FLORIDA BUILDING CODE, ENERGY CONSERVATION
CHAPTER C4—COMMERCIAL ENERGY EFFICIENCY
Form C402-2017 ALTERATIONS, RENOVATIONS and BUILDING SYSTEMS
Climate Zone: 2A
Project Name: 18340 LEARNING CITY DAYCARE @ LAKE MARY FOUR CORNERS PLAT_ Occupancy We: RETAIL
Address: 314 W LAKE MARY BLVD Alteration Renovation ® Building System
City, Zip Code: SANFORD. 32746 Building Permit No.:
Builder: Permitting Office:
Owner.
BUILDING ENVELOPE INFORMATION (Where changed)
Envelope Component Description
Requirement Efficiency
Location Unit Required Installed
Roof type EXISTING
Table C402.1.4 or
Table C402.1.3
U-factor or
R-value
Roofreflectance/Emittance
low slope roofs) EXISTING Table C402.3
Solar reflectance,
Thermal emittance
Wall type, above grade EXISTING
Table C402.1.4 or Table C402.1.3
U-factor or
R-value
Wall, below grade EXISTING
Floor type EXISTING
Vertical fenestrations X
Ef traal,.}f gyp,?
Table C4024
U-factor T=ec /Ef1y1c0.Ylt 0-SO IJ.510.8
SHGC
Skylights N/A
U-factor
SHGC
BUILDING SYSTEMS INFORMATION [for HVAC, service hot water or pool heating, lighting systems and replacement fenestration (C501.7)]
System Type (describe system)
Requirement
Efficiency
Location Unit Required Installed
Air-conditioning system ROOFTOP PACKAGED Tables C403.2.3 (1-3, 6-8, 9-11) SEER or EER, JEER 13 14.0
Heating system ELECTRIC Tables C403.2.3 (2-6) HSPF or COP AFOE, E, or E,
Ventilation/air handling system 1111 Tables C403.2.12.1(1-2) Fan power (cfm)
Ducts L jpble C403.2.9.1 R-value
Piping idd g o a n Tatjie C403.2J0 Inches
Hot water HEENOCW 404.2
r
EF, E„ COP
Lighting e types: (append list) f405.4.2 (I or 2) Lighting power density 0.87 0.87
Fenestrations: Enter informat® UILDING EN LOPE INFOR VJ(z box above.
Other: STATE OF
pP
COMPLIANCE IS BYANSt/ASHRA
Submit alternate form or append docu
I hereby certify that the plans an cif' a , ffJtJ culation are in compliance with the
Florida Building Code, Energy Co ati t /
Zg 8PREPAREDBY: (
DATE.
I hereby certify that this building is in compliance with the Florida Building Code, Energy Conservation:
OWNER/AGENT:
DATE:
Review of plans and specifications covered by this
calculation indicates compliance with the Florida Building
Code, Energy Conservation. Before construction is
completed, this building will be inspected for compliance
in accordance with Section 553.908, F.S.
