196 Towne Center Cir (a)
PROJECT CODE INFORMATION THE BUILDING SHALL BE IN COMPLIANCE WITH THE MOST RECENT VERSION OF THE FOLLOWING CODES, ALL WITH INCLUDED SANFORD AMENDMENTS: 2017 FLORIDA BUILDING CODE 2017 FLORIDA FUEL GAS CODE 2017 EXISTING BUILDING CODE 2017 FLORIDA TEST PROTOCOLS 2017 FLORIDA PLUMBING CODE 2017 FLORIDA ACCESSIBILITY CODE 2017 FLORIDA MECHANICAL CODE 2017 FLORIDA ENERGY CODE 2017 NATIONAL ELECTRICAL CODE ANSI A117.1 2003 2010 AMERICANS WITH DISABILITIES ACT (ADA) NFPA 13 INSTALLATION OF SPRINKLER SYSTEMS O.S.H.A. ADDRESS EXISTING BUILDING INFO AREA WASHINGTON PRIME GROUP TYPE NOTES EXISTING/RENOVATION CHARRISE WHITE ALTERATION LEVEL 2 INSTALLATION OF TWO (2) RESTROOMS. TEL: 317-986-8517 OCCUPANCY CLASS OCCUPANCY EXISTING AIR HANDLER UNIT(S) TCYREMAIN, NEW DUCT WORK AS CLASS NOTES MERCANTILE r ELECTRICAL M RETAIL STORE INFORMATION SQUARE FOOTAGE AREA OCC. LARSON DESIGN GROUP SQ. FT. % OF AREA NOTES UNALTERED M SUITE 201 4,190 88% EXISTING SPACE RENOVATED M 05/18/2018 565 12% 1 NEW M M0.1 0 0% Q � 0 3 ~ TOTAL MECHANICAL DEMOLITION PLAN 4,755 100% GROSS AREA WITHIN EXTERIOR WALLS MECHANICAL FLOOR PLAN FIRE PROTECTION SYSTEM ELEMENT PLUMBING REQUIRED PROVIDED NOTES SPRINKLER SYSTEM PD1.0 NO YES 05/18/2018 PORT. FIRE EXTINGUISHERS YES YES 05/18/2018 FIRE ALARM & DETECTION NO NO CONSTRUCTION TYPE OCCUPANCY CONST. TYPE NOTES M 1 IIB UNPROTECTED BUILDING MATERIALS ELEMENT 1 TYPE RATING NOTES STRUCTURAL FRAME IIB - EXISTING UNALTERED BEARING WALLS (EXT) - EXISTING UNALTERED BEARING WALLS (INT) - NONE NON-BEARING WALLS (EXT) - EXISTING UNALTERED NON-BEARING WALLS (INT) - EXISTING UNALTERED / NEW FLOOR CONSTRUCTION - EXISTING UNALTERED ROOF CONSTRUCTION - EXISTING UNALTERED PLUMBING FIXTURES OCCUPANTS MALE FEMALE 50%.OF FIXTURES TO BE MALE/ FEMALE NOTES 35 18 17 REQUIRED PROVIDED FIXTURE - REQUIRED MALE FEMALE MALE FEMALE WATER CLOSETS 1 PER 500 1 1 1 1 LAVATORIES 1 PER 750 1 1 1 1 BATHTUBS/SHOWERS NONE 0 0 DRINKING FOUNTAINS 1 PER 1000 1 2 (HIGH & LOW HC) SERVICE SINK NONE 1 1 DIRECTORY OF WORK ADDRESS CONTACT OF TWO (2) RESTROOMS. WASHINGTON PRIME GROUP INSTALLATION OWNER 111 MONUMENT CIRCLE CHARRISE WHITE INFORMATION SUITE 3500 TEL: 317-986-8517 MODIFICATIONS INDIANAPOLIS, IN 46204 EXISTING AIR HANDLER UNIT(S) TCYREMAIN, NEW DUCT WORK AS TENANT NOTED. SYMBOLS & ABBREVIATIONS ELECTRICAL MY LITTLE TOWN KIDS G3.0 INFORMATION RECEPTACLES AS NOTED. PLUMBING INSTALLATION LARSON DESIGN GROUP ARCHITECT: LAVATORY. 1000 COMMERCE PARK DRIVE ROBERT J. GEHR, AIA, NCARB ARCHITECT SUITE 201 PROJECT CONTACT: 05/18/2018 WILLIAMSPORT, PA 17701 KARA DEMMIEN 1 05/18/2018 TEL 570.244.2064 SCOPE OF WORK GENERAL INSTALLATION OF TWO (2) RESTROOMS. ARCHITECTURAL INSTALLATION OF NEW INTERIOR .PARTITIONS FOR RESTROOMS AND 05/18/2018 INSTALLATION OF NEW FINISHES. STRUCTURAL EXISTING, NO MODIFICATIONS MECHANICAL EXISTING AIR HANDLER UNIT(S) TCYREMAIN, NEW DUCT WORK AS 05/18/2018 NOTED. SYMBOLS & ABBREVIATIONS ELECTRICAL EXISTING SERVICE & PANEL TO REMAIN. INSTALLATION OF NEW G3.0 LIGHTS, & POWER RECEPTACLES AS NOTED. PLUMBING INSTALLATION OF NEW PLUMBING FIXTURES, WATER CLOSET, & DEMOLITION FLOOR PLAN LAVATORY. - DEFERRED SUBMITTALS • FIRE SPRINKLER MODIFICATIONS FIRE SPRINKLER NOTE ' CHANGES ARE -REQUIRED TO THE EXISTING FIRE SPRINKLER SYSTEM UNDER THIS SCOPE OF WORK, THE FIRE SPRINKLER SUB -CONTRACTOR SHALL SUBMIT TO THE BUILDING -AND FIRE DEPARTMENTS A FIRE SPRINKLER PLAN AND CALCULATIONS DOCUMENTING THE REVISIONS TO THE EXISTING SYSTEM. THE GENERAL CONTRACTOR SHALL TAKE ALL NECESSARY STEPS TO PROTECT THE INTEGRITY AND OPERATION OF THE EXISTING SYSTEM DURING CONSTRUCTION. ALL WORK SHALL COMPLY WITH NFPA 13, 1999 EDITION.. DRAWING INDEX SHEF-7# DESCRIPTION REVISIONS GENERAL INFORMATION G1.0 COVER SHEET/CODE INFORMATION 1 05/18/2018 G1.1 EGRESS/LIFE SAFETY PLAN 1 05/18/2018 G1.2 ADA ACCESSIBILITY DIGRAMS 1 05/18/2018 G2.0 SYMBOLS & ABBREVIATIONS W G3.0 SPECIFICATION/GENERAL NOTES cin cD V DEMOLrnON PLAN D.1.0 DEMOLITION FLOOR PLAN 1 05/18/2018 ARCHITECTURAL A1.0 FLOOR PLAN & INTERIOR ELEVATIONS 1 05/18/2018 A2.0 WALL TYPES DETAILS / DOOR SCHEDULES 1 05/18/2018 A3.0 REFLECTED CEILING PLAN 1 05/18/2018 MECHANICAL M0.1 MECHANICAL SPECIFICATIONS o� Q � 0 3 ~ MD1.0 MECHANICAL DEMOLITION PLAN 1 05/18/2018 M1.0 MECHANICAL FLOOR PLAN 1 05/18/2018 PLUMBING P0.1 PLUMBING SPECIFICATIONS c (P o 0- PD1.0 PLUMBING DEMOLITION PLAN 1 05/18/2018 P1.0 PLUMBING PLAN & DETAILS 1 05/18/2018 ELECTRICAL EO.1 ELECTRICAL SPECIFICATIONS ED1.0 ELECTRICAL DEMOLITION PLAN E1.0 POWER PLAN 1 05/18/2018 E2.0 LIGHTING PLAN 1 05/18/2018 E3.0 PANEL SCHEDULES & DETAILS . 5.ANEO ID BUILDING DIVISI01113 A rE"? ,1i I ISSUED SHALL PEE CONSTRUED TO SE A LIC�rtiSE TO PROCEED WITH THE WORK AND NOT AS AL1' ` r R? T'f TO VIOLATE: CANCEL, ALTER OR SET ASIDE PUNY OF THE PROVISIONS OF THE TECHNICAL CODES, NOsR- SHALL ISL:UANCE OF A PERMIT PREVENT THE 2" IILDI-NIG OFFICIAL FROM THEREAFTER REOU'RIr.';= A 'CORRECTION OF ERRORS IN PLANS, Oi i >T"i)'VTIOtd OR VIOLATIONS OF THIS CODE OFFICE PERMIT # .2?.1' 4 It Is a violation of the law for any person, unless acting under the direction of a licensed Architect, Engineer or Land Surveyor, to alter an item In any way. Plans, maps, specifications, studies, and reports not containing a red ink seal imprint on the cover sheet accompanied by an original signature by the licensed professional may have been fraudulently altered and shall not be considered an original copy. Copyright Protected 2018, Larson Design Group. 0 V. I- z r 5 �- _o N > ELU 0 w w 0 0 0 U W Z cin cD V coir. M p- 5O o C 0 9 a J V. I- r 5 ELU 0 IL 0 --I L z E O ° cin cD V coir. M p- 5O LL Y z U N rn Z�•a, NU a ° L� W` W ow JB U LL L o� Q � 0 3 ~ �� 3 O Y 3LL J j— L0 0 ■ (9 d- UM C z c (P o 0- NORTHw 0 E o Cv NLOn 0 0o aZ, CU X 0 �3--a- r - � - - - _- - - - -- - - - - �-=i--=- - -a =- - � -�-_�� �_� - - _ -�. _ ---_�- - - -- - _� --- - -- - - - - - - - - - - - - - - -- - - --- - - - - -- - - _ OIF F� 12" MIN. PULL SIDE PROVIDE THIS LETTERS AND NUMBERS: MOUNTED SIGNAGE � coMPREssED CARPET t/4' MAX FIN. FLOOR ibt 30 -ADDITIONAL SPACE IF 1. LETTERS AND NUMERALS SHALL BE RAISED 1/32' (0.8 MM) MINIMUM, x z LOW THRESHOLD A. DOOR MOUNTED SIGNAGE: Q � LLQ` 4$' THE DOOR HAS BOTH z_ UPPERCASE, SANS -SERIF OR SIMPLE SERIF AND SHALL BE ACCOMPANIED W WITH GRADE 2 BRAILLE. RAND CHARACTERS SHALL BE AT LEAST 5/8- E Z � 24" A LATCH AND A - � Vi'`'i` / 1. (UNISEX) -12" DIAMETER CIRCLE 1/4' THICK WITH 1/4' _ N =rlaaaua (16 MM) HEIGHT, BUT NO HIGHER THAN 2' (50 MM). PICTOGRAMS SHALL BE THICK TRIANGLE SUPERIMPOSED WITHIN CIRCLE. \ W TERICLOSER \� ACCOMPANIED BY THE EQUIVALENT VERBAL DESCRIPTION PLACED DIRECTLY �/ BELOW THE PICTOGRAM. THE BORDER DIMENSIONS OF THE PICTOGRAM 20 18 SHALL BE 6' (152 MM) MINIMUM IN HEIGHT. (ADAAG SEC. 4.30.4) 2 SIGNS ARE CENTERED ON THE DOOR 60' FROM THE #� NTERI FLOOR TRANSMON BETWEEN FLOOR FINISHES X o 9lo21d1 V INTERNATIONAL SYMBOLS FOR 4. LETTERS AND NUMBERS ON SIGNS SHALL HAVE A WIDTH -TO -HEIGHT B. WALL MOUNTED SIGNS t4� . ACCESSIBILITY ' RATIO BETWEEN 3:5 AND 1:1 AND A STROKE WIDTH -TO -HEIGHT RATIO a � z BETWEEN 1:5 AND 1:10. (ADAAG SEC. 4.30.2) . G Z Z 1. THE INTERNATIONAL SYMBOL OF ACCESSIBILITY IS EG A PICTOGRAM TO COMPLY : s WITH 703,6 5. THE CHARACTERS AND BACKGROUND OF SIGNS SHALL BE EGGSHELL, MATTE, INSTALLED ON THE WALL ADJACENT TO THE LATCH SIDE 2 a 48, X201 p OR OTHER NON -GLARE FINISH. CHARACTERS AND SYMBOLS SHALL OF THE DOOR. THE BORDER DIMENSION SHALL BE A Q 1 Z " Z SYMBOL OF ACCESSIBILITY MINIMUM OF 6' IN HEIGHT. NOTE IF NO WALL SPACE IS 12" 12 � TO COMPLY WITH 703.7 CONTRAST WITH THEIR BACKGROUND -EITHER LIGHT CHARACTERS ON AVAILABLE, SIGN IS TO BE PLACED ON THE NEAREST rF 112'[ IN. IN. A DARK BACKGROUND OR DARK CHARACTERS ON A LIGHT BACKGROUND. ADJACENT WALL, PREFERABLY ON RIGHT. HIGH FORWARD REACH LOAM co TEXT NOT IN PICTOGRAM (ADAAG SEC. 4.30.5) x 00 FIELD (5/8' TO 2' TALL) 2. VERBAL DESCRIPTION AS TO REST ROOM USAGE (I.E. a DOOR THRESHOLD 4A18» WOME 6. CHARACTERS AND NUMBERS ON SIGNS SHALL BE SIZED ACCORDING TO MEN'S REST ROOM) IS TO BE PLACED DIRECTLY BELOW THE VIEWING DISTANCE FROM WHICH THEY ARE TO BE READ. THE MINIMUM THE SYMBOL OF ACCESSIBILITY. _ (X) IN. a GRADE 2 BRAILLE HEIGHT IS MEASURED USING AN UPPER CASE X. LOWER CASE CHARACTERS a 1 PUSH SIDE 29 a ARE PERMITTED. (ADAAG SEC. 4.30.3) 3. SIGNS ARE CENTERED ON THE WALL 60" FROM THE X FLOOR. PROVIDE THIS 7. BRAILLE SHALL BE CONTRACTED (GRADE 2) BRAILLE AND SHALL COMPLY iv ADDITIONAL SPACE IF REQUIRED ADA SIGNAGE NTH SECTION 703.4. (ICC/ANSI SEC. 703.4.1) " 4. MOUNTING LOCATION ALLOWS A PERSON TO APPROACH (X) " WITHIN 3' OF THE SIGN WITHOUT ENCOUNTERING THE DOOR HAS BOTH WALL -SIGNAGE (TYP. 8. BRAILLE SHALL BE BELOW THE CORRESPONDING TEXT. IF TEXT IS PROTRUDING OBJECTS OR STANDING WITHIN THE SWING / } M A LATCH AND A TWO HINGED TWO HINGED MULTILINED, BRAILLE SHALL BE PLACED BELOW THE ENTIRE TEXT BRAILLE OF A DOOR CLOSER DOORS IN SERIES DOORS IN SERIES SHALL BE SEPARATED 3/8" (9.5 MM) MIN. FROM ANY OTHER TACTILE CHARACTERS AND 3/8" (9.5 MM) MIN. FROM RAISED BORDERS AND �a DECORATIVE ELEMENTS. BRAILLE PROVIDED ON ELEVATOR CAR CONTROLS -- Q-7 FRW APPROACH _ SHALL BE SEPARATED 3/16- (4.8 MM) MIN. EITHER DIRECTLY BELOW OR (Z) It is a violation of the law for < O ADJACENT TO THE CORRESPONDING RAISED CHARACTERS OR SYMBOLS. any person, unless acting under I (ICC/ANSI SEC. 703.4.4) Z _ LEVEL CHANGES O 48" the direction of a licensed SIGN LOCATIONS NOTES: 48" Architect, Engineer or Land ® `'® Surveyor, to alter an Item In 9. ALL BUILDING ENTRANCES THAT ARE ACCESSIBLE TO AND USABLE BY 1. 1/2" MAXIMUM TOTAL HEIGHT WITH 1/4", MAXIMUM VERTICAL any way. Plans, maps, PERSONS WITH DISABILITIES AND AT EVERY MAJOR JUNCTION ALONG OR CHANGE AT EDGEspecifications, studies, and 18» GENERAL RESTROOM SIGNAGE NOTES: reports not containing a red Ink LEADING TO AN ACCESSIBLE ROUTE OF TRAVEL SHALL BE IDENTIFIED 2. 1:2 SLOPED BEVEL REQUIRED IF LEVEL CHANGE IS OVER seal imprint on the cover sheet MI WITH A SIGN DISPLAYING THE INTERNATIONAL SYMBOL OF ACCESSIBILITY 1/4" VERTICAL 1. X SHALL BE $ 25 INCHES; Z SHALL BE Z X. accompanied by an original • AND WITH ADDITIONAL DIRECTIONAL SIGNS, AS REQUIRED, TO BE VISIBLE signature by the licensed PULL SIDE PULL SIDE TO PERSONS ALONG APPROACHING PEDESTRIAN WAYS. (ICC/IBC SEC. 1110) 3. LEVEL CHANGES OF MORE THAN 1/2" MUST BE RAMPED AND 2. WHEN X S 20 INCHES, THEN Y SHALL BE 48 INCHES MAXIMUM. professional may have been Z Z COMPLY WITH RAMP REQUIREMENTS. fraudulently altered and shall 3. WHEN X IS > 20 TO 25 INCHES, THEN Y SHALL BE 44 INCHES MAXIMUM. not be considered an original 10. WHERE PERMANENT IDENTIFICATION IS PROVIDED FOR ROOMS AND SPACES, copy. Copyright Protected 2018, 0®000 SIGNS SHALL BE INSTALLED ON THE WALL ADJACENT TO THE LATCH SIDE MAXIMUM FORWARD REACH OVER AN OBSTRUCTION Larson Design Group. - Z O 24" MI . 36" MIN O QQQQ OF THE DOOR. WHERE THERE IS NO WALL SPACE TO THE LATCH SIDE OF PROVIDE TACTILE 9 P• co 00000 THE NEARTHE ESTADJACENT UDING TWALL MOUNTING DOUBLE LEAF OHEIGHTISHALL BE 60GNS SHALL -(1525 MM CODE SECTIONPLACE ON SIGNAGE AS E703N� THRESHOLDS 00 a ABOVE THE FINISH FLOOR TO THE CENTERLINE OF THE SIGN. MOUNTING LEVEL -CHANGES 14- LOCATION FOR SUCH SIGNAGE SHALL BE SO THAT A PERSON MAY INTERNATIONAL INTERNATIONAL APPROACH WITHIN 3" (76 MM)OF THE SIGNAGE WITHOUT ENCOUNTERING SCALE: NTS TDD SYMBOL SYMBOL OF PROTRUDING OBJECTS OR STANDING WITHIN THE SWING OF A DOOR. ACCESS FOR (ADAAG SEC. 4.30.6) X Z Z HEARING IMPAIRED ACCESSIBLE 18" M PUSH SIDE PUSH SIDE 11. ADDITIONAL DIRECTIONAL SIGNS ALONG ACCESSIBLE PATH OF TRAVEL 4- 4" MAX WIDTH ANY AMOUNT 00 MI _ ARE REQUIRED. (ICC/IBC SEC. 1110) 00 - - "MI 10- 12. BUILDINGS REMODELED TO PROVIDE ACCESSIBLE SANITARY FACILITIES LLA FOR PUBLIC USE SHALL HAVE INFORMATION POSTED IN THE LOBBY AS C%1 PART OF THE BUILDING DIRECTORY. z / INTERNATIONAL SYMBOL OF ACCESSIBILITY: Q 30" * 48' MIN. IF DOOR HAS 54 MIN. 13. STANDARD USED TO IDENTIFY ACCESSIBLE FACILITIES CLEAR FLOOR SPACE HIGH AND LOW 14. WHITE FIGURE ON BLUE BACKGROUND, COLOR 15090 ON N IC4 X PARALLEL APPROACH SIDE REACH UMITS BOTH A LATCH ANDA #CLOSER FEDERAL STANDARD # 595A. DOORS AT PFI -P pNS FOR 15. WHEN ENFORCING AGENCY DETERMINES, IF APPROPRIATE, SPECIAL Z OPPOSITE WALLS LATCH APPROACH HINGE APPROACH RAISED INTERNATIONAL SYMBOLS FOR DESIGNS AND COLORS MAY BE APPROVED. O ACCESSIBILITY BRAI I F: (ICC/ANSI TABLE 703.4.31 z ? RG W FIG (B) >10" MIN. 10" 16 DOTS TO BE 0.09' (2.3 MM) TO 0.1" (1.5 MM) ON CENTER IN EACH CELL 24" MAX. 30"MAX,30' > 9" 9' 17. 0.241' (6.1 MM) TO 0.3' (7.6 MM) SPACE BETWEEN CELLS HORIZONTALLY. z W 1 REQUIRED DOOR CLEARANCES 18. 0.395" (10.0 MM) TO 0.4" (10.2 MM) SPACE BETWEEN CELLS HORIZONTALLY. QQR LATCH SIDE POST-,, SCALE: NTS EXIT Z ( z 2• FIELD (5/8" 19. DOTS RAISED 0:025' (0.6 MM) TO 0.037 (0.9 MM) ABOVE BACKGROUND. X X O ROUTE�TC EXIT � 20. DOTS BASE DIAMETER TO BE 0.059" (1.5 MM) TO 0.063' (1.6 MM). TACTILE SIGNAGE MOUNTING Q Q W R 1 C . HEIGHTS M Q Q Z GRADE 2 BRAILLE i\ a 1\rx..' N �N - TACTILE SIGNAGE �-- SYMBOLS 1 1/4' MI CANE RANGE 12' MAX CANE RANGE 1/2" M 2 SIDE REACH OVER AN OBSTRUCTK�N y (1 t/2 SCALE: NTS FIG (C) FIG (D) M BLOCKING, TYP. 00 FOR ALL ARAB BAR PROTRUDING OBJECTS R -� z LOCATIONS 1 1/4' MIN DIA ; %1 EACH REQUIREMENTS Y MAX DIA -��-'J 4 SCALE: NTS 5 SCALE: NTS WALL CIRCULAR o * 56" AT WALL -HUNG TOILETS MINIMUM 6" TOE KICK 36 4'-0" DRINKING FOUNTAIN NOTES FOR LOW HARDWARE DOORS Z SPACE TYP) 15" 15 DRINKING FOUNTAIN: HARDWARE. ENTRANCES. CL ( VERIFY KNEE & TOE HAND ACTIVATED DOOR OPENING HARDWARE IS ALL PRIMARY ENTRANCES TO BUILDINGS AND THRESHOLDS. O A. THE SPOUT SHALL PROVIDE A FLOW OF REQUIRED TO BE CENTERED BETWEEN 34 AND 44 INCHES FACIUIIES ARE REQUIRED TO BE MADE ACCESSIBLE. A THRESHOLDS ARE REQUIRED TO BE NO MORE L VERIFY KNEE &TOE CLEARANCES WITH _ THAN 1/2 INCH HIGH. BEVEL OR SLOPE THE EXPOSED EDGE O ALT DOOR CLEARANCES WITH SPECIFIED FIXTURE oX2G WATER AT LEAST 4" HIGH SO AS TO HIGH. LATCHING AND LOCKING DOORS THAT ARE HAND PRIMARY ENTRANCE IS DEFINED AS, '...ANY ENTRANCE TO A AT AN ANGLE NOT EXCEEDING 45 DEGREES SO THAT NO rn LOCATION SPECIFIED FIXTURE I Q ALLOW THE INSERTION OF A CUP OR ACTIVATED AND WHICH ARE IN A PATH OF TRAVEL HAVE TO FACILITY WHICH HASA SUBSTANTIAL FLOW OF PEDESTRIANS - RE: MECH w SINGLE VERTICAL CHANGE OF ELEVATION EXCEEDS 1/4' INCH. 'in °� o _ RE: MECH _ N -i GLASS UNDER THE FLOW OF WATER. BE OPERABLE WITH A SINGLE EFFORT BY LEVER TYPE TO ANY SPECIFIC MAJOR FUNCTION OF THE FACILITY. z_ z_ ca Z 00 g 0 HARDWARE, BY PANIC BARS, PUSH-PULL ACTIVATING BARS, REVOLVING DOORS CAN NOT BE USED AS A REQUIRED 1• EXIT DOORS, TOILET ROOM AND CHANGING ROOM DOOR TO _ 0 * NO FIXTURE z � z_ 30"x48" - OR OTHER HARDWARE DESIGNED TO PROVIDE PASSAGE ENTRANCE FOR THE HANDICAPPED. RECESSED DOORMATS ARE BE OPENABLE FROM INSIDE WITHOUT SPECIAL KNOWLEDGE 0o B. CONTROLS SHALL BE FRONT MOUNTED O WITHOUT REQUIRING THE ABIUTY TO GRASP THE OPENING REQUIRED TO BE ANCHORED TO PREVENT INTERFERENCE WITH FORCE OR NEED OF KEY. co MAY OVERLAP CLEAR OR SIDE MOUNTED NEAR THE FRONT HARDWARE. LOCKED EXIT DOORS ARE REQUIRED TO OPERATE WHEELCHAIR TRAFFIC. 2. SEE SPECIFICATION SHEET FOR RESPONSIBILITIES. CLEARANCE FLOOR EDGE. SPOUTS SHALL BE NO HIGHER AS DESCRIBED ABOVE IN THE DIRECTION OF EGRESS. DOOR WIDTHS AND HEIGHTS. x 30" 30" AREA THAN 36" MEASURED FROM THE FLOOR CLOSERS. REQUIRED EXIT DOORWAYS ARE 3• ALL HARDWARE TO BE LEVER TYPE. 60" Q MINIMU MINIMU OR GROUND SURFACES TO THE SPOUT THE MAXIMUM EFFORT TO OPERATE DOORS CANNOT REQUIRED TO HAVE A CLEAR OPENING NOT LESS THAN 32 ENTRANCE SIGNS. MINIMUM i� w OUTLET. EXCEED 8.5 POUNDS FOR EXTERIOR DOORS AND 5 POUNDS INCHES WIDE. FOR HINGED DOORS, THE OPENING IS ALL BUILDINGS ENTRANCES THAT ARE .- �/ z FOR INTERIOR DOORS. REQUIRED FIRE DOORS MAY REQUIRED MEASURED WITH THE DOOR AT A 90 DEGREE ANGLE FROM ACCESSIBLE TO AND USABLE BY PHYSICALLY HANDICAPPED C. WALL AND POST MOUNTED UP TO 15 POUNDS PRESSURE. THE PRESSURE IS TO BE ITS CLOSED POSITION. AT LEAST ONE OF A PAIR OF DOORS, PERSONS SHALL BE IDENTIFIED WITH AT LEAST ONE N y CANTILEVERED UNITS SHALL HAVE A MEASURED AT RIGHT ANGLES TO HINGED DOORS AND AT THE INCLUDING AUTOMATIC DOORS, HAS TO PROVIDE 111E 32 INCH STANDARD SIGN AND WITH ADDITIONAL DIRECTIONAL SIGNS (") LAVATORY DRINKING CENTER PLANE OF SLIDING OR FOLDING DOORS. CLEAR OPENING. DOOR HEIGHTS ARE REQUIRED TO BE A AS REQUIRED, TO BE VISIBLE TO PERSONS ALONG � WATER CLOSET WATER CLOSET AMBULATORY URINAL CLEAR KNEE SPACE BETWEEN THE .1 CLEARANCE BOTTOM OF THE APRON AND THE COMPENSATING DEVICES OR AUTOMATIC DOOR OPERATORS MINIMUM OF 80 INCHES. APPROACHING PEDESTRIAN WAYS. W M CLEARANCE STALL CLEARANCE STALL CLEARANCE FOUNTAIN PLAN 0 0 MAY BE UTILIZED TO MEET THE REQUIREMENTS. IF A DOOR C/) _ cD U FLOOR OR GROUND AT LEAST 27" HIGH HAS A CLOSER, THEN THE SWEEP PERIOD OF THE CLOSER D ca a 39"-41"lo .0L. 36" 30" WIDE, AND 17-19" DEEP. SUCH SHALL BE ADJUSTED SO THAT FROM AN OPEN POSITION OF (n 04 0 24" 15" 15" UNITS SHALL HAVE A MINIMUM CLEAR 70 DEGREES, THE DOOR WILL TAKE AT LEAST 3 SECONDS TO DLL CM O04 12" 42" FLOOR SPACE 30 X 48 TO ALLOW A _ - Y Z LUN rn MOVE TO A POINT 3 INCHES 75 mm FROM THE LATCH, DRINKING MEASURED TO THE LEADING EDGE OF THE DOOR. r` ._ °r g v v_ FOUNTAIN PERSON IN A WHEEL- CHAIR TO Z Q y a� 0 A PARTITION o � o a LL. j APPROACH THE UNIT FACING FORWARD. 3 � 6 � ao 0 x�� x�� 3 0 0 `�I- Q J 0 x a o N x Q D- _ D. THE FOLLOWING KNEE CLEARANCE IS U_ 'n o, "MIN o Ld > 0 w No 15' REQUIRED UNDERNEATH THE FOUNTAIN: W : > � o > _ MIN. ,�, N 27 MIN. FROM THE FLOOR TO THE U CL F- 0 3 _� '`� M i• `r o c~> 0° o ~ r o UNDERSIDE OF THE FOUNTAIN WHICH LEVER 34' TO ir 0 Y o 3 » �k �. o W I~- EXTENDS 8" MIN. MEASURED FROM THE 44' A.F.F. O r z " .. _ W o 18 15 w 7 w FRONT EDGE UNDERNEATH THE J a(D N Of MIN. D' FOUNTAIN BACK TOWARDS THE WALL; c 0) C - o DRINKING FOUNTAIN IF A MIN. 9" OF TOE CLEARANCE IS LEVER OR U SHAPED U p) ` N rn WATER CLOSETS LAVATORIES HANDLE MOUNTED AT -Fn 0 WATER CLOSET STALL URINALS ELEVATION PROVIDED, A MAX. OF 6" OF THE 48" 34" TO 48" AFF W W E o cc,4 TOE CLEARANCE OF CLEAR FLOOR SPACE REQUIRED AT Z 0 E 0 r III THE FIXTURE MAY EXTEND INTO THE 3 `j U) `n r- TOILET ROOM FIXTURES HEIGHTS -1- CLEARANCES TOE SPACE. 10" MIN. BorroM o U) o Z SCALE: 1/4"=1'-0" 90. RAIL O0i c o a r CLEAR EQ. EQ. s �ENTSOR/HARDWARE DETAIL ` w X16" o m w Q Z Q Q D' n Q W< a- =O m -H Q \ ~O ICV Q _ WN �O �F_ � � M� tt7Z if)Z O Of o o to TOILET SEAT SURFACE SANITARY DOORSURFACE CHILD -�/ �+ MIRROR OB COVER @TOWEL ED PAPERO COAT HOOK O SOAP NAPKIN BABY TOILET DISPENSER F DISPOSAL G CHANGING H TISSUE O PULLS at 9EXTINGUISHER MOUNED FIRE K PRO ECTION ACCESSIBILI 1 1 REOUIREMENT�7DISPENSER DISPENSER O(WOMEN'S ONLY) @STATION DISPENSER TOILET O SEAT PROJECT No. 11979-002 PARTITIONS A. ALL CONSTRUCTION SHALL BE COMPLETED IN STRICT ACCORDANCE WITH THE DRAWN BY 2010 2010 2010 2010 2010 ADA 2010 STANDARDS 305 2010 ADA STANDARDS 2010 STANDARDS 2010 STANDARDS 308 DESIGN GUIDELINES ESTABLISHED BY THE 2010 ADA STANDARDS FOR EBG STANDARDS STANDARDS 2010 STANDARDS STANDARDS STANDARDS OF & 308 OF ACCESSIBLE DESIGN, 404.2.7 & 604.8.2.2 ACCESSIBLE DESIGN (2010 STANDARDS) . STANDARDS SEE SECTIONS 604.7 & COORDINATE w APPv'D BY 603.3. 308 308 213.3.7, 603.4 308 ACCESSIBLE DESIGN, HEIGHT OF SHELF IN / B. UTILIZE EXTREME CARE TO ENSURE THAT ALL TOLERANCES, DIMENSIONS, AND RJG & 308 SEE SECTIONS 604.7 » 609.3 PARTITION MFG ' �+�+ �+ DOWN POSITION 34 ACCESSORY MOUNTING DIAGRAMS- & 609.3 MAX AFF CLEARANCES ARE CONSTRUCTED ACCURATELY. 7 » � _ C. TAKE ANY AND ALL ACTIONS NECESSARY TO CORRECT CONDITIONS WHICH ARE ADA ACCESSIBILITY SCALE: 1/4 =1 -0 IN THE OPINION OF THE STATE ACCESSIBILITY INSPECTOR IN VIOLATION OF NOTE: NOT ALL HANDICAP COMPONENTS MAY BE DIAGRAMS GUIDELINES AS THE DIRECT & SOLE RESULT OF DEVIATIONS FROM THE USED IN THIS PROJECT. THIS SHEET IS SHEET NO. CONSTRUCTION, DOCUMENTS OR INADEQUATE CONSTRUCTION CONTROL &, OR, PROVIDED FOR GENERAL REFERENCE ONLY TOLERANCES. G1. 