Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
3700 Narcissus Ave- Northport BLDG 2
140 120 100 v 80 N d a` 60 40 20 Fire Pump Curve 50 100 135 FIRE PUMP ACCEPTANCE TEST DATA - Refer to P&P F(A) - 512.12&DS 3-7N Northport Building 2 3700 Narcissus Avenue Sanford, Florida TESTEDBY BBGM 6/3/2020 PUMP Fairbanks Horizontal Split -case Serial 19-2576065 Model 6" 1823CF Approved Rated GPM 1500 Rated Head-ft(PSI) 90 Rated RPM 1775 DRIVER Weg Electric Motor HP 125 Model 404T5 Approved Rated Volt 460 Operating Volt 485 3 Phase 60 Cycles Rated FL Amps 139 Amps at 150% 131 Service Factor 1.15 CONTROLLER Eaton Jockey On (PSI) Jockey off (PSI) 145 160 Serial # Model 16F2281E-2 FD70-125D Approved Automatic Start (PSI) 130 Stop (PSI) 140 Pressures in PSI Streams Speed (RPM) Discharge Pressure Suction Net Pressure Pressure No Size Pitot Pressure GPM % Rated Capacity Volts Amps 1793 165 58 107 0 0 0 0 486 68 1788 155 49 106 2 1-3/4" 18 750 50 486 96 1785 120 24 96 3 1-3/4" 32 1500 100 485 123 1783 90 0 90 5 1-3/4" 25,25,24 2036 135 484 131 14,14 140 120 100 v 80 N d a` 60 40 20 Fire Pump Curve 50 100 135 �L — 12/16/2019 Certified By Date rii� aERR PENTAIR MURRAY EQUIPMENT SALES INC Customer Sales order: 2797895-A Size: 6--1823CF Type: A.P.M.: 1770 Stage: 1 Spec. Gravity: 1.0 Imp. Dia.: 15.625 ND/Serial No.: 2576065 Curve No: 306971 Test No: 1219253 Plotted BY: 4646, TF Date: 12/16/2019 CAPACITY - U.S. GALLONS PER MINUTE Eff. % 100 90 80 70 60 50 B.H.P. 40 200 30 150 20 1 100 10 50 0 0 2500