5 Arrangement of Egress: Travel distance increased up to 200' (ft) do to firesprinkler system 2.
6 Travel Distance — Re E 410T Si*HALLBE DIn floor Iead-ing
toE,411T door. 2.7
Discharge from Exits — O.K., will field verify 2.8
Illumination of Means of Egress —additional EXIT SIGNS may be required (power shut down test
required at night only) 2.9
Emergency Lighting — (1) foot candle (10 Ix & a minimum at any point of 0.1 foot-candle (
1 LX) measured along the path of egress at floor level. Therefore additional emergency
lights may be required, (power shut down test required at night only) Emergency
Lighting
required inside Main Electrical room and all rest rooms (*). 2.10
Marking of Means of Egress — O.K.; will field verify? 2.11
Special Features —Reserved 3.1
Protection of Vertical Openings — Class (B) mercantile shall have an automatic fire sprinkler system,
design criteria SHALL SHOW storage maximum height in storaze area
M. 3.2
Protection from Hazards — (See exception 36-3.2.1 .LSC 10 1) 3.3
Interior Finish — Not required, building has an automatic fire sprinkler system 3.4
Detection, Alarm and Communications System: (as per N.F.PA.72- 3-8.3.1.2 (99) Ed. 3.
5
Extinguishing Requirements — as per NFPA 10, .Three (3) fire extinguishers required per N.
F.P.A... #10 See blue prints (Minimal 4A 60 B.0 Rated) M. 2
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 IFAX (407) 302-2526
5.1 Utilities — as per LSC 7-1
5.2 HVAC — as per LSC 7-2 ,
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
Sanford City Code — Chapter9:
Required; Fire Sprinklers. Fire Department will field verify sight glass at all inspectors
test.
Monitoring: Requiredforfire sprinkler system and all inside and outside fire sprinkler valves.
Other: NFPA 1
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box — One (D required see application attached
3-7.1 Bldg. Address Number Posted and Legible — Post address in 6" six inch numbers
contrasting in color (see blue prints).
3
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION ,
300 N. Park Ave., Sanford, FI.32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 / FAX (407) 302-2526
Plans Review Sheet
Date: June 17, 2004 Business Address: 2011-2071 W P Ball Blvd.
Occ. Ch. 36, Mercantile Class `B'
Business Name: Tennant t-" Ph. (770) 394-1616
FAX (770)394-1314
Architect: Phillips Partnership
P H (770) 394-1616
Fax. (770) 394-1314
Contractor: T.B.A. (out to bid at time of submittal) Ph. ( )
viewe witch comment• Iea•se r prly to comments (]
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner
Comment: Plans reviewed as Mercantile Occupancy. FD reserves right to require
applicable code requirements if occupancy use changes. Sprinkler plans to be submitted for
review, permitting, and inspections. Sealed letter from Engineer of Record stating design
criteria for sprinkler system needs to be submitted with construction plans.
Separate permit required for Fire Alarm.
1.1 Fire Alarm requiredfor monitoring ofsprinkler system
1.2Application — New Building (6,027 s. + ft.)
1.3 Mixed — N/A, all restaurants under 50 occupancy load
1.4Special Definitions — Class `B" Mercantile Store (Under 30,000 sq ft.)
1.5Classification of Occupancy — Mercantile Store Class "B"
1.6 Classification of Hazard of Contents — Ordinary in office areas, and storage area
classified as "High Hazard" per L.S.C. 101
1.7 Minimum Construction — Shall comply with Florida Building Code 2001
mercantile occupancy Type IV, UNPROTECTED
1
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
t 300 N. Park Ave., Sanford, FI.32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 / FAX (407) 302-2526
1.8 2.2 Means of Egress Components — Reaz storage exits,XIT S+. A L BE D i i =A IFID
W/ITI. 4_4' .eUlow paint on floor leading to E-0111 door.
2.3 Capacity of Egress — salesfloor area based on one (1)_ person per 30 sqft., storage area
based on one (1) person per 300 sq. ft.