2 _. i - ABBREVIATIONS A 90 303p,y C= F 0921$$ K RED AaG P U ® AT C TO C CENTER TO CENTER FA FIRE ALARM K KIP (THOUSAND POUNDS) / PER (BETWEEN WORDS) UGND UNDERGROUND & AND CANTIL CANTILEVER FB FC BRK FLAT BAR FACE BRICK KB KFT KNEE BRACE THOUSAND FT POUNDS P PAR PUMP PARALLEL UH UL UNIT HEATER UNDERWRITER'S LABORATORIES A. A/C AMPERE, COMPRESSED AIR AIR CONDITIONING CAP - CB CAPACITY CATCH BASIN FD FLOOR DRAIN KLF KIPS PER LINEAR FOOT PB PUSH BUTTON UN UNLESS NOTED AB ANCHOR BOLT CBORE COUNTERBORE FDC FIRE DEPARTMENT KO KNOCK OUT PBO PROVIDED BY OTHERS UNC UNIFIED COARSE THREAD ABAN ABANDON(ED) CC CUBIC CENTIMETER CONNECTION KPL KSI KICK PLATE KIPS PER SQUARE INCH PC PLUMBING CONTRACTOR PIECE - UNEX UNEXCAVATED ABT ABOUT CCTV CLOSED CIRCUIT TELEVISION. FDMPR FIRE DAMPER KV KILOVOLT PCC PRECAST CONCRETE UNFIN UNFINISHED ABUT ABUTMENT CLSM CONTROLLED LOW STRENGTH FDN FOUNDATION . KVA KILOVOLT -AMPERE PCF POUNDS PER CUBIC FOOT UNF UNIFIED FINE THREAD ABV ABOVE CEM MATERIAL _ CEMENT FE FEC FIRE EXTINGUISHER FIRE EXTINGUISHER CABINET KVAR KILOVAR PEC - PHOTO ELECTRIC CELL UNIV LINO UNIVERSAL UNLESS NOTED OTHERWISE " AC ALTERNATING CURRENT CER CERAMIC FF EL FINISHED FLOOR ELEVATION KW KILOWATT PERF PERFORATED UR URINAL ACC ACI ACCESSIBLE AMERICAN CONCRETE INSTITUTE CERTS CERTIFICATES FGL FIBERGLASS PERP PH PERPENDICULAR PHASE ACM ALUMINUM COMPOSITE MATERIAL CFM CUBIC FOOT (FEET) PER FIN FIN FLR FINISHED FINISHED FLOOR L — PIBO PROVIDED AND INSTALLED � ACS ACCESS MINUTE BY OTHERS P V— ACT ACOUSTICAL CEILING TILE CFS CUBIC FOOT FEET PER ( ) FL FLOOR LINE L LEFT PL PLATE, PROPERTY LINE ADDL ADDITIONAL SECOND FLA FLG FULL LOAD AMPS FLANGE, FLOORING LAD LADDER PLAM PLASTIC LAMINATE V VENT, VOLT, VOLTAGE ADDM ADDENDUM CG CENTER OF GRAVITY FLJ FLOOR JOIST LAM LAMINATE PLF POUNDS PER LINEAR FOOT VAR VARIABLE, VARIATION, ADH ADHESIVE CHFR CHAMFER FLR FLOOR LAV LAVATORY PL` PLATE GLASS VARIES ADJ ADJACENT, ADJUSTABLE CHKD CHECKED, CHECKERED FLR PL FLOOR PLATE LBS POUNDS PW PLYWOOD VAV VARIABLE AIR VOLUME BOX AFF ABOVE FINISHED FLOOR CLG HT CEILING HEIGHT FOC - FACE OF CONCRETE LF LINEAR FEET PMF PRE -MOLDED FILLER, VB VACUUM BREAKER, VINYL AFG ABOVE FINISHED GRADE CI CAST IRON FOF FACE OF FINISH LG LENGTH PROBABLE MAXIMUM FLOOD BASE AGGR AGGREGATE CIP CAST -IN-PLACE, CAST IRON FOM FACE OF MASONRY LH LL LEFT HAND LIVE LOAD PRL PANEL VCB VACUUM CIRCUIT BREAKER, AHD AHU AHEAD AIR HANDLING UNIT CJ PIPE CONSTRUCTION JOINT FOS - FACE OF STUDS LLBB LONG LEG BACK TO BACK _- PR PREFIN PAIR PSHED VINYL COVER BASE AISC AMERICAN INSTITUTE OF STEEL CL CENTER LINE FPM FOOT (FEET) PER MINUTE LLH LONG LEG HORIZONTAL PS POOUNDUND S PER SQUARE FOOT VCT VINYL COMPOSITION TILE CONSTRUCTION CLG CEILING FPS FOOT (FEET) PER SECOND LLV LONG LEG VERTICAL - PSI POUNDS PER SQUARE INCH VEL VERT VELOCITY VERTICAL ALT ALTERNATE CLJ CONTROL JOINT FR FRAME LONG LONGITUDE, LONGITUDINAL PSIA POUNDS PER SQUARE INCH VEST VESTIBULE ALUM ALUMINUM CLO CLOSET FRP FIBER REINFORCED PLASTIC LPCR LOW PRESSURE CONDENSATE RETURN ABSOLUTE VIN VERIFY IN FIELD AMER STD AMERICAN STANDARD CLR CLEAR, CLEARANCE FS FAR SIDE, FEDERAL LPS LOW PRESSURE STEAM PSIG POUNDS PER SQUARE INCH VIN VINYL - ANC ANCHOR, ANCHORAGE CLWG CLEAR WIRE GLASS SPECIFICATION LPT LOW POINT) GAGE VSD VARIABLE SPEED DRIVE ANOD ANODIZED CM CENTIMETER FT FOOT FEET LS LUMP SUM PT PAINT, PRESSURE TREATED VTR VENT THRU ROOF APPD APPROVED CMP - CORRUGATED METAL PIPE FTG FOOTING LVL LAMINATED VENEER LUMBER, LEVEL PTD PAINTED APPROX APPROXIMATE CMU CONCRETE MASONRY UNIT FVNR FULL VOLTAGE LVR LOUVER _ PTN PARTITION APPV APPROVE _ CO CLEAR OPENING NON -REVERSING LWC LIGHTWEIGHT CONCRETE PTW PRESSURE TREATED WOOD W ARCH ARCHITECT, ARCHITECTURAL COL COLUMN FVR FULL VOLTAGE REVERSING LWIC LIGHTWEIGHT INSULATING CONCRETE PVC POINT OF VERTICAL ARR ARRANGEMENT CONIC CONCRETE CURVE, POLYVINYL CHLORIDE W WASTE, WATT, WEST, WIDE ASAP AS SOON AS POSSIBLE CONF CONFERENCE ASSY ASSEMBLY CONN CONNECTION, CONNECTOR W/ WITH ASTM _ AMERICAN SOCIETY OF TESTING CONSTR CONSTRUCTION G M Q W/0 WITHOUT AND MATERIALS -CONT CONTINUE, CONTINUATION, WB WET BULB, WOOD BASE AUTO AUTOMATIC CONTINUOUS G GIRDER, GROUND, GROUND MAINT- MAINTENANCE QA QUALITY ASSURANCE WBL WC WOOD BLOCKING WATER CLOSET AUX AUXILIARY COORD COORDINATE WIRE NATURAL GAS MAS MASONRY - QC QUALITY CONTROL AVG AVERAGE CORP CORPORATE, CORPORATION GA GAUGE OR GAGE MATL MATERIAL QT QUARRY TILE, QUART WD WOOD AWG AMERICAN WIRE GAGE CORR CORRIDOR, CORRUGATED GAB GRADED AGGREGATE BASE MAX MAXIMUM QTY QUANTITY WF WIDE FLANGE AWS AMERICAN WELDING SOCIETY CPT_ CARPET GALV GALVANIZED MBTUH BRITISH THERMAL WG WH WATER GAUGE, WIRE GUARD WATER HEATER AZ AZIMUTH CRS CS COLD ROLLED STEEL CARBON STEEL GB GRAB BAR _THOUSAND UNITS PER HOUR _ R_ WHM .WATT HOUR METER CSK COUNTERSINK GC GENERAL CONTRACTOR MC MECHANICAL CONTRACTOR WL WIND LOAD B CSMT CASEMENT GF GROUND FACE MOMENT CONNECTION R RADIUS RISER WO WALL OPENING, — CTB CERAMIC TILE BASE GFCI/GFI GROUND FAULT CIRCUIT MCB MAIN CIRCUIT BREAKER RIC RETURN AIR WHERE OCCURS, WORK ORDER BB - / BACK TO BACK CTF CERAMIC TILE FLOOR INTERRUPTION MCC MOTOR CONTROL CENTER MECHANICAL RC REINFORCED CONCRETE WP WORK POINT BC BOLT CIRCLE CTJ CONTRACTION JOINT GL GIRT LINE, GLASS, MECH RD ROOF DRAIN WSCT WAINSCOT BD BOARD CTR CENTER GROUND LEVEL MED MEDIUM RE: REFER TO � WINDOW UNIT BFILL BACK FILL CTW CERAMIC TILE WAINSCOT GND GROUND MEMB MEMBRANE RECPT RECEPTACLE WWR WELDED WIRE REINFORCING BITUM BITUMINOUS CTWALK CATWALK _ GOVT GPH GOVERNMENT GALLONS PER HOUR MEZZ MFD MEZZANINE MANUFACTURED REINF REINFORCING BK BACK CU COPPER GPM GALLONS PER MINUTE MFR MANUFACTURER REM REMOVABLE BL BASE LINE, BUILDING LINE CU . IN CUBIC INCH GPS GALLONS PER SECOND MH MANHOLE REVD. REQUIRED X BLDG BUILDING CU FT CU M CUBIC FEET CUBIC METER GR GRADE MI MALLEABLE IRON, MILE REV REVISION X — BY (BETWEEN DIMENSIONS) BLK BLKG BLOCK BLOCKING CU MM -CUBIC _MILLIMETER GR BM .GRADE BEAM MIL ONE THOUSANDTH INCH RFG - RH ROOFING RIGHT HAND XBRA CROSS BRACING BM BEAM, BENCH MARK CUB CUBICLE GRTG GT GRATING GIRDER TRUSS GROUT MIN MISC MINIMUM MISCELLANEOUS RM ROOM XMFR TRANSFORMER BOC BOTTOM OF CURB CU YD CYL CUBIC YARD CYLINDER GWB GYPSUM WALLBOARD MLDG MOLDING, MOULDING RO ROUGH OPENING XS XXS EXTRA STRING DOUBLE EXTRA STRONG BOD BOTTOM OF DUCT GWR GLYCOL WATER RETURN MLO MAIN LUGS ONLY RPM REVOLUTIONS PER MINUTE BOF BOTTOM OF FOOTINGRT GWS GLYCOL WATER SUPPLY MM MILLIMETER RIGHT BOP BOTTOM OF PIPERTU MO MASONRY OPENING ROOFTOP UNIT BOS BOTTOM OF STEEL D MR MOISTURE RESISTANT RWC RAINWATER CONDUCTOR Y BOT BOTTOM MTD MOUNTED — - BOW BP BOTTOM OF WALL BASE PLATE D DEEP, DEPTH, PENNY(NAIL) H MTL METAL YD YARD BRCG BRACING DB DRY BULB MV MERCURY VAPOR BRIG BEARING DBL DOUBLE H HIGH N_ 7 Z BRG PL BEARING PLATE DC DIRECT CURRENT HC HOLLOW CORE S SOUTH BRK BRICK DDC DEG DIRECT DIGITAL CONTROL DEGREE HCA HEADED CONCRETE ANCHOR N NORTH (S) SLOPES ZD ZONE DAMPER BRKT BS BRACKET BOTH SIDES DEMO DEMOLISH. DEMOLITION HDR HDW HEADER HARDWARE NA NAAMM NOT APPLICABLE NATIONAL ASSOCIATION OF SC SOLID CORE BSMT BASEMENT DET DF ::DETAIL DRINKING FOUNTAIN H HARDWOOD ARCHITECTURAL METAL MFR. SCHED SECT SCHEDULE SECTION BTU BRITISH THERMAL UNIT DFT DRY FILM THICKNESS HEEXX HEXAGONAL NATL NATIONAL SENS SENSIBLE BTUH BRITISH THERMAL UNIT PER DH DOUBLE HUNG HEX HD HEXAGONAL HEAD NC NORMALLY CLOSED SHN SHOWN HOUR DIA DIAMETER HG HOT GAS, HEAT GAIN, NEC NATIONAL ELECTRICAL SHT SHEET BTWN BVL BETWEEN BEVELED DIAG ' DIAGONAL, DIAGRAM HGR MERCURY HANGER NEMA CODE, NECESSARY R TRICAL- NATIONAL ELECTRICAL SHT MTL SHEET METAL BW BOTH WAYS DIFF DIFFERENCE HK HOOK MANUFACTURERS ASSOCIATION SHTHG SHEATHING DIM DL DIMENSION DEAD LOAD - HM HOLLOW METAL NESC NATIONAL ELEC SAFETY CODE SIM SJI SIMILAR STEEL JOIST INSTITUTE DMPR DAMPER HORIZ HORIZONTAL NF NEAR FACE SLBB SHORT LEG BACK TO DN DOWN HP HORSE POWER NIC NOT IN CONTRACT BACK DOM DOMESTIC HPS HIGH PRESSURE SODIUM NO NUMBER SP SPACE (D) (S) DP DEW POINT HPT HS HIGH POINT HIGH STRENGTH NOM NPT NOMINAL NATIONAL TAPER PIPE (THREAD) SPEC SPECIFICATION DR DOOR HSB HIGH STRENGTH BOLT NS NEAR SIDE SPF SPRUCE -PINE -FIR DS DISCONNECT SWITCH, HSS HOLLOW STRUCTURAL SHAPE NTS NOT TO SCALE SQ SQUARE DOWNSPOUT HT HEIGHTO SQ FT SQUARE FOOT DWG DRAWING HVAC HEATING, VENTILATION AND SQ IN SQUARE INCH AIR CONDITIONING SQ MI SQUARE MILE HVY HEAVY OA OUTSIDE AIR SS SANITARY SEWER HW HOT WATER OC ON CENTER - SST STD STAINLESS STEEL STANDARD HWR HOT WATER RETURN OD OUTSIDE DIAMETER STI STEEL E EAST HWS HOT WATER SUPPLY. OF OUTSIDE FACE STIR STIFFENER EA EACH HWY HIGHWAYOFM OUTSIDE FACE OF MASONRY STiR STIRRUP EAT ENTERING AIR TEMPERATURE HZ HERTZ OPH OPPOSITE HAND STOR STORAGE EC ELECTRICAL CONTRACTOR OPNG OPENING STRUCT STRUCTURAL EER ENERGY EFFICIENCY RATIO OPP OPPOSITE SQ YD SQUARE YARD EF EACH FACE OR OUTSIDE RADIUS SYMM SYMMETRICAL EFF EFFICIENCY _ OSB ORIENTED STRAND BOARD EJ EXPANSION JOINT IBC INTERNATIONAL BUILDING OSHA OCCUPATIONAL SAFETY AND EL EACH LAYER, ELEVATION CODE HEALTH ADMINISTRATION T ELEC ELECTRIC/ELECTRICAL IBO INSTALLED BY OTHERS OVHD OVERHEAD — ELEV ELEVATOR ID INSIDE DIAMETER OWJ OPEN -WEB JOIST EMB EMBANKMENT IE THAT IS OZ OUNCE T T&B TREAD TOP AND BOTTOM EMBED EMBEDMENT IF IJ INSIDE FACE ISOLATION JOINT T&G TONGUE AND GROOVE EMER EMERGENCY IN INCH TB TOWEL BAR EMT ELECTRICAL METALLIC TUBING INC INCORPORATED, INCREASE TC TERRA COTTA, TOP CHORD ENCL ENCLOSURE INCL INCLUDE TEMP TEMPORARY EOD EDGE OF DECK INFO INFORMATION THD THREAD . EOS EQ _ EDGE OF SLAB EQUAL INSUL INSULATE/INSULATION THK THICKNESS EQL SP EQUALLY SPACED INTMD INTERMEDIATE THRES THRU THRESHOLD THROUGH EQUIP EQUIPMENT' INT INTERIOR TO TOP OF ERV -ENERGY RECOVERY IPS IRON PIPE SIZE TOC TOP OF CONCRETE VENTILATOR IR INSIDE RADIUS TOF TOP OF FOOTING ES EACH SIDE, -EDGE OF TOG - TOP OF GRATING SHOULDER, ELECTROSTATIC TOJ TOP OF JOIST ESP EXTERNAL STATIC PRESSURE � TOS. TOP OF STEEL EVAP EVAPORATOR TRS TRUSS EW EWC EACH WAY ELECTRIC WATER COOLER J -BOX JUNCTION BOX TRTD TREATED EXC EXCAVATE JAN CLO JANITOR'S CLOSET TS TOW TUBE STEEL' TOP OF DUCT EXP EXPANSION JST JOIST TOW TOP OF WALL EX EXISTING JT JOINT TV TELEVISION _ EXT EXTERNAL, EXTERIOR TYP TYPICAL EXT GR EXTERIOR GRADE SYMBOLS DRAWING NUMBER 0 A0.0 - SHEET NUMBER 0 0 0 0 FIRST FLOOR ` A0.0 0.0 A0.0 D Ao.O B 100.00 `— C DETAIL BUILDING SECTION EXTERIOR INTERIOR FLOOR MARKER SECTION MARKER ELEVATION ELEVATION ELEVATION MARKER MARKER MARKER TAG CORRIDOR 001 Di 1 A (A i 01 Q1 1� 000 0 DOOR WINDOW WALL COLUMN EXISTING KEY DEMO REVISION ROOM NAME TAG TAG TYPE TAG GRID TAG COLUMN NOTE KEY NOTE AND NUMBER GRID TAG NOTE HATCH PATTERNSJ WALL LEGEND ® ACOUSTIC TILE ® FINISH WOOD EXISTING TO REMAIN OR NEW LOW WALL ASSEMBLY ASPHALT GLASS NEW STUD WALL ASSEMBLY ® ROOFING F9 INSULATION GRANULAR NEW MASONRY WALL ASSEMBLY ® (LOOSE OR BATT) SUBBASE ® BRICK ® PLYWOOD - _ _ _ _ _ _ _ WALL / SOFFIT ABOVE CONCRETE RIGID (CAST -IN-PLACE ® INSULATION OR PRECAST) ®CONCRETE WOOD MASONRY EARTH OR ® STEEL FIRE RATINGS ILII BACKFILL CONCRETE El (FINISHED) � • � 1 -HOUR FIRE RATED ASSEMBLY I� ■ ■ I� 2 -HOUR FIRE RATED ASSEMBLY ■ ■ ■ I� 3 -HOUR FIRE RATED ASSEMBLY ■ ■ ■ ■ I� 4 -HOUR FIRE RATED ASSEMBLY NOTE: NOT ALL ABBREVIATIONS AND SYMBOLS MAY BE USED IN THIS PROJECT. THIS SHEET IS PROVIDED FOR GENERAL REFERENCE ONLY 90 303p,y Q I. 0921$$ �V RED AaG /201 It is a violation of the law for -any person, unless acting under the direction of a licensed Architect, Engineer or Land Surveyor, to alter an item in any way. Plans, mops, specifications, studies, and reports not containing a red ink seal imprint on the cover sheet accompanied by an original signature by the licensed professional may have been fraudulently altered and shall not be considered an original copy. Copyright Protected 2018, Larson Design Group. z 0 U-1 w 0 0 \ U W N a 0 0 z n 0 0 - c rn m O 0 L ca J n N T Cl) 0 LL 0 0 cZ=n CD U Ci W �LL (1) o MM M0 YQ w 04r 00 t Q' 3()0 �w 1 sU) W C 2 LL co L Q> LLr0 U WU J F- �3 ir O 3 W L vl�o U.��f1N0 co Q rn Z N E DEO�M 3 � L) LO Cj Cn i o o Z Lo cu = z Jo a r PROJECT NO. 11979-002 DRAWN BY EBG APPV'D BY RJG SYMBOLS & ABBREVIATIONS SHEET NO. G2.0 GENERAL NOTES DIVISION i GENERAL REQUIREMENTS/GENERAL CONDITIONS (CONT) DIVISION V METALS DIVISION VIII DOORS + WINDOWS (CONT.) DIVISION IX FINISHES (CONT.) N o 0 B. ACCESS DOORS: F. VINYL COMPOSITION TiLE: 1. VISIT THE SITE AND VERIFY ALL EXISTING CONDITIONS. BRING ANY DEVIATIONS TO THE ATTENTION OF THE TENANT'S PROJECT MANAGER. I. GUARANTEE: 1. A WRITTEN GUARANTEE SHALL BE PROVIDED ON ALL LABOR AND MATERIALS FOR A A. METAL STUDS 1, 20 GA. MINIMUM AT NON -SALES WALLS, AT STOREFRONT OR WALLS WITH DECKS ABOVE. " 1. PROVIDE FLUSH TYPE METAL DOORS MIN 16 X 20". OR AS SPECIFIED ON THE 1. REFER TO RESPONSIBILITY SCHEDULE AND FINISH SCHEDULE 2• ALL EDGE CONDITIONS AT TRANSITIONS TO BE FLOATED UP FOR SMOOTH EVEN 0 0 PERIOD OF NO LESS THAN ONE YEAR FROM THE DATE OF THE SUBSTANTIAL COMPLETION " 2. 25 GA. MINIMUM, AT 16 O.C. MAXIMUM, AT TYPICAL PARTITIONS UNLESS OTHERWISE DRAWINGS, MANUFACTURED FORM # 16 GA. STEEL, COMPLETE WITH FLUSH FLANGE TYPE TRANSITION. AL . DIMENSIONS SHOWN SHALL BE CONSIDERED APPROXIMATE. CONTRACTOR SHALL FIELD 2. L OF THE PROJECT. NOTED. FRAMES MANUFACTURED FROM # 16 GA. STEEL, WITH ANCHORS. 2. INSTALL ACCESS DOORS WHERE NECESSARY TO PROVIDE ACCESS CONCEALED 3. ALL SUBFLOORS TO BE MOISTURE TESTED AND RESULTS COMPARED TO VERIFY ALL DIMENSIONS PRIOR TO COMMENCING THE WORK. FAILURE TO DO SO SHALL PLACE 2: THE TENANTS REPRESENTATIVES SIGNATURE AND DATE OF ACCEPTANCE IS REQUIRED 3. CONTRACTOR SHALL PROVIDE ALL FASTENERS, SCREWS, BOLTS, CUPS, ANCHORS, AND AS APPROVED BY VALVES, AND OTHER EQUIPMENT REQUIRING SERVICE OR INSPECTION A MANUFACTURERS RECOMMENDED INSTALLATION GUIDELINES. ANY PROBLEMS DUE TO FULL RESPONSIBILITY FOR ANY ERRORS UPON THE CONTRACTOR. IN ORDER TO ACTIVATE THIS GUARANTEE. THIS GUARANTEE SHALL COVER ALL OF THE ANGLES, BRIDGES, BRACKETS, SLEEVES, ETC. AS REQUIRED. a MOISTURE TESTING TO BE REPORTED TO TENANT'S REPRESENTATIVE IMMEDIATELY. .GENERAL AND SUBCONTRACTOR'S WORK. ALL DEFECTS DISCOVERED DURING THIS _ THE TENANT'S PROJECT MANAGER. 3. ACCESS DOORS SHALL BE SUITABLE FOR INSTALLATION IN THE SPECIFIED WALL AND 4. 1/8" X 12" X 12" VINYL RESIDENT TILES WITH 4" HIGH X 1/8" THICK, TOP -SET, 3. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL SETBACKS, AND/OR GUARANTEE PERIOD SHALL BE REPAIRED TO THE OWNER AND/OR TENANT'S SATISFACTION B. METAL STANDARDS CEILING MATERIALS. STRAIGHT VINYL BASE (PRE FORMED CORNERS ARE REQUIRED). SEE FINISH SCHEDULE. EASEMENTS, EXISTING UTILITIES, AND ANY UNDERGROUND OR SURFACE STRUCTURE OR AT CONTRACTOR'S EXPENSE AT NO COST TO THE OWNER AND/OR TENANT. 1. FURNISH AND INSTALL PER PLANS AND MANUFACTURER'S RECOMMENDATIONS. 4. ACCESS DOORS LOCATED IN FIRE -RATED WALLS, FLOORS, CEILING -FLOOR OR 5. FILL ALL CRACKS, JOINTS, ETC., IN SUB -FLOOR WITH CRACK FILLER APPROVED BY CONDITIONS PRIOR TO COMMENCING THE WORK. CEILING -ROOF ASSEMBLIES SHALL BE UL FIRE RATED LISTED AND LABELED. FLOORING6. A J. SUPERVISION: C. STRUCTURAL STEEL, AND/OR HEAVY GAUGE METAL FRAMING 5. FINISH TO MATCH ADJACENT SURFACES. INSTALL RRIALS WITH WEATHERPROOF TYPE ADHESIVES AS RECOMMENDED BY 4. UPON COMPLETION OF THE WORK, PROVIDE A WALL FRAME WITH CLEAR PLEXI FACE OVER 1. PROVIDE A FULL TiME, QUALIFIED SUPERVISOR ON THE JOB SITE. ANY WORK 1. INSTALL FRAMING, CONNECTION PLATES, SCREWS, BOLTS, ETC. AS SHOWN IN PLANS AND 6. PROVIDE KEYED LOCK AT ALL PANELS IN COMMON AREAS. FLOORING MANUFACTURER FOR MATERIALS AND SURFACE INVOLVED. THE MANAGER'S DESK CONTAINING THE CERTIFICATE OF OCCUPANCY._ REQUIRED TO BE COMPLETED DURING NON -BUSINESS HOURS SHALL BE INCLUDED IN THE DETAILS.. Z r, '? BID. D. PROTECTIVE CORNER GUARDS C. STOREFRONT: G. FIBERGLASS REINFORCED PANELS 1/8": 5. SECURE AND PAY FOR ALL PERMITS AND LICENSES NECESSARY FOR THE EXECUTION OF 2. PROVIDE A JOB SITE TELEPHONE AND FAX MACHINE DURING THE CONSTRUCTION 1. PROVIDE AND INSTALL METAL CORNER GUARDS (2"x2"x42") AT ALL OUTSIDE CORNERS OR 1, FURNISH ALL NECESSARY MATERIALS, LABOR AND EQUIPMENT FOR THE COMPLETE 1. REFER TO RESPONSIBILITY SCHEDULE AND FINISH SCHEDULE. THE WORK. PERIOD. NOTIFY TENANT'S REPRESENTATIVE IMMEDIATELY OF TELEPHONE AND FAX AS SPECIFIED IN THE PLANS; SPACKLE AND SAND SMOOTH. INSTALLATION OF FRAMING AS SHOWN ON THE DRAWINGS AND SPECIFIED HEREIN. 2. PROVIDE AND INSTALL FIBERGLASS REINFORCED PANELS ON SURFACES AS SHOWN ON NUMBERS. 2. ALL GLASS FRAMING SHALL BE SET IN CORRECT LOCATIONS AS SHOWN IN THE PLANS. 6. SEE RESPONSIBILITY SCHEDULE TO CLARIFY RESPONSIBILITIES FOR SPECIFIED WORK. 3. COORDINATE AND SCHEDULE ALL NON -BUSINESS HOUR WORK WITH BUILDING E. REVEALS DETAILS AND SHALL BE LEVEL, SQUARE, PLUMB, AND IN ALIGNMENT WITH OTHER WORK 3. INSTALL PER MANUFACTURER'S INSTRUCTIONS. MANAGER. 1. INSTALL METAL REVEALS; SIZE AND LENGTH AS INDICATED ON PLANS. PROVIDE BLOCKING OR BACKING AS REQUIRED TO SECURE IN PLACE. IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND APPROVED SHOP DRAWINGS. H. WALK -OFF MAT: T.B.D. (ROLL -UP TYPE) SPECIFICATIONS K. UTILITIES: 1. PROVIDE ALL TEMPORARY UTILITIES (INCLUDING, BUT NOT LIMITED TO, WATER, 2. PAINT OR FINISH PER PLANS. 3. PROTECT STOREFRONT FROM DAMAGE BEFORE, DURING, AND AFTER INSTALLATION. DIVISION I GENERAL REQUIREMENTS/GENERAL CONDITIONS SEWERAGE, ELECTRICAL POWER, FUEL AND TELEPHONES) AND THE COSTS ASSOCIATED WITH THESE. PROVIDE TENANT'S REPRESENTATIVE WITH ALL UTILITY COMPANY NAMES, F. EXPANSION JOINTS 1. INSTALL PER PLANS AND MANUFACTURER'S RECOMMENDATIONS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR A COMPLETE AND OPERATIONAL TENANT SPACE INCLUDING, BUT NOT LIMITED TO ALL FINISHES, MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE NUMBERS, CONTACTS AND ACCOUNT NUMBERS (TENANT WILL TRANSFER ACCOUNTS TO 2• USG 093 FOR CEILINGS AND WALLS, AS MAY BE INDICATED IN THE DRAWINGS. DIVISION IX FINISHES DIVISION X SPECIALTIES PROTECTION. THEIR NAME AT TURNOVER).AL 3. 100 OR 200 SERIES AS REQUIRED FOR APPLICATION (OPTIONAL 1" DEPTH) WITH ELASTOMERIC FILLER TO MATCH FINISH AS MANUFACTURED BY CONSPEC SYSTEMS INC., A. GYPSUM DRYWALL A. LAVATORY FIXTURES: A. COORDINATION: L TRASH REMOVAL- 877-CONSPEC. 1. INSTALL ALL GYPSUM DRYWALL SYSTEMS COMPLETE WITH PARTITION FRAMING, CEILING 1. REFER TO MECHANICAL DRAWINGS. 1. OBTAIN A COPY OF THE TENANT CONTRACTOR GUIDELINES HANDBOOK AND COMPLY WITH 1. PROVIDE FOR DAILY REMOVAL OF ALL TRASH, RUBBISH AND SURPLUS MATERIALS SUSPENSION SYSTEMS, AND RELATED ACCESSORIES, PARTS, MATERIALS, ETC. AS SHOWN ON _ THE REQUIREMENTS. NOTE IN PARTICULAR THE INSURANCE REQUIREMENTS, UTILITY LOCATIONS, RESULTING FROM CONSTRUCTION, FIXTURING, AND MERCHANDISING OF THE DEMISED G. SUSPENSION SYSTEM DRAWINGS AND AS SPECIFIED. INSTALL ALL MATERIALS PER MANUFACTURER'S B. LAVATORY ACCESSORIES: CONSTRUCTION PROCEDURES, TEMPORARY BARRICADE WALLS, CONSTRUCTION MATERIAL PREMISES. 1. PROVIDE AND INSTALL UNISTRUT SPACE FRAME GRID SYSTEM PER MANUFACTURERS SPECIFICATIONS AND RECOMMENDATIONS. 1. REFER TO ARCHITECTURAL DRAWINGS. STORAGE, HAUL OFF AND PERMIT INFORMATION. SPECIFICATIONS AS REQUIRED FOR LIGHTING, CEILING ACCESSORIES OR MECHANICAL 2, GYPSUM DRYWALL- U.S. GYPSUM 5/8" THICK FIRE CODE SHEETROCK (TYPE -X") PANELS 2. INSTALL IN -WALL BLOCKING AS REQUIRED TO PROVIDE ADEQUATE SUPPORT. 2. COORDINATE WORK WITH WORK OF OTHER TRADES, THE LANDLORD'S FORCES, OTHER M. CLEAN UP AT TURNOVER: SYSTEMS SUSPENSION. OF STANDARD QUALITY OR EQUAL 3. INSTALL ACCESSORIES OVER FINISHED WALL SURFACE. TENANT CONTRACTORS, AND TENANT STORE OPERATIONS IN ORDER TO AVOID CONFLICTS AND 1. PROVIDE A PROFESSIONAL CLEANING SERVICE FOR ALL AREAS OF THE STORE AT THE 2. SUPPORT FROM STRUCTURE WITH THREADED RODS AND NUTS AS REQUIRED. OR DETAILED. 3. FASTENERS: DRYWALL SCREWS OF PROPER SIZE AND TYPE. EXPEDITE THE COMPLETION OF THE PROJECT. COMPLETION OF THE PROJECT AND BEFORE TURNING THE PROJECT OVER TO THE 3. CONTACT UNISTRUT CORPORATION 800-468-9510. 4. ACCESSORIES AND TRIM: U.S. GYPSUM BOARD OR GOLD BOND SYSTEM OF COMPONENTS C. SIGNS/SIGNAGE: 3. FURNISH LABOR, MATERIALS, EQUIPMENT AND APPLIANCES NECESSARY TO COMPLETE THE TENANT. WORK TO INCLUDE, BUT NOT BE LIMITED TO ALL CEILING SURFACES, FLOOR AND PERFORATED TAPE. ALL METAL TRIM SHALL BE PERFORATED FLANGE TYPE FOR 1. REFER TO ELECTRICAL PLANS. . INSTALLATION OF ALL ITEMS FURNISHED BY OTHERS. AND WALL SURFACES, BOTH INTERIOR AND EXTERIOR. THE STORE IS TO BE CLEAN AND COMPOUND FINISH. 2. ALL TEMPORARY SIGNS AND BANNERS ARE PROVIDED BY OTHERS. INSTALL ALL . READY FOR MERCHANDISING. 5. PROVIDE A LEVEL 4 FINISH PRIOR TO THE APPLICATION OF THE FINAL FINISHES. REFER TEMPORARY SIGNS AND BANNERS PER OWNER'S DIRECTION. DIVISION VI WOOD +PLASTICS B. PROTECTION: 2. STOREFRONT IS TO BE CLEAN OF ALL DUST, GLUE, GROUT, AND MISAPPLIED PAINT. TO THE GYPSUM ASSOCIATION GUIDELINES FOR A DESCRIPTION OF THE DESIRED LEVEL 3. STOREFRONT SIGN PROVIDED BY OTHERS. 1. ERECT A TEMPORARY BARRICADE AT THE STOREFRONT ONLY IF REQUIRED BY THE 3. HVAC FILTERS TO BE CHANGED FOLLOWING THE CLEANING. - 4. COORDINATE INSTALLATION WITH TENANT`S VENDOR. GUIDELINES.. A. CARPENTRY & BLOCKING: B. CEILING SYSTEMS DIVISION XI EQUIPMENT 2. PROTECT THE PROPERTY OF ADJACENT TENANTS, COMMON AREAS, AND NEUTRAL PIERS AT N. INSURANCE: 1. BEFORE USING WOOD FRAMING OR BLOCKING OF ANY TYPE, CONFIRM CODE -1. FURNISH AND INSTALL CEILING SYSTEMS COMPLETE WITH SUSPENSION SYSTEM AND ALL TiMES. ANY DAMAGE THAT OCCURS AS A RESULT OF DEMOLITION 1. SECURE, PAY FOR AND MAINTAIN, DURING CONSTRUCTION, ALL OF THE INSURANCE RESTRICTIONS. IF USE OF WOOD IS PERMITTED BY REQUIREMENTS, ADHERE TO THE RELATED ACCESSORIES AS INDICATED ON DRAWINGS. A. RECEIVE AND INSTALL PER MANUFACTURER'S INSTRUCTION ALL EQUIPMENT AND FIXTURES. (OR CONSTRUCTION) IS TO BE REPAIRED TO LIKE NEW CONDITION. - POLICIES REQUIRED. - WORK SHALL NOT COMMENCE UNTiL ALL REQUIRED INSURANCE HAS FOLLOWING GUIDELINES: 2. ALL LIGHT GAUGE METAL FRAMING AND CEILING SUSPENSION COMPONENTS FOR SOFFITS, BEEN OBTAINED AND CERTIFICATES OF SUCH INSURANCE HAVE BEEN DELIVERED. a. USE NEW LUMBER BEARING GRADE AND TRADEMARK OF ASSOCIATION UNDER WHICH IT GYPSUM BOARD AND LAY -IN CEILINGS SHALL BE ANCHORED TO THE STRUCTURAL JOISTS C. CONTRACT CONSIDERATIONS: LANDLORD MUST BE NAMED AS "ADDITIONAL INSURED". CERTIFICATE OF INSURANCE WAS PRODUCED. b. LAYOUT, CUT, FIT AND ERECT FRAMING FOR ROUGH AND FINISHED WORK. INSTALL AND BEAMS ONLY. PROVIDE AND INSTALL ANY ADDITIONAL FRAMING REQUIRED. B. AUDIO SYSTEM 1. SCHEDULE OF VALUES SHALL COVER WORK PERFORMED BY CONTRACTOR, EACH SUBCONTRACTOR AND ALL BLOCKING, NAILERS, FURRING AND OTHER -ROUGH AND FINISHED MATERIALS AS REQUIRED. 3. SUSPENSION SYSTEMS SHALL BE ADEQUATE TO SUPPORT LIGHTING FIXTURES, CEILING 1. REFER TO ELECTRICAL PLANS. a. SUBMIT A PRINTED SCHEDULE ON FORM INCLUDED WITH BID PROPOSAL MAJOR SUPPLIERS. BRACE, PLUMB, AND LEVEL MEMBERS IN TRUE ALIGNMENT AND RIGIDLY SECURE IN PLACE GRILLES, DIFFUSERS, AND OTHER TYPICAL CEILING ACCESSORIES. 4. PROVIDE SYSTEM COMPONENTS FROM SINGLE MANUFACTURER. 2 PROVIDED BY OTHERS. COORDINATE INSTALLATION WITH TENANTS VENDOR. b. INCLUDE A DIRECT PROPORTIONAL AMOUNT OF OVERHEAD AND PROFIT WITH EACH UNE ISM, 0. INDEMNIFICATION: WITH SUFFICIENT NAILS, SPIKES, SCREWS AND BOLTS AS NECESSARY. 