Loading...
HomeMy WebLinkAbout1700 OLD ENGLAND LOOP (A) 01-000117 (10)6. Provide an approved digital communicator to transmit the fire alarm and supervisory signals to a central station. The digital communicator shall be UL and FM listed for fire reporting to a central station and shall conform to the requirements to NFPA 71, 7. Fire Alarm Systems wiring: alarm initiating circuits shall be 16 AWG stranded or larger, with 7 stands (maximum), or 14 AWG solid. Alarm indicating circuits shall be 14 AWG solid or larger. Install per manufacturers wiring diagrams. 8. Provide surge protector on all FACP power circuits and all communications lines between buildings as recommended by the equipment manufacturer. D. SCOPE: 1. Provide a fire alarm control panel in each building to monitor pull stations and sprinkler system tamper and flow switches. 2. Digital communicator shall notify independant monitoring company and fire station, This signal shall precisely identify the address and number of the building in alarm. PART 3 - EXECUTION 3.01 APPARATUS IDENTIFICATION A. Ponelboord, circuit breakers in ponelboards, motor disconnect switches, starters and other apparatus used for the operation or control of, circuits, appliances or equipment shall be properly identified by means of engraved laminated plastic descriptive nameplates mounted on the apparatus using contact cement. Cardholders in any form are acceptable in the living units. 3.02 GROUNDING A A separate grounding conductor, sized in accordance with NEC Table 250-95 shall be provided in the conduit with the circuit conductors for all lighting, power and feeder circuits. B. All electrical equipment enclosures and conductor enclosures shall be grounded. 3,03 INSTALLATION: 2.06 SWITCHES D. Grounding System: At incoming service and separately DIVISION 16 - ELECTRICAL 00 joists, and adjusting his risers or other apparatus to 4 derived service locations, provide 3/4" x 20' copper SECTION 16000 - ELECTRICAL WORK GENERAL PROVISIONS A. Provide silent type standard grade 15 amp, 120V for all QD clad ground rods with grounding electrode conductor in accordance with NEC Table 250-94 to achieve a W to the Owner. B. single pole, double pole, three-way and four-way UJ a! 1 sized maximum resistance of 25 OHMS. Bond to incoming PART 1 -GENERAL switches. Z metallic water supply. 1,01 DESCRIPTION OF WORK 2.07 LIGHTING FIXTURES 2.12 DISCONNECT SWITCHES A. Provide oil labor, materials and equipment for a A. Fixture schedule shows required type of fixture only. A. Shall be general duty safety switches with 100,OOOA �n a complete and operating electrical system. D. Determine modifications required to make fixtures short circuit rating, and shall be listed in accordance and all other electrical equipment provided shall be suitable for ceilings as installed, and furnish with U.L. 98. The cover shall be interlocked so that B. Codes and Standards: All electrical work shall be in fixtures adapted to the ceiling used. Fixtures shall the door cannot be opened with the handle in the "on" E. strict compliance with OSHA requirements, the 1993 be U.L. approved. This contractor shall protect the position, except by the intentional operation of a National Electrical Code, the local county electrical fixtures and lamps and shall replace broken ports. All concealed release (defeater) mechanism. Provide code and Power Company standards. All materials shall lenses and louvers in any area shall be cleaned after fusible switch for A/C units as per U.L. listing and be new and free from defects, and shalt bear the all trades have completed their work in that area. local code requirements. Provide dual element, time Underwriters` label for its intended use. Provide new lamps for all lighting fixtures. delay fuses in all fusible switches. C. Permits, Fees and Notices: Secure and pay for all 2.08 BALLASTS 2.13 ELECTRIC MOTOR AND EQUIPMENT WIRING required by the work of this Division. Provide final inspection certificate(s) as applicable. A, Ballasts for fluorescent fixtures shall be Underwriters' Laboratories Class P, high power factor, A. Provide a complete branch circuit wiring, starter and rapid start type with CBM approval where applicable. disconnect switch far all orator driven equipment, When "package" D. Contractor shall thoroughly investigate site before Ballasts shall be "A" sound rating except where this motor driven equipment is provided with a bidding. No changes will be allowed in contract price rating is not available (e.g., ballasts