2.4 Number of Exits — (Minimal of Two (2) required EXITS)
2.5 Arrangement of Egress: Travel distance increased up to 200' (ft) do to fire sprinkler system
2.6 Travel Distance DDLINi ' AT1EiD W/IiTH 4_4 ' yeUlow p 11 , ton11001r.
leading to EXIT door.
2.7 Discharge from Exits — O.K., will field verify
2.8 Illumination of Means of Egress —additional EXIT SIGNS may be required (power shut
down test required at night only)
2.9 Emergency Lighting - (1) foot candle (10 Ix & a minimum at any point of 0.1
foot-candle (1 LX) measured along the path of egress at floor level. Therefore
additional emergency lights may be required, (power shut down test required at night
only)
Emery,ency Lighting required inside Main Electrical room and all rest rooms (*).
2.10 Marking of Means of Egress — O.K.; will field verify?
2.11 Special Features —Reserved
3.1 Protection of Vertical Openings — Class (B) mercantile shall have an automatic fire
sprinkler system, design criteria SHALL SHOW storage maximum height in
storage area M.
3.2 Protection from Hazards - (See exception 36-3.2.1 .LSC 101)
3.3 Interior Finish — Not required, building has an automatic fire sprinkler system
3.4 Detection, Alarm and Communications System: (as per N.F.PA.72- 3-8.3.1.2 (99)
Ed.
3.5 Extinguishing Requirements —as per NFPA 10, TWO (2) fire extinguishers required
per N.F.P.A... #10 See blue prints (Minimal 4A 60 B.0 Rated) M.
2
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI.32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 / FAX (407) 302-2526
5.1 Utilities — as per LSC 7-1
5.2 HVAC — as per LSC 7-2
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
Sanford City Code — Chapter9:
Required; Fire Sprinklers. Fire Department will field verify sight glass at all inspectors
test.
Monitoring: Required for fire sprinkler system and all inside and outside fire sprinkler valves.
Other: NFPA 1
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box — One (1 re uired see application attached
3-7.1 Bldg. Address Number Posted and Legible — Post address in 6" six inch numbers
contrasting in color (see blueprints).
3
SANFORD FIRE 6EPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI.32771 / P. O. Box 1788, Sanford, Fl. 32772
407 302-2520 / FAX (407) 302-2526
Plans Review Sheet
Date: June 15, 2004 Business Address: 1601-1691 W.P. Ball Blvd.
Occ. Ch. 36, Mercantile Class "A"
Business Name: Tenant "E "
Architect: Phillips Partnership
P H (770) 394-1616
Fax. (770) 394-1314
P H (770) 394-1616
Fax. (770) 394-1314
Contractor: T.B.A. Out to bid at submittal time Ph. ( )
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examine
jW
Comment: Plans reviewed as Mercantile Occupancy. FD reserves right to require
applicable code requirements if occupancy use changes. Sprinkler plans to be submitted for
review, permitting, and inspections. Sealed letter from Engineer of Record stating design
criteria for sprinkler system needs to be submitted with construction plans.
Application — New Building (19,200 s. q. ft.)
1.1 Mixed — N/A,
1.2Special Definitions — Class "A" Mercantile Store (Over 19,200 sq ft .)
1.3Classification of Occupancy — Mercantile Store Class "A"
1.4 Classification of Hazard of Contents — Ordinary in office areas, and storage area
classified as "High Hazard" per L.S.C. 101
1.5 Minimum Construction — Shall comply with Florida Building Code 2001
mercantile occupancy
1.6 2.2 Means of Egress Components —
iWIjWXV. ", gftnw pain o, ,floor leadi-n;Q to OT door. M.
1
SANFORD FIRE DEPART MENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI.32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 / FAX (407) 302-2526
2.3 Capacity of Egress — saleslloor area based on one (])_person per 30 sq ft., storage area
based on one (1) person per 300 sq. ft.