5. INSTALL CEILING AND SUSPENSION SYSTEMS IN STRICT ACCORDANCE WITH c.. REVISE SCHEDULE TO LIST APPROVED CHANGE ORDERS, WITH EACH APPLICATION FOR 1. TO THE FULLEST EXTENT PERMITTED BY LAW, INDEMNIFY AND HOLD HARMLESS THE c. FURNISH AND INSTALL ROUGH AND FINISHED PLYWOOD, FURRING SUPPORTS, ETC. d. FURNISH AND INSTALL ALL ROUGH HARDWARE, ANCHORS, BOLTS, ETC. AS REQUIRED FOR MANUFACTURER'S RECOMMENDATIONS AND ALL APPLICABLE BUILDING CODE REQUIREMENTS. DIVISION )(11 FURNISHINGS PAYMENT. LANDLORD, TENANT, AND ARCHITECT AND THEIR AGENTS AND EMPLOYEES FROM AND FINISHED CEILING SHALL BE LEVEL, WITH JOINTS SNUG AND SQUARE, AND IN PERFECT 2. PAYMENT AND WAIVER OF LIENS: AGAINST ALL CLAIMS, DAMAGES, LOSSES AND EXPENSES, INCLUDING BUT NOT LIMITED TO, ATTORNEY'S FEES ARISING OUT OF OR RESULTING FROM THE PERFORMANCE OF THE CARPENTRY WORK. e. ALL EXISTING OR NEW WOOD SHALL BE FIRE RETARDANT AND MUST BE IDENTIFIED WITH CONDITION. 6. MATERIALS AND FINISHES: A. REFER TO THE RESPONSIBILITY SCHEDULE. a. PAYMENT APPLICATION SUBMIT PER THE OWNER'S REPRESENTATIVE'S WORK, PROVIDED THAT ANY SUCH CLAIM, DAMAGE, LOSS OR EXPENSE IS ATTRIBUTABLE 'A UL LABEL CERTIFYING ,THIS CLASSIFICATION. a. REFER TO REFLECTED CEILING PLAN FOR SPECIFIED MATERIALS AND FINISHES. _FORMS: REQUIREMENTS. - TO BODILY INJURY, SICKNESS, DISEASE- OR DEATH, OR TO INJURY OR TO DESTRUCTION b. LEAVE ONE CASE OF CEILING TILES FOR LATER REPLACEMENT. B. RECEIVE, ASSEMBLE AND PLACE OFFICE AND NON -SALES EQUIPMENT AND FIXTURES. b. UTILIZE SCHEDULE OF VALUES FOR LISTING ITEMS IN APPLICATION FOR PAYMENT. OF TANGIBLE PROPERTY (OTHER THAN THE WORK ITSELF) INCLUDING THE LOSS OF USE B. MILLWORK: 1. RECEIVE AND INSTALL ALL OWNER PROVIDED FINISHED MILLWORK CABINETS PANELING REFER TO RESPONSIBILITY SCHEDULE. c. ALL PAYMENTS FOR THIS PROJECT ARE TO BE ALLOCATED FOR THIS PROJECT ONLY FOR PAYMENTS TO SUB -CONTRACTORS, MATERIAL SUPPLIERS, AND AGENTS AUTHORIZED BY RESULTING THEREFROM. DOORS AND FRAMES, ETC., AS SHOWN DRAWINGS OR AS DIRECTED. C. PAINTING AND FINISHING 1, PROVIDE A SATISFACTORY FINISH THROUGHOUT, UNLESS SPECIFICALLY STATED C. RECEIVE, ASSEMBLE AND PLACE/INSTALL ALL SALES AREA FIXTURES. SPECIFIC CONTRACTORS TO PERFORM WORK OR SUPPLY MATERIALS TO THIS PROJECT. SUBMIT P. BACKGROUND COMPUTER-AIDED CONTRACT DESIGN DOCUMENTS: 2. CUT, FIT, AND INSTALL ALL MILLWORK AND SET PLUM AND TRUE IN ACCORDANCE WITH ASSEMBLY/INSTALLATION DRAWINGS PROVIDED. OTHERWISE. PARTIAL WAIVERS OF LIENS INCLUDING SUBCONTRACTORS AND MATERIAL SUPPLIERS. 1. IN THE EVENT THAT THE GENERAL CONTRACTOR OR ANY SUBCONTRACTORS REQUIRE EVDRILL WHERE NECESSARY TO PREVENT 3. BACK CUT FLAT TRIM TO PR WARPING. 2. USE ONLY THE PAINT AND RELATED MATERIALS SPECIFIED. DIVISION XIII SPECIAL CONSTRUCTION d. SUBMIT A UPDATED CONSTRUCTION PROGRESS SCHEDULE. BACKGROUND DRAWINGS, COPIES OF THESE DRAWINGS MAY BE PROVIDED SUBJECT TO -ENT 3. COVER ALL SURFACES THOROUGHLY. IF THE NUMBER OF COATS SPECIFIED DOES NOT THE FOLLOWING CONDITIONS: "USE SPLITTING. 4. CONFIRM BLOCKING REQUIREMENTS WITH VENDORS PRIOR TO CLOSING UP ALL ACCOMPLISH THE INTENT. THEN APPLY ADDITIONAL COATS OF SPECIFIED MATERIAL TO GIVE SEE FINISH SCHEDULE. A. NO ANTICIPATED WORK UNDER THIS SECTION. CONFIRM WITH TENANT'S REPRESENTATIVE. 3. CHANGE PROCEDURES: a. A SEPARATE AGREEMENT TITLED OF COMPUTER-AIDED DESIGN DOCUMENTS" ASSEMBLIES. - SATISFACTORY COVERAGE. a. OWNER'S REPRESENTATIVE WILL ADVISE OF MINOR CHANGES IN .THE WORK NOT INVOLVING MUST BE SIGNED BY THE CONTRACTOR/SUBCONTRACTOR BEFORE THE TRANSFER OF THE - 4. PREPARE BY CLEANING ALL SURFACES FREE OF LOOSE DIRT AND DUST. PREPARE ALL AN ADJUSTMENT TO CONTRACT SUM/PRICE OR CONTRACT TIME. FILES. METAL SURFACES IN STRICT ACCORDANCE WITH MANUFACTURERS WRITTEN SPECIFICATIONS. - DIVISION XIV CONVEYING SYSTEMS b. MAINTAIN DETAILED RECORDS OF WORK DONE ON TiME AND MATERIAL BASIS TO b. CONTRACTOR MUST AGREE TO USE THE PROJECT FILES ONLY FOR THE LIMITED 5. PAINTED DRYWALL TO RECEIVE ONE COAT LATEX PRIMER AND TWO COATS OF SPECIFIED SUBSTANTIATE COSTS FOR CHANGES IN THE WORK. PURPOSE AS DESCRIBED IN THE AGREEMENT. PAINT. TINT PRIMER TO APPROXIMATE SHADE OF THE FINAL COAT TO PRODUCE AN EVEN RESULT IN THE FINISH COAT. DRY ALL COATS THOROUGHLY BEFORE APPLYING SUCCEEDING DIVISION VII THERMAL + MOISTURE PROTECTION c. CHANGE ORDER FORMS: SUBMIT PER THE .OWNER'S REPRESENTATIVE'S REQUIREMENTS. d. EXECUTION OF CHANGE ORDERS: OWNER'S REPRESENTATIVE WILL ISSUE CHANGE ORDERS c. CONTRACTOR MUST AGREE TO REIMBURSE WJCA INC. OR THE TENANT FOR THE USE OF THE DOCUMENTS PER THE AGREEMENT. CONTRACTOR MAY REIMBURSE WJCA INC. COATS. FOLLOW MANUFACTURER'S RECOMMENDATIONS FOR RE -COAT TIME. A. NO ANTICIPATED WORK UNDER THIS SECTION. CONFIRM WITH TENANT'S REPRESENTATIVE. FOR SIGNATURES OF PARTIES AS PROVIDED IN THE CONDITIONS OFTHECONTRACT. DIRECTLY OR MAY AGREE TO CREDIT TENANT AN AMOUNT AGREED UPON WITH ARCHITECT A. VAPOR BARRIER: - 1. PROVIDE AND INSTALL 10 MIL POLYETHYLENE BELOW ALL REQUIRED PATCH AREAS AT 6. PUTTY ALL NAIL HOLES, COUNTER SUNK SCREWS, BOLTS, CRACKS, ETC. BEFORE - e. SUBMIT A UPDATED CONSTRUCTION PROGRESS SCHEDULE. & TENANT`S REPRESENTATIVE. SLAB ON GRADE CONDITIONS AND 4 MIL. POLYETHYLENE AT WALLS THAT RECEIVE BATT APPLYING FINISH. 7, SAND ALL WOOD SURFACES SMOOTH AND EVEN BEFORE APPLYING FINISH. DIVISION XV MECHANICAL 4. ALTERNATIVES: Q. DAMAGED FREIGHT (TENANT FURNISHED MATERIALS): INSULATION. 8. BEFORE STARTING FINISH WORK, REMOVE HARDWARE, ACCESSORIES, PLATES, LIGHTING a. ACCEPTED ALTERNATIVES WILL BE IDENTIFIED IN OWNER -CONTRACTOR AGREEMENT. 1. OPEN BOXES/CARTONS WITH OBVIOUS DAMAGE B. ELASTOMERIC CRACK BRIDGING: FIXTURES AND SIMILAR ITEMS, OR PROVIDE AMPLE PROTECTION FOR SUCH ITEMS. 9. PAINT ALL REGISTERS, LOUVERS, GRILLES, EMERGENCY LIGHTS, SPEAKERS, TRIM LIGHTS, A. REFER TO MECHANICAL DRAWINGS FOR SPECIFICATIONS. b. ALTERNATES MUST BE SUBMITTED WITH BID PROPOSAL, AS SEPARATE ADD OR DEDUCT 2• INSPECT FREIGHT BEFORE SIGNING THE FREIGHT BILL, NOTE SPECIFICALLY THE ITEMS O 1. PROVIDE AND INSTALL ELASTOMERIC CRACK BRIDGING AS MANUFACTURED BY NATIONAL EXPOSED PIPING, ACCESS DOORS, VENTS, FIRE EXTINGUISHER CABINETS, EQUIPMENT ITEMS. BASE BID SHALL INCLUDE ALL ITEMS AND MANUFACTURERS AS ENUMERATED ON DAMAGED. APPLIED CONSTRUCTION PRODUCTS, INC. 800-633-4622 OR APPROVED EQUAL MOUNTING BOARDS, ETC. UNLESS FACTORY FINISHED. PAINT TO MATCH ADJACENT WORK DRAWINGS AND/OR SPECIFICATIONS. 3. AFTER THE DAMAGE IS NOTED ON THE FREIGHT BILL, HAVE CARRIERS DRIVER ALSO UNLESS OTHERWISE NOTED OR DIRECTED. DIVISION XVI ELECTRICAL c. COORDINATE RELATED WORK AND MODIFY SURROUNDING WORK AS REQUIRED. SIGN IN ORDER TO VERIFY THAT BOTH PARTIES AGREE TO THE EXTENT OF THE DAMAGE. C. BATT INSULATION: 10. MAKE FINISH WORK UNIFORM OR APPROVED FINISH, SMOOTH, FREE OF RUNS, SAGS, CLOSE OUT: 4. WHEN DAMAGE 1S DISCOVERED UPON UNPACKING THE FREIGHT, INSPECT ALL PACKING 1, PROVIDE AND INSTALL A MINIMUM OF R-13 FRICTION FIT (OR AS DICTATED BY CODE), AND DEFECTIVE BRUSHING AND CLOGGING. MAKE EDGES OF PAINT ADJOINING OTHER A. REFER TO ELECTRICAL DRAWINGS FOR SPECIFICATIONS. 5. - THE FINAL TEN PERCENT RETENTION ON THIS PROJECT MUST INCLUDE SIGNED AND FOR SIGNS OF DAMAGE OR ABUSE. THE FREIGHT BILL IS TO BE NOTED WITH THE FULL BATT INSULATION AS MANUFACTURED BY OWENS-CORNING FIBERGLASS OR EQUAL AT MATERIALS OR COLORS SHARP AND CLEAN WITHOUT OVERLAPPING. a. EXECUTED WAIVERS OF LIEN INDICATING 100% COMPLETION AND 100% PAYMENT IN FULL BY - SPECIFIED DAMAGE. 5. CONTACT THE TENANT'S REPRESENTATIVE WITHIN 48 HOURS OF TAKING RECEIPT OF ALL EXTERIOR WALLS AND WHERE INDICATED IN THE DRAWINGS. D. CARPET: ALL SUB -CONTRACTORS AND MATERIAL SUPPLIERS. MATERIALS TO INFORM THEM OF ANY LOSS. FAX ALL REQUIRED DOCUMENTATION TO D. WATERPROOF MEMBRANE: 1. REFER TO RESPONSIBILITY SCHEDULE AND FINISH SCHEDULE. b. PROVIDE A LIST OF ALL SUBCONTRACTORS, INCLUDING ADDRESS AND PHONE NUMBERS TENANT'S REPRESENTATIVE. 1. PROVIDE AND INSTALL A (M) 30 MIL. (MIN.) WATERPROOF MEMBRANE. 2. CARPET AND ADHESIVE SHOULD BE CONDITIONED ON SITE AT A TEMPERATURE OF NO STALLED IN A PICTURE FRAME ON BACK OF THE MANAGER'S OFFICE DOOR. INSTALLED 6. IF TENANT'S CONTRACTOR FAILS TO FOLLOW THIS PROCEDURE, TENANT'S CONTRACTOR 2. EXTEND A MINIMUM OF 6" UP VERTICAL SURFACES IN TOILET ROOMS OR AS REQUIRED. LESS THAN 60 DEGREES. ALL SUBFLOORS MUST BE SMOOTH AND LEVEL, FREE OF DIRT, c. OPERATION MANUALS, MAINTENANCE INSTRUCTIONS, ETC. SHALL BE RESPONSIBLE FOR ALL COSTS RELATED TO THE REPLACEMENT OF MISSING OR - WAX AND OLD ADHESIVES. A d. THE GENERAL CONTRACTOR SHALL PROVIDE INBUILT DRAWINGS TO THE OWNERS DAMAGED TENANT FURNISHED MATERIALS. E. FIRESTOPPING: 3. PROVIDE PREMIUM MULTi PURPOSE 1000 ADHESIVE TO ASSURE FULL WARRANTY REPRESENTATIVE THAT REFLECTS ALL CHANGES THE PROJECT DURING THE CORES OF 1. PROVIDE AND INSTALL UL TESTED FIRESTOPPING ASSEMBLIES AS ARE APPLICABLE FOR PROTECTION IN ALL DIRECT GLUE APPLICATIONS. USE A MINIMUM OF 1/8 X 1/8 X 1/8 CONSTRUCTION AT THE COMPLETION OF PROJECT. EACH CONDITION ENCOUNTERED. - IN THE ABSENCE OF TESTED ASSEMBLIES, PROVIDE INCH V NOTCHED TROWEL FOR APPLICATION. ONE GALLON WILL HANDLE 10-15 YARDS OF D. QUALITY OF WORK: FIRESTOPPING ASSEMBLIES AS RECOMMENDED BY THE FIRESTOPPING SYSTEM CARPET. A DRYING TiME OF 30-40 MINUTES IS CRITICAL BEFORE PLACING THE CARPET 1. ALL WORK SHALL BE PERFORMED IN A SAFE AND WORKMANLIKE MANNER IN ACCORDANCE MANUFACTURER'S STAFF ENGINEERS AND AS APPROVED BY AUTHORITIES HAVING INTO THE ADHESIVE. DIVISION II SITE CONSTRUCTION WITH ACCEPTED CONSTRUCTION STANDARDS AND O.S.H.A. REQUIREMENTS. ALL CONSTRUCTION JURISDICTION. 4. PROVIDE AND INSTALL TRANSITION STRIPS. TRANSITION STRIPS MUST BE NEW SHALL BE IN STRICT ACCORDANCE WITH THE PLANS UNLESS A VARIANCE IS APPROVED BY THE 2. PROVIDE FIRESTOPPING MATERIALS AND THICKNESS AS REQUIRED TO MAINTAIN THE FIRE MATERIALS AND MUST CONFORM TO ALL CODE REQUIREMENTS AND INDUSTRY QUALITY - TENANT AND ALL AUTHORITIES HAVING JURISDICTION. A. VERIFY EXISTING CONDITIONS AND LOCATIONS OF UTILITIES, ROOF DRAINS, HVAC RATINGS OF THE ASSEMBLIES INTO WHICH THE MATERIALS ARE INSTALLED. 3. STRICTLY MATCH UL TESTED ASSEMBLIES. STANDARDS. 5. COMPLETED INSTALLATION TO BE FREE OF STAINS OR SNAGS DUE TO CONSTRUCTION 2. ALL EQUIPMENT AND MATERIALS UNDER THE CONTRACT ARE TO BE NEW UNLESS OTHERWISE EQUIPMENT, ETC. PRIOR TO COMMENCING THE WORK. 4. INSTALL FIRESTOPPING WITHOUT GAPS AND VOIDS OF ANY KIND. WORK. SPECIFIED IN THE PLANS. 5. INSPECT FIRESTOPPING WORK AND REPAIR OR REPLACE WORK WHICH HAS BEEN E. CODE COMPLIANCE: B. DEMOLITION: 1. SCOPE OF WORK -THIS PORTION OF THE WORK INCLUDES ALL LABOR, MATERIALS DAMAGED, DISTURBED, OR REMOVED BEFORE FIRESTOPPING IS CONCEALED OR ENCLOSED. 1. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO MAKE CERTAIN THAT ALL WORK IS IN AND SERVICES NECESSARY FOR THE REASONABLY INCIDENTAL TO COMPLETE ALL 6. PROVIDE ANCHORAGE ACCESSORIES AND OTHER COMPONENTS AS NEEDED TO PROVIDE COMPLIANCE WITH ALL CODES, ORDINANCES, AND REGULATIONS OF ALL CONSTITUTED PUBLIC DISMANTLING, DEMOLITION, AND SALVAGE AS SHOWN AND NOTED ON THE DRAWINGS AND COMPLETE, EFFECTIVE FIRESTOPPING SYSTEMS COMPLYING WITH UL TESTED ASSEMBLIES. AUTHORITIES HAVING JURISDICTION. THIS INCLUDES BUT IS NOT LIMITED TO LOCAL BUILDING SPECIFIED HEREIN. IN GENERAL, THE ITEMS TO BE PERFORMED UNDER THIS SECTION F. FIRE CAULKING: - CODE REQUIREMENTS, FIRE DEPARTMENT REGULATIONS, UTILITY COMPANY REQUIREMENTS, SHALL INCLUDE, BUT ARE NOT LIMITED TO: REMOVAL OF ALL EXISTING ACOUSTICS AND 1. ALL SLEEVES, OPENINGS, ETC. THROUGH FIRE RATED WALLS AND FLOORS SHALL BE FIRE O.S.H.A., AND THE BEST TRADE PRACTICES. GYPSUM WALL BOARD, CEILING AND FRAMES, LIGHT FIXTURES, FLOORING, DOORS AND SEALED WITH CALCIUM SILICATE, SILICONE "RTY" FOAM, "3M" FIRE RATED SEALANTS OR E. RESILIENT SHEET FLOORING: WALLS, FURRED OUT COLUMN ENCLOSURES, AND STOREFRONT AND AS SPECIFIED ON THE EQUAL. 1. REFER TO RESPONSIBILITY SCHEDULE AND FINISH SCHEDULE F. DIMENSIONS: 1. UNLESS OTHERWISE NOTED, ALL DIMENSIONS ARE MEASURED FROM FINISHED FACE TO DRAWINGS. 2, DISCONNECTION OF SERVICES: 2. ALL EDGE CONDITIONS AT TRANSITIONS TO BE FLOATED UP FOR SMOOTH EVEN FINISHED FACE OF MATERIALS, FACE OF STOREFRONT, OR LEASE LINE. a. EXISTING SERVICES THAT WILL BE DISRUPTED BY CONSTRUCTION WORK SHALL BE G. ACOUSTICAL INSULATION: TRANSITION. 2. VERIFY ALL PROPOSED DIMENSIONS WITH FIELD CONDITIONS. ADVISE TENANT`S RE-ROUTED AS NECESSARY TO PROVIDE TEMPORARY CONTINUATION SERVICE. 1. PROVIDE AND INSTALL ASTM C665, UNFACED, 0.32 K -VALUE, WIDTHS TO COORDINATE 3. ALL SUBFLOORS TO BE MOISTURE TESTED AND RESULTS COMPARED TO REPRESENTATIVE OF ANY DISCREPANCY BETWEEN THE DRAWINGS AND ACTUAL JOB CONDITIONS b. DISCONNECTED SERVICES SHALL BE PLUGGED AND SEALED IN AN APPROVED MANNER WITH FRAMING FOR FRICTION FIL, THICKNESS SHOWN OR IF NOT SHOWN, FILL CAVITY. MANUFACTURERS RECOMMENDED INSTALLATION GUIDELINES. ANY PROBLEMS DUE TO BEFORE BEGINNING THE WORK. c. SPRINKLER SHUT DOWN SHALL BE COORDINATED WITH THE BUILDING PRIOR TO MOISTURE TESTING TO BE REPORTED TO TENANT'S REPRESENTATIVE IMMEDIATELY. 3. ALL ANGLES SHALL BE 90 OR 45 DEGREES UNLESS OTHERWISE NOTED IN THE EXECUTION OF WORK. 4. RESILIENT SHEET FLOORING WITH INTEGRAL 4" HIGH, RADIUSED COVE BASE. SEE FINISH CONSTRUCTION DOCUMENTS. 3. ABANDONED ELECTRICAL WIRING: SCHEDULE. a. CONDUITS AND OTHER UTILITIES ENCOUNTERED IN THE PROGRESS OF THE DEMOLITION 5. FILL ALL CRACKS, JOINTS, ETC., IN SUB -FLOOR WITH CRACK FILLER APPROVED BY G. SHOP DRAWINGS & SUBMITTALS: THAT ARE TO BE ABANDONED SHALL BE DISCONNECTED AND THE ENDS PLUGGED IN AN FLOORING MANUFACTURER, 1. SUBMIT THE NUMBER OF OPAQUE REPRODUCTIONS WHICH CONTRACTOR REQUIRES, PLUS APPROVED MANNER. ANY ABANDONED UTILITIES INTERFERING WITH WORK UNDER THIS 6. INSTALL ALL MATERIALS WITH WEATHERPROOF TYPE ADHESIVES AS RECOMMENDED BY TWO COPIES, TO TENANT`S REPRESENTATIVE FOR APPROVAL CONTRACT SHALL BE REMOVED ONLY TO THE EXTENT THAT THEY INTERFERE WITH NEW DIVISION VIII DOORS + WINDOWS FLOORING MANUFACTURER FOR MATERIALS AND SURFACE INVOLVED. 2. SUBMITTALS MUST BE SCHEDULED SO AS NOT -TO IMPEDE THE PROGRESS OF THE WORK. CONSTRUCTION. - 3. MARK EACH COPY TO IDENTIFY APPLICABLE PRODUCTS, MODELS, OPTIONS, AND OTHER A. DOORS AND HARDWARE: DATA. SUPPLEMENT MANUFACTURER'S STANDARD DATA TO PROVIDE INFORMATION SPECIFIC TO 1. FURNISH AND INSTALL ALL DOORS, FRAMES, HARDWARE AND RELATED PARTS AND DIVISION III CONCRETE THIS PROJECT. MATERIALS AS INDICATED ON DRAWINGS AND RESPONSIBILITY SCHEDULE. 4. INDICATE SPECIAL UTILITY AND ELECTRICAL CHARACTERISTICS, UTILITY CONNECTION 2. HOLLOW METAL FRAMES: K.D. MINIMUM 16 GA. SIZE, SHAPE AND PARTITION TYPE PER A. PATCHING (WHEN REQUIRED) REQUIREMENTS, AND LOCATION OF UTILITY OUTLETS FOR SERVICE FOR FUNCTIONAL EQUIPMENT DOOR SCHEDULE. AND APPLIANCES. 1. INSTALL MINIMUM 3000 PSI CONCRETE FILLER AND PATCHING WHERE EXISTING SLAB 1 3. LABELED DOORS: PROVIDE U.L. LABEL DOORS AND FRAMES PER APPLICABLE STATE 5. IDENTIFY VARIATIONS FROM -CONTRACT DOCUMENTS AND PRODUCT OR SYSTEM LIMITATIONS HAS BEEN REMOVED FOR UNDER SLAB CONDUITS, PLUMBING, ETC. AND LOCAL BUILDING CODES, WHERE REQUIRED. WHICH MAY AFFECT THE CONSTRUCTION PROGRESS. 4. FABRICATE AND ERECT TRUE, PLUMB, AND SQUARE AS SPECIFIED AND DETAILED AND 6. DIRECT ALL SUBMITTALS TO THE TENANT'S REPRESENTATIVE. B. CONCRETE SLAB AS PER MANUFACTURER'S RECOMMENDATIONS. '1. INSTALL MINIMUM 3000 PSI CONCRETE WITH 6" X 6" - W1.4 X W1.4 W.W.F. AT MID 5. AUTOMATIC SLIDING DOORS, ALUMINUM DOORS AND FRAMES WITH SIDELIGHTS, TRANSOM H SAMPLES: LEVEL OVER 6 MIL VAPOR BARRIER( AT SLAB ON GRADE CONDITIONS OR ADHERE TO AND AC11VE DOOR LEAVES, OVERHEAD OPERATOR AND EMERGENCY BREAKOUT PER APPLICABLE BUILDING CODES. 1. SUBMIT THREE COPIES OF SAMPLE TO TENANT'S REPRESENTATIVE FOR APPROVAL WHEN REQUIRED BY INDIVIDUAL SPECIFICATION SECTION. LOCAL CODE REQUIREMENTS). INSTALL CONTROL JOINTS AT MAXIMUM 200 SF. 6. SEE DOOR SCHEDULE FOR SPECIFIC INFORMATION AND HARDWARE. 2. INCLUDE IDENTIFICATION ON EACH SAMPLE WITH FULL PROJECT INFORMATION. DIVISION IV MASONRY OF F�0 3 gaPy c 000216• FRED A 20181 It is a violation of the law for any person, unless acting under the direction of a licensed Architect. Engineer or Land Surveyor, to alter an item in any way. Plans, maps, specifications, studies, and reports not containing a red ink seal imprint on the cover sheet accompanied by an original - signature by the licensed professional may have been fraudulently altered and shall not be considered an original copy. Copyright Protected 2018. Larson Design Group. PROJECT NO. 11979-002 DRAWN BY EBG APPV'D BY RJG SPECIFICATION/GENERAL NOTES V z N o 0 � S Z w o 0 0 0 U W y cj� a ON l4 p 0 LLrn PROJECT NO. 11979-002 DRAWN BY EBG APPV'D BY RJG SPECIFICATION/GENERAL NOTES F N o 0 a J LL o 0 14 (O U y cj� a ON l4 p 0 LLrn O a)c n ' Z a SP ) °' 00V' 004)_2 - - =3W0 OW ��' O�° ~ J ■ LL rn : > _j W Lt U ao o ir 0 W Lv�o" W C� ¢ re) U .a.N0) to rej Z r, '? E 0 3 �°°�'� No E Z Lo N0-= Jorma r PROJECT NO. 11979-002 DRAWN BY EBG APPV'D BY RJG SPECIFICATION/GENERAL NOTES K.3 DEMOLITION FLOOR PLAN NOTE= REFERENCE MD1.0, PD1.0 & ED1.0 FOR MECHANICAL, PLUMBING & ELECTRICAL DEMOLITION WORK. DEMOLITION GENERAL NOTES A. CONTRACTOR BID TO BE BASED IN EXISTING CONDITIONS, CONTRACTOR IS RESPONSIBLE TO VISIT THE SITE BEFORE BIDDING. B. LEVEL FLOORS TO MATCH EXISTING SPACES THROUGHOUT NO GREATER THAN 1/8" DEVIATION OVER 10'-0- C. ALL DEMOLITION WORK INVOLVING MECHANICAL, ELECTRICAL, OR PLUMBING WORK MUST COMPLY WITH ALL APPLICABLE CODES IN REGARD TO THESE ITEMS. D. CONTRACTOR IS TO PROTECT ALL EXISTING CONDITIONS THAT ARE TO REMAIN FROM DAMAGE DURING DEMOLITION PHASE OF WORK. ITEMS DAMAGED ARE TO BE REPAIRED BY THE CONTRACTOR AT HIS EXPENSE. E. CONTRACTOR IS TO VERIFY WITH THE LANDLORD WHICH ITEMS TO BE REMOVED WILL REMAIN THE PROPERTY OF THE LANDLORD, DISPOSE OF, OR STORE SUCH ITEMS AS DIRECTED. F. G.C. TO REMOVE EXISTING FLOOR FINISH AND ADHESIVES AS REQUIRED AND PREPARE EXISTING FLOOR AS REQUIRED TO RECEIVE NEW FLOOR FINISH. PATCH, FILL, LEVEL, AND GRIND CONCRETE SLAB AS REQUIRED TO PROVIDE A SMOOTH LEVEL SURFACE FOR APPLICATION OF NEW FINISHES. CONFIRM THAT ALL FLOORS THROUGHOUT ARE LEVEL, AT THE SAME ELEVATION FROM SPACE TO SPACE. G. PATCH AND REPAIR ALL CONCRETE SLAB DAMAGE. J. PATCH, REPAIR, AND PRIME COAT ALL EXISTING GWB TO REMAIN AND PREPARE FOR NEW FINISHES AS SCHEDULED. K. G.C. TO PATCH AND REPAIR ALL CONSTRUCTION AND FINISHES TO REMAIN. KEYED DEMOLITION NOTES (X 1. REMOVE EXISTING DOOR, HARDWARE & FRAME (SHOWN DASHED). 2. REMOVE EXISTING NON -LOAD BEARING WALL CONSTRUCTION (SHOWN DASHED). PATCH & REPAIR ADJACENT FINISHES TO REMAIN, INCLUDING WALLS, FLOORS, CEILINGS, AND ROOF AS REQUIRED. 3. EXISTING CEILING SYSTEM TO REMAIN. PATCH & REPAIR TO "LIKE NEW" CONDITION. 4. EXISTING FLOOR FINISH TO REMAIN. PATCH & REPAIR TO "LIKE NEW" CONDITION. 5. EXISTING COLUMN TO REMAIN. 6. SAWCUT/TRENCH FLOOR AS REQUIRED TO EXTEND NEW SANITARY LINE AS REQ'D. G.C. TO VERIFY EXACT LOCATION IN FIELD. REF: 2/D1.0. 7. G.C. TO DEMO EXISTING PLUMBING FIXTURE AS INDICATED AND PREPARE FOR RELOCATION. 8. G.C. TO DEMO PORTION OF EXISTING WALL/CONSTRUCTION AS SHOWN/REQUIRED TO ALLOW FOR NEW DOOR ROUGH OPENING. PATCH AND REPAIR ADJACENT WALLS AND FLOOR AS REQUIRED. 9. EXISTING MOP SINK AND WATER HEATER (ABOVE) TO REMAIN. 10. EXISTING ELECTRICAL PANEL (A) TO REMAIN. REF: ELECTRICAL DWGS 11. EXISTING ELECTRICAL PANEL (B) TO REMAIN. REF: ELECTRICAL DWGS 12. EXISTING TELE/DATA BOARD. 13. EXISTING 75KVA TRANSFORMER TO REMAIN. 14. EXISTING 45KVA TRANSFORMER TO REMAIN. 15. G.C. TO DEMO EXISTING PLUMBING ACCESSORIES AND PREPARE FOR NEW. 16. EXISTING WATER CLOSET TO REMAIN. G.C. TO PATCH & REPAIR TO "LIKE NEW" CONDITION. 17. EXISTING WALL FINISHES TO REMAIN. PATCH & REPAIR TO LIKE NEW CONDITION. It is a violation of the law for any person, unless acting under the direction of a licensed Architect, Engineer or Land Surveyor, to alter an item In any way. Plans, maps, specifications, studies, and reports not containing a red ink seal Imprint on the cover sheet accompanied by an original signature by the licensed professional may have been fraudulently altered and shall not be considered an original copy. Copyright Protected 2018, Larson Design Group. In z 0 N N S z w Ld0 0 U LTJ V) LLI I- a 0 0 z SYMBOL DESCRIPTION EXISTING REMAIN - EXISTING TO BE REMOVED _ C1 #40 ® 24" O.C. CONCRETE SLAB J LL a> in E 0 0 CHEMICAL ANCHOR EXISTING EQUAL TO HILT] HY-150 CONCRETE SLAB (n � � ri o All �_ 0 LL� . c N N v) pC d e S2 Z W z .� U) QW J t cn w c a LL L ' ..: W > v - 0v M BACKFILL AND TAMP FIRM TO REMOVE VOIDS SAND BASE FOR NEW PIPE -..I04 L ■ (9 SEE PLUMBING SHEET FOR AS " PER CODE 3 THICKNESS MIN. }- W c v ¢ 0 v_� ` a Vi .N PIPING 0 m n Z 0 r IK) POUR BACK DETAIL o E c� N W 2 EZLn SCALE: 3/4"=V-0» a 0 z rn -��3: a LL r SYMBOL DESCRIPTION EXISTING REMAIN EXISTING TO BE REMOVED APPV'D BY RJG DEMOLITION FLOOR PLAN O Of Wr-%.r'-'1 8 f- � �_01 17»36" 42" 9 36" \\\ a in W1 11 / w - - -�� - � w O �] - © 0 42 N 0� C3 EL 24 00 x �� cflw 00< � 0 Z g" � � � � `a� �� Wl -�" *\ � mo � � 0 N Bl N N ^ 61 ~ m B1 0 / B1 _% 17-7� L 17 B1 131-YL18" 15 PIPE PROTECTION KIT. MIN. SEE FIXTURE NOTES MEN'S MEN'S MEN'S 2 RR ELEVATION RR ELEVATION RR ELEVATION SCALE: 3/8"=1'-0" (105 OPPOSITE HAND) `3 SCALE: 3/8"=1'-0" (105 OPPOSITE HAND) 4 SCALE: 3/8"=1'-0" (105 OPPOSITE HAND) EX �EX01 4'_8w 6 EQ. EQ. 18" 1100 i " 4VERT 6 Iz r7 0 a 1 -9 EX \ o � 12 42" \ x N ¢ of 11 36» M 0 1 J 24" o M m ¢ / Y x 0D_ 00 x 6Ld / �� 0�m `-< MD_/ F-- O 0 N � EX PIPE PROTECTION KIT. a' SEE FIXTURE NOTES EX '—P1,' 3'-2" 10 10 \ 0 `W1�` 0 O m M o B1 B. 0. CLG ® T- 0 MEN'S RR ELEVATION 5SCALE: 3/8"=1'-0" (105 OPPOSITE HAND) EX. B.O. CLG T-0 EX 9 36" 42" s 7C"4 s 0 O) a - Z 8" 0 LO — EX CV r KEYED PLAN NOTES- xQ 1. INFILL EXISTING OPENING WITH LIKE MATERIALS, TO MATCH EXISTING SURROUNDING WALLS. 