for High Output control panel which includes starter, this contractor for work required to comply with existing conditions. Lamp,) in which case the rating shall be the best will not provide starter. Motor connections shall be E. Workmanship shall meet N.E.C.A, guidelines. available. All fluorescent ballast shall be the energy mode with flexible conduit. saving type. B. Starters shall be all of one manufacture: G.E., F. If, through errors or omissions, the intent of 209 METERING EQUIPMENT Westinghouse, Square -D or I.T.E. Provide an overload Architect/Engineer with regard to any detail is not element in each phase. clear, or is capable of more than one interpretation, A. ll be Square -D wall mounted Multi -metering equipment shall such matters must be brought to the attention of the EZ Meter -Pack or manufactured by G.E. or Westinghouse. 2.14 TELEPHONE PREWIRiNG Architect/Engineer in writing before the submission of Ail components shall have been tested and Underwriter's bids, and the Architect/Engineer shall make correction Laboratories listed for use as an integral part of the A Provide all necessary e and related or explanation in writing. Otherwise, no extra charge l cmp accessories required by local telephone company for by local will be allowed for the work or material which the multi -metering system. complete prewired unit installation of telephone Architect/Engineer will require, provided that it comes B. All components shall be factory assembled and all service to telephone company interface. within a reasonable interpretation of the Drawings and current -carrying parts shall be plated bus bars. Specifications. Individual units shall be constructed with an integral 2.15 TELEVISION RECEPTION PREWIRING G. The plans and specifications are intended as a general sliding bolt assembly for a completely bussed meter A. Provide all necessary wiring, boxes, and related description of the work to be performed. All items not center. accessories required for complete prewired installation specifically mentioned or shown, but necessary for the C. Meter sockets shall be 4 jaw non -circuit closing type of television reception service to each unit. completion of the installation , shall be furnished and with fifth jaw provisions when used on network systems. installed by this Contractor. This Contractor shall Sockets shall be rated as noted ont he drawings. Meter 2,16 RESIDENTIAL UNIT SMOKE DETECTORS: thoroughly acquaint himself with the Mechanical, socket jaws must be spring reinforced and front Architectural, Structural and Electrical plans before removable. A Shall be photo -electric type with local alarm suitable submitting his final bid. No additional compensation for 120VAC operation. Smoke detectors shall be will be allowed due to the Contractor's failure to D. Main fusible switch and meter -breaker components shall interconnected so that activation of a single detector familiarize himself with the plans. SUBMITTALS be of such design to permit arrangement to allow wiring shall alarm all detectors within that living unit. 1.02 at the top or bottom in the some assembly, Equipment All detectors shall hove battery back-up feature. Submit five (5) copies of technical information on all shall be so arranged as to permit the installation of major equipment in binders. Mark-up prints of the units with different branch ratings in the some meter design drawings with red pencil as items are installed, center. 2.17 FIRE ALARM SYSTEM and submit two copies showing an accurate "As -Built" E. The meter center shall be U.L. listed with an A Fire alarm system and its components and system record of the entire system. Give the Owner integrated equipment rating equal to or greater than operations shall also meet the approval of the local instructions in operation of the system. Secure from the available current at the meter center (minimum of fire department. the Owner a signed memo stating that technical 42000 AMP at 240 volt). Obtain approval and coordinate information, as -built drawings and instructions in short circuit current with power company for metering B. FUNCTIONS operation have been received. Submit memo to the Architect. equipment. 1. Upon actuation of any manual alarm station or automatic alarm initiating device they shall PART 2 -PRODUCTS 2.10 LOADCENTERS illuminate the zone LED at the control panel and A. Shall be load centers Squore-D Type 00 or equal units remote annunciators. 