BUILDING OFFICIAL:
DATE:
u
0
1
1
1
1
1
1
1
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
PERMIT
FLORIDA BUILDING CODE — ENERGY CONSERVATION, 6th EDITION (2017) C-101
Copyu ht 0 20171CG ALL RIGHTS RESERVED Accesed by David Loucks on DEC n, 2017 s 59.Io AM pursuant to License AFteement wnh ICC No further tepioduction or
d su ibut'on a,,tho zed. .ANY UNAU I IORIZLD RLPRODUCI ION OR DISfRIBUl ION IS A VIOLATION OC'IlHE FEDERAL COPYRICI I I' ACT AND I -I IE LICENSE
AGRENIENT, ,AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
4
4 .Air System Sizing Summary t®r R'TU-1
Project (Name: 18340 Learning City Daycare - Sanford 10/15/201 E
Pr pared hy. Loucks Engineering, Inc. 01:15PM
Air System Information
Air System Name - ---------------------------------- --- RTU-1
Equipment Class ......... .............. ____-.-.....__-- - . ---- UNDEF
Air System Type -- ----- - --- ............... . ----- -- SZCAV
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM Sum of space airflow rates
Space CFM ._._._.------ ------- Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load ------ - - - _---------- ----- ----------------------- 1.6 Tons
Total coil load - ----------- --- ----- ------------ ------ 18.7 MBH
Sensible coil load _--- ----- 15.1 MBH
Coil CFM at Aug 1600 .._____---- ------------- 724 CFM
Max block CFM-._-------------- 724 CFM
Sum of peak zone CFM----------------------------- _....... 724 CFM
Sensible heat ratio .....------------------- ..__----------------- 0.808
ft2/Ton -- - - ------ - --- -... - -- ---- -- 437.3
BTU/(hr-ftz) ... . . .................. ------------------------- 27.4
Water flow @ 10.0 °F rise ........-..- 3.74 gpm
Central Heating Coil Sizing Data
Max coil load ....--------- ----------.--------------------4.4 MBH
Coil CFM at Des Htg . _--- --------------------- ..__..724 CFM
Max coil CFM ----- ------------------- ---- ---- ---- -- ...... 724 CFM
Water flow @ 20.0 °F drop _--------------------- ._-------------- 0.44 gpm
Supply Fan Sizing Data
Actual max CFM ....____.._.......__.724 CFM
Standard CFM ------------- -...._-------------------------------- _- --------- 724 CFM
Actual max CFM/ftZ.----- ---- -------------------------- ---------------------- 1.06 CFM/ftz
Outdoor Ventilation Air Data
Design airflow CFM---------- _____.- 60 CFM
CFM/ft2--------------------- -----------------. ........ 0.09 CFM/ftz
Number of zones ---- - . ..........--- -- ----- _........... -.1
Floor Area ----- --- ....- - ---------- ----- -------- - ----- ----- 681.0 ft2
Location ------------ ----------- _......... ___--------- Miami IAP, Florida
Calculation Months. _....___---------- -------- -_----- Jan to Dec
Sizing Data ------ -- --- --.-.......... -- ......... -._--------- ------- Calculated
Load occurs at ------------------ -------------------------------------------- Aug 1600
CA DB / WB .------------------------------------------- 90.7 / 76.9 F
Entering DB / WB -------.-- ------------------ ------...... 77.4 / 65.5 F
Leaving DB / WB .-- -- --------------- ----------- 58.1 / 57.0 F
Coil ADP ._ ------------------- --------- - ---------------------- 55.9 F
Bypass Factor ------- - ---- ----- -- -- -- -- 0.100
Resulting RH .. ..... - ---- - - -- 53
Design supply temp. ...----- --- - --- 58.0 F
Zone T-stat Check ------------- --------------- --— 1 of 1 OK
Max zone temperature deviation ..__---------------------- 0.0 F
Load occurs at -- ...... ------------------------ -- - --- Des Htg
BTU/(hr-ft2) 6.4
Ent. DB / Lvg DB -_ - -... --- --- -- -------- 67.8 / 73.4 °F
Fan motor BHP --- ----.......... 0.00 BHP
Fan motor kW ----------------------------------------------------- 0.00 kW
Fan static .--------------------------- -- ----- 0.00 in wg
CFM/person ------ ----------------------------------------- 13.70 CFM/person
Hourly Analysis Program v4.50 Page 1 of 1
Zone Skiing Summary -for 'TU-1
Project Name: 183`40 Learning City Daycare - Sanford 10/15/201 £
Prepared ty: Loucks Engineering, Inc. 01:15PAJ
Air System Information
Air System Name ----- _------ ------------ ----------- -- .----- __ RTU-1
Equipment Class - .... .------- -- ---- - - - ---- --- - UNDEF
Air System Type .. - ........... . ........ ............. SZCAV
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM _..._------..._----------- Sum of space airflow rates
Space CFM Individual peak space loads
Zone Sizing Data
Number of zones .---- ---------------------------------------------- I
Floor Area - - ......... -- - --------------------- -- - -- . -- .. 681.0 ft'
Location ...... ... __.------ ----- _--- ------- ___ ....... Miami IAP, Florida
Calculation Months ..--------- .___----- ......_____.....Jan to Dec
Sizing Data - - ---- - ----- ------------------------------------. Calculated
Maximum Design Minimum Time Maximum Zone
Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name MBH) CFM) CFM) Load MBH) ft') CFM/ft'
Zone 1 12.9 724 724 Sep 1600 2.9 681.0 1.06
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Zone Name /
Space Name Mult.