2.4 Number of Exits — (4) EXITS
2.5 Arrangement of Egress O.K. — Five remotely locatedfrom the otherfive (5) exits
2.6 Travel Distance — Rear EXlt SHA, L B • DIiLIiN/EA, Tt DWI/TrH 4.4 .ellow paint on .00r,
2.7 Discharge from Exits — O.K., will field verify
2.8 Illumination of Means of Egress —additional EXIT SIGNS may be required (power shut
down test required at night only)
2.9 Emergency Lighting — (1) foot candle (10 Ix & a minimum at any point of 0.1
foot-candle (1 LX ) measured along the path of egress at floor level.Therfore
additional emergency lights may be required, (power shut down test required at night
only) Emer eng cy Lights required In all rest rooms & Main Electrical Room M.
2.10 Marking of Means of Egress — O.K.; will field verify
2.11 Special Features —Reserved
3.1 Protection of Vertical Openings — Class (A) mercantile shall have an automatic fire
sprinkler system, design criteria shows rack storage maximum height in storage
area * >
3.2 Protection from Hazards — (See exception 36-3.2.1 .LSC 10 1)
3.3 Interior Finish — Not required, building has an automatic fire sprinkler system
3.4 Detection, Alarm and Communications System: (as per N.F.PA.72- 3-8.3.1.2 (99)
Ed.
3.5 Extinguishing Requirements — as per NFPA 10, (8) EIGHT 4A60 rated fire
extinguishers required per N.F.PA. # 10 (see blueprints for locations).
5.1 Utilities — as per LSC 7-1
5.2 HVAC — as per LSC 7-2 Tie into fire alarm
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
2
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI.32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 / FAX (407) 302-2526
Sanford City Code — Chapter9:
Required; Fire Sprinklers. Fire Department will field verify sight glass at all inspectors
test.
Monitoring: Required on all fire sprinkler valves (includes inside and out)
Other: NFPA 1
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box — One (1) required already (application attached)
3-7.1 Bldg. Address Number Posted and Legible — Post address in 6" six inch numbers
contrasting in color (see blueprints).
3
4
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI.32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 / FAX (407) 302-2526
Plans Review Sheet
Date: June 15, 2004 Business Address: 1401-1481 W.P. Ball Blvd.
Occ. Ch. 36, Mercantile Class "A"
Business Name: Tenant "F"
Architect: Phillips Partnership
P H (770) 394-1616
Fax. (770) 394-1314
P H (770) 394-1616
Fax. (770) 394-1314-
Contractor: T.B.A. Out to bid at submittal time Ph. ( )
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner —?
Comment: Plans reviewed as Mercantile Occupancy. FD reserves right to require
applicable code requirements if occupancy use changes. Sprinkler plans to be submitted for
review, permitting, and inspections. Sealed letter from Engineer of Record stating design
criteria for sprinkler system needs to be submitted with construction plans.
Application — New Building (18,800 s. q. ft.)
1.1 Mixed — N/A,
1.2Special Definitions — Class "A" Mercantile Store (Over 18,800 sq ft .)
1.3Classiiication of Occupancy — Mercantile Store Class "A"
1.4 Classification of Hazard of Contents — Ordinary in office areas, and storage area
classified as "High Hazard" per L.S.C. 101
1.5 Minimum Construction — Shall comply with Florida Building Code 2001
mercantile occupancy
1.6 2.2 Means of Egress Components — Rear storag exits,
IWhTI'H 4'N v .11lo,w pa-int on Hoer le-01 door. M.
1
SANFORD FIRE DEPARTMENT '
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI.32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 / FAX (407) 302-2526
2.3 Capacity of Egress — sales floor area based on one (])_person per 30 sqft., storage area
based on one (1) person per 300 sq. ft.
2.4 Number of Exits — (4) EXITS
2.5 Arrangement of Egress O.K. — Five remotely locatedfrom the otherfour (4) exits
2.6 Travel Distance — ,ear E+XhT SH.4L BE DIt 1IN/E, D WAITH 4.4 .ely low pain on r.00r,
2.7 Discharge from Exits — O.K., will field verify
2.8 Illumination of Means of Egress —additional EXIT SIGNS may be required (power shut
down test required at night only)
2.9 Emergency Lighting — (1) foot candle (10 Ix & a minimum at any point of 0.1
foot-candle (1 LX ) measured along the path of egress at floor level.Therfore
additional emergency lights may be required, (power shut down test required at night
only) Emer ency Lights required In all rest rooms & Main Electrical Room M.