2. EXISTING DOOR TO REMAIN. PROTECT DURING DEMOLITION AND CONSTRUCTION. 3. EXISTING COLUMN TO REMAIN. 4. EXISTING MOP SINK AND HOT WATER ABOVE TO REMAIN. REF: P1.0. 5. ADA CLEAR FLOOR AREA (TYP.). 6. INSTALL NEW MIRROR. 7. INSTALL NEW TOILET ROOM SIGNAGE. 8. INSTALL NEW GRAB BARS. 9. INSTALL NEW TOILET PAPER DISPENSER. 10. INSTALL NEW BABY CHANGING STATION. 11. 12. INSTALL NEW UTILITY HOOKS. INSTALL NEW SOAP DISPENSER. MANUFACTURER / CATALOG NO. It is a violation of the law for any person, unless acting under " NEW WALL CONSTRUCTION the direction of a licensed 13. INSTALL NEW CHILD SEAT. Architect, Engineer or Land Surveyor, to alter an item in BRADLEY CORPORATION #250-15 OR EQUAL SOAP DISPENSER any way. Plans, maps. BABY CHANGING STATION KOALA CORPORATION #KB208-01, SURFACE MOUNTED, BABY CHANGING STATION & studies, spe14. IDENTIFYING DOOR PLAQUE. FINISH: GRAY INSTALL NEW PAPER TOWEL DISPENSER. ports nications, ini redInkreports not containing z M E IDENTIFYING DOOR PLAQUE. FINISH: GRAY seal imprint on the cover sheet BOBRICK #B-670, SURFACE MOUNTED, STAINLESS STEEL, BRIGHT POLISHED FINISH, o 0 U accompanied by an original UNDERSINK PIPE COVER TRUEBRO LAV. SHIELD #2018 -AS -L1 20"x18" signature by the licensed A. professional may have been B. ALL ADA CONFORMING, WHEELCHAIR ACCESSIBLE LAVATORY P -TRAPS AND ANGLE fraudulently altered and shall VALVE ASSEMBLIES TO BE COVERED WITH THE MOLDED, ANTIMICROBIAL TRUBRO, GENERAL NOTES not be considered an original copy. Copyright Protected 2018, C. ALL PLUMBING ACCESSORIES TO BE SUPPLIED & INSTALLED BY G.C. Larson Design Group. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING PLUMBING FIXTURES & EXISTING A. VERIFY INTERIOR AND EXTERIOR DIMENSIONS, NOTIFY ARCHITECT IMMEDIATELY WITH ACCESSORIES (INCLUDING LANDLORD INSTALLED PLUMBING FIXTURES & (1) :3 W� ACCESSORIES) COMPLY WITH PLANS & HANDICAPPED CODES AND LAWS. CONTRACTOR SHALL VERIFY COMPLIANCE TO FLOOR PLAN, ENLARGED PLANS & = () W C x 0 ELEVATIONS THIS SET. NOTIFY ARCHITECT WITH ANY DISCREPANCIES. J H0 LL LLo DISCREPANCIES. ao 03 2 2-y O 3 Cam O ■ 6 CL ('0 (V W C ¢�� B. REFER TO A2.0 FOR DOOR SCHEDULE AND FOR FINISH KEY. V .LM2dNOo 1`0ri E''ON p Z E D r, M J 3 c0Q-�o Loozin CC %_j J C. DIMENSIONS SHOWN ARE CLEAR DIMENSIONS GYP BD TO GYP BD. [ D. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALING ON THE CONSTRUCTION J DOCUMENTS. DO NOT SCALE. J E. UPON POSSESSION OF THE PREMISES, DIMENSIONS OF SPACE SHALL BE VERIFIED G C SHALL SUBMIT NOTED DISCREP CES TO ANI THE ARCHITECT/ENGINEER, TENANT PROJECT MANAGER, AND REQUIRED VENDORS WITHIN 3 DAYS OF THE START OF CONSTRUCTION. N z F. PATCH & FIRE STOP GYP. BD. PARTITIONS AS REQUIRED BY LOCAL CODES. 0 0 In G. APPROVED FIRE EXTINGUISHERS SHALL BE FURNISHED AND INSTALLED BY GC AS w w REQUIRED BY LOCAL AUTHORITY. U 0 o H. ALL SALES AREA WALLS TO BE FLUSH, LEVEL, AND SQUARE. w I. EXISTING CONDITIONS TO REMAIN TO BE PATCHED, REPAIRED, OR REPLACED TO BRING TO "LIKE NEW" CONDITIONS, VERIFY REUSE WITH LANDLORD MANAGER. J. REF: G1.2 FOR ALL ADA DETAIL MOUNTING HEIGHTS K. PROVIDE ALL NECESSARY BLOCKING FOR ALL WALL MOUNTED ITEMS. L. DOOR TRIM VENDOR SUPPLIED MOLDING. M. INSTALL NEW ADA COMFORMING WHEELCHAIR ACCESSIBLE LAVATORY P -TRAP AND Q ANGLE VALVE ASSEMBLIES. o _ 1z CL JOTE: LEGEND o LL RESTROOM PLUMBING FIXTURES/ACCESSORIES 0 D BE INSTALLED PER 2010 ADA STANDARDS. DOTE: ISULATE ALL EXPOSED HOT WATER AND DRAIN NES. SYMBOL DESCRIPTION MANUFACTURER / CATALOG NO. EXISTING PARTITION " NEW WALL CONSTRUCTION X WALL TYPE (SEE WALL TYPE SCHEDULE ON SHEET A2.0) XXX DOOR DESIGNATION (SEE DOOR SCHEDULE ON SHEET A2.1) RESTROOM ACCESSORIES SCHEDULE DESCRIPTION MANUFACTURER / CATALOG NO. GRAB BARS BRADLEY CORPORATION SERIES 812 - 1 1/2"0 STANDARD FINISH, OR EQUAL TOILET PAPER DISPENSER BRADLEY CORPORATION #5224 OR EQUAL MIRROR BRADLEY CORPORATION #781 - 18"W x 30" H PAPER TOWEL DISPENSER BRADLEY CORPORATION #250-15 OR EQUAL SOAP DISPENSER IMPERIAL BAG & PAPER CO. GOJO CHROME DISPENSER #1919-04 BABY CHANGING STATION KOALA CORPORATION #KB208-01, SURFACE MOUNTED, BABY CHANGING STATION & 0 IDENTIFYING DOOR PLAQUE. FINISH: GRAY CHILD PROTECTION SEAT KOALA CORPORATION #KB102, SURFACE MOUNTED, BABY CHANGING STATION & z M E IDENTIFYING DOOR PLAQUE. FINISH: GRAY UTILITY HOOK BOBRICK #B-670, SURFACE MOUNTED, STAINLESS STEEL, BRIGHT POLISHED FINISH, o 0 U 1/2"x2", FLANGE 2"x2" UNDERSINK PIPE COVER TRUEBRO LAV. SHIELD #2018 -AS -L1 20"x18" FIXTURE NOTES: A. REF: G1.2 FOR ALL ADA DETAIL MOUNTING HEIGHTS B. ALL ADA CONFORMING, WHEELCHAIR ACCESSIBLE LAVATORY P -TRAPS AND ANGLE VALVE ASSEMBLIES TO BE COVERED WITH THE MOLDED, ANTIMICROBIAL TRUBRO, o n o, Cq LU INC "LAV -GUARD" UNDERSINK PROTECTIVE PIPE COVER MODEL #103. C. ALL PLUMBING ACCESSORIES TO BE SUPPLIED & INSTALLED BY G.C. D. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING PLUMBING FIXTURES & EXISTING ACCESSORIES (INCLUDING LANDLORD INSTALLED PLUMBING FIXTURES & (1) :3 W� ACCESSORIES) COMPLY WITH PLANS & HANDICAPPED CODES AND LAWS. CONTRACTOR SHALL VERIFY COMPLIANCE TO FLOOR PLAN, ENLARGED PLANS & = () W C x 0 ELEVATIONS THIS SET. NOTIFY ARCHITECT WITH ANY DISCREPANCIES. PROJECT NO. 11979-002 DRAWN BY EBG IAPPV'D BY RJG FLOOR PLAN SHEET NO. A1.0 c 0 C a� 0 c 0 CU J N L Ci 0 J IL z M E o 0 U D ,CD^ L W CL 0 C I� O c � N � W z o n o, Cq LU Z +� 00.E (1) :3 W� o w = () W C x 0 J H0 LL LLo W0 ao 03 2 2-y O 3 Cam O ■ 6 CL ('0 (V W C ¢�� V .LM2dNOo 1`0ri E''ON p Z E D r, M 3 c0Q-�o Loozin CC %_j J o a LL PROJECT NO. 11979-002 DRAWN BY EBG IAPPV'D BY RJG FLOOR PLAN SHEET NO. A1.0 4 REFLECTED CEILING LEGEND SYMBOL DESCRIPTION o NEW 2X4 ACT CEILING a EXISTING 2X4 ACT CEILING DNEW 2X4 LED PANEL LIGHT 2 EXISTING 2X4 LIGHT 0'-0" FINISHED CEILING HEIGHT �—� NEW EMERGENCY SIGN 10 1 NEW SUPPLY DIFFUSERS. any way. Plans, maps, EXISTING SUPPLY DIFFUSERS. reports not containing a red ink NEW EXHAUST DIFFUSERS. Q EXISTING EXHAUST DIFFUSERS. Fr L±-] - I El �-j KEYED NOTES: ❑x -- 1.- EXISTING ACT CEILING TO REMAIN. PATCH & REPAIR AS REQUIRED. OF P40 9'0 08 o a N OFFICE 2 201 U It is a violation of the law for 103 J - GENERAL NOTES Architect. Engineer or Land Surveyor, to alter an item in any way. Plans, maps, specifications, studies, and reports not containing a red ink seal imprint on the cover sheet Q signature by the licensed professional may have been Q A. GC TO VERIFY ALL CONDITIONS AT CEILING AREAS PRIOR TO INSTALLATION not be considered an original copy. Copyright Protected 2018. Larson Design Group. OF NEW MATERIALS. NOTIFY ARCHITECT OF ANY EQUIPMENT, PIPING, OR OTHER OBSTRUCTIONS THAT MAY INTERFERE WITH DESIGNATED WORK. SALES B. ELEVATION HEIGHTS SHOWN ARE MEASURED ABOVE BLDG FINISHED FLOOR 101 ( ( UNLESS NOTED OTHERWISE. EX. 11'-0" H I C. REFER TO LIGHTING PLAN FOR MORE INFORMATION ON LIGHTING. D. EXISTING CEILING SYSTEM TO REMAIN UNLESS NOTED OTHERWISE. REPLACE ANY DAMAGED ACT / GYP CEILING SYSTEM. 0 E. ALL NEW CEILING TILES TO MATCH EXISTING. F. REFER TO MECHANICAL PLANS FOR MORE INFORMATION ON MECHANICAL � 5 EQUIPMENT. Fr L±-] - I El �-j KEYED NOTES: ❑x -- 1.- EXISTING ACT CEILING TO REMAIN. PATCH & REPAIR AS REQUIRED. OF P40 9'0 08 o a 92108 0 ED A 201 It is a violation of the law for any person, unless acting under the direction of a licensed Architect. Engineer or Land Surveyor, to alter an item in any way. Plans, maps, specifications, studies, and reports not containing a red ink seal imprint on the cover sheet accompanied by an original signature by the licensed professional may have been fraudulently altered and shall not be considered an original copy. Copyright Protected 2018. Larson Design Group. N z 0 � 5 Z LJL w 0 0 U W 0 V) Q 0 0 z 0 C7 c _ rn U) m c 0 E2 ca J r N � L �/y\� •J J IL N o 0 cp U 0 0 (!) O 04 o �O M rn 32 Q U :3W OW �(f) WC L J r • LLL (� ¢ WV j J f3 J r 10 ir O O 3 J L v o ' CDC14 L V c � O .-IdN� Z DE0r, 3 � �C) N �'� NovZcn C0 O _ O xx J o 3: (L LL PROJECT NO. 11979-002 DRAWN BY EBG APPV'D BY - RJG REFLECTED CEILING PLAN SHEET NO. A3.0 AS MEANING FURNISHED AND INSTALLED BY CONTRACTOR WITH THE EXCEPTION SERVICES WILL BE SHUT DOWN ONLY DURING THE TIME ACTUALLY REQUIRED TO TIGHT WITH DAP CMC DUCT SEALER. JOINTS ALSO SHALL BE RIVETED OR CONNECTED 2. FILTERS MUST BE IN UNITS AT ANY TIME FANS ARE OPERATED. " STEEL COMPLETE WITH FLUSH FLANGE TYPE FRAMES MANUFACTURED FROM 16 - WHERE ITEMS ARE PROVIDED BY TENANT" SHALL BE INTERPRETED AS MEANING "FURNISHED BY TENANT INSTALLED BY CONTRACTOR % EXCEPT WHERE NOTED ( ) DUCT D MAKE THE NECESSARY CONNECTION TO THE EXISTING WORK. THIS CONTRACTOR - SHALL GIVE AMPLE WRITTEN NOTICE IN ADVANCE TO THE OWNER OF ANY REQUIRED GAUGE STEEL, PROVIDED WITH ANCHORS. ACCESS DOORS SHALL BE SUITABLE FOR WITH SHEET METAL SCREWS. - R. SYSTEM TESTING. ADJUSTING AND BALANCING OTHERWISE. SHUT DOWN. INSTALLATION IN WALL OR CEILING MATERIALS SHOWN IN ROOM FINISH SCHEDULES. PROVIDE ACCESS DOORS FOR ALL CONCEALED_ VALVES, VENTS, DAMPERS, FIRE 9. SOFT ELASTOMER BUTYL GASKETS WITH ADHESIVE BACKING SHALL BE USED TO - A. GENERAL CONDITIONS 5. EQUIPMENT AND MATERIALS IN TRANSIT SHALL UTILIZE FREIGHT ELEVATOR OR BANDS C -CLAMPS WITH RETAINING CLIPS CHANNELS, HANGER RODS, ETC. INTERVALS. ALL SQUARE ELBOWS SHALL BE PROVIDED WITH DOUBLE WALLED VANES 1. TESTING ADJUSTING AND BALANCING OF ALL WORK SHALL BE COMPLETED BY AN INDEPENDLNT CONTRACTOR WHO IS CURRENTLY LICENSED BY THE ASSOCIATED DOWN HVAC UNIT. STAIRS. SAID EQUIPMENT OR MATERIALS SHALL BE DISASSEMBLED AS REQUIRED TO NECESSARY FOR THE INSTALLATION OF WbRK. ON MAXIMUM 3" CENTERS. PROVIDE SEAL CLASS "C" ON ALL TRAVERSE JOINTS A. SERVICE: RECTANGULAR,r, SUPPLY -AIR AND RETURN -AIR DUCTS. 1. DRAWINGS AND GENERAL PROVISIONS OF CONTRACT, INCLUDING GENERAL AND - MEET THE RESTRICTIONS IMPOSED BY THE BUILDING OR ITS COMPONENT FACING. DOORS IN CARPETED OR TILED AREAS SHALL BE RECESSED WITH TILE- UNLESS SUPERSEDED BY MORE STRINGENT LOCAL CODES. ALL DUCT CONNECTIONS 1. MATERIAL: INSULATION BOARD, 6 PSF MINIMUM AND PLAIN FACING. SUPPLEMENTARY CONDITIONS AND ALL OTHER SPECIFICATION SECTIONS (IF PROVIDED CONSTRAINTS AND THEN REASSEMBLED IN THE NEW WORK AREA. HANGERS SHALL BE FASTENED TO BUILDING STEEL, CONCRETE, OR MASONRY, BUT ARE TO BE RIGID AND LEAK FREE ASSEMBLIES. 2. THICKNESS: 2 INCHES. AS PART OF THE CONTRACT) ARE A PART OF THIS CONTRACT. - NOT TO PIPING OR DUCTWORK. DUCTWORK SHALL NOT BE SUPPORTED FROM ROOF DAMPERS CONTROLS AND OTHER ITEMS IN DUCTWORK THAT REQUIRE SER VECE OR INSPECT16N. IF THE ACCESS PANEL LOCATION IS EXPOSED TO THE SALES AREA, IT 3. NUMBER OF LAYERS: TWO. TOTAL THICKNESS = 4" - 6. ALL WORK SHALL BE DONE WITH A MINIMUM OF NOISE AND DISTURBANCE TO DECKING AND/OR BRIDGING BUT SHALL BE SUSPENDED FROM THE TOP CHORD OF 3. - DURING THE CONSTRUCTION PHASE OF THE PROJECT ANY DUCTWORK 4. VAPOR RETARDER REQUIRED: YES. 2. THE TERM "CONTRACTOR" SHALL MEAN THE "MECHANICAL CONTRACTOR HIRED BUSINESS ROUTINE. ALL WORK SCHEDULES SHALL BE COORDINATED WITH AND BAR JOISTS, STEEL OR OTHER STRUCTURE. DUCTWORK SHALL CLEAR ALL SPRINKLERS INSTALLED IS TO BE COMPLETELY SEALED UP OF ANY OPENINGS, EITHER AT THE - ' • TO COMPLETE THE WORK OUTLINED IN THESE PLANS AND SPECIFICATIONS" UNLESS APPROVED BY, THE TENANTS CONSTRUCTION MANAGER. AND OTHER OBSTACLES AND SHALL BE HUNG AS HIGH AS POSSIBLE IN WORK AND BEGINNING OR END OF A DUCT RUN OR AT A BRANCH, COLLAR DIFFUSER OR A. INORGANIC GLASS FIBERS PREFORMED AND BONDED BY THERMOSETTING RESIN. - OTHERWISE SPECIFIED. - 7. SINCE THESE ARE SECURE FLOORS, ALL DELIVERIES WORKERS WORK STORAGE AREAS. WHERE INTERFERENCE'S OCCUR IN ORDER TO SUPPORT DUCTWORK OR PIPING THE CONTRACTOR MUST INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS REGISTER TO AVOID DIRT OR OTHER CONTAMINANTS FROM ENTERING THE SYSTEM. MUST COMPLY WITH ASTM C 612, TYPE 1A AND 18 1. KNAUF INSULATION OR APPROVED EQUIVALENt. 3. THE CONTRACTOR FOR THIS WORK IS REQUIRED TO REVIEW ALL DRAWINGS FOR OPERATORS ETC. REQUIRED BY THE CONTRACTOR FOR WdRK PERFORMED IN ANY AREA OR S(TE BUILDING SHALL BE IN STRICT CONFORMANCE TO THE RULES AND WHICH SHALL BE LOCATED WHERE THEY DO NOT INTERFERE WITH ACCESS TO FIRE 4. EXCEPT WHERE OTHERWISE INDICATED, CONSTRUCT DUCT SYSTEMS TO 2 INCH 3. BALANCE AIR AND WATER QUANTITIES TO WITHIN PLUS OR MINUS 5 PERCENT ALL OTHER TRADES. -. REGULATIONS OF THE OWNER. DAMPERS, VALVES, ACCESS DOORS AND OTHER EQUIPMENT SERVICE REQUIREMENTS WATER GAUGE PRESSURE CLASSIFICATION VERIFY WHETHER RETURN OR EXHAUST A. INSULATION INSTALLED OUTDOORS: FLAME SPREAD RATING OF 25 OR LESS AND SERVICES, TOOLS TRANSPORTATION INCIDENTALS AND DETAILS NECESSARY TO AND/OR OTHER TRADES. HANGER TYPES AND INSTALLATION METHODS ARE SUBJECT DUCT IS POSITIVE OR NEGATIVE PRESSURE). PRESSURE TEST DUCTS FOR LEAKAGE. SMOKE DEVELOPED RATING OF 50 OR LESS. 4. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ITS SUBCONTRACTORS WITH A FULL SET OF BID DOCUMENTS INCLUDING SPECIFICATIONS 8. CONTRACTOR SHALL PROTECT THEIR WORK AND EQUIPMENT FROM DAMAGE, TO LANDLORD CRITERIA. - REMAKE LEAKING JOINTS AND APPLY SEALANTS AS REQUIRED TO FABRICATE A SYSTEM THAT DOES NOT EXCEED 5 PERCENT LEAKAGE OR LESS AS STATED BY B. APPLY INSULATION AS FOLLOWS: AND MUST COORDINATE ITS WORK AND INSPECTIONS AND THE WORK AND INSPECTION VANDALS ETC. ANY ITEM THAT IS DAMAGED, VANDALIZED OR STOLEN PRIOR TO ACCEPTANCE OF BUILDING BY OWNER AND ARCHITECT SHALL BE REPLACED BY 3. - HANGERS FOR ALL INSULATED PIPING SHALL BE SIZED AND INSTALLED FOR THE PRESSURE CLASS RATINGS IN SMACNA STANDARDS. 1. FLEXIBLE COLLARS SHALL BE PROVIDED IN ALL CONNECTIONS BETWEEN - OF THEIR SUBCONTRACTORS WITH ALL OTHER TRADES ON SITE TO CONFORM WITH RESPECTIVE CONTRACTOR AT NO CHARGE TO TENANT. OUTER DIAMETER OF INSULATION. INSTALL 6 INCH LONG SPLIT CIRCLE GALVANIZED ASSOCIATED WIRING AND SAFETY SWITCHES FOR SUCH MOTORS SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. STARTERS SHALL MEET ALL A. APPLY TWO -LAYER INSULATION WITH JOINTS TIGHTLY BUTTED AND STAGGERED THE GENERAL CONTRACTORS TIME SCHEDULE. - - ° COORDINATE THE ENTIRE INSTALLATION WITH LANDLORD AS REQUIRED. FIELD VERIFY THE EXACT TYPE, SIZE LOCATION REQUIREMENTS ETC. OF EXISTING EQUIPMENT, SADDLE BETWEEN THE HANGER AND THE PIPE INSULATION. 5. AS A MINIMUM, CROSSBREAK ALL FLAT SURFACES OR REINFORCE WITH A BEAD AT LEAST 3 INCHES. SECURE LAYERS WITH ADHESIVE, MECHANICAL FASTENERS OR 9. IT IS SPECIFICALLY THE INTENTION OF THIS SPECIFICATION TO HOLD THE DOCUMENTS PRIOR TO SUBMISSION OF BID. OTHERWISE, TENANTS CONSTRUCTION APPROXIMATELY 3/8 INCH WIDE BY 3/16 INCH DEEP ON 12 INCH CENTERS TO BANDING. FASTENERS SHALL BE LOCATED A MAXIMUM OF 3" FROM EACH EDGE AND . 5. BY SUBMITTING A QUOTATION OR PROPOSAL THE MECHANICAL CONTRACTOR CONTRACTOR RESPONSIBLE FOR ALL DAMAGE DONE TO ANY EXISTING FACILITIES 4. HANGERSAND PIPING OF DISSIMILAR METALS SHALL BE DI -ELECTRICALLY PREVENT VIBRATIONS. - NO GREATER THAN 12" APART. . EXPRESSLY STATES AND WARRANTS THAT. ALL DRAWINGS AND SPECIFICATIONS HAVE EQUIPMENT PAINTING, OR ARCHITECTURAL AND STRUCTURAL FEATURES OF THE SEPARATED FROM ONE ANOTHER. - OPERATION ON VOLTAGE VARIATION OF PLUS OR MINUS 10 PERCENT, 40 DEGREES C BEEN THOROUGHLY REVIEWED, CONTRACTOR HAS BECOME FAMILIARIZED WITH JOB BUILDING SY EITHER THEIR OWN WORKMEN OR BY ANY OF THEIR SUBCONTRACTORS. P. ACCESS DOORS 6. INSTALL RIGID ROUND AND RECTANGULAR METAL DUCT WITH SUPPORT B. ON EXPOSED APPLICATIONS FINISH INSULATION WITH A SKIM COAT OF SITE CONDITIONS AND IS TOTALLY QUALIFIED TO PERFORM ALL OF THE WORK THE CON�fRACTOR SHALL REPAIR ANY DAMAGE DONE BY THEIR OWN WORKMEN OR WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SYSTEMS INDICATED IN SMACNA STANDARDS. NO WOOD SHALL BE USED TO SUPPORT MINERAL -FIBER, HYDRAULIC -SETTING CEMENT TO SURFACE OF INSTALLED REQUIRED. SUBCONTRACTORS AND THE OWNER AT THEIR DISCRETION, MAY WITHHOLD PAYMENTS 1. FURNISH STEEL ACCESS DOORS AND FRAMES MINIMUM 16 INCHES BY 20 OR BRACE DUCTS. PROVIDE SWAY AND SEISMIC BRACING AS REQUIRED BY STATE AND LOCAL CODES OR BY LANDLORD. INSULATION. WHEN DRY, APPLY FLOOD COAT OF LAGGING ADHESIVE AND PRESS ON ONE LAYER OF GLASS CLOTH OR TAPE. OVERLAP EDGES AT LEAST 1 INCH (25 MM). 6. BEFORE SUBMITTING A FINAL PROPOSAL THE CONTRACTOR SHALL EXAMINE THE EQUAL TO THE REASONABLE COST OF THE REPAIRS. INCHES OR AS REQUIRED FOR ADEQUATE ACCESS YO THE GENERAL CONTRACTOR STANDARD FOR THE BASE BID. MANUFACTURERS APPLY FINISH COAT OF LAGGING ADHESIVE OVER GLASS CLOTH OR TAPE. THIN THE _ SITE OF THE PROPOSED WORK TO DETERMINE THE EXISTING CONDITIONS THAT MAY AFFECT THE PROPOSAL. IF DISCREPANCIES ARE NOTED BETWEEN THE DOCUMENTS 10 THIS CONTRACTOR OR THEIR WORKMEN SHALL NOT BE PERMITTED TO USE ANY FOR ALL LOCATIONS WHERE NECESSARY TO PROVIDE ACCESS TO CONCEALED VALVES - AND OTHER EQUIPMENT REQUIRING SERVICE OR INSPECTION. LOCATION, TYPE SIZE 7. WHERE DUCTS PASS THROUGH ROOFS FLOORS AND FIRE RATED PARTITIONS, j2 FINISH COAT TO ACHIEVE SMOOTH FINISH. OUTDOOR JACKET: POLYGUARD PRODUCTS, 'ALUMAGUARD 'FLEXCLAD AND THE EXISTING CONDITIONS THE ARCHITECT SHALL BE NOTIFIED AND THE PART OF THE EXISTING BUILDING AS A SHOP WITHOUT THE APPROVAL OF THE AND NUMBER WILL BE DETERMINED BY THE CONTRACTOR AND APPROVED BY THE PROVIDE AS MINIMUM 1-1 2 INCH BY 1-1 / INCH BY 1/8 INCH STEEL ANGLE INC. 60' OR MFM BUILDING PRODUCTS CORP. 400". ACID RESISTANT FIRE RETARDANT FIBERGLASSED NEOPRENE CONNECTOR, A MINIMUM _ OF SIX (6? INCHES IN LENGTH. THE CONNECTOR SHALL BE FASTENED TO EQUIPMENT OWNER AND ARCHITECT. EXCEED CODES OR THE LANDLORD'S TENANT CRITERIA THE CONTRACTOR IS STILL FRAMES AT EACH SIDE 0 OPENING. THE ANNULAR SPACE BETWEEN DUCT AND 2. FURNISH TO THE TENANTS CONSTRUCTION MANAGER ALL CERTIFICATES OF CONTRACTOR SHALL RECEIVE CLARIFICATION BEFORE SUBMITTING A BID. THE A D PRESSURE READINGS. TENANT CONSTRUCTION MANAGER TO SUIT EQUIPMENT REQUIREMENTS. GENERAL ANGLE FRAMES SHALL BE CAULKED WITH SILICONE SEALANT OR FIREPROOFED AS Q. SYSTEM CLEANOUT SUBMISSION OF A PROPOSAL SHALL INDICATE THAT ALL CHARGES AND COSTS MADE 11, WHERE THE WORK MAKES TEMPORARY SHUTDOWN OF SERVICES UNAVOIDABLE, CONTRACTOR WILL INSTALL ACCESS DOORS AND FRAMES. REQUIRED BY THE ASSEMBLY FIRE RATING. CONTRACTOR TO PROVIDE FIRE OR REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. NECESSARY BY EXISTING CONDITIONS ARE INCLUDED AND THAT THE COMPLETE SYSTEM AS DESCRIBED HEREIN WILL BE FURNISHED AT THE PROPOSED COST. THEY SHALL BE MADE AT NIGHT OR AT SUCH TIMES AS WILL CAUSE THE LEAST 2• ACCESS DOORS LOCATED IN FIRE -RATED WALLS, FLOORS, CEILING -FLOOR, OR COMBINATION FIRE / SMOKE DAMPERS AT EACH PENETRATION WHERE REQUIRED BY CODE. 1. UPON COMPLETION OF INSTALLATION CLEAN ENTIRE SYSTEM BEFORE INSTALLING AIR OUTLETS. CONTRACTOR TU PROVIDE A CERTIFICATION THAT CLEANING 1. MOUNT THERMOSTATS 4'-0" (ADA COMPLYING), THERMOSTAT SENSORS 5'-0" INTERFERENCE WITH THE ESTABLISHED OPERATING ROUTINE. CEILING -ROOF ASSEMBLIES SHALL BE FIRE RATED, U.L LISTED AND LABELED. EQUIPMENT AND DUCT FABRICATION DRAWINGS TO THE TENANT'S CONSTRUCTION WAS ACCOMPLISHED PRIOR TO PROJECT CLOSEOUT. 1 7. WHEN USED, THE TERM "PROVIDED BY CONTRACTOR""SHALL BE INTERPRETED 12. THIS CONTRACTOR SHALL ARRANGE THE WORK SO AS TO ASSURE THAT - 3. ACCESS DOORS SHALL BE FLUSH TYPE MANUFACTURED FROM 14 GAUGE 8. ALL TRAVERSE JOINTS AND SEAMS IN SUPPLY AIR DUCT SHALL BE SEALED AIR 4. SMOKE DETECTORS AND REMOTE TEST STATION AS MEANING FURNISHED AND INSTALLED BY CONTRACTOR WITH THE EXCEPTION SERVICES WILL BE SHUT DOWN ONLY DURING THE TIME ACTUALLY REQUIRED TO TIGHT WITH DAP CMC DUCT SEALER. JOINTS ALSO SHALL BE RIVETED OR CONNECTED 2. FILTERS MUST BE IN UNITS AT ANY TIME FANS ARE OPERATED. " STEEL COMPLETE WITH FLUSH FLANGE TYPE FRAMES MANUFACTURED FROM 16 - WHERE ITEMS ARE PROVIDED BY TENANT" SHALL BE INTERPRETED AS MEANING "FURNISHED BY TENANT INSTALLED BY CONTRACTOR % EXCEPT WHERE NOTED ( ) DUCT D MAKE THE NECESSARY CONNECTION TO THE EXISTING WORK. THIS CONTRACTOR - SHALL GIVE AMPLE WRITTEN NOTICE IN ADVANCE TO THE OWNER OF ANY REQUIRED GAUGE STEEL, PROVIDED WITH ANCHORS. ACCESS DOORS SHALL BE SUITABLE FOR WITH SHEET METAL SCREWS. - R. SYSTEM TESTING. ADJUSTING AND BALANCING OTHERWISE. SHUT DOWN. INSTALLATION IN WALL OR CEILING MATERIALS SHOWN IN ROOM FINISH SCHEDULES. PROVIDE ACCESS DOORS FOR ALL CONCEALED_ VALVES, VENTS, DAMPERS, FIRE 9. SOFT ELASTOMER BUTYL GASKETS WITH ADHESIVE BACKING SHALL BE USED TO - B. GENERAL REQUIREMENTS - 13. ALL MOTORS, FANS CONTROLS, FIXTURES, HVAC UNIT DUCTWORK AND OTHER DAMPERS, EXPANSION JOINTS PULL BOXES SHOCK ABSORBERS DRAINS, MOTORS, FANS, PUMPS AND ANY SEAL FLANGED JOINTS. 