Cooling
Sensible
MBH)
Time
of
Load
Air
Flow
CFM)
Heating
Load
MBH)
Floor
Area
ft')
Space
CFM/ft'
Zone 1
Directors Office 1 3.0 Oct 1600 163 0.6 133.0 1.22
Food Prep 1 1.8 Jul 1400 99 0.1 100.0 0.99
Lobby 1 7.2 Oct 1600 394 1.9 239.0 1.65
Storage/Janitor 1 0.7 Jul 1300 37 0.1 117.0 0.32
Toilet (entry) 1 1 0.3 Jul 1300 15 0.1 46.0 0.33
Toilet (entry) 2 1 0.3 Jul 1300 15 0.1 46.0 0.33
Hourly Analysis Program v4.50 Page 1 of 1
Project Name: 18340 Learning City Daycare -Sanford
Ventilation Sizing Summary for RTU-1
10/15/5/2018
Prepared by: Loucks Engineering, Inc.
0 20,1 ;-.,
b
1. Summary
Ventilation Sizing Method ............. --- -------------------------- _Sum of Space OA Airflows - -
Design Ventilation Airflow Rate ---------------- --- -------- ---- ----------------- .------ ------------- ------------- -- 60 CFM
2. Space Ventilation Analvsis Table
Zone Name / Space Name Mult.
Floor
Area
ftz)
Maximum
Occupants
Maximum
Supply Air
CFM)
Required
Outdoor Air
CFM/person)
Required
Outdoor Air
CFM/W)
Required
Outdoor Air
CFNI)
Required
Outdoor Air
of supply)
Uncorrected
Outdoor Air
CFM)
Zone 1
Directors Office 1 133.0 1.0 162.9 0.00 0.00 11.3 0.0 11.3
Food Prep 1 100.0 1.0 99.3 0.00 0.00 8.5 0.0 8.5
Lobby 1 239.0 2.4 394.3 0.00 0.00 26.3 0.0 26.3
Storage/Janitor 1 117.0 0.0 37.1 0.00 0.12 0.0 0.0 14.0
Toilet (entry) 1 1 46.0 0.0 15.3 0.00 0.00 0.0 0.0 0.0
Toilet (entry) 2 1 46.0 0.0 15.3 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 724.2 60.1
Hourly Analysis Program v4.50 Page 1 of 1
Air Systems Design Laud Summary for RTU-1
P,6ject Name: 18340 Learning City Daycare - Sanford 10/15/2018
Prepared by: Loucks Engineering, Inc. 01:15PM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600
COOLING OA DB / WB 90.7 °F / 76.9 °F
HEATING DATA AT DES HTG
HEATING OA DB / WB 46.0 °F / 38.6 °F
ZONE LOADS Details
Sensible
BTU/hr)
Latent
BTU/hr) Details
Sensible
BTU/hr)
Latent
BTU/hr)
Window & Skylight Solar Loads 48 ft2 809 48 ft2
Wall Transmission 301 ft2 1625 301 ft2 892
Roof Transmission 681 ft2 1814 681 ft2 794
Window Transmission 48 ft2 552 48 ft2 956
Skylight Transmission 0 ft2 0 0 ft2 0
Door Loads 0 ft2 0 0 ft2 0
Floor Transmission 681 ft2 0 681 ft2 295
Partitions 0 ft2 0 0 ft2 0
Ceiling 0 ft2 0 0 ft2 0
Overhead Lighting 743 W 2207 0 0
Task Lighting 0 W 0 0 0
Electric Equipment 1416 W 4552 0 0
People 4 901 900 0 0 0
Infiltration 423 790 0 0
Miscellaneous 0 0 0 0
Safety Factor 0%/0% 0 0 0% 0 0
Total Zone Loads 12883 1690 2937 0
Zone Conditioning 14154 1690 2810 0
Plenum Wall Load 0% 0 0 0
Plenum Roof Load 0% 0 0 0
Plenum Lighting Load 0% 0 0 0
Return Fan Load 724 CFM 0 724 CFM 0
Ventilation Load 60 CFM 941 1901 60 CFM 1543 0
Supply Fan Load 724 CFM 0 724 CFM 0
Space Fan Coil Fans 0 0
Duct Heat Gain / Loss 0% 0 0% 0
Total System Loads 15095 3591 4353 0
Central Cooling Coil 15095 3592 0 0
Central Heating Coil 0 4353
Total Conditioning 15095 3592 4353 0
r-Y Positive values are clg loads
Negative values are htg loads
Positive values are htg loads
Negative values are clg loads
Hourly Analysis Program v4.50 Page 1 of 1
Air Systorn Sizing Summary for RTU-2
Proiect,Name: 16340 Learning City Daycare - Sanford 10/15/2018
Prepared by: Loucks Engineering, Inc. 01:15PM