2.01 CONDUIT manufactured by G.E. or Westinghouse. Main ratings and a. Operate all audible and visual alarm signals. A. Ail wires shall be concealed in conduit, (1/2" min.) branch circuit breaker ratings shall be of size and including grounding wires. When conduit is located number as indicated on drawings. Load centers shall be b. Audible devices must notify building occupants below slab an grade or underground, it shall be PVC plug -on type construction. All current carrying parts in accordance with ANSI S3.41, "AUDIBLE Schedule 40 (3/4" min.). Provide all empty conduits of the bus assembly shall be plated. Terminals for y EMERGENCY EVACUATION SIGNAL". with pullwires. EMT and ENT may be used where feeder conductors to mains and branch neutral shall be permitted by code. Conduits shall be sized per N.E.C. U,L. listed as suitable for the type of conductor 2. It shall be possible to silence the alarm signals specified. The load center bus assembly shall be before operating the reset switch by depressing 2.02 CONDUCTORS enclosed in a steel cabinet. The size of the wiring the signal silence switch. However, with the gutters and gauge steel shall be in accordance with signals silenced subsequent zone alarms will A. All conductors shall be copper (#12 min), THHN/THWN U.L. standards No. 67 and No. 50. Fronts shall include respond to the signals. insulation. Comply with the N.E.C. Articles 300 and door and be provided with a directory for circuit 310. Ali conductors shall be new, free from kinks and identification (typewritten). Load center boxes and 3, Power failure, opens, grounds or any other defects when installed. Where local authorities fronts shall have corrosion resisting phosphate disarrangement of system wiring or components permit, aluminum conductors may be used for service . treatment and baked -enamel finishLoadcenters shall shall be indicated by a visual and audible trouble entrance and panel feeders as indicated on riser be U.L. listed and meet Federal Specification WP -115a signal at remote annunciators and the fire diagrams. as Type 1, Class 2. control panel. The trouble signal may be B. NM cable may be used instead of wire in conduit for all B Branch circuit breakers up to 150 amperes shall be silenced, but the trouble light must remain branch circuits within the living units where permitted Square -D Type 00, 01, or approved equal. All breakers illuminated until the system has been returned to by local authorities. shall be plug -on type, toggle action with quick -make, normal, at which time the trouble signal shall quick -break mechanism. All multi -pole breakers shall resound until the trouble silence switch has been C. SER Coble may be used instead of wire in conduit for be single -operating handle, common -trip variety. returned to the normal position. tenant panel feeders from the meter center where permitted by local authorities and indicated on drawings. Circuit breakers shall be U.L. listed and meet the C. EQUIPMENT requirements of Federal Spec. WC -375B, Class 1. 2.03 SUPPORTS 1. Fire alarm annunciator panel and control panels 2.11 SERVICE ENTRANCE EQUIPMENT shall be located as indicated on the drawings. A. Provide all supports for material and equipment. A. Meter Sockets: Provide meter sockets which comply with 2. Provide a minimum of one zone for each floor. 2,04 COVER PLATES requirements of power company supplying Provide additional zones as required for fire electrical power to service -entrance equipment of this protection tamper and flow switches. A. All plates shall be white plastic. building project. B. Obtain installation requirements from power company and 3. Fire alarm horn/light units shall be surface 2.05 RECEPTACLES be governed accordingly. Coordinate locations of stub mounted with red finish or stainless steel trim, ups and routing prior to installation, Relocate Light lens shall be silk screened with the word "FIRE" A. Provide standard grade 15 amp, 2 pole, 3 wire, with equipment improperly installed due to lack of in red lettering. back and side wiring capability and suitable for split coordination at no additional cost. circuit operation. 