2.10 Marking of Means of Egress — O.K.; will field verify
2.11 Special Features —Reserved
3.1 Protection of Vertical Openings - Class (A) mercantile shall have an automatic fire
sprinkler system, design criteria shows rack storage maximum height in storm
area * >
3.2 Protection from Hazards — (See exception 36-3.2.1 .LSC 10 1)
3.3 Interior Finish — Not required, building has an automatic fire sprinkler system
3.4 Detection, Alarm and Communications System: (as per N.F.PA.72- 3-8.3.1.2 (99)
Ed.
3.5 Extinguishing Requirements — as per NFPA 10, (6) six t 4A60 rated fire
extinguishers required per N.F.PA. #10 (see blueprints for locations).
5.1 Utilities — as per LSC 7-1
5.2 HVAC — as per LSC 7-2 Tie into fire alarm
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
K
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 / FAX (407) 302-2526
Sanford City Code — Chapter9:
Required; Fire Sprinklers. Fire Department will field verify sight glass at all inspectors
test.
Monitoring: Required on all fire sprinkler valves (includes inside and out)
Other: NFPA 1
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box — One (1) required already (application attached)
3-7.1 Bldg. Address Number Posted and Legible — Post address in 6" six inch numbers
contrasting in color (see blueprints).
3
SANFORD FIRE DE.PARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI.32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 / FAX (407) 302-2526
Plans Review Sheet
Date: June 17, 2004 Business Address: 1351-1391 WY Ball Blvd.
Occ. Ch. 36, Mercantile Class `B'
Business Name: Tennant "B"
Architect: Phillips Partnership
Ph. (770) 394-1616
FAX (770)394-1314
P H (770) 394-1616
Fax. (770) 394-1314
Contractor: T.B.A. (out to bid at time of submittal)
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner
Ph.( )
Comment: Plans reviewed as Mercantile Occupancy. FD reserves right to require
applicable code requirements if occupancy use changes. Sprinkler plans to be submitted for
review, permitting, and inspections. Sealed letter from Engineer of Record stating design
criteria for sprinkler system needs to be submitted with construction plans.
Separate permit required for Fire Alarm.
1.1 Fire Alarm required for monitoring of sprinkler system
1.2Application — New Building (8,802 s. q. ft.)
1.3 Mixed — N/A, all restaurants under 50 occupancy load
1.4Special Definitions — Class "B" Mercantile Store (Under 30,000 sq ft.)
1.5Classification of Occupancy — Mercantile Store Class "B"
1.6 Classification of Hazard of Contents — Ordinary in office areas, and storage area
classified as "High Hazard" per L.S.C. 101
1.7 Minimum Construction — Shall comply with Florida Building Code 2001
mercantile occupancy Type IV, UNPROTECTED
w
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 / FAX (407) 302-2526
1.8 2.2 Means of Egress Components —Rear storage exifis, EXbT S+ A L : D i D 11EA END
2.3 Capacity of Egress — sales floor area based on one (])_person per 30 sq ft., storage area
based on one (1) person per 300 sq. ft.
2.4 Number of Exits — (Minimal of Two (2) required EXITS)
2.5 Arrangement of Egress: Travel distance increased up to 200' (ft) do to fire sprinkler system
2.6 Travel Distance —Rear :X I T S+HAL BE DIiLINiEATED WII TI. 4_4yeUlow paint on oor leading
to E+XIrTdoor. 2.
7 Discharge from Exits — O.K., will field verify 2.
8 Illumination of Means of Egress —additional EXIT SIGNS may be required (power shut down
test required at night only) 2.
9 Emergency Lighting — (1) foot candle (10 Ix & a minimum at any point of 0.1 foot-
candle (1 LX) measured along the path of egress at floor level. Therefore additional
emergency lights may be required, (power shut down test required at night only)
Emergency
Lighting required inside Main Electrical room and all rest rooms (*). 2.
10 Marking of Means of Egress — O.K.; will field verify? 2.
11 Special Features —Reserved 3.
1 Protection of Vertical Openings — Class (B) mercantile shall have an automatic fire sprinkler
system, design criteria SHALL SHOW storage maximum height in storage
area M. 3.