1. TESTING ADJUSTING AND BALANCING OF ALL WORK SHALL BE COMPLETED BY AN INDEPENDLNT CONTRACTOR WHO IS CURRENTLY LICENSED BY THE ASSOCIATED DOWN HVAC UNIT. EQUIPMENT FOR USE IN CHIS CONTRACT SHALL BE PROTECTED BY TARPAULIN OR BY OTHER ITEM REQUIkING SERVICE. DOORS IN PLASTER OR CONCRETE SURFACES SHALL HAVE A RECESSED DOOR WITH CONCRETE OR PLASTER 10. DUCT TRANSITIONS SHALL NOT EXCEED 30 DEGREES SLOPE EXCEPT AS AIR BALANCING COUNCIL AABC OR NATIONAL ENVIRONMENTAL BALANCING BUREAU ) 1. THE MECHANICAL SUBCONTRACTORS QUOTING ON THEIR SPECIFIC SCOPE OF BOXING AS SOON AS DELIVERED TO THE SITE AND SHALL BE KEPT CLEAN AND DRY. THE MOTORS FACING. DOORS IN CARPETED OR TILED AREAS SHALL BE RECESSED WITH TILE- SPECIFICALLY NOTED OTHERWISE. NEBB . NO OTHER BALANCE REPORTS WILL BE REVIEWED OR ACCEPTED. ALL WORK/SERVICES TO CONTACT THE LOCAL BUILDING DEPARTMENT/AGENCY TO DISCUSS CODE ISSUES IDIOSYNCRASIES REGARDING THEIR SERVICES AND THE QUOTE UNITS, FIXTURES FANS, DUCTWORK AND MOVING PARTS SHALL BE KEPT COVERDD SO AS TO ELIMINATE DIRT DUST AND OTHER MATERIALS ENTERING FACING. NO ACCESS DOORS ARE REQUIRED IN 2 X 2 AND 2 X 4 LAY -IN 11. PROVIDE ACCESS TO ALL MOTORIZED DAMPERS, FIRE DAMPERS FIRE //SMOKE BALANCING WORK MUST BE COMPLETE AND DONE IN ACCORDANCE WITH THE MOST RECENT STANDARDS OF THEIR SOCIETY. PAYMENT OF ALL COSTS FOR TESTING SHALL ASSOCIATED WITH THE SERVICES TO THE GENERAL CONTRACTOR FOR THIS PROJECT. THIS CONTRACTOR TO BE FAMILIAR WITH THE SITE WHERE SUCH SERVICES WORK THE PARTS DURING ERECTION AND CONSTRUCTION WORK ON THE BUILDING. SHOULD IT BE FOUND THAT ANY PARTS ARE DAMAGED DUE TO CARELESSNESS ON THE PART ACOUSTIC TILE CEILING. PROVIDE COLORED PINS TO DENOTE ACCESS TILES FURNISH FACTORY MADE METAL ACCESS DOORS COMPLETELY FLUSH ALLAN HEAD SCREWDRIVER OPERATED, WITH FRAMES AND CAM -TYPE CAYCH WITH STAINLESS DAMPERS CONTROLS AND OTHER ITEMS IN DUCTWORK THAT REQUIRE SER VECE OR INSPECT16N. IF THE ACCESS PANEL LOCATION IS EXPOSED TO THE SALES AREA, IT BE MADE BY THE HVAC CONTRACTOR. , WILL BE PERFORMED THIS SPECIFIC USE AND THE IDIOSYNCRASIES ASSOCIATED WITH OF THE CONTRACTOR IN NOT PROVIDING PROPER PROTECTION, SUCH PART OR PARTS CUTTING SHALL HAVE PRIOR APPROVAL BY THE TENANT'S CONSTRUCTION MANAGER MUST BE APPROVED BY THE TENANT'S CONSTRUCTION MANAGER PRIOR TO 2. THE CONTRACTOR SHALL INSTALL NEW FILTERS IN ALL UNITS PRIOR TO THE THE LIFE, SAFETY AND HEALTH ASSOCIATED WITH THIS WORK AND TO INDICATE ON SHALL BE REPLACED BY THE CONTRACTOR AT THEIR OWN COST AND EXPENSE. ALL STEEL STUD. DOORS SHALL BE NOT LESS THAN 12 X 12 FOR HAND ACCESS. - INSTALLATION. LAY -IN SUPPLY AND RETURN AIR DIFFUSERS GRILLES AND REGISTERS AIR BALANCING. THE COMPLETE AIR BALANCE SHALL TAKE PLACE WITH OUTSIDE AIR THE QUOTE ANY ITEMS REQUIRED THAT ARE NOT NECESSARILY SHOWN ON THE OPENINGS IN DUCTS, PIPING CONDUITS ETC., SHALL BE PROPERLY PROTECTED WITH TIMES. DOORS IN WALLS AND CEILING SHALL BE PRIME COATED CARBON STEEL. FURNISH FIRE RATED DOORS FOR FIRE RATED CONSTRUCTION. RATING OF DOOR BE WITH PLASTER FRAMES MAY BE USED AS ACCESS LOCATIONS. DAMPERS IN MINIMUM POSITION. DRAWINGSSPECIFICATIONS. /SPECIFICATIONS. TEMPORARY CAPS OR PLUGS AT ALL .MUST SAME MAINTENANCE MANUAL I LACK OF SUCH CONTRACTORS REVIEW WILL BE CAUSE FOR REJECTION WITHOUT RATING AS CONSTRUCTION. 12. ALL BRANCHES AND TAKEOFFS SHALL BE EQUIPPED WITH MANUAL VOLUME 3. BALANCE AIR AND WATER QUANTITIES TO WITHIN PLUS OR MINUS 5 PERCENT 2. THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, G. DISCREPANCIES IN DOCUMENTS - Q. ELECTRIC MOTORS CONTROLLING DEVICES HAVING AN INDICATING AND LOCKING DEVICE. - OF THAT INDICATED ON THE DRAWINGS. ANY REQUIRED CHANGES IN SHEAVES BELTS, PULLEYS OR THE ADDITION SERVICES, TOOLS TRANSPORTATION INCIDENTALS AND DETAILS NECESSARY TO 1. ALL WORK SHALL BE PERFORMED IN A NEAT AND PROFESSIONAL MANNER . IN THE OPERATION AND MAINTENANCE MANUALS LEFT ON SITE AT JOB COMPLETION. OF DAMPERS REQUIRED TO ACHIEVE SPECIFIED FLbW PROVIDE COMPLEYE AND FULLY FURCTIONAL MECHANICAL SYSTEMS AS SHOWN ON 1. DRAWINGS (PLANS. SPECIFICATIONS AND DETAILS) ARE DIAGRAMMATIC AND 1• FURNISH, INSTALL AND ALIGN ALL MOTORS REQUIRED FOR THIS EQUIPMENT, I. FLEXIBLE CONNECTIONS RATES SHALL BE PROVIDED BY THE HVAC CONTRACTOR WITH NO ADDITIONAL COST , TO THE TENANT. - INDICATI= T Tl�AND INTENT OF YSTE�.WHERE THE DRAWINGS, CALLED FOR IN THE SPECIFICATIONS (IF SUPPLIED) AND AS REQUIRED BY JOB CONDITIONS. ALL WORK NOT SPECIFICALLY NOTED AS BEING BY DRAWING EXISTING SITE SPECIFICATIONS UNLESS THEY ARE FACTORY INSTALLED ON THE UNIT. ALL STARTERS AND 1. FLEXIBLE COLLARS SHALL BE PROVIDED IN ALL CONNECTIONS BETWEEN - DRAWINGS OR SCHEDULES SHALL NOT RELIEVE THE CONTRACTOR FROM THE LANDLORD SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. CLOSELYSU13MIlIAL R IN OF [HE GENERAL CONIHAG[OH 15 RESPONSIBLE E ASSOCIATED WIRING AND SAFETY SWITCHES FOR SUCH MOTORS SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. STARTERS SHALL MEET ALL VIBRATING EQUIPMENT FANS, ROOFTOP UNITS, WATER SOURCE HEAT PUMPS, AIR HANDLERS 4. THE BALANCE REPORT SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION: COORDINATE THE ENTIRE INSTALLATION WITH LANDLORD AS REQUIRED. FIELD VERIFY THE EXACT TYPE, SIZE LOCATION REQUIREMENTS ETC. OF EXISTING EQUIPMENT, TENANTS CONSTRUCTION MANAGER IN WRITING OF VARIATIONS TO THE CONTRACT REQUIREMENTS AS DEFINED IN THE ELECTRICAL SPECIFICATIONS. FAN POWERED VAV BOXES ETC.) AND DUCTS OR CASINGS. ALSO PROVIDE rLEXIBLE CONNECTIONS WHERE DUCTS CROSS BUILDING EXPANSION JOINTS. PIPE AND DUCTS SERVING THE TENANT SPACE PRIOR TO SUBMISSION OF BID. DOCUMENTS PRIOR TO SUBMISSION OF BID. OTHERWISE, TENANTS CONSTRUCTION 2. DESIGN CONSTRUCTION AND PERFORMANCE CHARACTERISTICS OF MOTORS 2. FLEXIBLE AIR DUCT MAY ONLY BE USED IN VERTICAL APPLICATIONS WITH A� AABC OR NEBB CERTIFICATION NUMBER AND SIGNATURE OF BALANCING C NTRACTOR. 3. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH MANAGERS INTERPRETATION OF CONTRACT DOCUMENTS OR CONDITIONS SHALL B SHALL CONFIRM TO ALL APPLICABLE PROVISIONS OF LATEST NEMA ANSI ISEE STANDARDS FOR ELECTRICAL EQUIPMENT. ALL MOTORS SHALL BE S�1ITABLE FOR 2. FLEXIBLE CONNECTIONS SHALL BE CONSTRUCTED OF NEOPRENE -COATED FLAMEPROOF FABRIC. PROVIDE ADEQUATE JOINT FLEXIBILITY TO ALLOW FOR - B INSTRUMENTATION LIST WITH LAST CALIBRATION DATES. - T. INDOOR AIR QUALITY - OTHER AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE PROVIDED - OPERATION ON VOLTAGE VARIATION OF PLUS OR MINUS 10 PERCENT, 40 DEGREES C MOVEMENT AND PREVENT THE TRANSMISSION OF VIBRATION. C MAKE AND MODEL NUMBERS OF ALL HVAC EQUIPMENT TESTED. EVEN THOUGH NOT SPECIFICALLY MENTIONED IN BOTH. ANY MATERIAL OR LABOR H. TRADE NAMES AND MANUFACTURERS AMBIENT TEMPERATURE AND HAVE A SERVICE FACTOR OF NOT LESS THAN 1.15. PRIOR TO CONSTRUCTION. D AIR CFM AND STATIC PRESSURE READINGS DISCHARGE AND SUCTION AS ( ) WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE 1. NO ANALYSIS HAS BEEN MADE WITH REGARD TO SOURCES OR POTENTIAL 3. FLEXIBLE CONNECTIONS ARE TO BE RATED FOR THE OPERATING PRESSURE OF M ASURED BY PITOT TUBE DUCT TRAVERSE AT THE UNITS. SPECIFICATIONS BUT WHICH IS NECESSARY TO COMPLETE THE WORK OR WHICH IS USUALLY INCLUbED IN 1. WHERE TRADE NAMES AND MANUFACTURERS ARE USED ON THE DRAWINGS OR IN THE SPECIFICATIONS THE EXACT EQUIPMENT SHALL BE USED AS A MINIMUM R. LOW VOLTAGE (24 VOL!) WIRING - THE SYSTEM. E) MOTOR NAMEPLATE DATA WITH ACTUAL FIELD VOLTAGE AND AMPERAGE WORK OF SIMILAR CHARACTER, SHALL BE PROVIDED AS PART STANDARD FOR THE BASE BID. MANUFACTURERS L SUPPLY AND RETURN AIR TAKEOFF FITTINGS CONTAMINATION. READINGS FOR EACH LEG. OF THE CONTRACT. - CONSIDERED AS AN EQUIVALENT OR BETTER IN ALL ASPECTS TO THAT SPECIFIED WILL BE 1. THE CONTRACTOR IS TO INSTALL ALL LOW VOLTAGE WIRING REQUIRED FOR 4. FINAL CONNECTIONS TO EXHAUST FANS) SHALL BE WITH A HEAVY AIRTIGHT F MOTOR AND FAN RPM, SHEAVE SIZES AND BELT SIZES AND LENGTHS. 4. WHERE THE DRAWINGS AND / OR SPECIFICATIONS CALL FOR ITEMS WHICH SUBJECT TO REVIEW IN WRITING BY THE TENANT'S CONSTRUCTION MANAGER PRIOR TO ACCEPTANCE. THE USE OF THEIR EQUIPMENT. THIS WORK INCLUDES ALL TRANSFORMERS AND DEVICES TO MAKE THIS A COMPLETE FUNCTIONAL SYSTEM. - - ACID RESISTANT FIRE RETARDANT FIBERGLASSED NEOPRENE CONNECTOR, A MINIMUM _ OF SIX (6? INCHES IN LENGTH. THE CONNECTOR SHALL BE FASTENED TO EQUIPMENT G OUTSIDE, RETURN, MIXED AND SUPPLY AIR TEMPERATURES AT FULL COOLING. H WATER BALANCE DATA INCLUDING GPM WITH INLET AND OUTLET TEMPERATURE EXCEED CODES OR THE LANDLORD'S TENANT CRITERIA THE CONTRACTOR IS STILL ANY UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO REMOVAL AND REPLACEMENT 2. FURNISH TO THE TENANTS CONSTRUCTION MANAGER ALL CERTIFICATES OF AND DU WITH TWO FLEXIBLE REMOVABLE BRASS STRAPS OR ALTERNATE APPROVED A D PRESSURE READINGS. RESPONSIBLE FOR PROVIDING THE SYSTEM AS DESIGNED AND DESCRIBED ON THE AT THE CONTRACTOR'S EXPENSE. 2. ALL WORK IS TO CONFORM TO THE ELECTRICAL SPECIFICATIONS AND THE METHOD. MAKE AND MODEL NUMBERS OF ALL -AIR DISTRIBUTION EQUIPMENT. DRAWINGS, UNLESS SPECIFICALLY NOTED OTHERWISE. SHOP DRAWINGS REQUIREMENTS OF THE AUTHORITIES HAVING JURISDICTION. J. THERMOSTATS5. FINAL BALANCED AIR VOLUMES AT ALL OUTLETS INCLUDING RETURNS WHEREI. LTED). THE CONTRACTOR SHALL OBTAIN AND COMPLY WITH DETAILED REQUIREMENTS OF LEASE EXTRACTS FROM THE LANDLORD AND TENANT. 1. SUBMIT THREE COPIES OF MATERIAL LISTS AND SHOP DRAWINGS FOR ALL 3. ANY CONDUIT REQUIRED BY CODE OR THE LANDLORD WILL BE INSTALLED BY THE ELECTRICAL SUBCONTRACTOR. 1. MOUNT THERMOSTATS 4'-0" (ADA COMPLYING), THERMOSTAT SENSORS 5'-0" K) INDEXED PLAN WITH DIFFUSER AND RETURN LOCATIONS. - EQUIPMENT AND DUCT FABRICATION DRAWINGS TO THE TENANT'S CONSTRUCTION CONDENSATE DRAIN AND BE TRAPPED IN ACCORDANCE WITH MANUFACTURER S ABOVE FINISHED FLOORS AND SET DATE TIME TEMPERATURE, ETC. TURN OVER OF TIGHT CONSTRUCTION AND THAT ALL SOURCES OF CONTAMINATION FROM TRAPS, 6. COORDINATE LOCATIONS OF ALL AIR OUTLETS WITH ALL WALLS LIGHTS, ` MANAGER FOR REVIEW PRIOR TO ORDERING EQUIPMENT. SUBMISSIONS MUST BE 4. SMOKE DETECTORS AND REMOTE TEST STATION OPERATING INSTRUCTIONS TO TENANT RtPREStNTATIVE. 5. ALL CONTROL SEQUENCES SHALL BE TESTED AND OPERATING STATUS SPRINKLER HEADS, CEILING TILES AND DECORATIVE CEILING FIXTURES PRIOR TO EARLY ENOUGH TO ALLOW THE TENANT'S CONSTRUCTION MANAGER EIGHT WORKING GENERAL LOCATION AND INTENT OF THE MECHANICAL SYSTEMS. BECAUSE OF THE SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL DUCT AND PIPE CONTRACTOR SHALL MAKE ANY FINAL CORRECTIONS TO DRAWINGS ANb CERTIFY THE RECORDED IN THE REPORT. INSTALLATION. - DAYS FOR REVIEW WITHOUT CAUSING DELAYS OR CONFLICTS TO THE JOB'S PROGRESS. SUBMITTALS SHALL BE IN ACCORDANCE WITH THE GENERAL CONDITIONS I. IONIZING TYPE ARE TO BE USED ON THE RETURN SIDE OF THE AHU AND PHOTO -TYPE ARE BE USED ON THE SUPPLY SIDE. ON ALL OTHER TYPES OF 2. THERMOSTATS SHALL BE PROVIDED WITH KEY OPERATED SECURITY COVERS AND DESCRIPTIVE NAMEPLATES. 6. THREE COPIES OF THE BALANCE REPORT SHALL BE SUBMITTED THROUGH THE 7 ALL MECHANICAL WORK SHALL BE INSTALLED SO AS TO BE READILY I HVAC UNITS WHERE SMOKE GENERAL CONTRACTOR TO THE TENANT'S CONSTRUCTION MANAGER FOR REVIEW AND OFF�O.1r0X\O * 10092168 -----� ED w1� It is a violation of the law for any person, unless acting under the direction of a licensed Architect, Engineer or Land Surveyor, to after an item in any way. Plans, maps, specifications, studies, and reports not containing a red ink seal imprint on the cover sheet accompanied by an original signature by the licensed professional may have been fraudulently altered and shall not be considered an original copy. Copyright Protected 2018, Larson Design Group. V) z g 0 N W Z W lx M I-- :2 "., �0 w N CL 0 c rn co Q 0 c 0 W J ACFOR OPERATION, SERVICE MAINTENANCE AND REPAIR. THE CONTRACTOR USING SING THE MANUFACTUS RERLISTED ON THE DRAWINGS. SHOP DRAWINGS SHALL INCLUDE ALL DATA THAT PERTAINS TO THE REQUIREMENTS SET FORTH ON THE ETECTORS ARE REQUIRED, USE FIELD INSTALLED IONIZING TYPE IN RETURN DUCTWORK AND PHOTO -TYPE ON THE SUPPLY LOCATED K. COMMENT. . IS RESPONSIBLE FOR PROVIDING SUFFICIENT ACCESS TO ALL EQUIPMENT FOR DRAWINGS AND IN THE SPECIFICATIONS. THE SUBMITTAL SHALL INCLUDE BUT NOT BE BEFORE THE FIRST TAKEOFF. ONCE ACTIVATED, THE SMOKE DETECTOR WILL SHUT FLEXIBLE AIR DUCT I : 0 0 SERVICE. - LIMITED TO CUTS OR CATALOGS INCLUDING DESCRIPTIVE LITERATURE AND DOWN HVAC UNIT. 0 7. THE BALANCING CONTRACTOR SHALL PERFORM ALL APPLICABLE TESTING AND .. CHARACTERISTICS OF EQUIPMENT SHALL SHOW MAJOR DIMENSIONS ROUGHING -IN 1. FLEXIBLE DUCT FOR CONNECTIONS SHALL BE A FACTORY FABRICATED BALANCING FUNCTIONS REQUIRED FOR THE SYSTEM DESIGNED IN THESE DRAWINGS. 8.' THE CONTRACTOR SHALL DO ALL CUTTING CORE DRILLING CHASING OR PHIS DATA CAPACITY CURVES PRESSURE DROPS CODE COMPLIANCE MOTOR AND DRIVE - ii. SMOKE DETECTORS SHALL HAVE THEIR OWN REMOTE KEY TEST STATION SYSTEM ASSEMBLY CONSISTING OF AN INNER SLEEVE INSULATION AND AN OUTER MOISTURE THE BALANCING CONTRACTOR SHALL RECHECK ANY ITEMS THAT THE TENANT DEEMS NECESSARY AT NO ADDITIONAL CHANNELING AND PATCHING REQUIRED FOR ANY WORK UNDER CONTRACT. DATA AND ELECtRICAL DATA. OBSERVE SPEdAL INSTRUCTIONS WHEN REQUIRED. WITH AUDIBLE AND VISUAL ALARM, SIMPLEX MODEL 4098-9842 OR APPROVED BARRIER. THE INNER SLEEVE SHALL BE CONSTRUCTED OF A CONTINUOUS VINYL COST TO THE TENANT. . CUTTING SHALL HAVE PRIOR APPROVAL BY THE TENANT'S CONSTRUCTION MANAGER SUBMITTALS SHALL BEAR THE STAMP OF THE GENERAL AND SUBCONTRACTOR EQUIVALENT. ALARM TO HAVE CANDELA SETTING OF 75 AND A HIGH VOLUME HORN COATED SPRING STEEL WIRE HELIX FUSED TO A CONTINUOUS LAYER OF FIBERGLASS O= O 3 L i� AND THE LANDLORD OR LANDLORDS REPRESENTATIVE. PATCHING SHALL MATCH SHOWING THAT HE HAS REVIEWED AND CONFIRMED THAT THEY ARE IN CONFORMANCE TONE SETTING. IMPREGNATED AND COATED VINYL. A 1 1/4 THICK LAYER OF INSULATING BLANKET 8 FINAL BALANCE REPORT SHALL BE INCLUDED IN THE OP OPERATION AND FINISH OF SURROUNDING AREA. - WITH THE CONTRACT DOCUMENTS OR INDICATE WHERE EXCEPTIONS TAKE PLACE. - . - OF FIBERGLASS WOOL SHALL ENCASE THE INNER SLEEVE AND BE SHEATHED WITH AN MAINTENANCE MANUAL LACK OF SUCH CONTRACTORS REVIEW WILL BE CAUSE FOR REJECTION WITHOUT ALARM SYSTEM MAY BE DELETED WHERE NOT REQUIRED BY LANDLORD OR BY LOCAL OUTER MOISTURE BARRIER OF A BIDIRECTIONAL REINFORCED METALIZED VAPOR S. FINAL HVAC INSPECTIONS . C. CODES __ REVIEW BY TENANT'S CONSTRUCTION MANAGER. ALL SHOP DRAWINGS MUST APPEAR CODE. BARRIER. THE FLEXIBLE DUCT SHALL BE RATED FOR A MAXIMUM WORKING VELOCITY L_ (6 0 _ x 1. ALL WORK SHALL BE PERFORMED IN A NEAT AND PROFESSIONAL MANNER . IN THE OPERATION AND MAINTENANCE MANUALS LEFT ON SITE AT JOB COMPLETION. A. HEATING, VENTILATION AND AIR CONDITIONING OF 6000 FPM AND SHALL BE LISTED BY THE UNDERWRITERS LABORATORIES UNDER THEIR UL -181 STANDARDS AS A CLASS 1 DUCT AND SHALL COMPLY WITH NFPA 1. ASIDE FROM NORMAL INTERIM INSPECTIONS OF WORK IN PLACE THE TENANTSHALL USING GOOD CONSTRUCTION PRACTICES. ALL WORK SHALL CONFORM TO THE LATEST 2. TENANT'S CONSTRUCTION MANAGERS OR ARCHITECTS REVIEW OF SHOP - STANDARD - 90A. THE FLEXIBLE DUCT SHALL BE THERMAFLEX M -KC OR APPROVED HAVE THE RIGHT TO HAVE AN INDEPENDENT HVAC CONTRACTOR INSPECT THE FINISHED HVAC INSTALLATION UPON COMPLETION FOR - ADOPTED EDITION OF THE LANDLORDS CRITERIA- STATE COUNTY AND LOCAL CODES THE AND ORDINANCES THE LATEST EDITIONS OF AS�iRAE SfiANDARDS THE LIFE SAFETY AND DRAWINGS OR SCHEDULES SHALL NOT RELIEVE THE CONTRACTOR FROM 1. BEFORE STARTING WORK, THIS CONTRACTOR SHALL EXAMINE THE ARCHITECTURAL, STRUCTURAL MECHANICAL AND ELECTRICAL PLANS AND . EQUIVALENT. FLEXIBLE DUCT SHALL ROUTE FROM SHEET METAL DUCTWORK TO CEILING DIFFUSERS ONLY. THERE SHALL BE NO EXPOSED FLEXIBLE DUCT. COMPLIANCE WITH THE PLANS SPECIFICATIONS AND CODES. THE INSTALLING CONTRACTOR WILL BE RESPONSIBLE Td CODE, THE APPLI' BUILDING CODE, UNDERWRITERS RATbRIES, THE RESPONSIBILITY FOR ERRORS OMISSIONS OR OTHER DEFICIENCIES OR DEVIATIONS IN THE SHOP DRAWINGS FROM THE CONSTRUCTION DOCUMENTS. SPECIFICATIONS TO SEQUENCr, COORDINATE AND INTEGRATE THE VARIOUS ELEMENTS BRING ALL ITEMS REPORTED BY THE INDEPENDENT HVAC CONTRACTOR UP TO PLANS NATIONAL ELECTRICAL CODE NFPA 70 90A AND 96 AND ALL OTHER APPLICABLE OF THE HVAC SYSTEM, MATERIALS AND EQUIPMENT WITH OTHER CONTRACTORS TO 2. FLEXIBLE AIR DUCT MAY ONLY BE USED IN VERTICAL APPLICATIONS WITH AND SPECIFICATIONS REQUIREMENTS AT NO ADDITIONAL COST TO THE TENANT. CODES ENFORCED BY AUTHaRITIES HALING JURISDICTION. THE CHANGES REQUIRED BY 3. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR AND OR THEIR AVOID INTERFERENCES AND CONFLICTS. PRIOR APPROVAL FROM THE TENANT'S CONSTRUCTION MANAGER. T. INDOOR AIR QUALITY - ANY APPLICABLE CODES SHALL BE INCLUDED IN THE BID. AFTER THE CONTRACT IS ISSUED NO ADDITIONAL COST -DUE TO CODE ISSUES SHALL BE REIMBURSED BY THE SUBCONTRACTORS TO FURNISH SHOP DRAWINGS AND SUBMITTALS 09 ANY AND ALL EQUIPMENT DUCT, DAMPERS, CONTROLS ETC. TO THE ARCHITECT FOR THEIR REVIEW B. HVAC EQUIPMENT (REFER TO PLANS FOR SCHEDULE OF EQUIPMENTS 3. FLEXIBLE DUCT SHALL NOT EXTEND OVER 5 FEET IN LENGTH AT ANY ONE - TENANfi TO THE CONTRACTOR. PRIOR TO CONSTRUCTION. LOCATION. 1. NO ANALYSIS HAS BEEN MADE WITH REGARD TO SOURCES OR POTENTIAL 1. PRIMARY HVAC UNITS ARE TO BE AS SCHEDULED. EQUIVALENTS MAY BE __ SOURCES OF INDOOR OR OUTDOOR AIR CONTAMINANTS OR LEVELS OF D. LICENSES, PERMITS, INSPECTIONS AND FEES J. RECORD DRAWINGS - (CONFIRM REQ'D WITH TENANT &LANDLORD) SUBSTITUTED WITH WRITTEN APPROVAL ONLY. ALL COMPRESSORS ARE TO INCLUDE A L SUPPLY AND RETURN AIR TAKEOFF FITTINGS CONTAMINATION. 1. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL LICENSES, PERMITS, 5 YEAR EXTENDED WARRANTY. 1. RECTANGULAR DUCT 2. IT IS THE RESPONSIBILITY OF THE GENERAL AND MECHANICAL CONTRACTOR TO INSPECTIONS AND FEES REQUIRED OR RELATED TO THIS WORK. 1. THE CONTRACTOR SHALL MAINTAIN ONE COPY OF DRAWINGS AND SPECIFICATIONS ON THE JOB SITE TO RECORD DEVIATIONS FROM CONTRACT 2. ALL EQUIPMENT SHALL BE COMPLETE IN EVERY RESPECT WITH ALL DEVICES, INFORM THE TENANT'S REPRESENTATIVE LANDLORD AND TENANT'S ARCHITECT IF ANY SOURCE OR POTENTIAL SOURCE 2. FURNISH TO THE TENANTS CONSTRUCTION MANAGER ALL CERTIFICATES OF DRAWINGS, SUCH AS LOCATIONS OF CONCEALED PIPING VALVES AND DUCTS � APPURTENANCES AND ACCESSORIES PROVIDED TO MEET THE DESIGN INTENT AND OPERATION OF THE SYSTEMS SHOWN ON THE DRAWINGS AND SPECIFIED. A. PROVIDE 45 DEGREE RECTANGULAR TAKEOFFS FROM MAIN DUCTWORK TO RECTANGULAR BRANCHES. OF INDbOR AIR CONTAMINATION IS IDENTIFIED. INSPECTION AND FINAL INSPECTION APPROVAL AT COMPLETION OF PROJECT. - REVISIONS ADDENDUM'S AND CHANGE ORDERS SIGNIFICANT DEVIATIONS MADE NECESSAR'( BY FIELD CONDITIONS, APPROVED LQUIPMENT SUBSTITUTIONS AND - 3. EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE 2. SPIRAL DUCT 3. PRIOR TO ENCLOSING SPACES SUCH AS PLUMBING CHASES, AIR SHAFTS AND RETURN AIR PLENUMS CLEAN ALL AREAS THOROUGHLY. THE CONTRACTOR SHALL E DRAWINGS CONTRACTOR'S COORDINATION WITH OTHER TRADES AND EXACT ROUTING OF ALL MANUFACTURERS INSTRUCTIONS. ALL AIR CONDITIONING EQUIPMENT MUST HAVE A GUARANTEE THAT THE PLENUM CHAMBER USED FOR RECIRCULATING OF AIR WILL BE - SANITARY AND DOMESTIC WATER PIPING UNDER FLOOR. CONDENSATE DRAIN AND BE TRAPPED IN ACCORDANCE WITH MANUFACTURER S A. PROVIDE SADDLE OR DIRECT CONNECTION OF A BRANCH DUCT INTO A LARGER OF TIGHT CONSTRUCTION AND THAT ALL SOURCES OF CONTAMINATION FROM TRAPS, 1. DRAWINGS PLANS AND SPECIFICATIONS ARE DIAGRAMMATIC I ( ) RTIC AND INDICATE THE 2. AT COMPLETION OF THE PROJECT AND BEFORE FINAL APPROVAL THE DATA. SEE DRAWINGS FOR ADDITIONAL DETAILS. DUCT. THE DIAMETER OF THE BRANCH SHALL NOT EXCEED TWO THIRDS OF THE DIAMETER OF THE MAIN. PROTRUSIONS INTO THE MAIN ARE NOT ALLOWED. SOIL STACKS DOWNSPOUTS VENTS EXHAUST DISCHARGES AND OTHER SOURCES WILL BE ENCLOSED SO THAT NO CGNTAMINATED AIR WILL BE RECIRCULATED. GENERAL LOCATION AND INTENT OF THE MECHANICAL SYSTEMS. BECAUSE OF THE SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL DUCT AND PIPE CONTRACTOR SHALL MAKE ANY FINAL CORRECTIONS TO DRAWINGS ANb CERTIFY THE 4. SECONDARY DRAIN PANS ARE REQUIRED TO BE INSTALLED BENEATH ALL OFFSETS FITTINGS AND ACCESSORIES THAT MAY BE REQUIRED. THE MECHANICAL ACCURACY OF EACH PRINT BY SIGNATURE THEREON. THE DRAWINGS ARE TO BE INDOOR AIR CONDITIONING EQUIPMENT WITH THE EXCEPTION OF AIR TERMINAL BOXES. N. DAMPERS 4. PRIOR TO COMMENCING CONSTRUCTION ACTIVITIES SHUT OFF THE HVAC SYSTEM, CONTRAG�TOR MUST OBTAIN APPROVED CONSTRUCTION DRAWINGS FROM THE GENERAL TURNED OVER TO THE TENANT. SECONDARY PANS ARE TO PROTECT ENTIRE UNIT. PROVIDE CONDENSATE PUMPS AS 1 PRUf6�MANUAL LOCKING QUADRANT VOLUME CONTROL DAMPERS WITH BLOCK OFF ALL AIR GRILLS DIFFUSERS AND OTHER OPENINGS OUTSIDE THE IMMEDIATE AREA. CONTRACTOR BEFORE BEGINNING ANY WORK., K. GUARANTEE. WARRANTY - REQUIRED. CONDENSATE SHALL BE DIRECTED TO MOP SINK, LAVATORY TRAP OR HANDLE OPERATORS IN EACH BRANCH DUCT AND AS SHOWN ON PLANS TO FACILITATE AIR BALANCING. CONSTRUCTION OPENINGS TO ADJACENT TENANT SPACES SHALL BE COVERED WITH FILTER MEDIA TO PREVENT DUST AND OTHER AIRBORNE 2. LAYOUT SHOWN ON THE DRAWINGS IS BASED ON A PARTICULAR MAKE OF OTHER APPROVED DRAIN. CONTAMINANTS FROM PASSING TO ADJOINING SPACES. UIPTHE EQUIPMENT. IF ANOTHER MAKE OF EQUIPMENT IS USED WHICH REQUIRES 1. THE MECHANICAL CONTRACTOR SHALL INCLUDE IN THE PROPOSAL A ONE YEAR C. TOILET EXHAUST FANS 2. -WHERE ACCESS TO BALANCING DAMPER IS RESTRICTED OR IN AREAS WITH MODIFICATION OR CHANGE OF ANY DESCRIPTION FROM D 0 F M THE DRAWINGS OR GUARANTEE WARRANTY ON ALL EQUIPMENT AND Q T MATERIAL INSTALLED 0 R REFURBISHED SHEET ROCK CEILINGS, E LINGS YOUNG REGULATORS SHALL BE USED. D 5. CONTRACTOR TO INSTALL TEMPORARY EXHAUST SYSTEM TO VENTILATE . SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE AS PART OF THIS WORK, FOR ALL MATERIALS AND WORK UN A TE R DER THE CONTRACT AND GOOD REPAID, OR REPLACE AT THEIR OWN EXPENSE, ANY DEFECTIVE WORKL MAKE 1. WHERE SHOWN ON DRAWINGS PROVIDE A TOILET EXHAUST FAN COMPLETE WITH 3. ALL RECTANGULAR PERS IN OUTSIDE AIR AND RELIEF AIR DUCTS ARE TO 0 CONSTRUCTION SITE AND UNDER HOURS OF CONSTRUCTION, EVEN SITE RNORMAL NEGATIVE PRESSURE DURING ALL BUSINESS HOURS. MAKING ALL SUCH MODIFICATIONS AND CHANGES INCLUDING THOSE INVOLVING OTHER TRADES WITH THE COST THEREOF INCLUDED IN THE BID. IN SUCH CASE - MATERIAL OR EQUIPMENT WHICH MAY BE DISCOVERED WITHIN A PERIOD OF i2 _ GRAVITY BACKDRAFT DAMPER. ALL DUCTWORK, ROOF OPENINGS AND CAPSDAM NECESSARY TO PROVIDE A COMPLETE EXHAUST SYSTEM SHALL BE PROVIDED BY THE BE OPPOSED BLADE TYPE. ALL RECTANGULAR DAMPERS IN RETURN AIR DUCTS TO CONTRACTOR SHALL SUBMIT DRAWINGS AND SPECIFICATIONS PRIOR TO STARTIUG MONTHS FROM THE DATE OF WRITTEN ACCEPTANCE OF THE INSTALLATION BY THE CONTRACTOR. REFER TO PLANS FOR APPLICABILITY. BE PARALLEL BLADE TYPE. ALL OUTSIDE AIR DUCT DAMPERS MUST ALSO BE OF THE 6. CONTRACTOR TO INSTALL TEMPORARY BARRIERS TO PROTECT ADJACENT - WORK SHOWING ALL SUCH MODIFICATIONS AND CHANGES. THE PROPOSAL SHALL BE TENANT'S CONSTRUCTION MANAGER. IN CASE OF REPLACEMENT OR REPAIR OF LOW LEAKAGE TYPE. SPACES FROM DUST PARTICULATES, VAPORS AND NOISE. WHERE TEMPORARY BARRIERS SUBJECT TO THE APPROVAL OF THE TENANT'S CONSTRUCTION MANAGER. EQUIPMENT DUE TO FAILURE WITHIN THE GUARANTEE PERIOD, THE GUARANTEE ON - ARE INSTALLED ALWAYS MAINTAIN FIRE EXITS AND EXITWAYS. THAT PORTION OF WORK SHALL BE EXTENDED FOR A PERIOD OF 12 MONTHS FROM D. VIBRATION ISOLATION DEVICES 4. ALL MOTORIZED DAMPERS NOT FURNISHED WITH EQUIPMENT ARE TO BE - F. EXISTING LEASE SPACE CONDITIONS THE DATE OF SUCH REPLACEMENT OR REPAIR. THIS GUARANTEE, WARRANTY IS TO HONEYWELL DAMPERS. - 1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF THE INCLUDE ALL LABOR MATERIAL PARTS ETC. NECESSARY TO MAINTAIN THE SYSTEM. IN SATISFACTORY OftRATION ROR A PtRIOD OF ONE YEAR STARTING FROM THE 1 . VIBRATING EQUIPMENT HUNG FROM STRUCTURE SHALL BE ISOLATED WITH 0. DIFFUSERS. GRILLES AND REGISTERS DEMOLITION OF EXISTING MECHANICAL WORK IN THE SPACE NOT SHOWN TO BE REUSED IN THE NEW TENANT SPACE. DATE OF ACCEPTANCE OF THE SYSTEM BY THE TENANT. IT SHALL ALSO INCLUDE ONE SUMMER TO WINTER CHANGEOVER AND ONE WINTER TO SUMMER CHANGEOVER � RUBBER AND SPRING DEVICES. VIBRATING EQUIPMENT SUPPORTED FROM FLOOR OR DECK SHALL BE ISOLATED WITH HOUSED SPRING MOUNT DEVICES. 