a
Air System Information
Air System Name - -------......-- ..-- ----- ----- ----- RTU-2
Equipment Class ------------ --_._-------- ------ ---- UNDEF
Air System Type ........... .-- ----------- - -- --- --------- ---- SZCAV
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ---------- -- __ ------ Sum of space airflow rates
Space CFM Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load ----- --... ._---- --- ... . . . ......... 3.1 Tons
Total coil load ------------- ------- ......-.-------- - --------- 37.0 MBH
Sensible coil load _---------------------- --__ -- - ------------- 21.7 MBH
Coil CFM at Jul 1500-_----------- _..... 760 CFM
Max block CFM .__ ------------ -..................... ... - - 760 CFM
Sum of peak zone CFM-..----.--____.._-- ------------ 760 CFM
Sensible heat ratio ._ - --------------------------- ................. 0.587
ftz/Ton ............ -_- 404.9
BTU/(hr-ft2) .. - . ....... . - -..._...... - 29.6
Water flow @ 10.0 OF rise ----- .......... ._------------ 7.40 gpm
Central Heating Coil Sizing Data
Max coil load ....-------------------- ...... . ......-------- 12.4 MBH
Coil CFM at Des Htg _ -- 760 CFM
Max coil CFM -------------- 760 CFM
Water flow @ 20.0 OF drop---------------------------- 1.24 gpm
Supply Fan Sizing Data
Actual Max CFM ------------ 760 CFM
Standard CFM---------------- ----------- ---------------- 760 CFM
Actual Max CFM/ftZ.--.------ .--------------------- --- 0.61 CFM/ft2
Outdoor Ventilation Air Data
Design airflow CFM-------_.------------------------------------------ 416 CFM
CFM/ftz----------------------------------------------- -------------- 0.33 CFM/ft2
Number of zones .--- -------------- ---- — - - .....---..........._.1
Floor Area ___...... ..... - --------------------- .-... 1248.0 ft2
Location ._ ...... ............ .------------ -. Miami IAP, Florida
Calculation Months_ __ -------- ............._.._.__Jan to Dec
Sizing Data ---.----..----.-------------------- ._._- --------.Calculated
Load occurs at --------------------._----------- Jul 1500
CA DB / WB -- ---------------- - ------------------------ 91.0 / 77.0 OF
Entering DB / WB ..._- ._...._...--.- 84.4 / 71.9 OF
Leaving DB / W B . - - - ------- _ 58.0 / 57.0 OF
CoilADP -------------------- --- -- ----- ------ -- 55.1 OF
Bypass Factor. -__-._---._-.- 0.100
Resulting RH -------- --................... - - 54
Design sup ply temp.._____ -. ----------- 58.0 OF
Zone T-stat Check ...._................._...- -- --------------- 0 of 1 OK
Max zone temperature deviation ------- _ 0.0 OF
Load occurs at - ----------------- - -------------- ------ - Des Htg
BTU/(h r-ft2) -- ----------- ---- - --------- - --- ----------------------- 9.9
Ent. DB / Lvg DB ----------- - _------------ ------------- 56.9 / 72.0 OF
Fan motor BHP.----------- -- ----------- ----- - ------------------- 0.00 BHP
Fan motor kW ----------- - --------- ---- --------------- - 0.00 kW
Fan static - ---------- ---- ------------ ------ -------------------- ---- 0.00 in wg
CFM/person - --- - -------------------- - __ -------------- - - 17.32 CFM/person
Hourly Analysis Program v4.50 Page 1 of 1
Zone Sizing Summary for RTU-2
r ect Name: 18340 Learning City Daycare - Sanford 10/15/201