4. Pull stations shall be non -coded, manually C. Surge Arresters: Furnish and install main secondary operated, single action with break glass rod. B, Ground Fault Interrupter: Provide "specification service surge arresters on line side of the main Provide weatherproof covers for all pulistations grade" duplex receptacles, ground fault circuit switch, Arrester shall be 3 -pole, with 650 volts exposed to rain. interrupters (GFI), feed-thru type, capable of maximum rating. Arrester shall permit a maximum 5. Residential unit horns shoe be flush mounted in a protecting connected lownstream receptacles on single discharge voltage of 2.2 KV at a 1.5KA current level, single gang box with a red finish. circuit, grounding type UL rated Class A, 20 amperes Unit shall be sealed in an extruded aluminum housing, rating, 120 volts, with solid state ground fault complete with 18 inch copper wire leads and mounting sensing and signaling, 5 milliamperes ground fault trip bracket. Arrester shall be Joslyn No. J9200-9 or level; and equip with local test/reset buttons. approved equal. 6. Provide an approved digital communicator to transmit the fire alarm and supervisory signals to a central station. The digital communicator shall be UL and FM listed for fire reporting to a central station and shall conform to the requirements to NFPA 71, 7. Fire Alarm Systems wiring: alarm initiating circuits shall be 16 AWG stranded or larger, with 7 stands (maximum), or 14 AWG solid. Alarm indicating circuits shall be 14 AWG solid or larger. Install per manufacturers wiring diagrams. 8. Provide surge protector on all FACP power circuits and all communications lines between buildings as recommended by the equipment manufacturer. D. SCOPE: 1. Provide a fire alarm control panel in each building to monitor pull stations and sprinkler system tamper and flow switches. 2. Digital communicator shall notify independant monitoring company and fire station, This signal shall precisely identify the address and number of the building in alarm. PART 3 - EXECUTION 3.01 APPARATUS IDENTIFICATION A. Ponelboord, circuit breakers in ponelboards, motor disconnect switches, starters and other apparatus used for the operation or control of, circuits, appliances or equipment shall be properly identified by means of engraved laminated plastic descriptive nameplates mounted on the apparatus using contact cement. Cardholders in any form are acceptable in the living units. 3.02 GROUNDING A A separate grounding conductor, sized in accordance with NEC Table 250-95 shall be provided in the conduit with the circuit conductors for all lighting, power and feeder circuits. B. All electrical equipment enclosures and conductor enclosures shall be grounded. 3,03 INSTALLATION: A. The Contractor shall adopt his work to job conditions N a and make such changes as required and permitted by the V Architect, such as moving his work to clear beams, 00 joists, and adjusting his risers or other apparatus to 4 avoid interferences with windows and openings: or rrnn V raising or lowering his work to permit the passing of o ductwork or the work of other trade: all as required or QD as job conditions dictate, without any additional costs W to the Owner. B. Examine areas and conditions under which work is to be UJ a! 1 performed and products are to be installed and notify General Contractor in writing of conditions detrimental to proper and timely completion of the work. Do not Z proceed with the work until unsatisfactory conditions have been corrected in a manner acceptable to the Installer. C. Do not allow or cause any of the work of this division UMZ or cause other divisions of work to be covered up or Q enclosed until it has been inspected, tested and Q approved by the Architect and by oil other authorities �n a having jurisdiction. D. All switchboards, ponelboards, transformers, switches, outlets, coverplates, signs, lighting fixtures, and any and all other electrical equipment provided shall be thoroughly cleaned of all dirt, oil, concrete, etc. Any dents, scratches or other visible blemishes shall be corrected and the appearance and corrosion resistance of the equipment made "like new", to the satisfaction for the Architect/Engineer. E. Perform all adjustments necessary to ensure proper system operation in accordance with manufacturer written instructions, END OF SECTION 16000 S.G.M. ENGINEERING, INC. F A C I L I T I E S C 0 N S U L T I N G E N G I N E E R S 600 S. North Lake Blvd.cA TEL: (407) 767-5188 Suite 230 �FAX: (407) 767-5772 Altamonte Springs E-mail: sgmeng®iog.net Florida, 32701 Project number: 2011q W Q r M M � ^ N a o V o 4 00 Z 4 4 rrnn V Z o QD W Q N W D o tn h ^ r ❑ V W oE F_ E> M W � o c 0 z W � 06 = E a W � U N W oE = a rn 06 = E a W � U N W oE = a W LoLn' UJ a! 1 0 Z a' Ll UMZ Q a Q J �n a Z 0 a rr c.� cn Li D I LJ F-- a a I UJ a! 1 Ll JOB NO.8 DRAWN BY; BAV CHECKED BY APPROVED BY GR5 DATE 5/15100 SHEET N0. SP -4 C