1. PROVIDE DIFFUSERS GRILLES AND REGISTERS AS SCHEDULED. DEVICES TO BE A NEW SET OF FILTERS AT THE TIME OF STARTUP AND TWELVE (12) MONTHLY FILTER COMPLETE WITH FRAMES AND ALL ACCESSORIES. ALL DIFFUSERS GRILLES AND 2. THE CONTRACTOR SHALL INCLUDE AND WILL BE HELD RESPONSIBLE FOR THE CHANGES DURING THE FIRST YEAR. THE NORMAL PREVENTATIVE MAINTENANCE WORK 2. EXAMINE DEAD LOAD AND OPERATING LOAD CONDITIONS WHEN SELECTING REGISTERS IN SHEET ROCK CEILINGS TO BE PROVIDED WITH PLASTER FRAMES. FINISH C #40 REMOVAL OF ALL EXISTING FIRE PROTECTION PLUMBING FIXTURES PIPING HVA SHALL BE PERFORMED AT THE TIME OF THE FILTER CHANGES. USE ONLY DEVICES. ADJUST FOR PROPER ALIGNMENT AND LOADING. AVOID "GROUNDING" THE TO BE COORDINATED WITH INTERIOR FINISHES. - . UNITS REFRIGERANT RECAPTURE EXHAUST DANS DUCTWORK Et. AND ASSOCIATED PLEATED TYPE AIR FILTERS. ISOLATOR. ROOF CURBS NOT TO BE REUSE6 ON THIS PROJECT UNLESS' SPECIFICALLY NOTED AL 2. INSTALL ALL AIR DEVICES AS LOCATED ON THE ARCHITECTURAL REFLECTED OTHERWISE. CONTRACTOR MUST VERIFY WITH THE LANDLORD ALL PRESUMED L OPERATIONS MANUALS 3. CHECK HANGER ROD SIZE FOR ALLOWABLE LOADS AT THE ISOLATING DEVICE CEILING PLAN THE MECHANICAL PLAN. - . ABANDONED EQUIPMENT, PIPES DUCTWORK AND EQUIPMENT PRIOR TO REMOVAL. ROOF CURBS SHALL BE REM0IJED AND THE ROOF PATCHED UNLESS NOTED FOR 1. ONE COPY OF EACH OPERATION AND MAINTENANCE MANUAL FOR ALL AND THE UPPER AND LOWER ATTACHMENTS TO STRUCTURES DUCTS EQUIPMENT ETC. P. DUCTWORK INSULATION - REUSE OR RECONFIGURATION ON PLANS. ROOF PATCHING SHALL BE PERFORMED AT EQUIPMENT FURNISHED ON THE JOB SHALL BE PROVIDED TO THE TENANT BOUND . THE CONTRACTOR'S EXPENSE BY A ROOFING CONTRACTOR APPROVED BY THE TOGETHER IN A 3 INCH THREE RING BINDER. THE BINDER SHALL INCLUDE BUT NOT BE LIMITED TO INSTALLATION, MAINTENANCE AND OPERATING 4. CONSULT MANUFACTURER FOR APPLICATION DATA. 1. ALL NEW SUPPLY AND RETURN AIR DUCTWORK WITHIN 10' OF HVAC UNIT SHALL LANDLORD. ALL EXTRANEOUS ITEMS IN THE SPACE OR ON THE ROOF (ABOVE THIS INSTRUCTIONS, PAMPHLETS OR BROCHURES REVIEWED SHOP DRAWINGS AND WARRANTIES OBTAINED BE ACOUSTICALLY LINED. DUCT SIZES SHOWN ON THE DRAWING ARE INTERNAL FREE - SPACE) NOT APPLICABLE TO THE NEW WORK OR PART OF THE LANDLORD'S OR ANOTHER TENANT'S ACTIVE SYSTEM MUST BE REMOVED AND ROOF/WALL/FLOOR FROM EACH MANUFACTURER OF PRINCIPAL ITEMS OF EQUIPMENT. - G. CURBS AND STEEL FRAMING FOR SUPPORT AREA SIZES. INTERNAL LINER SHALL BE 1 1 2 THICK DUCT LINER EQUIVALENT TO _ JOHNS MANVILLE "PERMACOTE LINACOUSTIC CR VALUE" 6.3) AND SHALL BE • PATCHED/REPAIRED TO MATCH THE EXISTING STRUCTURE. EXISTING ABANDONED M. SLEEVES - 1. THIS CONTRACTOR WILL PROVIDE ALL NECESSARY CURBS AND STEEL FRAMING APPLIED TO THE DUCTWORK WITH FIRE RESISTIVE ADHESIVES AND CADMIUM OR PIPES, DUCTS OR EQUIPMENT IN THE FLOOR EMBEDDED IN CONCRETE OR OTHERWISE REQUIRED TO INSTALL ALL HVAC EQUIPMENT. CURBS SHALL BE A MINIMUM OF 14 COPPER PLATED MECHANICAL FASTENERS. INACCESSIBLE ARE TO BE CUT OFF AND SEALED BELOW OR WITHIN FLOOR OR WALL 1. THE CONTRACTOR SHALL PROVIDE SLEEVES TO PROTECT EQUIPMENT OR INCHES HIGH AND OF THE SAME MANUFACTURER AS THE EQUIPMENT SUPPORTED. INSULATE UNDER THE COMPRESSOR SECTION TO PREVENT CONDENSATION. ALL 2. ALL OUTSIDE AIR AND UNEXPOSED DUCTWORK WITHIN BUILDING, EXCEPT WHERE LEVEL WHEN THEY ARE NOT REUSED IN THIS PROJECT.. FACILITIES IN THE INSTALLATION. EACH SLEEVE SHALL EXTEND THROUGH ITS RESPECTIVE FLOOR WALL, OR PARTITION AND SHALL BE CUT FLUSH WITH EACH CURBS MUST BE INSTALLED SO THAT THE TOP OF CURBS ARE "DEAD" LEVEL. ALL ACOUSTICALLY LINED, SHALL HAVE 2 INCH, FIBERGLASS DUCT WRAP INSULATION WITH - IF REQUIRED BY THE LANDLORD OR CODES, ABANDONED PIPING AND/OR DUCTWORK SURFACE EXCEPT SLEEVES THAT PENETRATE THE FLOOR, WHICH SHALL EXTEND 2 PENETRAThONS OF EXISTING STRUCTURE SHALL BE DONE IN ACCORDANCE WITH THE FSK FACING EQUIVALENT TO JOHNS MANVILLE MICROLITE XG TYPE 75 (INSTALLED . MUST BE REMOVED TO POINT OF ORIGIN. CONFIRM THE EXTENT OF DEMOLITION PRIOR INCHES ABOVE THE FLOOR. LANDLORDS GUIDELINES AT THIS CONTRACTORS EXPENSE. ALL CONNECTIONS TO R VALUE = 5.6). TO BID AND INCLUDE IN BID PROPOSAL ROOFTOP EQUIPMENT SHALL BE INSIDE THE CURB (CONDENSATE DRAIN, POWER 2. ALL SLEEVES AND OPENINGS THROUGH FIRE RATED WALLS AND/OR FLOORS WIRING CONTROL WIRING ETC. )• 3. LEADING EDGES OF DUCT INSULATION SHALL BE OVERLAPPED BY ADJOINING 3. ACTIVE LANDLORD OR OTHER TENANT SERVICES ENCOUNTERED IN WORK SHALL SHALL BE FIRE SEALED WITH APPROVED SEALANTS RATED FOR THE APPLICATION SO INSULATION FOR 6" MINIMUM AND THEN SEALED WITH FOIL VAPOR BARRIER ADHESIVE BE PROTECTED AND SUPPORTED. IF EXISTING SERVICES NOT ANTICIPATED REQUIRE AS TO MAINTAIN THE FIRE RATING OF THE ASSEMBLY. CONFORM TO THE U.L H. METAL DUCTWORK - NO FIBERGLASS DUCT ALLOWED AND DUCT MASTIC SO THAT NO FIBERGLASS INSULATION IS VISIBLE. - RELOCATION, CONTACT THE TENANT'S CONSTRUCTION MANAGER IMMEDIATELY. ALL ASSEMBLY RATING OF THE FLOOR OR WALL COSTS FOR REPAIR OF DAMAGES TO ACTIVE LANDLORD OR OTHER TENANT SERVICES 1. NO DUCTWORK SHALL BE FABRICATED PRIOR TO APPROVAL BY THE TENANT'S 4. ALL INSULATION ON EXISTING PIPING OR DUCTS THAT IS WETTED, DAMAGED, . DURING CONSTRUCTION SHALL BE PAID FOR BY THE CONTRACTOR CAUSING THE 3. SLEEVES IN BEARING AND MASONRY WALLS FLOORS AND PARTITIONS SHALL BE CONSTRUCTION MANAGER. DEVIATIONS FROM DESIGN MUST BE APPROVED BY DISTURBED OR REMOVED SHALL BE REPLACED. DAMAGE. STANDARD WEIGHT STEEL PIPE FINISHED WITH SMOOTH EDGES. FOR OTHER THAN TENANT'S CONSTRUCTION MANAGER PRIOR TO FABRICATION OR INSTALLATION. ALL MASONRY PARTITIONS, THROUGH SUSPENDED CEILINGS OR FOR CONCEALED VERTICAL DUCT MAINS ARE TO BE RECTANGULAR. ALL DUCT BRANCHES TO DIFFUSERS ARE TO 5. INSTALL INSULATION PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S - 4. TIE-INS AND MODIFICATIONS TO EXISTING LANDLORD SERVICES MUST BE DONE PIPING, SLEEVES SHALL BE 22 GAUGE GALVANIZED STEEL MINIMUM. BE_ ROUND SPIRAL DUCT. WRITTEN INSTRUCTIONS AND IN ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICES. WITH MINIMUM INTERRUPTION OF LANDLORD OPERATION AND DURING HOURS INSULATION MUST COMPLY WITH NFPA 90A. - SPECIFIED BY THE LANDLORD. THE CONTRACTOR IS RESPONSIBLE FOR CONFIRMING 4. DUCT SLEEVES SHALL BE MINIMUM 14 GAUGE STEEL EXACT WORKING HOURS OF THIS WORK WITH THE LANDLORD PRIOR TO SUBMITTING 2. ALL DUCTWORK SHALL BE PROVIDED AND INSTALLED IN ACCORDANCE WITH 6. ALL INSULATION SHALL HAVE A FLAME SPREAD RATING OF NOT MORE THAN 25 I - THEIR BID. THE CONTRACTOR SHALL INCLUDE IN THEIR BID ALL PREMIUM TIME REQUIRED TO PERFORM MODIFICATIONS DURING OTHER THAN NORMAL WORKING N. HANGERS SMACNA LOW VELOCITY AND "HVAC DUCT CONSTRUCTION STANDARDS MANUAL LATEST EDITION AND ASHRAE USING PRIME SHEETS OF AND A SMOKE DEVELOPED RATING OF NO HIGHER THAN WHEN TESTED IN ACCORDANCE WITH ASTM C 411 OR AS REQUIRED BY LOCAL CODES. HOURS. ALL SUCH WORK MUST BE COORDINATED WITH THE LANDLORD. 1. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, GALVANIZED STEEL. CONFORM TO THE REQUIREMENTS IN THE REFERENCED STANDARD FOR METAL THICKNESS, 'D - REINFORCING TYPES AND INTERVALS, TIE ROD APPLICATIONS AND JOINT TYPES AND 7. NOT REQ -- -- - . . .. - - -_- -_--- - -- -- -----_- - - =- . - - ---- --- - - - ; - - ----- - - - - OFF�O.1r0X\O * 10092168 -----� ED w1� It is a violation of the law for any person, unless acting under the direction of a licensed Architect, Engineer or Land Surveyor, to after an item in any way. Plans, maps, specifications, studies, and reports not containing a red ink seal imprint on the cover sheet accompanied by an original signature by the licensed professional may have been fraudulently altered and shall not be considered an original copy. Copyright Protected 2018, Larson Design Group. V) z g 0 N W Z W lx M I-- :2 "., �0 w N CL 0 c rn co Q 0 c 0 W J PROJECT NO. 11979-002 DRAWN BY EBG APPY D BY. RJG MECHANICAL SPECIFICATIONS SHEET NO. M0. - N M J LL : 0 0 CO (p U 0 E2 (o a (j) 0 0 (I) M o '- LL t1 Y z 0) 0 rNi, w N ,. C ZQ a) �U, -6t- a) > 3N a> W -v W o OWN J . . W� LL L W ir_ > O 3 0- . U 0 f_ 3 � O= O 3 L i� ,j W L l� ■ UIi,(0N U c�, cn 0 'vii 2)0 ia-`V°' rel Z 0 nor) E 3 cv ��o 0 CO L_ (6 0 _ x OCOi _jo§ d a PROJECT NO. 11979-002 DRAWN BY EBG APPY D BY. RJG MECHANICAL SPECIFICATIONS SHEET NO. M0. _ � - � - ' . � - -- - - - - -_ -- - - - _ c - - - -�-_ __ - _ - - - -_ _ - — � _ - � _ _ _� ���_��-�»-_-_�___�`� - - ___� -_�- _c -__ate=- _-_-._.moi �-___ __ - - _ _ - - — _ - _ - - _ - _ _ - -_ - _. -___ G. GENERAL REQUIREMENTS BECOMES CRUSHED, CUT, SPLIT OR DEFORMED DURING THE POURING OF THE FLOOR SLAB. N E A. GENERAL 1. SUBMIT SHOP DRAWINGS FOR PLUMBING SYSTEMS, INCLUDING BUT NOT LIMITED TO FIXTURES AND EQUIPMENT WITH J W 0 ADEQUATE DETAILS AND SCALES TO CLEARLY SHOW CONSTRUCTION. INDICATE THE OPERATING CHARACTERISTICS 0 CD U E. CUTTING, PATCHING AND DRILLING PLUMBING SYSTEMS AND EQUIPMENT G. PIPE SUPPORTS �0 1. CONFORM TO ALL GENERAL AND SPECIAL CONDITIONS OF CONTRACT AS SPECIFIED BY SITE ENGINEERS AND/OR 32Qa o W 2. CONTRACTOR SHALL REVIEW AND INDICATE HIS APPROVAL OF EACH SHOP DRAWINGS PRIOR TO SUBMITTAL FOR 1. PIPE SUPPORTS FOR HOT PIPE SHALL BE ANVIL FIG. 181 OR EQUAL. OWNER. 1. PATCH AND FINISH TO MATCH ADJACENT AREAS THAT HAVE BEEN CUT, DAMAGED OR MODIFIED AS A RESULT OF THE A. GENERAL Q W J L V) W C • � NOTED. DO NOT START WORK OR FABRICATION UNTIL SHOP DRAWINGS HAVE BEEN REVIEWED BY THE ENGINEER AND 2. VISIT SITE, CHECK FACILITIES AND CONDITIONS AND MAKE ALL NECESSARY OBSERVATIONS AND MEASUREMENTS. INSTALLATION OF THE MECHANICAL SYSTEMS. RETURNED TO THE CONTRACTOR. ao 03 3. SUBMITTALS WILL BE REVIEWED ONLY FOR GENERAL COMPLIANCE WITH THE CONTRACT DOCUMENTS AND NOT FOR NOTE CONDITIONS UNDER WHICH WORK IS TO BE PERFORMED AND TAKE ALL ITEMS INTO CONSIDERATION IN BID. 2. EXACT LOCATION OF ROOF TOP MECHANICAL UNITS SHALL BE APPROVED BY THE STRUCTURAL ENGINEER. 1. CONTRACTORS BIDDING THIS PROJECT SHALL VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH ALL CONDITIONS W.��aNa, C `° a, 3. SYSTEMS ARE TO BE COMPLETE AND WORKABLE IN ALL RESPECTS, PLACED IN OPERATION AND PROPERLY CONTRACTOR SHALL FURNISH AND INSTALL ALL SUPPLEMENTAL SUPPORT STEEL FOR EQUIPMENT AND ROOF AFFECTING THEIR WORK. SUBMISSION OF A BID ON THIS PROJECT SHALL BE CONSTRUED AS HAVING SUCH INSTALLATION. ADJUSTED. PENETRATIONS AFTER APPROVAL OF STRUCTURAL ENGINEER. 3 �0 NWr SUBMITTAL OR ACCOMPANYING DOCUMENTS THE NATURE AND REASON FOR THE VARIATIONS. 0 Ezux-) 5. EACH MANUFACTURER OR HIS REPRESENTATIVE MUST CHECK THE APPLICATION OF HIS EQUIPMENT AND CERTIFY AT KNOWLEDGE. 4. CONTRACTOR SHALL PROVIDE HIS OWN CLEAN-UP, REMOVAL AND LEGAL DISPOSAL OF ALL RUBBISH DAILY. INSULATION 2. VERIFY EXACT CONDITIONS IN FIELD AND COORDINATE WITH THESE DRAWINGS AND OTHER TRADES BEFORE 5. CONTRACTOR SHALL PROTECT HIS WORK, HIS EXISTING AND ADJACENT PROPERTY AGAINST WEATHER. BEGINNING NEW WORK. CHANGES THAT MIGHT BE NECESSARY BECAUSE OF PHYSICAL CHARACTERISTICS OF EQUIPMENT THAT HAVE NOT 6. CONTRACTOR SHALL PROTECT HIS WORK, MATERIALS, APPARATUS AND FIXTURES FROM DAMAGE. ANY WORK BEEN CALLED TO THE ENGINEER'S ATTENTION AT THE TIME OF SUBMITTAL 3. DETERMINE EXACT LOCATIONS FOR ALL EQUIPMENT, PIPING, CONDUITS AND DUCTWORK IN FIELD. MATERIALS AND METHODS A. DAMAGED BY FAILURE TO PROVIDE PROTECTION REQUIRED, SHALL BE REMOVED AND REPLACED WITH NEW MATERIAL A. PLUMBING INSULATION (AS MANUFACTURED BY OWENS CORNING, KNAUF, SCHULLER OR CERTAINTEED) 1. THIS SECTION INCLUDES BASIC PLUMBING MATERIALS AND METHODS TO COMPLEMENT OTHER SECTIONS IN THIS AT THE CONTRACTOR'S EXPENSE.- 4. COORDINATE WORK OF THIS CONTRACT WITH OTHER TRADES. CONFLICTS SHALL IMMEDIATELY BE BROUGHT TO THE B. SUPPORTS 7. ARRANGE FOR AND OBTAIN OWNER'S AND INSURANCE REPRESENTATIVE'S PERMISSION FOR ANY SERVICE 1. INSULATE ALL ABOVE GRADE HOT AND COLD WATER PIPING WITH MOLDED FIBER GLASS HAVING AN ALL SERVICE JACKET. 1. ATTENTION OF THE SITE ENGINEERS. SITE ENGINEER'S RESOLUTION TO CONFLICTS SHALL BE FINAL. SHUTDOWNS. 5. ANY DISCREPANCIES BETWEEN WHAT IS SHOWN ON DRAWINGS OR SPECIFIED AND THE ACTUAL CONDITIONS IN THE S. THE CONTRACTOR SHALL BE SOLELY' RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, SEQUENCES OF B. INSULATION THICKNESS SCHEDULE: 1) LESS THAN 2" DIAMETER PIPE: THICK -HW ANDS' THICK -CW; 2) 2"-8" DIAMETER FIELD SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE SITE ENGINEERS BEFORE PROCEEDING. ESCUTCHEONS. WHERE SURFACE IS TO RECEIVE A PAINT FINISH, MAKE ESCUTCHEONS PRIME PAINTED; OTHERWISE CONSTRUCTION AND THE SAFETY OF WORKMEN. -1" PIPE: 1-1/2" THICK. 6. BUILDING AND SURFACES DAMAGED DURING INSTALLATION SHALL BE REPAIRED, REPLACED, AND/OR RESTORED TO INSULATION. 9. NO PIPING, DUCTWORK, WIRING, ETC. SHALL BE INSTALLED OR ROUTED ABOVE ELECTRICAL PANELS AND EQUIPMENT. IDENTIFYING DEVICES AND LABELS - ORIGINAL CONDITION AFTER COMPLETION OF WORK AND BEFORE ACCEPTANCE BY OWNER. 1. PROVIDE METAL EQUIPMENT NAMEPLATES PERMANENTLY FASTENED TO EQUIPMENT WITH PERATIONAL DATA 10. THE CONTRACTOR SHALL COORDINATE AND OBTAIN A WRITTEN APPROVAL IDENTIFYING THE ELECTRICAL 1.INSULATE ALL ABOVE -GRADE, HORIZONTAL RAIN CONDUCTORS AND ROOF DRAIN SUMPS WITH ONE (1) INCH THICK MOLDED ENGRAVED OR STAMPED. _ 2. IDENTIFY ALL PIPES AND VALVES UNEXPOSED AREAS, AND ACCESSIBLE CEILINGS AND SHAFTS. CHARACTERISTICS OF ALL MECHANICAL EQUIPMENT PRIOR TO ORDERING OF EQUIPMENT. NO ADDITIONAL PAYMENT FIBER GLASS HAVING TYPE ASJ JACKET AND MANUFACTURED BY OWENS-CORNING FIBERGLASS COMPANY. B. EQUIPMENT COLOR CODE IDENTIFICATION BANDS OR MARKER BACKGROUNDS TO IDENTIFY CONTENTS OF PIPE AND DIRECTION WILL BE MADE FOR LACK OF CONTRACTOR COORDINATION OF ELECTRICAL CHARACTERISTICS. 2.INCLUDE INSULATION OF FITTINGS AND VALVES. KEEP VAPOR BARRIERS INTACT. APPLY TO MANUFACTURER'S RUNS AT NOT OVER 20 FOOT INTERVALS. 11. DURING CONSTRUCTION THE CONTRACTOR MAY UNCOVER AN EXISTING CONDITION THAT WILL HAVE TO BE RECOMMENDATIONS. 1. PLUMBING CONTRACTOR TO FURNISH ALL PLUMBING EQUIPMENT INDICATED AND/OR SCHEDULED ON THE DRAWINGS MODIFIED. ANY SUCH WORK_ WHICH COMES UNDER THE JURISDICTION OF THIS CONTRACTOR SHALL BE DONE BY THIS COMPLETE WITH BASES, ISOLATORS, SUPPORTS AND OTHER REQUIRED ACCESSORIES, CONTRACTOR WITHOUT EXTRA COST TO THE OWNER, AS THOUGH FULLY DETAILED ON PLANS AND/OR DESCRIBED PIPING AND VALVES 2. INSTALL COMPLETE AND PLACE IN PROPER OPERATION PER MANUFACTURER'S RECOMMENDATIONS, LUBRICATE AND IN THE SPECIFICATIONS. 12. ALL DIMENSIONS, MEASUREMENTS AND PROJECT CONDITIONS SHALL BE CHECKED AND VERIFIED IN THE FIELD BY ADJUST AS REQUIRED. FURNISH AND INSTALL CLEAN SET OF FILTERS PRIOR TO BALANCING. THE CONTRACTOR. REFER ALL DIFFERENCES, IN WRITING, TO THE OWNER'S REPRESENTATIVE FOR CONSIDERATION A . GENERAL 3. EQUIPMENT TO BE MADE AND MODEL AS SCHEDULED UNLESS ALTERNATE EQUIPMENT OF EQUIVALENT QUALITY AND PRIOR TO PROCEEDING WITH THE WORK. THE CONTRACTOR SHALL BEAR THE COST OF RECTIFYING WORK NOT PERFORMANCE IS SUBMITTED AS A SUBSTITUTION PRIOR TO BIDDING. ALL SUBSTITUTIONS ARE SUBJECT TO APPROVED BY THE OWNER'S REPRESENTATIVE, CAUSED BY LACK OF COORDINATION AND OR NOTIFICATION. 1. LABEL ALL PIPING AND SHOW DIRECTION OF FLOW EVERY 20 FEET ON CENTER. ACCEPTANCE WITHOUT QUALIFICATION BY OWNER, ENGINEER AND SITE ENGINEERS. 13. INSTALL ALL EQUIPMENT IN FULL ACCORDANCE WITH LOCAL CODE REQUIREMENTS, OTHER SPECIFICATION SECTION REQUIREMENTS, AND MANUFACTURER RECOMMENDATIONS. B. CONNECTIONS TO EQUIPMENT B. CODES, PERMITS, STANDARDS AND REGULATIONS 1.PROVIDE VALVED WATER CONNECTION FOR EQUIPMENT. PLUMBING INSTRUMENTS AND CONTROLS 2.INCLUDE ACCESSORIES REQUIRED BY CODE, DRAWING OR MANUFACTURER'S INSTRUCTIONS. 1. CONFORM TO ALL APPLICABLE CODES (LOCAL, STATE, NATIONAL CODES, NFPA, OSHA, ETC.). GOVERNMENT A. GENERAL REGULATIONS, UTILITY COMPANY REQUIREMENTS, AND APPLICABLE STANDARDS. C. SANITARY AND STORM SEWERS 2. OBTAIN PERMITS AND PAY ALL FEES, ARRANGE FOR ALL REQUIRED INSPECTIONS AND APPROVALS. 1. AFTER INSTALLATION, CHECK ALL EQUIPMENT AND PERFORM START UP IN ACCORDANCE WITH THE 1. PVC PIPING SHALL NOT BE INSTALLED UNLESS PERMITTED BY CODE. MANUFACTURER'S INSTRUCTIONS. C. DRAWINGS 2.. SANITARY STORM SEWER AND VENT MATERIAL SHALL BE AS FOLLOWS: OF 2• ALL PIPING SHALL BE TESTED AND FREE OF LEAKS AS REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION. 3. AS PART THE FINAL INSPECTION PROCESS, THE GENERAL CONTRACTOR SHALL SCHEDULE AND PAY FOR A COMPLETE 3. WORK THAT IS SCHEDULED TO BE CONCEALED OR INSULATED SHALL REMAIN UNCOVERED UNTIL REQUIRED TESTS 1. THE SYSTEMS AS SHOWN ON PLUMBING DRAWINGS ARE DIAGRAMMATIC. CONFIRM ALL DIMENSIONS BY FIELD SEWER LINE VIDEO INSPECTION. PROVIDE A DVD COPY OF THE ENTIRE VIDEO INSPECTION TO THE OWNER. HAVE BEEN COMPLETED. IF THE CONSTRUCTION SCHEDULE REQUIRES, ARRANGE FOR TESTS ON SECTIONS OF THE 2. MEASUREMENT. THE EXACT LOCATIONS FOR FIXTURES, EQUIPMENT AND PIPING WHICH IS NOT COVERED BY DRAWINGS, SHALL BE D. ABOVE GRADE SANITARY/STORM SEWER AND VENT MATERIAL SHALL BE AS FOLLOWS: (EXISTING TIE-IN FOR ROOF DRAIN IS SYSTEM AT A TIME. SCH 40 PVC) 4. BALANCE ALL SYSTEMS, CALIBRATE CONTROLS, CHECK FOR PROPER OPERATION AND SEQUENCE UNDER ALL OBTAINED FROM .THE SITE ENGINEERS OR HIS REPRESENTATIVE IN THE FIELD AND THE WORK SHALL BE LAID OUT. CONDITIONS AND MAKE ALL NECESSARY ADJUSTMENTS. ACCORDINGLY. 1. NO -HUB CAST IRON PIPE CISPI 1-301-78. 5. INSTRUCT OWNER IN OPERATION OF SYSTEMS AND SUBMIT OPERATING AND MAINTENANCE MANUAL FOR ALL D. BASE EQUIPMENT, MATERIALS AND SUBSTITUTIONS. 2. PVC-DWV PLASTIC ASTM D1785 WITH ASTM D2665 DWV SOLVENT WELD SOCKET FITTINGS. EQUIPMENT AND SYSTEMS. 3. SCHEDULE 40 GALVANIZED STEEL PIPE, ASTM A120-83 WITH CAST_ IRON SCREWED FITTINGS ANSI B16.22 1983. 6. SUBMIT AIR AND WATER BALANCE REPORT FROM INDEPENDENT AABC OR NEBB CERTIFIED SUBCONTRACTOR FOR 1. ALL EQUIPMENT AND MATERIALS SHALL BE NEW, FREE OF DEFECTS AND U.L. LABELED.ALL AIR AND WATER SYSTEMS PER AABC OR NEBB STANDARDS. 2. BASE BID MANUFACTURERS ARE INCLUDED IN THE SPECIFICATIONS OR LISTED IN THE NAME OR MAKE OF ANY E. SITE STORM AND SANITARY SEWERS ARTICLE, DEVICE, MATERIAL, FORM OF, CONSTRUCTION, FIXTURE, ETC. STATED IN THIS SPECIFICATIONS, WHETHER ORI. "OR "STANDARD". UP TO 15" -PVC PLASTIC ASTM D3034 SDR 35 WITH ASTM D3212 GASKET JOINTS. TESTING. ADJUSTING, AND BALANCING NOT THE WORDS APPROVED EQUAL" ARE USED, SHALL BE KNOWN AS A 3. ALL PROPOSALS SHALL BE BASED ON "STANDARDS" SPECIFIED. F. DOMESTIC WATER PIPING A. BALANCING, START UP AND INSTRUCTIONS 4. THE EQUIPMENT SCHEDULES ON THE DRAWINGS INDICATE MANUFACTURERS EQUIPMENT MODEL NUMBERS THAT THIS DESIGN HAS BEEN BASED ON. THE USE OF OTHER MANUFACTURES EQUIPMENT THAT IS LISTED AS ACCEPTABLE ALTERNATES AND REFLECTS ANY ADDITIONAL COST OF SUCH CHANGES SHALL BE PAID BY THE CONTRACTOR. 1. INSTALL DOMESTIC WATER PIPING AS INDICATED ON DRAWINGS. INCLUDE ALL FITTINGS, VALVES, HANGERS AND 1. AFTER EQUIPMENT IS PLACED IN OPERATION, SYSTEMS SHALL BE BALANCED WITH REPORT SUBMITTED TO OWNER. 5. SUBSTITUTIONS ARE SUBJECT TO THE APPROVAL THE OWNER. IF A SUBSTITUTION IS SUBMITTED, IT IS THE OTHER ACCESSORIES INCLUDING WATER'METER AND BACKFLOW PREVENTER. EXTEND DOMESTIC WATER PIPING TO -2. START UP AND PLACE ALL SYSTEMS IN OPERATION AND TAG ALL SWITCHES AND CONTROLS WITH PERMANENT CONTRACTOR'S RESPONSIBILITY EVALUATE IT ANDD CERTIFY THAT THE SUBSTITUTION IS EQUIVALENT IN ALL ALL FIXTURES AND EQUIPMENT REQUIRED FOR COMPLETE INSTALLATION. LABELS INSTRUCT OWNER ON PROPER OPERATION AND PREVENTATIVE MAINTENANCE OF SYSTEM. RESPECTS TO THE BASE SPECIFICATIONS. 