repared by: Loucks Engineering, Inc. 01:15PD
Air System Information
Air System Name...____ __ ________...... RTU-2
Equipment Class ......... .................. _........ .._.... UNDEF
Air System Type.-, ----- ..---- --- - --------- ------ SZCAV
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM-.--__------ Sum of space airflow rates
Space CFM -_ Individual peak space loads
Zone Sizing Data
Number of zones -- ----- -- ---- --------------------- - - - 1
Floor Area .... ....... ........ _.............. .. ___--- ---- _._- --_...1248.0 ftz
Location ----------- .._._-..____.._........... Miami IAP, Florida
Calculation Months ------------- __-_--------------------------- Jan to Dec
Sizing Data ------------------------- - - ---------------------Calculated
Maximum Design Minimum Time Maximum Zone
Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name MBH) CFM) CFM) Load MBH) w) CFM/ft'
Zone 1 13.9 760 760 Jul 1400 1.5 1248.0 0.61
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Zone Name /
Space Name Mult.
Cooling
Sensible
MBH)
Time
of
Load
Air
Flow
CFM)
Heating
Load
MBH)
Floor
Area
ft2)
Space
CFM/ft2
Zone 1
3-12 months 1 1 6.0 Jul 1400 325 0.5 420.0 0.77
3-12 months 2 1 6.0 Jul 1400 325 0.5 420.0 0.77
Front Hall 1 2.0 Jul 1300 110 0.5 408.0 0.27
Hourly Analysis Program v4.50 Page 1 of 1
Ventilation Sizing Summary for RTU-2
Project Name: 18340 Learning City Daycare - Sanford 10/15/2018
Prepared by: Loucks Engineering, Inc. 01115PM
Summary
Ventilation Sizing Method ----------------- _._.____--------------- Sum of Space OA Airflows
Design Ventilation Airflow Rate_....................................__......._..___................___.. 416 CFM
2. Space Ventilation Analysis Table
Zone Name / Space Name Mult.
Floor
Area
ftz)
Maximum
Occupants
Maximum
Supply Air
CFM)
Required
Outdoor Air
CFM/person)
Required
Outdoor Air
CFM/ftz)
Required
Outdoor Air
CFM)
Required
Outdoor Air
of supply)
Uncorrected
Outdoor Air
CFM)
Zone 1
3-12 months 1 1 420.0 12.0 324.8 10.00 0.18 0.0 0.0 195.6
3-12 months 2 1 420.0 12.0 324.8 10.00 0.18 0.0 0.0 195.6
Front Hall 1 408.0 0.0 110.3 0.00 0.06 0.0 0.0 24.5
Totals (incl. Space Multipliers) 760.0 415.7
Hourly Analysis Program v4.50 Page 1 of 1
Air System Design Load Summary for RTU-2
Project Name: 18340 Learning City Daycare - Sanford 10/15/2018
Prepared by Loucks Engineering, Inc. 01:15PIM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500
COOLING OA DB / WB 91.0 °F / 77.0 °F
HEATING DATA AT DES HTG
HEATING OA DB / WB 46.0 °F / 38.6 °F
ZONE LOADS Details
Sensible
BTU/hr)
Latent
BTU/hr) Details
Sensible
BTU/hr)
Latent
BTU/hr)
Window & Skylight Solar Loads 0 ft2 0 0 ft2
Wall Transmission 0 ft2 0 0 ft2 0
Roof Transmission 1248 ft2 4033 1248 ft2 1455
Window Transmission 0 ft2 0 0 ft2 0
Skylight Transmission 0 ft2 0 0 ft2 0
Door Loads 0 ft2 0 0 ft2 0
Floor Transmission 1248 ft2 0 1248 ft2 0
Partitions 0 ftZ 0 0 ft2 0
Ceiling 0 ft2 0 0 ft2 0
Overhead Lighting 1296 W 3808 0 0
Task Lighting 0 W 0 0 0
Electric Equipment 420 W 1344 0 0
People 24 4562 2880 0 0 0
Infiltration 0 0 0 0
Miscellaneous 0 0 0 0
Safety Factor 0%/0% 0 0 0% 0 0
Total Zone Loads 13747 2880 1455 0
Zone Conditioning 15205 2880 1608 0
Plenum Wall Load 0% 0 0 0
