HomeMy WebLinkAbout3700 Narcissus Ave- Northport BLDG 1Fire Pump Curve 140 120 100 d 80 / 5 N N d y 60 a Z 40 20 50 100 1S0 FIRE PUMP ACCEPTANCE TEST DATA - Refer to P&P F(A) - 512.128,DS 3-7N Northport Building 1 3700 Narcissus Avenue Sanford, Florida TESTED BY BGM 6/3/2020 PUMP Fairbanks Horizontal Split -case ISerial 19-2575517 IModel 6" 1823CF Approved Rated GPM 1500 Rated Head-ft(PSI) 90 Rated RPM 1775 DRIVER Weg Electric Motor HP 1 125 Model 404TS Approved Rated Volt 460 Operating Volt 486 3 Phase 60 Cycles Rated FL Amps 139 Amps at 150% 128 Service Factor 1.15 CONTROLLER Eaton Jockey On (PSI) Jockey off (PSI) 145 160 Serial # Model 16F2281E-1 FD70-125D Approved Automatic Start (PSI) 130 Stop (PSI) 140 Pressures in PSI Streams Speed (RPM) Discharge Suction Net Pressure Pressure Pressure No Size Pitot Pressure GPM % Rated Capacity Volts Amps 1794 169 62 107 1 0 0 0 0 487 68 1787 156 52 104 2 1-3/4" 18 750 50 486 96 1783 125 31 94 3 1-3/4" 32 1500 100 486 123 1781 80 0 80 5 1-3/4" 25 2250 150 486 128 Fire Pump Curve 140 120 100 d 80 / 5 N N d y 60 a Z 40 20 50 100 1S0 7.rs t 12/13/2019 ® Fairbanks Morse Certified By Date MURRAY EQUIPMENT SALES INC Customer Sales Order: 2797895 Sire: 6"-1823CF Type: A.P.M.: 1770 Stage: 1 Spec. Gravity: 1.0 Imp. Dia.: 15.625 NO/Serial No.: 2575517 Curve No: 306454 Teat No: 1219231 Plotted By: 4646, TF Data: 12/13/2019 CAPACITY - U.S. GALLONS PER MINUTE Fff 0 100 90 80 70 60 50 B.H.P. 40 400 30 300 20 200 10 100 0 0