1. INCLUDE UNIONS, OR OTHER DISCONNECT MEANS, STOPS OR VALVES FOR ISOLATION OF FIXTURES AND EQUIPMENT. 6. COORDINATE ALL APPROVED SUBSTITUTIONS. ANY COSTS RESULTING FROM SUBSTITUTION SHALL BE THE VALVES TO.BE FULLY COMPATIBLE WITH PIPING FOR SERVICE INTENDED AS MANUFACTURED BY NIBCO, CRANE OR RESPONSIBILITY OF " AND PAID FOR BY THE CONTRACTOR. APPROVED SHOP DRAWINGS DO NOT ABSOLVE THIS MILWAUKEE. INCLUDE HOSE OR DRAIN VALVES AT LOW POINTS WHERE FIXTURES CANNOT BE USED FOR DRAINAGE. CONTRACTOR FROM THIS RESPONSIBILITY. 2. DOMESTIC WATER PIPING SHALL BE AS FOLLOWS: E. ALL EQUIPMENT SHALL BE INSTALLED IN FULL ACCORDANCE WITH THE MANUFACTURER'S DATA AND INSTALLATION ABOVE "L" INSTRUCTIONS. IT IS THIS CONFORM THESE REQUIREMENTS PRIOR TO STARTING WORK. a. GRADE -TYPE HARD COPPER ASTM 688-832. WITH WROUGHT COPPER FITTINGS ASTM 616.22 1980 AND NON -LEAD OR ANTIMONY SOLDER JOINTS. F. WARRANTY b. BELOW GRADE - TYPE "K" SOFT COPPER WITHOUT JOINTS. C. FLUSH, VENT AND SANITIZE ALL WATER PIPING WITH CHLORINE AS REQUIRED PER AWWA, LOCAL BUILDING - 1. FULLY WARRANT ALL MATERIALS, EQUIPMENT AND WORKMANSHIP FOR (1) YEAR FROM DATE OF ACCEPTANCE. DEPARTMENT AND HEALTH DEPARTMENT CODES. 2. EXTEND ALL MANUFACTURERS' WARRANTIES TO OWNER. d. DOMESTIC HOT AND COLD WATER PIPING UNDER CONCRETE FLOOR TO BE COVERED WITH SAND SO THAT 3. REPAIR OR REPLACE WITHOUT CHARGE TO THE OWNER ALL ITEMS FOUND DEFECTIVE DURING THE WARRANTY PIPING WILL NOT BECOME EMBEDDED IN THE FLOOR SLAB. PERIOD. IN THE CASE OF REPLACEMENT OR REPAIR DUE TO FAILURE WITHIN THE WARRANTY PERIOD, THE WARRANTY 4. ALL PIPING UNDER "K" ON THAT PORTION OF THE WORK SHALL BE EXTENDED FOR A MINIMUM PERIOD OF ONE (1) YEAR FROM THE DATE OF CONCRETE FLOOR SHALL BE TYPE SOFT COPPER, CONTINUOUS. NO SPLICES OR FITTINGS WILL SUCH REPLACEMENT OR REPAIR. BE ALLOWED. 5. EXTREME CAUTION MUST BE TAKEN SO THAT NO COPPER PIPING AND INSULATION UNDER CONCRETE FLOORS G. SHOP DRAWING SUBMITTALS BECOMES CRUSHED, CUT, SPLIT OR DEFORMED DURING THE POURING OF THE FLOOR SLAB. N E 6. ALL PIPING UNDER CONCRETE FLOORS SHALL BE COVERED INSIDE A PVC PIPE 0 1. SUBMIT SHOP DRAWINGS FOR PLUMBING SYSTEMS, INCLUDING BUT NOT LIMITED TO FIXTURES AND EQUIPMENT WITH J W 0 ADEQUATE DETAILS AND SCALES TO CLEARLY SHOW CONSTRUCTION. INDICATE THE OPERATING CHARACTERISTICS 0 CD U FOR EACH REQUIRED ITEM. CLEARLY IDENTIFY EACH ITEM ON THE SUBMITTAL AS TO MARK, LOCATION AND USE, USING G. PIPE SUPPORTS �0 m i40 SAME IDENTIFICATION AS PROVIDED ON THE CONSTRUCTION DOCUMENTS. 32Qa o W 2. CONTRACTOR SHALL REVIEW AND INDICATE HIS APPROVAL OF EACH SHOP DRAWINGS PRIOR TO SUBMITTAL FOR 1. PIPE SUPPORTS FOR HOT PIPE SHALL BE ANVIL FIG. 181 OR EQUAL. z REVIEW. SHOP DRAWINGS WILL NOT BE REVIEWED BY THE ENGINEER UNLESS THE CONTRACTOR'S APPROVAL IS 2. PIPE SUPPORTS FOR NATURAL GAS SHALL BE ANVIL FIG. 260 OR EQUAL. Q W J L V) W C • � NOTED. DO NOT START WORK OR FABRICATION UNTIL SHOP DRAWINGS HAVE BEEN REVIEWED BY THE ENGINEER AND rn j J 0 RETURNED TO THE CONTRACTOR. ao 03 3. SUBMITTALS WILL BE REVIEWED ONLY FOR GENERAL COMPLIANCE WITH THE CONTRACT DOCUMENTS AND NOT FOR J `O O ■ 6 CD C14 DIMENSIONS OR QUANTITIES. THE SUBMITTAL REVIEW SHALL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY W.��aNa, C `° a, FOR PURCHASE OF ANY ITEM IN FULL COMPLIANCE WITH THE CONTRACT DOCUMENTS OR ITS COMPLETE AND PROPER Vi Z INSTALLATION. 4. WHERE SUBMITTALS VARY FROM THE CONTRACT REQUIREMENTS, THE CONTRACTOR SHALL CLEARLY INDICATE ON 3 �0 NWr SUBMITTAL OR ACCOMPANYING DOCUMENTS THE NATURE AND REASON FOR THE VARIATIONS. 0 Ezux-) 5. EACH MANUFACTURER OR HIS REPRESENTATIVE MUST CHECK THE APPLICATION OF HIS EQUIPMENT AND CERTIFY AT TIME OF SHOP DRAWING SUBMITTAL THAT THE EQUIPMENT SPECIFIED HAS BEEN PROPERLY APPLIED AND CAN BE T INSTALLED, SERVICED AND MAINTAINED WHERE INDICATED ON THE DRAWINGS. ADVISE ENGINEER IN WRITING WITH SUBMITTAL DRAWINGS OF ANY POTENTIAL PROBLEMS. THE MANUFACTURER SHALL BE RESPONSIBLE FOR ANY CHANGES THAT MIGHT BE NECESSARY BECAUSE OF PHYSICAL CHARACTERISTICS OF EQUIPMENT THAT HAVE NOT BEEN CALLED TO THE ENGINEER'S ATTENTION AT THE TIME OF SUBMITTAL BASIC MATERIALS AND METHODS A. GENERAL 1. THIS SECTION INCLUDES BASIC PLUMBING MATERIALS AND METHODS TO COMPLEMENT OTHER SECTIONS IN THIS SPECIFICATION AND REQUIREMENTS INDICATED ON THE MECHANICAL DRAWINGS. B. SUPPORTS AND HANGERS 1. INSTALL HANGERS, SUPPORTS, CLAMPS AND ATTACHMENTS AS REQUIRED TO PROPERLY SUPPORT PIPING FROM BUILDING STRUCTURE.. THE INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS OF MSS SP -69 AND SP -89. C. ESCUTCHEONS 1. FIT ALL PIPE PASSING THROUGH WALLS, FLOORS OR CEILINGS IN FINISHED ROOMS WITH STEEL OR BRASS ESCUTCHEONS. WHERE SURFACE IS TO RECEIVE A PAINT FINISH, MAKE ESCUTCHEONS PRIME PAINTED; OTHERWISE MAKE ESCUTCHEONS NICKEL OR CHROME PLATED. WHERE PIPING IS INSULATED, FIT ESCUTCHEONS OUTSIDE INSULATION. D. IDENTIFYING DEVICES AND LABELS - 1. PROVIDE METAL EQUIPMENT NAMEPLATES PERMANENTLY FASTENED TO EQUIPMENT WITH PERATIONAL DATA ENGRAVED OR STAMPED. _ 2. IDENTIFY ALL PIPES AND VALVES UNEXPOSED AREAS, AND ACCESSIBLE CEILINGS AND SHAFTS. 3. COLOR CODE IDENTIFICATION BANDS OR MARKER BACKGROUNDS TO IDENTIFY CONTENTS OF PIPE AND DIRECTION OF FLOW LOCATED NEAR EACH VALVE AND FITTING, ON BOTH SIDES OF PIPE PASSING THROUGH WALLS AND ON LONG RUNS AT NOT OVER 20 FOOT INTERVALS. OF F� 0 4 Sep# Off, r 92103 0 It is a violation of the law for any person, unless acting under the direction of a licensed Architect, Engineer or Land Surveyor, to alter on item in any way. Plans, maps, specifications, studies, and reports not containing a red ink seal imprint on the cover sheet accompanied by an original signature by the licensed professional may have been fraudulently altered and shall not be considered an original copy. Copyright Protected 2018, Larson Design Group. A 5 O 5 N raj Z W 11K LLI � o � U W V) V) CL 0 0 c rn .N a� 0 c 0 i2 CU J PROJECT NO. 11979-002 DRAWN BY EBG APPV'D BY RJG PLUMBING SPECIFICATIONS I P0.1 N E 0 0 J W 0 0 CD U CR CL �0 m i40 32Qa o W (0 U 4-100 (1) z a� =3 W v Q W J L V) W C • � rn j J 0 WV ao 03 Q O 3 J `O O ■ 6 CD C14 W.��aNa, C `° a, U Vi Z W E - �EooM 3 �0 NWr 00 0 Ezux-) O - 2 T PROJECT NO. 11979-002 DRAWN BY EBG APPV'D BY RJG PLUMBING SPECIFICATIONS I P0.1 OFFICE 103 It is a violation of the law for any person, unless acting under - the direction of a licensed Architect. Engineer or Land Surveyor, to alter an item in any way. Plans, maps, specifications, studies, and reports not containing a red ink seal imprint on the cover sheet accompanied by an original signature by the licensed professional may have been fraudulently altered and shall not be considered an original copy. Copyright Protected 2018. Larson Design Group. RESTROOM -106 DOME 2 SCALE: 3/8»=1'-0» STIC WATER PIPING PLAN KEYED NOTES x] 1. INSTALL NEW PLUMBING FIXTURE IN LOCATION SHOWN. VERIFY SIZE AND POINT OF CONNECTION IN FIELD. 2. EXISTING MOP SINK AND WATER HEATER ABOVE TO REMAIN. FIXTURE SHALL BE CLEANED AS REQUIRED TO "LIKE NEW" CONDITION. SHOULD ANY FIXTURES REQUIRE REPLACEMENT, CONTRACTOR SHALL IMMEDIATELY NOTIFY OWNER'S REPRESENTATIVE AND SUBMIT A WRITTEN COST PROPOSAL TO REPLACE INCLUDING A TIME ESTIMATE TO COMPLETE REPAIRS. CONTRACTOR SHALL ALSO ROD DRAINS TO INSURE PROPER FLOW. 3. CONNECT NEW 4" SANITARY LINE TO EXISTING MIN. 4" SANITARY LINE. VERIFY SIZE AND POINT OF CONNECTION IN FIELD. 4• CONNECT NEW 1/2" WATER TO EXISTING 1/2" MIN. COLD WATER AND HOT WATER LINE. VERIFY SIZE AND POINT OF CONNECTION IN FIELD. 5• CONNECT BACK TO NEAREST EXISTING SANITARY VENT LINE. VERIFY EXACT LOCATION IN FIELD. 6. EXISTING LAVATORY TO BE RELOCATED. FIXTURE SHALL BE CLEANED AS REQUIRED TO "LIKE NEW" CONDITION. SHOULD ANY FIXTURES REQUIRE REPLACEMENT, CONTRACTOR SHALL IMMEDIATELY NOTIFY OWNER'S REPRESENTATIVE AND SUBMIT A WRITTEN COST PROPOSAL TO REPLACE INCLUDING A TIME ESTIMATE TO COMPLETE REPAIRS. CONTRACTOR SHALL ALSO ROD DRAINS TO INSURE PROPER FLOW. 3ENERAL NOTES A. CONTRACTOR TO VERIFY EXISTING CONDITIONS PRIOR TO ANY INSTALLATION. B. THE PLUMBING SYSTEM (SANITARY, WASTE DISTRIBUTION) AND ALL ASSOCIATED EQUIPMENT WILL BE INSTALLED AND MAINTAINED IN ACCORDANCE WITH THE FULL REQUIREMENTS OF THE PLUMBING CODE. DO NOT RUN PIPING ABOVE ELECTRICAL PANELS OR IN CODE REQUIRED CLEARANCE SPACES. COORDINATE ALL ROUTES WITH ALL TRADES PRIOR TO INSTALLATION. �. CONTRACTOR TO VERIFY EXACT TIE IN POINT AND INVERT IN FIELD. _. VENTS THROUGH ROOF SHALL NOT BE LOCATED WITHIN 10'-0" OF OUTSIDE AIR SUPPLIES. VENTS SHALL BE LOCATED NO CLOSER THAN 5-0" TO ANY PARAPET. MINIMUM U/G WASTE PIPING SHALL BE 3". CONTRACTOR TO VERIFY EXISTING WATER RISER, BACKFLOW PREVENTER, DOUBLE CHECK VALVE, AND METER ARE EXISTNG. VERIFY CODE AND WATER AUTHORITY COMPLIANCE. MODIFY EXISTING / INSTALL NEW IF / AS REQ'D. SCALE: 3/8"=1'-0" PLUMBING FIXTURE SCHEDULE LEGEND SANITARY SEWER - CONNECTIONS - - MARK DESCRIPTION MANUFACTURER MODEL # (I-- NOTES WASTE VENT COLD HOT LL W TEE - TURNED DOWN ° TEE - TURNED UP GATE VALVE BALL VALVE 0i2 CHECK VALVE oc SHUT-OFF VALVE IN VERTICAL LINE T WCO FURNISH ADA CLOSET & TANK, ADA OPEN FRONT -00- DW DOUBLE CLEANOUT ® EXISTING METER L a� 00 SEAT, FLOOR FLANGE, CLOSET BOLTS & CAPS, WAX P1 WATER CLOSET ZURN Z5560 4" 2" 1/2" - RING, SUPPLY STOP & TUBE. FLUSH CONTROL MUST LL 0 • In LL Q 7W7 ir J LLJ BE LOCATED ON THE WIDE SIDE OF THE WC (SIDE �o,� 3 O--,,cO 3 t3 Wa D CC OPPOSITE THE WALL) Z5340 METERING Z 0E0r,n FURNISHED WITH LAVATORY, ZURN Z866BO GOOSE P2 LAVATORY ZURN FAUCET ON 4" 2" 1-1/2" 1/2" 1/2" NECK FAUCET, SELF CLOSING/METERING WALL �0 v Z `n CENTERS ca o = N HANGER KIT, SUPPLY STOP AND TUBES, DRINK KIT & -j , 3 (L CO �o TAILPIECE. P3 EXISTING MOP -- -- -- -- -- -- BASIN 0 z P4 RELOCATED -- -- - CL 0 LAVATORY 0 C: cm (D WH EXISTING WATER -- -- -- -- -- -- m HEATER -- I PROJECT NO. 11979-002 DRAWN BY , EBG APPV'D BY RJG PLUMBING PLAN & DETAILS SHEET NO. NPLAN ORTH P 1 ` • 0 LEGEND SANITARY SEWER - DOMESTIC COLD WATER - - DOMESTIC HOT WATER - - - - - - PLUMBING VENT -i (I-- UNION - G ELBOW - TURNED DOWN o ELBOW - TURNED UP LL W TEE - TURNED DOWN ° TEE - TURNED UP GATE VALVE BALL VALVE 0i2 CHECK VALVE oc SHUT-OFF VALVE IN VERTICAL LINE T WCO WALL CLEANOUT -00- DW DOUBLE CLEANOUT ® EXISTING METER I PROJECT NO. 11979-002 DRAWN BY , EBG APPV'D BY RJG PLUMBING PLAN & DETAILS SHEET NO. NPLAN ORTH P 1 ` • 0 N co Z LL W Z ►� E O 0i2 co a �j z N W LL PCZ rn o IN p� LU ^ rn L a� 00 z U0 N W 00 L"' W LL 0 • In LL Q 7W7 ir J LLJ 0 I'r �o,� 3 O--,,cO 3 t3 Wa D CC C cO O N Z 0E0r,n N 3 C0 c"'� CO �0 v Z `n ca o = N Q -j , 3 (L CO �o 0 0 z CL 0 0 C: cm (D O C: 0 0 m I PROJECT NO. 11979-002 DRAWN BY , EBG APPV'D BY RJG PLUMBING PLAN & DETAILS SHEET NO. NPLAN ORTH P 1 ` • 0 co 0 LL W Z ►� E 0 0 (0 0 0i2 co a fA� O � �o LL PCZ rn o IN p� LU ^ rn Z Q 0) a� 00 z U0 N W O� L"' W LL 0 • In LL Q ir J j —1 p J — ° 0 I'r �o,� 3 O--,,cO 3 Wa 0 d ^ (D N CC C cO O 0- C14 to Kj Z 0E0r,n 3 C0 c"'� �0 v Z `n ca o = co -j , 3 (L I PROJECT NO. 11979-002 DRAWN BY , EBG APPV'D BY RJG PLUMBING PLAN & DETAILS SHEET NO. NPLAN ORTH P 1 ` • 0 SHEET NO. EO. I CAIJtllvb YVVMr\ tLLUIKII:AL JNtGIM;AIIUNJ JLALING ANU V1NL1'KUUV1NU tMtKULNI:T LtU LIUMIN1i ,t!' "�� - 0 A. PRIOR TO CONSTRUCTION & INSTALLATION, CONTRACTOR TO VERIFY EXISTING CONDITIONS AND A. ALL ELECTRICAL WORK TO CONFORM TO:- A. INSTALL FIRESTOPPING TO MAINTAIN ALL RATINGS AT ALL FIRE SEPARATIONS. A. MANUFACTURERS: bj zPit 1 NOTIFY ARCHITECT/ENGINEER OF CONFLICTS OR CONDITIONS WHICH INTERFERE WITH INSTALLATION AS SET FORTH IN CONTRACT DOCUMENTS. 1. NFPA 70 (NATIONAL ELECTRIC CODE) - CURRENT VERSION 2. NECA ELECTRICAL CONTRACTORS B. FIRE RATED SURFACE: - B. 1. AS SPECIFIED BY LIGHT FIXTURE SCHEDULE. PRODUCT DESCRIPTION: SELF-CONTAINED LED EMERGENCY LIGHTING UNIT, WITH Od - (NATIONAL ASSOCIATION) - STANDARD OF INSTALLATION 1. SEAL OPENING AT AS FOLLOWS: SELF -TEST DIAGNOSTICS. - B. CONTRACTOR RESPONSIBLE FOR ALL NEW FLOOR OPENINGS, EXCAVATIONS, AND 1 3. NETA ATS (INTERNATIONAL ELECTRICAL TESTING ASSOCIATION) - ACCEPTANCE TESTING C. INSTALL 12 GAGE STEEL SLEEVE THROUGH OPENING AND EXTENDING BEYOND MINIMUM OF 1 INCH ON C. BATTERY: 12 VOLT, NICKEL -CADMIUM TYPE, WITH 1.5 HOUR CAPACITY. * * PENETRATIONS,UNLESS SPECIFICALLY NOTED. UNLESS SPECIFICALLY NOTED, UPON COMPLETION, SPECIFICATIONS FOR ELECTRICAL POWER DISTRIBUTION EQUIPMENT AND SYSTEMS. - EACH SIDE OF BUILDING ELEMENT. D. BATTERY CHARGER: DUAL -RATE TYPE, WITH SUFFICIENT CAPACITY TO RECHARGE DISCHARGED BATTERY TO FULL CHARGE WITHIN TWELVE HOURS. ALL PENETRATIONS TO BE SEALED TO MAINTAIN FIRE RATING AS SPECIFIED ON ARCHITECTURAL 4. NFPA 72 (NATIONAL FIRE PROTECTION ASSOCIATION - NATIONAL FIRE ALARM CODE). D. SIZE SLEEVE ALLOWING MINIMUM OF 1 INCH VOID BETWEEN SLEEVE AND BUILDING ELEMENT. E. HOUSING: WHITE PLASTIC. 9 . ti C. DRAWINGS. ALL CUTTING AND PATCHING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR, UNLESS 5. ALL APPLICABLE LOCAL CODES. E. PACK VOID WITH BACKING MATERIAL. F. INDICATORS: LAMPS TO INDICATE AC ON AND RECHARGING. VOLTMETER TO INDICATE BATTERY VOLTAGE. 002168 v - CLEARLY INDICATED B. ALL WORK SHOWN ON THIS DRAWING IS THE RESPONSIBILITY OF THE CONTRACTOR, UNLB=ARLY F. SEAL ENDS OF SLEEVE WITH UL LISTED FIRE RESISTIVE SILICONE COMPOUND TO MEET FIRE RATING OF G. TEST SWITCH: TRANSFERS UNIT FROM EXTERNAL POWER SUPPLY TO INTEGRAL BATTERY SUPPLY. AS PART OF ANOTHER PRIME CONTRACT. INDICATED AS PART OF ANOTHER PRIME CONTRACT. STRUCTURE PENETRATED. H. AIM AND ADJUST LAMP FIXTURES TO PROVIDE OPTIMAL COVERAGE. � D. COORDINATE ANY NEW ROOF PENETRATIONS WITH THE OTHER TRADES. C. PROVIDE TEMPORARY POWER REQUIRED FOR ALL TRADES. 1. WHERE CABLE TRAY, BUS, CABLE BUS, CONDUIT, WIREWAY, OR TROUGH PENETRATES FIRE RATED RED AAG� E. REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO ACCOMMODATE NEW D. MATCH OWNERS EXISTING STANDARD EQUIPMENT. SURFACE, INSTALL FIRESTOPPING PRODUCT IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED EXIT SIGNS - /201 CONSTRUCTION. I E. COORDINATE WORK TO MINIMIZE OUTAGE DURATION. - INSTRUCTIONS. - A. MANUFACTURERS: F. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND EXTENSION F. OBTAIN ALL REQUIRED PERMITS & INSPECTIONS. G. NON -RATED SURFACES: 1. AS SPECIFIED IN LIGHT FIXTURE SCHEDULE. WORK. G. PROVIDE FOR ELECTRICAL INSPECTIONS AND SUBMIT REPORTS TO THE OWNER. 1. SEAL OPENING THROUGH NON -FIRE RATED ROOF OPENING AS FOLLOWS: B. PRODUCT DESCRIPTION: EXIT SIGN FIXTURE, WITH SELF -TEST DIAGNOSTICS. G. _ MAINTAIN ACCESS TO EXISTING BOXES AND OTHER INSTALLATIONS REMAINING ACTIVE AND H. SUBMIT O&M MANUALS TO OWNER UPON COMPLETION OF WORK. H. INSTALL 12 GAGE STEEL SLEEVE THROUGH OPENING AND EXTENDING BEYOND MINIMUM OF 1 INCH ON C. FACE: STENCIL FACE WITH RED LETTERS. - - REQUIRING ACCESS. MODIFY INSTALLATION OR PROVIDE ACCESS PANEL. 1. PROVIDE TRAINING SESSION FOR DESIGNATED MAINTENEANCE PERSONNEL. EACH SIDE OF BUILDING ELEMENT. - - D. DIRECTIONAL ARROWS: UNIVERSAL TYPE FOR FIELD ADJUSTMENT. H. EXTEND EXISTING RACEWAY AND BOX INSTALLATIONS USING MATERIALS AND METHODS J. PROVIDE SUBMITTALS FOR ALL ELECTRICAL EQUIPMENT, EXCLUDING WIRE, CONDUIT, AND 1. SIZE SLEEVE ALLOWING MINIMUM OF 1 INCH VOID BETWEEN SLEEVE AND BUILDING ELEMENT. E. MOUNTING: AS INDICATED ON DRAWINGS OR UNIVERSAL, FOR FIELD SELECTION. - COMPATIBLE WITH EXISTING ELECTRICAL INSTALLATIONS, OR AS SPECIFIED. FASTENERS. J. INSTALL TYPE OF FIRESTOPPING MATERIAL RECOMMENDED BY MANUFACTURER. F. BATTERY: 12 VOLT, NICKEL -CADMIUM TYPE, WITH 1.5 HOUR CAPACITY. I. CLEAN AND REPAIR EXISTING COMPONENTS TO REMAIN OR TO BE REINSTALLED. 1. HANDHOLES. 1. EXTERIOR WALL OPENINGS BELOW GRADE: ASSEMBLE RUBBER LINKS OF MECHANICAL SEAL TO G. BATTERY CHARGER: DUAL -RATE TYPE, WITH SUFFICIENT CAPACITY TO RECHARGE DISCHARGED BATTERY TO FULL CHARGE WITHIN TWELVE HOURS. J. PROVIDE ACCESS TO EXISTING WIRING CONNECTIONS REMAINING ACTIVE AND REQUIRING ACCESS. 2. - PANELBOARDS - SHOP DRAWINGS (INDICATE OUTLINE AND SUPPORT POINT DIMENSIONS, SIZE OF CONDUIT AND TIGHTEN IN PLACE, IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. H. LAMPS: LED. MODIFY INSTALLATION OR INSTALL ACCESS PANEL. VOLTAGE, MAIN BUS AMPACITY, INTEGRATED SHORT CIRCUIT AMPERE RATING, CIRCUIT 1. INPUT VOLTAGE: 120 VOLTS. K. EXTEND EXISTING CIRCUITS USING MATERIALS AND METHODS COMPATIBLE WITH EXISTING BREAKER AND FUSIBLE SWITCH ARRANGEMENT AND SIZES) AND CATALOG DATA SHOWING PANELBOARDS G. POSITION EXIT SIGN DIRECTIONAL ARROWS AS INDICATED ON DRAWINGS. ELECTRICAL INSTALLATIONS, OR AS SPECIFIED. - - SPECIFIED FEATURES OF STANDARD PRODUCTS. A. MANUFACTURERS: - L RING OUT CIRCUITS IN EXISTING PANEL AFFECTED BY THE WORK. WHERE ADDITIONAL CIRCUITS ARE 3. ENCLOSED SWITCHES - SWITCH RATINGS AND ENCLOSURE DIMENSIONS. 1. EATON/CUTLER-HAMMER. - NEEDED, REUSE CIRCUITS AVAILABLE FOR REUSE. INSTALL NEW BREAKERS. 4. DEVICES - MANUFACTURER'S CATALOG INFORMATION SHOWING DIMENSIONS, COLORS, AND 2. GE ELECTRICAL. FIRE ALARM SYSTEM M. TAG UNUSED CIRCUITS AS SPARE AND SWITCH BREAKER TO THE "OFF" POSITION. CONFIGURATIONS. 3. SIEMENS/ITE. A. SYSTEM DESCRIPTION: NONCODED ADDRESSABLE SYSTEM, WITH AUTOMATIC SENSITIVITY CONTROL OF CERTAIN SMOKE DETECTORS AND . N. WHERE EXISTING CIRCUITS ARE INDICATED TO BE REUSED, USE SENSING MEASURING DEVICES TO 5. LUMINAIRES (INCLUDING EMERGENCY & EXIT FIXTURES) - CATALOG INFORMATION SHOWING 4. SQUARE D MODEL. MULTIPLEXED SIGNAL TRANSMISSION, DEDICATED TO FIRE -ALARM SERVICE ONLY. It is a violation of the law for VERIFY CIRCUITS FEEDING PROJECT AREA OR ARE NOT IN USE. .- DIMENSIONS, RATINGS, AND PERFORMANCE DATA. B. BOLT -ON CIRCUIT BREAKER TYPE, DISTRIBUTION ,LIGHTING AND APPLIANCE BRANCH CIRCUIT-PANELBOARD. B. SUBMITTALS .- any person, unless acting under 0. PROVIDE NEW UPDATED DIRECTORIES WHERE MORE THAN THREE CIRCUITS HAVE BEEN MODIFIED K. SELECT MATERIALS, SIZES, AND TYPES OF ANCHORS, FASTENERS, AND SUPPORTS TO CARRILOADS C. PANELBOARD BUS: COPPER CURRENT CARRYING COMPONENTS, RATINGS AS INDICATED ON DRAWINGS. 1. PRODUCT DATA: FOR EACH TYPE OF PRODUCT INDICATED. the direction of a licensed Architect, Engineer or Land OR REWIRED. - OF EQUIPMENT AND RACEWAY, INCLUDING WEIGHT OF WIRE AND CABLE IN RACEWAY. FURNISH COPPER GROUND BUS IN EACH PANELBOARD; FURNISH INSULATED GROUND BUS AS INDICATED ON 2. SHOP DRAWINGS: FOR FIRE -ALARM SYSTEM. INCLUDE PLANS, ELEVATIONS, SECTIONS, DETAILS, AND ATTACHMENTS TO OTHER WORK. Surveyor, to alter an Item in P. IDENTIFY SALVAGE ITEMS IN COOPERATION WITH OWNER. REMOVE AND PROTECT ITEMS TO BE DRAWINGS. C. FIELD QUALITY -CONTROL REPORTS any way. Plans, ms. a, SALVAGED AND TURN OVER TO OWNER. - GROUNDING SYSTEMS D. MINIMUM INTEGRATED SHORT CIRCUIT RATING: 22,000 AMPERES RMS SYMMETRICAL FOR 240 VOLT 1. OPERATION AND MAINTENANCE DATA: FOR FIRE -ALARM SYSTEMS AND COMPONENTS TO INCLUDE. IN EMERGENCY, OPERATION, AND reports�nott�containngjea' redInk Q. CAREFULLY REMOVE EQUIPMENT, MATERIALS, OR FIXTURES WHICH ARE TO BE REUSED. A. GROUNDING SYSTEM RESISTANCE: 25 OHMS. - PANELBOARDS; 65,000 AMPERES RMS SYMMETRICAL FOR 480 VOLT PANELBOARDS. MAINTENANCE MANUALS. seal imprint on the cover sheet B. GROUNDING SYSTEMS: E. MOLDED CASE CIRCUIT BREAKERS: NEMA AB 1, BOLT -ON TYPE THERMAL MAGNETIC TRIP CIRCUIT BREAKERS, D. INSTALLER QUALIFICATIONS: accompanied by an original signature by the licensed MINOR ELECTRICAL DEMOLITION 1. MECHANICAL CONNECTORS: BRONZE CONNECTORS, SUITABLE FOR GROUNDING AND WITH COMMON TRIP HANDLE FOR ALL POLES, LISTED AS TYPE SWD FOR LIGHTING CIRCUITS, TYPE HACR FOR 1. PERSONNEL SHALL BE TRAINED AND CERTIFIED BY MANUFACTURER FOR INSTALLATION OF UNITS. professional may have been A. DEMOLI110N DRAWINGS ARE BASED ON CASUAL FIELD OBSERVATION AND EXISTING RECORD BONDING APPLICATIONS IN CONFIGURATIONS U ATIONS REQUIRED FOR PARTICULAR AIR CONDITIONING EQUIPMENT I EQ T C RCUITS, CLASS A GROUND FAULT INTERRUPTER CIRCUIT BREAKERS AS 2. INSTALLATION SHALL BE BY PERSONNEL CERTIFIED BY NICET AS FIRE -ALARM LE II VEL TECHNICIAN. fraudulently altered and shall a considered erect ant DOCUMENTS. REPORT DISCREPANCIES TO ARCHITECT/ENGINEER BEFORE DISTURBING EXISTING INSTALLATION. INDICATED ON DRAWINGS. DO NOT USE TANDEM CIRCUIT BREAKERS. E. OBTAIN FIRE -ALARM SYSTEM FROM SINGLE SOURCE FROM SINGLE MANUFACTURER. ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: conot py. pyre d 2nal INSTALLATION. - C. EXOTHERMIC CONNECTIONS: EXOTHERMIC MATERIALS, ACCESSORIES, AND TOOLS FOR F. ENCLOSURE: NEMA PB 1, TYPE 1 - LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION. Larson Design Group. B. CEASE OPERATIONS IMMEDIATELY WHEN STRUCTURE APPEARS TO BE IN DANGER AND NOTIFY PREPARING AND MAKING PERMANENT FIELD CONNECTIONS BETWEEN GROUNDING SYSTEM G. CABINET BOX: 6 INCHES DEEP, 20 INCHES WIDE FOR 240 VOLT AND LESS PANELBOARDS, 20 INCHES WIDE FOR F. FIRE -ALARM SIGNAL INITIATION SHALL BE BY ONE OR MORE OF THE FOLLOWING DEVICES: ARCHITECT/ENGINEER. DO NOT RESUME OPERATIONS UNTIL DIRECTED. COMPONENTS. 480 VOLT PANELBOARDS. 1. MANUAL STATIONS. I C. VERIFY WIRING AND EQUIPMENT INDICATED TO BE DEMOLISHED SERVE ONLY ABANDONED D. WIRE: STRANDED COPPER. H. CABINET FRONT: SURFACE DOOR -IN -DOOR TYPE, FASTENED WITH HINGE AND LATCH, HINGED DOOR WITH 2. HEAT DETECTORS. FACILITIES. E. GROUNDING ELECTRODE CONDUCTOR: SIZE TO MEET NFPA 70 AND LOCAL MUNICIPALITY FLUSH LOCK, METAL DIRECTORY FRAME, FINISHED IN MANUFACTURER'S STANDARD GRAY ENAMEL. OUTER 3. SMOKE DETECTORS. D. PROVIDE TEMPORARY EGRESS SIGNAGE AND EMERGENCY LIGHTING. REQUIREMENTS. PANELBOARD TRIMS SHALL COVER ALL LIVE PARTS. SWITCHING DEVICE HANDLES SHALL BE ACCESSIBLE. 