Plenum Roof Load 0% 0 0 0
Plenum Lighting Load 0% 0 0 0
Return Fan Load 760 CFM 0 760 CFM 0
Ventilation Load 416 CFM 6492 12413 416 CFM 10769 0
Supply Fan Load 760 CFM 0 760 CFM 0
Space Fan Coil Fans 0 0
Duct Heat Gain / Loss 0% 0 0% 0
Total System Loads 21697 15293 12377 0
Central Cooling Coil 21697 15294 0 0
Central Heating Coil 0 12377
Total Conditioning 21697 15294 12377 0
Key: Positive values are clg loads
Negative values are htg loads
Positive values are htg loads
Negative values are clg loads
Hourly Analysis Program v4.50 Page 1 of 1
Air System Sizing Summary for TU-3
Project Name: -i 8340 Learning City Daycare - Sanford 1Oil 5/2018 Prepared
by: Loucks Engineering, Inc. 01.16PM z
Air
System Information Air
System Name ---------------------------------------- -- RTU-3 Equipment
Class ..... - - --------- --- - - - -- UNDEF Air
System Type ------------------ ---_...... ----- --------------- . SZCAV Sizing
Calculation Information Zone
and Space Sizing Method: Zone
CFM ___------ _-------------- Sum of space airflow rates Space
CFM _- -- Individual peak space loads Central
Cooling Coil Sizing Data Total
coil load -- - - -- 3.1 Tons Total
coil load ---_...------- ------------------------- --------------------.37.2 MBH Sensible
coil load ------------- ....----- --------- .._-------- ------------- 22.1 MBH Coil
CFM at Jul 1500_..._---------------- ----- ------ -- ................786 CFM Max
block CFM--.------------------------------------------------ 786 CFM Sum
of peak zone CFM---- .------------------------------------------------ 786 CFM Sensible
heat ratio..._._._.._. 0.595 ft2/
Ton - -- --- 364.3 BTU/(
hr-ft2) _ --- - - -- 32.9 Water
flow @ 10.0 °F rise _..__.__..._._...........___..._... 7.44 gpm Central
Heating Coil Sizing Data Max
coil load . - -- 12.5 MBH Coil
CFM at Des Htg 786 CFM Max
coil CFM ---------- ------------------------- 786 CFM Water
flow @ 20.0 °F drop 1.25 gpm Supply
Fan Sizing Data Actual
max CFM ------------------------------------ ------------- 786 CFM Standard
CFM ------ - - - ----- ---- 786 CFM Actual
max CFM/ft2------- ---- ------- .---- ---------------------------- 0.70 CFM/ft2 Outdoor
Ventilation Air Data Design
airflow CFM 406 CFM CFM/
ft2 -- -- - - - --- 0.36 CFM/ft2 Number
of zones - ------------------- - - 1 Floor
Area . - - ------------- - -- -- ---- ----------1128.0 ft2 Location ... ... _..._.......__..---- --- ____--- _..
Miami [AP, Florida Calculation
Months _________ ___..._._--------------_.Jan to Dec Sizing
Data.---------- --------------------- Calculated Load
occurs at ..---------------------- Jul 1500 CA
DB / WB------------------- -- - -- - 91.0 / 77.0 F Entering
DB / WB ............... - 84.0 / 71.5 F Leaving
DB / WB--------- - ... - 58.0 / 57.0 F Coil
ADP ----------------- --- - 55.1 F Bypass
Factor ---------------- _--- ----- 0.100 Resulting
RH -_ 54 Design
supply temp.._ ...._...... - - -- - 58.0 F Zone
T-stat Check ----------------------------------------------------------- 0 of 1 OK Max
zone temperature deviation -------------------------- 0.1 F Load
occurs at------------------- ---- ---------.._---------------------- -_ Des Htg BTU/(
hr-ftz) .----- -- - ---------------------------------11.1 Ent.