2 Protection from Hazards — (See exception 36-3.2.1 .LSC 101) 3.
3 Interior Finish — Not required, building has an automatic fire sprinkler system 3.
4 Detection, Alarm and Communications System: (as per N.F.PA.72- 3-8.3.1.2 (99) Ed.
3.
5 Extinguishing Requirements —as per NFPA 10. TWO (2) fire extinguishers required per
N.F.P.A... #10 See blue prints (Minimal 4A 60 B.0 Rated) M. 2
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI.32771 / P. O. Box 1788, Sanford, FI.32772
407 302-2520 / FAX (407) 302-2526
5.1 Utilities — as per LSC 7-1
10*
5.2 HVAC — as per LSC 7-2
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
Sanford City Code — Chapter9:
Required; Fire Sprinklers. Fire Department will field verify sight glass at all inspectors
test.
Monitoring: Required forfire sprinkler system and all inside and outside fire sprinkler valves.
Other: NFPA 1
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box — One (1 re uired see application attached
3-7.1 Bldg. Address Number Posted and Legible — Post address in 6" six inch numbers
contrasting in color (see blueprints).
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
Plans Review Sheet
Date: June 1, 2005 Business Address: 1401 W.P. Ball Blvd.
Occ. Ch. 36 New Mercantile Movie Stop
Business Name: Game Stop @ 1425 W.P. Ball Blvd.
Contractor: Unknown at time of submittal
Ph. (770) 522-9270
FAX. (770) 522-9273
Architect: Phillips Partnership Phone (770) 394-1616
Fax (770) 394-1314
Reviewed [ ] RBVIEWGI 1Vll C4irI?1TiE1!i ::::: ,.. ] Rejected [I
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner
Comment: Plans reviewed as Mercantile Occupancy Class "C". FD reserves right to require
applicable code requirements if occupancy use changes.
Application — New Building. 3,624 sq. ft. New Mercantile occupancy
Mixed — N/A
1.1 Special Definitions — N/N
1.2 Classification of Occupancy — Class `B" (LESS THAN 3,000 sq. ft.)
1.3 Classification of Hazard of Contents — Ordinary per 6.2.2.2. F.F.P.C.
1.4 Minimum Construction — N/R (NO SPECIAL REQUIRMENTS)
2.2 Means of Egress Components-islesshallbe:mai iairredat all times
2.3 Capacity of Egress — QT Less:t ian 40:occupc nts
2.4 Number of Exits — Two (2)
2.5 Arrangement of Egress — O.K., will field verify, per section 7.5>F.F.P.C.
1
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Ff. 32771 / P. O. Box 1788, Sanford, Ff. 32772
407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
2.6 Travel Distance — Shall not exceed 75'36- 2.4.
1...' ...:. :... ..... .. .......... l.k.6r-e.irow.. sI
We wad through stockroom .............2.
8 Illumination of Means of Egress — O.K.; will field verify 2.
9 Emergency Lighting — O.K.; will field verify 2.
10 Marking of Means of Egress — O.K.,- will field verify 2.
11 Special Features - Reserved 3.
1 Protection of Vertical Openings — Provide a basic degree of compartments 3.
2 Protection from Hazards — NIN 3.
3 Interior Finish — Class "B" "A" or "C" allowed per 10.2. & 1 3.
4 Detection, Alarm and Communications Systems — Not required 3.
5 Extinguishing Requirements 6..P aspertwo (2) AI.C:*.A--::`- zt ngurs3iers required
3.
6 Corridors — 4
Special Provisions 5
Building Services 5.
1 Utilities — as per sec 9-1 5.
2 HVAC — as per sec 9-2 5.
3 Elevators, Escalators, Conveyors (4A-47) — N/A 5.
4 Rubbish Chutes, Incinerators, and Laundry Chutes — N/A Sanford
City Code — Chapter 9 s,
e..r. Monitoring:
Other:
NFPA 1 3-
5.1 Fire Lanes — Not required 3-
6.1 Key Box — Not required 2
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
3-7.1 Bldg. Address Number Posted and Legible: Post address on building 6 in
size