4. AUTOMATIC SPRINKLER SYSTEM WATER FLOW. . E. DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILINGS SCHEDULED FOR REMOVAL. F. INSTALLATION: II. SURFACE TRIMS SHALL BE SAME HEIGHT AND WIDTH AS BOX. FLUSH TRIMS SHALL OVERLAP THE BOX BY 3/4 G. CONTINUOUSLY OPERATE ALARM NOTIFICATION APPLIANCES. - REMOVE CONDUIT, WIRE, BOXES, AND FASTENING DEVICES TO AVOID ANY INTERFERENCE WITH NEW 1. EQUIPMENT GROUNDING CONDUCTOR: INSTALL SEPARATE, INSULATED CONDUCTOR - OF AN INCH ON ALL SIDES. H. IDENTIFY ALARM AT FIRE -ALARM CONTROL UNIT AND REMOTE ANNUNCIATORS. INSTALLATION. - WITHIN EACH FEEDER AND BRANCH CIRCUIT RACEWAY. TERMINATE EACH END ON J. INSTALL RECESSED PANELBOARDS FLUSH WITH WALL FINISHES. L - _ TRANSMIT AN ALARM SIGNAL TO THE REMOTE ALARM RECEIVING STATION - F. - INSTALL TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE SUITABLE LUG, BUS, OR BUSHING. K. HEIGHT: 6 FEET TO TOP OF PANELBOARD; INSTALL PANELBOARDS TALLER THAN 6 FEET WITH BOTTOM NO J. GENERAL REQUIREMENTS FOR FIRE -ALARM CONTROL UNIT: - DURING CONSTRUCTION. 2. DO NOT FASTEN SUPPORTS TO PIPES, DUCTS, MECHANICAL EQUIPMENT, OR CONDUIT. MORE THAN 4 INCHES ABOVE FLOOR. - 1. FIELD -PROGRAMMABLE, MICROPROCESSOR -BASED, MODULAR, POWER -LIMITED DESIGN WITH ELECTRONIC, MODULES, COMPLYING WITH UL G. REMOVE EXPOSED ABANDONED WIRE, CABLE, CONDUIT, GROUNDING AND BONDING COMPONENTS, 3. OBTAIN PERMISSION FROM ARCHITECT/ENGINEER BEFORE USING POWDER -ACTUATED L. INSTALL FILLER PLATES FOR UNUSED SPACES IN PANELBOARDS. 864 AND LISTED AND LABELED BY AN NRTL. - FASTENERS AND SUPPORTS, AND ELECTRICAL IDENTIFICATION COMPONENTS, INCLUDING ANCHORS OR DRILLING OR CUTTING STRUCTURAL MEMBERS. M. PROVIDE TYPED CIRCUIT DIRECTORY FOR EACH BRANCH CIRCUIT PANELBOARD PER ARICHTECTURAL ROOM 2. ADDRESSABLE CONTROL CIRCUITS FOR OPERATION OF MECHANICAL EQUIPMENT. ABANDONED COMPONENTS ABOVE ACCESSIBLE CEILING FINISHES. CUT EMBEDDED CONDUITS DESIGNATIONS. REVISE DIRECTORY TO REFLECT CIRCUITING CHANGES TO BALANCE PHASE LOADS. 3. ALPHANUMERIC DISPLAY AND SYSTEM CONTROLS: ARRANGED FOR INTERFACE BETWEEN HUMAN OPERATOR AT FIRE -ALARM CONTROL AND SUPPORT ELEMENTS FLUSH WITH WALLS AND FLOORS. PATCH SURFACES DAMAGED BY HANGERS AND SUPPORTS N. MARK UNUSED CIRCUIT BREAKERS AS SPARE AND SWITCH TO OFF POSITION. UNIT AND ADDRESSABLE SYSTEM COMPONENTS INCLUDING ANNUNCIATION AND SUPERVISION. DISPLAY ALARM, SUPERVISORY, AND REMOVAL OF EXISTING COMPONENTS. - A. ANCHORS & FASTENERS TO BE CORROSION RESISTANT. 0. MEASURE STEADY STATE LOAD CURRENTS AT EACH PANELBOARD FEEDER; REARRANGE CIRCUITS IN COMPONENT STATUS MESSAGES AND THE PROGRAMMING AND CONTROL MENU. H. DISCONNECT ABANDONED CIRCUITS AND OUTLETS AND REMOVE ABANDONED RACEWAY, OUTLETS, B. ANCHOR AND FASTEN ELECTRICAL PRODUCTS TO BUILDING ELEMENTS AND FINISHES AS PANELBOARD TO BALANCE PHASE LOADS TO WITHIN 20 PERCENT OF EACH OTHER. MAINTAIN PROPER 4. KEYPAD: ARRANGED TO PERMIT ENTRY AND EXECUTION OF PROGRAMMING, DISPLAY, AND CONTROL COMMANDS AND TO INDICATE N BOXES, WIRE, AND CABLE INCLUDING ABOVE ACCESSIBLE CEILING FINISHES. CUT RACEWAY FLUSH FOLLOWS: PHASING FOR MULTI -WIRE BRANCH CIRCUITS. . CONTROL COMMANDS TO BE ENTERED INTO THE SYSTEM FOR CONTROL OF SMOKE -DETECTOR SENSITIVITY AND OTHER PARAMETERS. O . WITH WALLS AND FLOORS, AND PATCH SURFACES. REMOVE CONCEALED ABANDONED RACEWAY 1. CONCRETE STRUCTURAL ELEMENTS: PROVIDE EXPANSION ANCHORS. ENCLOSED SWITCHES K. ADDRESSABLE INITIATION DEVICES THAT COMMUNICATE DEVICE IDENTITY AND STATUS. US N N TO ITS SOURCE. 2. STEEL STRUCTURAL ELEMENTS: PROVIDE BEAM CLAMPS AND SPRING STEEL CLIPS. A. MANUFACTURERS: L. SMOKE SENSORS SHALL ADDITIONALLY COMMUNICATE SENSITIVITY SETTING AND ALLOW FOR ADJUSTMENT OF SENSITIVITY AT FIRE -ALARM CONTROL z w I. RECONNECT EQUIPMENT BEING DISTURBED BY RENOVATION WORK AND REQUIRED FOR CONTINUED 3. CONCRETE SURFACES: PROVIDE EXPANSION ANCHORS. 1. CUTLER -HAMMER. UNIT. lz Lj af SERVICE TO NEAREST AVAILABLE PANEL. REMOVE, RELOCATE, AND EXTEND EXISTING 4. HOLLOW MASONRY, PLASTER, AND GYPSUM BOARD PARTITIONS: PROVIDE TOGGLE BOLTS 2. SQUARE D. M. TEMPERATURE SENSORS SHALL ADDITIONALLY TEST FOR AND COMMUNICATE THE SENSITIVITY RANGE OF THE DEVICE. p., INSTALLATIONS TO ACCOMMODATE NEW CONSTRUCTION. AND HOLLOW WALL FASTENERS. 3. GE ELECTRICAL. N. ANNUNCIATOR AND DISPLAY: LIQUID -CRYSTAL TYPE, 1 LINE(S) OF 40 CHARACTERS, MINIMUM. 6 o 0 � J. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND EXTENSION 5. SOLID MASONRY WALLS: PROVIDE EXPANSION ANCHORS. 4. SIEMENS. - - 0. INITIATING DEVICE, NOTIFICATION APPLIANCE, AND SIGNALING LINE CIRCUITS: NFPA 72, CLASS B. j WORK. 6. SHEET METAL: PROVIDE SHEET METAL SCREWS. B. PRODUCT DESCRIPTION: NEMA KS 1 E TYPE HD WITH EXTERNALLY OPERABLE B HANDLE INTERLOCKED TO PREVENT P. AUTOMATICALLY TRANSMIT ALARM, SUPERVISORY, AND TROUBLE SIGNALS TO A REMOTE ALARM STATION. V K. CLEAN AND REPAIR EXISTING EQUIPMENT TO REMAIN (AFFECTED BY THE SCOPE OF THE PROJECT) 7. WOOD ELEMENTS: PROVIDE WOOD SCREWS. OPENING FRONT COVER WITH SWITCH IN ON POSITION, ENCLOSED LOAD INTERRUPTER KNIFE SWITCH. HANDLE Q. GENERAL REQUIREMENTS FOR MANUAL FIRE -ALARM BOXES: COMPLY WITH UL 38. BOXES SHALL BE FINISHED IN RED WITH MOLDED, RAISED -LETTER In OR TO BE REINSTALLED. - C. SUPPORTS: - LOCKABLE IN OFF POSITION, WITH PROVISIONS FOR THREE PADLOCKS. - OPERATING INSTRUCTIONS IN CONTRASTING COLOR; SHALL SHOW VISIBLE INDICATION OF OPERATION; AND SHALL BE MOUNTED ON RECESSED OUTLET L. PROTECT AND RETAIN POWER TO EXISTING ACTIVE EQUIPMENT REMAINING. I 1. FABRICATE SUPPORTS FROM STRUCTURAL STEEL OR FORMED STEEL MEMBERS. RIGIDLY C. SWITCH MECHANISM: TO BE QUICK -MAKE, QUICK -BREAK Q Q E K SUCH THAT, DURING NORMAL OPERATION OF THE SWITCH BOX.. IF INDICATED AS SURFACE MOUNTED, PROVIDE MANUFACTURERS SURFACE BACK BOX. M. CAP ABANDONED EMPTY CONDUIT AT BOTH ENDS AND MARK AS SPARE. WELD MEMBERS OR INSTALL HEXAGON HEAD BOLTS TO PRESENT NEAT APPEARANCE THE OPERATION OF THE CONTACTS SHALL NOT BE CAPABLE OF BEING RESTRAINED BY THE OPERATING HANDLE R. DOUBLE -ACTION MECHANISM REQUIRING TWO ACTIONS TO INITIATE AN ALARM, PULL -LEVER] TYPE; WITH INTEGRAL ADDRESSABLE MODULE ARRANGED WITH ADEQUATE STRENGTH AND RIGIDITY. INSTALL SPRING LOCK WASHERS UNDER AFTER THE CLOSING OR OPENING ACTION OF THE CONTACTS HAS STARTED. TO COMMUNICATE MANUAL -STATION STATUS (NORMAL, ALARM, OR TROUBLE) TO FIRE -ALARM CONTROL UNIT. RACEWAY AND BOXES NUTS. 2. INSTALL SURFACE MOUNTED CABINETS AND PANELBOARDS WITH MINIMUM OF FOUR D. E. FUSE CLIPS: DESIGNED TO ACCOMMODATE NEMA FU 1, CLASS R, J FUSES. ENCLOSURE: NEMA CONFIGURATION TO MEET CONDITIONS S. T. STATION RESET: KEY- OR WRENCH -OPERATED SWITCH. GENERAL REQUIREMENTS FOR SYSTEM SMOKE DETECTORS: A. PROVIDE RACEWAY AND BOXES LOCATED AS INDICATED, AND AT OTHER LOCATIONS REQUIRED ANCHORS. 1. INTERIOR DRY LOCATIONS: TYPE 1. 1. INTEGRAL ADDRESSABLE MODULE: ARRANGED TO COMMUNICATE DETECTOR STATUS NORMAL ALARM OR TROUBLE TO FIRE -ALARM (NORMAL, � ) FOR SPLICES, TAPS, WIRE PULLING EQUIPMENT CONNECTIONS AND COMPLIANCE WITH 3. IN WET AND DAMP LOCATIONS INSTALL STEEL CHANNEL SUPPORTS TO STAND CABINETS 2. EXTERIOR LOCATIONS: TYPE 3R. CONTROL UNIT. � " REGULATORY REQUIREMENTS. RACEWAY AND BOXES ARE SHOWN IN APPROXIMATE LOCATIONS AND PANELBOARDS 1 INCH OFF WALL. 3. INDUSTRIAL LOCATIONS: TYPE 4X. 2. BASE MOUNTING: DETECTOR AND ASSOCIATED ELECTRONIC COMPONENTS SHALL BE MOUNTED IN A TWIST -LOCK MODULE THAT N UNLESS DIMENSIONED. PROVIDE RACEWAY TO COMPLETE WIRING SYSTEM. 4. INSTALL SHEET METAL CHANNEL TO BRIDGE STUDS ABOVE AND BELOW CABINETS AND F. SERVICE ENTRANCE: SWITCHES IDENTIFIED FOR USE AS SERVICE EQUIPMENT ARE TO BE LABELED FOR THIS CONNECTS TO A FIXED BASE. PROVIDE TERMINALS IN THE FIXED BASE FOR CONNECTION TO BUILDING WIRING. M � ao B. UNDERGROUND MORE THAN 5 FEET OUTSIDE FOUNDATION WALL: PROVIDE SCHEDULE 80 PVC. PANELBOARDS RECESSED IN HOLLOW PARTITIONS. APPLICATION. FURNISH SOLID NEUTRAL ASSEMBLY AND EQUIPMENT GROUND BAR. 3. SELF -RESTORING: DETECTORS DO NOT REQUIRE RESETTING OR READJUSTMENT AFTER ACTUATION TO RESTORE THEM TO NORMAL OPERATION. PROVIDE CAST METAL BOXES OR NONMETALLIC HANDHOLES WHERE REQUIRED. BUILDING WIRE AND CABLE - G. FURNISH SWITCHES WITH ENTIRELY COPPER CURRENT CARRYING PARTS. 4. INTEGRAL VISUAL -INDICATING LIGHT: LED TYPE INDICATING DETECTOR HAS OPERATED AND POWER -ON STATUS a C. UNDERGROUND WITHIN 5 FEET FROM FOUNDATION WALL- PROVIDE RIGID STEEL CONDUIT OR THICKWALL NONMETALLIC CONDUIT SCHEDULE 80 PVC). PROVIDE CAST METAL OR NONMETALLIC ( ) A. PROVIDE PRODUCTS AS FOLLOWS: H. SWITCH RATING: HORSEPOWER RATED FOR AC AS INDICATED ON DRAWINGS. 5. PHOTOELECTRIC SMOKE DETECTORS: - 6. DETECTOR ADDRESS SHALL BE ACCESSIBLE FROM FIRE -ALARM CONTROL UNIT AND SHALL BE ABLE TO IDENTIFY THE DETECTOR'S o z - BOXES. - 1. SOLID CONDUCTOR FOR FEEDERS AND BRANCH CIRCUITS 10 AWG AND SMALLER. 1. SHORT CIRCUIT CURRENT RATING: 200,000 RMS SYMMETRICAL AMPERES WHEN USED WITH OR PROTECTED BY LOCATION WITHIN THE SYSTEM AND ITS SENSITIVITY SETTING. D. IN OR UNDER SLAB ON GRADE: PROVIDE THICK WALL NONMETALLIC CONDUIT. PROVIDE CAST OR 2. STRANDED CONDUCTORS FOR CONTROL CIRCUITS. 3. CONDUCTOR NOT SMALLER THAN #12 AWG FOR POWER AND LIGHTING CIRCUITS. J. CLASS R OR CLASS J FUSES (30-600 AMPERE SWITCHES EMPLOYING APPROPRIATE FUSE REJECTION SCHEMES). HEIGHT: 5 FEET TO OPERATING HANDLE. U. AN OPERATOR AT FIRE -ALARM CONTROL UNIT, HAVING THE DESIGNATED ACCESS LEVEL, SHALL BE ABLE TO MANUALLY ACCESS THE FOLLOWING FOR - Ca. E. NONMETALLICMETAL BOXES. OUTDOOR LOCATIONS, ABOVE GRADE: PROVIDE RIGID STEEL CONDUIT. PROVIDE CAST METAL OR 4. CONDUCTOR NOT SMALLER THAN #16 AWG FOR CONTROL CIRCUITS. K. INSTALL FUSES FOR FUSIBLE DISCONNECT SWITCHES. - EACH DETECTOR: 1. PRIMARY STATUS. � - o NONMETALLIC OUTLET, PULL, AND NEMA -3R RATED JUNCTION BOXES. 5. 10 AWG CONDUCTORS FOR 20 AMPERE 120 VOLT BRANCH CIRCUITS LONGER THAN 75 FEET. - 2. DEVICE TYPE. 0 F. IN SLAB ABOVE GRADE: PROVIDE THICKWALL NONMETALLIC CONDUIT. PROVIDE CAST NONMETALLIC . B. 6. 10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH CIRCUITS LONGER THAN 200 FEET. WIRING METHODS: PROVIDE THE FOLLOWING WIRING METHODS: WIRING DEVICES A. MANUFACTURERS: 3. PRESENT AVERAGE VALUE. r CM G. BOXES. WET AND DAMP LOCATIONS: PROVIDE THICKWALL NONMETALLIC CONDUIT. PROVIDE CAST METAL 1. CONCEALED DRY INTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN 1. PASS & SEYMOUR LEGRAND. - - 4. PRESENT SENSITIVITY SELECTED. 5. SENSOR RANGE (NORMAL, DIRTY ETC.). 0 OR NONMETALLIC OUTLET, NEMA -3R RATED JUNCTION, AND PULL BOXES. PROVIDE FLUSINIOUNTING INSULATION IN RACEWAY. 2. ABOVE ACCESSIBLE CEILINGS: USE ONLY BUILDING WIRE, TYPE THHN THWN INSULATION, IN / 2. HUBELL. 3. LEVITON. - V. HEAT DETECTORS GENERAL REQUIREMENTS FOR HEAT DETECTORS: COMPLY WITH UL 521. a o OUTLET BOX IN FINISHED AREAS. RACEWAY. 4. GENERAL ELECTRIC. W. REMOTE ANNUNCIATOR E2 - H. CONCEALED DRY LOCATIONS: PROVIDE ELECTRICAL METALLIC TUBING. PROVIDE SHEET -METAL 3. WET OR DAMP INTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN THWN INSULATION, / B. PRODUCT DESCRIPTION: NEMA WD 1, HEAVY-DUTY, AC ONLY SPECIFICATION GRADE SWITCH RECEPTACLE. ALL / 1. ANNUNCIATOR FUNCTIONS SHALL MATCH THOSE OF FIRE -ALARM CONTROL UNIT FOR ALARM, SUPERVISORY, AND TROUBLE - cm -j BOXES. PROVIDE FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS. PROVIDE HINGED IN RACEWAY. DEVICES TO BE SPECIFICATION GRADE OR BETTER. INDICATIONS. MANUAL SWITCHING FUNCTIONS SHALL MATCH THOSE OF FIRE -ALARM CONTROL UNIT, INCLUDING ACKNOWLEDGING, SILENCING, 1. ENCLOSURE FOR LARGE PULL BOXES. MINIMUM RACEWAY SIZE: 3/4 INCH UNLESS OTHERWISE SPECIFIED. 4. UNDERGROUND LOCATIONS: USE ONLY BUILDING WIRE TYPE THHN THWN INSULATION IN / C. BODY HANDLE: IVORY PLASTIC WITH TOGGLE HANDLE. / ESETTING, AND TESTING. - 2. MOUNTING: FLUSH CABINET, NEMA 250, TYPE 1. J. ARRANGE RACEWAY AND BOXES TO MAINTAIN HEADROOM AND PRESENT NEAT APPEARANCE. GROUP RELATED RACEWAY; SUPPORT USING CONDUIT RACK; PROVIDE SPACE ON EACH FOR 25 C. RACEWAY. WIRE AND CABLE ROUTING INDICATED IS APPROXIMATE UNLESS DIMENSIONED. INCLUDE WIRE D. E. RATINGS: MATCH BRANCH CIRCUIT AND LOAD CHARACTERISTICS, MINIMUM 20A. GFCREG RECEPTACLE: CONVENIENCE RECEPTACLE WITH INTEGRAL GROUND FAULT CIRCUIT INTERRUPTER TO MEET - 3. DISPLAY TYPE AND FUNCTIONAL PERFORMANCE: ALPHANUMERIC DISPLAY AND LED INDICATING LIGHTS SHALL MATCH THOSE OF FIRE - 9 AND CABLE LENGTHS WITHIN 10 FT OF LENGTH SHOWN. REGULATORY REQUIREMENTS. ALARM CONTROL UNIT. PROVIDE CONTROLS TO ACKNOWLEDGE, SILENCE, RESET, AND TEST FUNCTIONS FOR ALARM, SUPERVISORY, AND TROUBLE K. PERCENT ADDITIONAL RACEWAYS. RACEWAY ROUTING IS SHOWN IN APPROXIMATE LOCATIONS UNLESS DIMENSIONED. ROUTE TO D. COMPLETELY AND THOROUGHLY SWAB RACEWAY BEFORE INSTALLING WIRE. F. WP RECEPTACLE: (WEATHERPROOF) TO BE GFI PROTECTED. - X. SIGNALS. - - EQUIPMENT INSTALLATION N N �, >, .COMPLETE WIRING SYSTEM. E. F. NEATLY TRAIN AND LACE WIRING INSIDE BOXES, EQUIPMENT, AND PANELBOARDS. SPECIAL TECHNIQUES --BUILDING WIRE IN RACEWAY: WALL PLATES 1. COMPLY WITH NFPA 72 FOR INSTALLATION OF FIRE -ALARM EQUIPMENT. c7 J N Z E L. DO NOT SUPPORT RACEWAY WITH WIRE, PERFORATED PIPE STRAPS, CEILING SUPPORT WIRES OR 1. PULL CONDUCTORS INTO RACEWAY AT SAME TIME. A. MANUFACTURERS: 2. INSTALL WALL -MOUNTED EQUIPMENT WITH TOPS OF CABINETS NOT MORE THAN 72 INCHES (1830 MM) ABOVE THE FINISHED FLOOR. �3 LL r7 � o 0 M. OTHER PIPING SYSTEMS. ROUTE EXPOSED &ABOVE ACCESSIBLE CEILINGS RACEWAY PARALLEL AND PERPENDICULAR TO G. 2• INSTALL BUILDING WIRE 4 AWG AND LARGER WITH PULLING EQUIPMENT. 1. PASS & SEYMOUR LEGRAND. Y. Z. LOCATE DETECTORS NOT CLOSER THAN FEET (1 M) FROM AIR -SUPPLY DIFFUSER OR RETURN -AIR OPENING. LOCATE DETECTORS NOT CLOSER THAN 12 INCHES (300 MM) FROM ANY PART OF A LIGHTING FIXTURE. 0 12 (R a N. WALLS. DO NOT CROSS CONDUITS IN SLAB. 11. SPECIAL TECHNIQUES -CABLE: - PROTECT EXPOSED CABLE FROM DAMAGE. 2. TAYMAC 20510 (WEATHERPROOF -IN -USE). -3. HUBELL (BELL/RACO). AA. FIRE -ALARM CONTROL UNIT: SURFACE MOUNTED, WITH TOPS OF CABINETS NOT MORE THAN 72 INCHES (1830 MM) ABOVE THE FINISHED FLOOR. c O c N o 0. INSTALL NO MORE THAN EQUIVALENT OF THREE 90 DEGREE BENDS BETWEEN BOXES. INSTALL 2. SUPPORT CABLES ABOVE ACCESSIBLE CEILING, USING SPRING METAL CLIPS OR CABLE TIES 4. LEVITON. - AB. GROUND FIRE -ALARM CONTROL UNIT AND ASSOCIATED CIRCUITS; COMPLY WITH IEEE 1100. INSTALL A GROUND WIRE FROM MAIN SERVICE GROUND TO I) tL t o ''1 0) CONDUIT BODIES TO MAKE SHARP CHANGES IN DIRECTION, AS AROUND BEAMS. INSTALL FACTORY TO SUPPORT CABLES FROM STRUCTURE OR CEILING SUSPENSION SYSTEM. DO NOT REST CABLE ON CEILING PANELS. 5. GENERAL ELECTRIC. AC. FIRE -ALARM CONTROL UNIT. ENGAGE AFACTORY- AUTHORIZED SERVICE REPRESENTATIVE TO TRAIN OWNER'S MAINTENANCE PERSONNEL TO ADJUST, OPERATE. AND MAINTAIN FIRE- �[ Z Q w N n v+ 2 U v ELBOWS FOR BENDS IN METAL CONDUIT LARGER THAN 2 INCH SIZE. 3. USE SUITABLE CABLE FITTINGS AND CONNECTORS. B INSTALL DECORATIVE PLATES ON SWITCH, RECEPTACLE, AND BLANK OUTLETS IN FINISHED AREAS. ALARM SYSTEM. Z CO ap co " v -0 - P. AVOID MOISTURE TRAPS; INSTALL JUNCTION BOX WITH DRAIN FITTING AT LOW POINTS INCONDUIT SYSTEM. H. SPECIAL TECHNIQUES - DIRECT BURIAL CABL • Q E. C. DECORATIVE COVER PLATE: NYLON. INSTALL JUMBO SIZE PLATES FOR OUTLETS INSTALLED IN WALLS. JUMBO COVER PLATE: NYLON. . 3 J 2 v W L cn W e Q. INSTALL FITTINGS TO ACCOMMODATE EXPANSION AND DEFLECTION WHERE RACEWAY CROSSES 1. TRENCH AND BACKFILL FOR DIRECT BURIAL CABLE INSTALLATION. INSTALL WARNING TAPE D. .MASONRY WEATHERPROOF COVER PLATE (RECEPTACLE): IMPACT RESISTANT PLASTIC PLATE WITH HINGED AND ( ) O �-- V . LL � Q v W SEISMIC, CONTROL AND EXPANSION JOINTS. ALONG ENTIRE LENGTH OF DIRECT BURIAL CABLE, WITHIN 3 INCHES OF GRADE. - GASKETED DEVICE COVER. COVER TO BE RATED FOR WET LOCATION WHILE IN USE AND TO BE LOCKABLE. J v � - R. INSTALL SUITABLE PULL SIRING OR CORD IN EACH EMPTY RACEWAY EXCEPT SLEEVES AND 2. USE SUITABLE DIRECT BURIAL CABLE FITTINGS AND CONNECTORS. E WEATHERPROOF COVER PLATE (SWITCH): GASKETED CAST METAL PLATE WITH HINGED AND GASKETED I W V ap 0 3 NIPPLES. I. SPECIAL TECHNIQUES -WIRING CONNECTIONS: DEVICE COVER OR LEVER SWITCH MECHANISM. (P&S CA-31G/HUBBELL/BELL/RACO 5125 OR EQUAL) S. CLOSE ENDS AND UNUSED OPENINGS IN WIREWAY. 1. CLEAN CONDUCTOR SURFACES BEFORE INSTALLING LUGS AND CONNECTORS. F. KITCHEN AREAS: 302 430 STAINLESS STEEL, WEATHERPROOF FOR STARTUPS. / = ` o M 3 0 0 T. INSTALL PULL BOXES AND JUNCTION BOXES ABOVE ACCESSIBLE CEILINGS AND IN UNFINISHED 2. MAKE SPLICES TAPS AND TERMINATIONS TO A CARRY FULL AMPACITY OF CONDUCTORS WITH G. INSTALL GALVANIZED STAMPED STEEL PLATES ON OUTLET BOXES AND JUNCTION BOXES IN UNFINISHED J � v 3 (' a r, 0 CD AREAS ONLY. NO PERCEPTIBLE TEMPERATURE RISE. AREAS, ABOVE ACCESSIBLE CEILINGS, AND ON SURFACE MOUNTED OUTLETS. N to 0 U. IN ACCESSIBLE CEILING AREAS: INSTALL OUTLET AND JUNCTION BOXES NO MORE THAN 6 INCHES 3. TAPE UNINSULATED CONDUCTORS AND CONNECTORS WITH ELECTRICAL TAPE TO 150 H. INSTALL DEVICES PLUMB AND LEVEL - %' W C) U Q N FROM CEILING ACCESS PANEL OR FROM REMOVABLE RECESSED LUMINAIRE. PERCENT OF INSULATION RAZING OF CONDUCTOR. -TAP 1. INSTALL SWITCHES WITH OFF POSITION DOWN. 2 U •N � a C14 � V. LOCATE FLUSH MOUNTING BOX IN MASONRY WALL TO REQUIRE CUTTING OF MASONRY UNIT 4. INSTALL SPLIT BOLT CONNECTORS OR MULTI BLOCKS FOR COPPER CONDUCTOR J. INSTALL RECEPTACLES WITH GROUNDING POLE ON TOP, OR TO THE LEFT (IF MOUNTED HORIZONTALLY. W r7 N E i • N .CORNER ONLY. COORDINATE MASONRY CUTTING TO ACHIEVE NEAT OPENING. SPLICES AND TAPS, 6 AWG AND LARGER. K. CONNECT WIRING DEVICE GROUNDING TERMINAL TO OUTLET BOX WITH BONDING JUMPER AND BRANCH Z 0 E 0 r, n W. DO NOT INSTALL FLUSH MOUNTING BOX BACK-TO-BACK IN WALLS; INSTALL WITH MINIMUM 6 5. INSTALL SOLDERLESS PRESSURE CONNECTORS WITH INSULATING COVERS FOR COPPER CIRCUIT EQUIPMENT GROUNDING CONDUCTOR. � C o N � o INCHES SEPARATION. INSTALL WITH MINIMUM 24 INCHES SEPARATION IN ACOUSTIC RATED CONDUCTOR SPLICES AND TAPS, 8 AWG AND SMALLER. - L. CONNECT WIRING DEVICES BY WRAPPING SOLID CONDUCTOR AROUND SCREW TERMINAL. INSTALL STRANDED Q O v W C5 E In WALLS. 6. INSTALL INSULATED SPRING WIRE CONNECTORS WITH PLASTIC CAPS FOR COPPER CONDUCTOR SPLICES AND TAPS, CONDUCTOR FOR BRANCH CIRCUITS 10 AWG AND SMALLER. WHEN STRANDED CONDUCTORS ARE USED IN LIEU R Cl) o v ._ X. DO NOT FASTEN BOXES TO CEILING SUPPORT WIRES OR OTHER PIPING SYSTEMS. 10 AWG AND SMALLER. 7. TERMINATE EXISTING OF SOLID, USE CRIMP ON FORK TERMINALS FOR DEVICE TERMINATIONS. DO NOT PLACE BARE STRANDED o - Y. SUPPORT BOXES INDEPENDENTLY OF CONDUIT. ALUMINUM CONDUCTORS WITH TIN-PLATED, ALUMINUM -BODIED CONDUCTORS DIRECTLY UNDER DEVICE SCREWS. - -��� a Z. USE FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS. COMPRESSION CONNECTORS ONLY. FILL WITH ANTI -OXIDANT COMPOUND BEFORE INSTALLING M. ADJUST DEVICES AND WALL PLATES TO BE FLUSH AND LEVEL . T. AA. SET FLOOR BOXES LEVEL AND FLUSH WITH FINISH FLOORING MATERIAL CONDUCTOR. AB. INSTALL CONDUIT TO PRESERVE FIRE RESISTANCE RATING OF PARTITIONS AND OTHER 8. INSTALL SUITABLE REDUCING CONNECTORS OR MECHANICAL CONNECTOR ADAPTORS FOR INTERIOR LUMINAIRES ELEMENTS. CONNECTING ALUMINUM CONDUCTORS TO COPPER CONDUCTORS. A. ALL FIXTURES TO BE SPECIFICATION GRADE OR BETTER. AC. ROUTE CONDUIT THROUGH ROOF OPENINGS FOR PIPING AND DUCTWORK OR THROUGH SUITABLE J. GROUND CONDUCTORS: B. PERFORMANCE REQUIREMENTS: FOR AREAS OF ASSEMBLY, SUBMIT POINT -BY -POINT LIGHT LEVEL ROOF JACK WITH PITCH POCKET 1. FOR 6 AWG AND SMALLER: GREEN. CALCULATIONS WASSEMBLIES, LWITTH AD. ALIGN ADJACENT WALL MOUNTED OUTLET BOXES FOR. SWITCHES, THERMOSTATS, AND SIMILAR 2. FOR 4 AWG AND LARGER: IDENTIFY WITH GREEN TAPE AT BOTH ENDS AND VISIBLE POINTS C. PROVIDE INTERIOR LUMINAIRE FEATURES, OPTIONS, AND ACCESSORIES AS I DEVICES. INCLUDING JUNCTION BOXES. I SCHEDULED. . K. ALL WIRING SHALL BE #12 CU UNLESS SPECIFIED OTHERWISE. D. INSTALL SUSPENDED LUMINAIRES USING PENDANTS SUPPORTED FROM SWIVEL HANGERS. INSTALL PENDANT LENGTH REQUIRED TO SUSPEND LUMINAIRE AT INDICATED HEIGHT. . IDENTIFICATION E. SUPPORT LUMINAIRES LARGER THAN 2 X 4 FOOT SIZE INDEPENDENT OF CEILING FRAMING. A. IDENTIFY ELECTRICAL COMPONENTS AS FOLLOWS: F. INSTALL SURFACE MOUNTED LUMINAIRES PLUMB AND ADJUST TO ALIGN WITH BUILDING LINES AND WITH - 1. ENGRAVED LAMINATED PLASTIC NAMEPLATE FOR EACH ELECTRICAL DISTRIBUTION, EACH OTHER. SECURE TO PREVENT MOVEMENT. - CONTROL EQUIPMENT ENCLOSURE, AND COMMUNICATION CABINET. G. EXPOSED GRID CEILINGS: SUPPORT SURFACE -MOUNTED LUMINAIRES ON GRID CEILING DIRECTLY FROM 2. CLOTH TYPE WIRE MARKER FOR EACH CONDUCTOR AT PANELBOARD GUTTERS, AND PULL BUILDING. FASTEN SURFACE MOUNTED LUMINAIRES TO CEILING GRID MEMBERS USING BOLTS, SCREWS, - I BOXES. - RIVETS, OR SUITABLE CLIPS. _ 3. RACEWAY MARKER FOR EACH RACEWAY WHERE IT STUBS ABOVE THE CEILING OR BELOW H. INSTALL RECESSED LUMINAIRES TO PERMIT REMOVAL FROM BELOW. _ THE FLOOR. I. INSTALL RECESSED LUMINAIRES USING ACCESSORIES AND FIRESTOPPING MATERIALS TO MEET 4. UNDERGROUND WARNING TAPE ALONG LENGTH OF EACH UNDERGROUND RACEWAY OR REGULATORY REQUIREMENTS FOR FIRE RATING. CABLE, 3" BELOW FINISHED GRADE. TAPE TO BE 4 -INCH WIDE PLASTIC TAPE, DETECTABLE J. INSTALL CLIPS TO SECURE RECESSED GRID -SUPPORTED LUMINAIRES IN PLACE. -I - . TYPE, COLORED YELLOW WITH SUITABLE WARNING LEGEND DESCRIBING BURIED K. CONNECT LUMINAIRES TO BRANCH CIRCUIT OUTLETS USING FLEXIBLE CONDUIT. MAXIMUM LENGTH FIXTURE - - ELECTRICAL LINES. WHIP TO BE 5 FEET. PROJECT NO. 11979-002 L. MAKE WIRING CONNECTIONS TO BRANCH CIRCUIT USING BUILDING WIRE WITH INSULATION SUITABLE FOR _ - TEMPERATURE CONDITIONS WITHIN LUMINAIRE. DRAWN BY EBG M. AIM AND ADJUST LUMINAIRES TO PROVIDE LIGHT LEVELS CONSISTENT WITH DESIGN. APPV'D BY RJG ELECTRICAL SPECIFICATIONS SHEET NO. EO. I C