DB / Lvg DB . — - -------------------------------------- 57.5 172.2 °F Fan
motor BHP ----------------------- -- -- - -- Fan
motor kW -- ------ -------- ----- Fan
static ----.._...._--- --------------- CFM/
person 0.
00 BHP 0.
00 kW 0.
00 in wg 16.
91 CFM/person Hourly
Analysis Program v4.50 Page 1 of 1
r.
Zone Sizing Summary for RTC!-3
roject Name: 18340 Learning City Daycare - Sanford 10/15/201
repared by:,Loucks Engineering, Inc. 01:16P
Air System Information
Air System Name --------------------- - --------------------- ---- RTU-3
Equipment Class. - ....... - - --- - .. UNDEF
Air System Type --------- -------------- --------------------------- SZCAV
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM Sum of space airflow rates
Space CFM------------ _._ Individual peak space loads
Zone Sizing Data
Number of zones ----_.....-...... -... -........... .......... --........1
Floor Area . - — - - - - - -------1128.0 ft2
Location --- ------ _.____..... .__-._------------------ Miami IAP, Florida
Calculation Months .---------------- ..........._..._...__...-_.-Jan to Dec
Sizing Data ---------------------- ----- -------- .................. ......... Calculated
Maximum Design Minimum Time Maximum Zone
Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name MBH) CFM) CFM) Load MBH) ft2) CFM/ft2
Zone 1 14.3 786 786 Jul 1500 2.5 1128.0 0.70
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Zone Name /
Space Name Mult.
Cooling
Sensible
MBH)
Time
of
Load
Air
Flow
CFM)
Heating
Load
MBH)
Floor
Area
ft2)
Space
CFM/ft2
Zone 9
1 yrs 1 1 6.1 Jul 1400 334 0.8 420.0 0.79
1 yrs 2 1 6.8 Jun 1700 372 1.4 420.0 0.89
Toilet (1yr)(3-12months) 1 0.3 Jul 1300 15 0.1 45.0 0.33
MIDDLE Hall 1 1.2 Jul 1300 66 0.3 243.0 0.27
Hourly Analysis Program v4.50 Page 1 of 1
Ventilation Sizing Summary for RTU-3
Project Name: 18340 Learning City Daycare - Sanford 10/15/20.18
Prepared by: Loucks Engineering, Inc. O'i`:16PM
1. Summary
Ventilation Sizing Method -__ ----------------- ____.......__...Sum of Space OA Airflows
Design Ventilation Airflow Rate-------.----------------------------------------------------------------------- 406 CFM
2. Space Ventilation Analysis Table
Zone Name / Space Name Mult.
Floor
Area
ft2)
Maximum
Occupants
Maximum
Supply Air
CFM)
Required
Outdoor Air
CFM/person)
Required
Outdoor Air
CFM1W)
Required
Outdoor Air
CFNI)
Required
Outdoor Air
of supply)
Uncorrected
Outdoor Air
CFM)
Zone 1
1 yrs 1 1 4200. 12.0 333.9 10.00 0.18 0.0 0.0 195.6
1 yrs 2 1 420.0 12.0 371.8 10.00 0.18 0.0 0.0 195.6
Toilet (1yr)(3-12months) 1 45.0 0.0 15.0 0.00 0.00 0.0 0.0 0.0
MIDDLE Hall 1 243.0 0.0 65.7 0.00 0.06 0.0 0.0 14.6
Totals (incl. Space Multipliers) 786.4 405.8
Hourly Analysis Program v4.50 Page 1 of 1
Air System Design L02d Summary for RTU-3
P,roject.Name: 16340 Learning City Daycare - Sanford 10/15/2018
Prepared,by,, Loucks Engineering, Inc. 01:16PM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500
COOLING OA DB / WB 91.0 °F / 77.0 °F
HEATING DATA AT DES HTG
HEATING OA DB / VVB 46.0 °F / 38.6 °F
ZONE LOADS Details
Sensible
BTU/hr)
Latent
