HomeMy WebLinkAbout1700 OLD ENGLAND LOOP (A) 01-000117 (8)® TRANSFORMER, VERIFY EXACT LOCATIONS WITH POWER COMPANY.
SITE LIGHTING LEGEND
METER & HOUSE PANEL, VERIFY EXACT LOCATIONS
Fm]
DAY-BRITE #FL125HS12 FLOODLIGHT, WALL MOUNTED AT UNDERSIDE OF EAVE CONNECTION TO CARPORT/GARAGE
KIM AFL1-70MH120/GR HORIZONTAL FLOOD, MOUNTED ON ARCH JB1/DB-P FOR SIGN LTS Q WEATHERPROOF JUNCTION BOX.
S #
KIM #CFL1 /70MH120/GR COMPACT FLOOD, MOUNTED ON ARCH JB1 /VG -P FOR LANDSCAPE LTS NOTES: 1. ALL FIXTURES AND POLES SHALL BE ANODIZED BRONZE.
T H USE PANEL.
El-o
EMCO #ECA181-F-400HPS-BRP-F-LU400 WITH 30' MOUNTING HEIGHT DIRECT BURIAL ROUND
CONNECT FIXTURE TO CLOSES 0 FIBERGLASS POLE 2. COORDINATE EXACT LOCATION OF LANDSCAPE LIGHTING
FT,RCTRICAL SITE PLAN
SCALE: 1"=50'-O"
PLAN KEY NOTES:O
1. ALL TRANSFORMER LOCATIONS SHOWN
ARE PRELIMINARY. VERIFY EXACT
LOCATIONS WITH LOCAL POWER COMPANY.
2. ALL EXTERIOR BUILDING AND SITE
LIGHTS ARE TO BE CONTROLLED BY
PHOTOCELL OR PHOTOCELL/CONTACTOR
ARRANGEMENT,
3. CIRCUIT DESIGNATIONS:
9: HP- 2
------ CIRCUIT NUMBER
HOUSE PANEL
BUILDING NUMBER
4. CONNECTION FOR LANDSCAPE/SIGN
LIGHTING. SEE LANDSCAPE DRAWINGS
FOR TYPES AND QUANTITIES. EVENLY
DISTRIBUTE FIXTURES ON CIRCUITS
INDICATED.
5. CONNECTION TO GATE OPERATOR.
VERIFY EXACT LOCATION.
6. CONNECTION FOR GATE CARD READER.
PROVIDE CONDUITS FROM CARD READER
TO GATE OPERATOR AS REQUIRED BY
MANUFACTURER,
7. COMPACTOR SERVICE. SEE RISER
DIAGRAM ON SHEET AM -E1.
g. ALL SITE LIGHTING WIRING SHALL
BE #10 THWN Cu.
9. WIRE TO HOUSE PANEL.
10, ALL POOL DECK LIGHTING TO BE CONTROLLED
BY 24 HOUR TIMER, ALL OTHER POOL AREA
LIGHTING IS CONTROLLED BY PHOTOCELL.
SC,AI,F
25 50 OC
NORTH_ _ -
_ _ _ ( IN FEET )
1 inch 50 ft.
200
r hl
DRAWN BY
CHECKED BY v5G
APPROVED BY GR5
DATE ---- --- -- -- 5/I5/00
SHEET N0.
16.4