BTU/hr) Details
Sensible
BTU/hr)
Latent
BTU/hr)
Window & Skylight Solar Loads 0 ft2 0 0 ft2
Wall Transmission 282 ft2 1031 282 ft2 835
Roof Transmission 1128 ft2 3645 1128 ft2 1315
Window Transmission 0 ft2 0 0 ft2 0
Skylight Transmission 0 ft2 0 0 ft2 0
Door Loads 0 ft2 0 0 ft2 0
Floor Transmission 1128 ft2 0 1128 ft2 343
Partitions 0 W 0 0 ft2 0
Ceiling 0 ft2 0 0 ft2 0
Overhead Lighting 1254 W 3684 0 0
Task Lighting 0 W 0 0 0
Electric Equipment 420 W 1344 0 0
People 24 4562 2880 0 0 0
Infiltration 0 0 0 0
Miscellaneous 0 0 0 0
Safety Factor 0%/0% 0 0 0% 0 0
Total Zone Loads 14267 2880 2494 0
Zone Conditioning 15785 2880 2106 0
Plenum Wall Load 0% 0 0 0
Plenum Roof Load 0% 0 0 0
Plenum Lighting Load 0% 0 0 0
Return Fan Load 786 CFM 0 786 CFM 0
Ventilation Load 406 CFM 6310 12182 406 CFM 10382 0
Supply Fan Load 786 CFM 0 786 CFM 0
Space Fan Coil Fans 0 0
Duct Heat Gain / Loss 0% 0 0% 0
Total System Loads 22095 15062 12488 0
Central Cooling Coil 22095 15063 0 0
Central Heating Coil 0 12488
Total Conditioning 220951 15063 12488 0
Key: Positive values are clg loads
Negative values are htg loads
Positive values are htg loads
Negative values are clg loads
Hourly Analysis Program v4.50 Page 1 of 1
Air System Sizing Summary for RTC!-4
1r,qect Name: 18340 Learning City Daycare - Sanford 10/15/201
Irepared hy:,Loucks Engineering, Inc. 01 16PN
Air Systern Information
Air System Name RTU-4
Equipment Class .... .................. ............... ..... . .. .... UNDEF
Air System Type .................. SZCAV
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM -------- --------------- Sum of space airflow rates
Space CFM - - , Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 3.2 Tolls
Total coil load ----------------------- 38.5 MBH
Sensible coil load 23.9 MBH
Coil CFM at Jul 1500 - - --------- -------- ------------------------- 889 CFM
Max block CFM 889 CFM
Sum of peak zone CFM ------------- - -- -- -- _ ---- -- 889 CFM
Sensible heat ratio - - ----- --- ---- - - - 0.621
ft2/Ton ----------------- ---- ---- - ----- ___ --------- ---------------------- 406.7
BTU/(hr-ft2) - - - ---------------------------- 29.5
Water flow @ 10.0 'F rise 7.71 gpm
Central Heating Coil Sizing Data
Max coil load ------------- --------------------------- 14.3 MBH
Coil CFM at Des Htg __._..._..___.__.________.__.____.889 CFM
Max coil CFM --- -- - ------------------ 889 CFM
Water flow @ 20.0 'F drop 1.43 gpm
Supply Fan Sizing Data
Actual max CFM 889 CFM
Standard CFM 889 CFM
Actual max CFM/ft2 0.68 CF M/ft2
Outdoor Ventilation Air Data
Design airflow CFM
CF M/ft2 ... . .... ..
388 CFM
0.30 CF M/ft2
Number of zones . --------- - ,,, - -_ .................. , 1
Floor Area . .................. ........ ... .---1306.0 ft2
Location.-, ------ Miami IAP, Florida
Calculation Months -- - ----- ---.__...._....._...._.__.Jan to Dec
Sizing Data ------------------------ --- Calculated
Load occurs at ............... Jul 1500
CA DB / VVB -- --------- ----------------------------------- ------- 91.0/77.0 F
Entering DB WB ------- ------- - --- ---- 82.9/70.5 F
Leaving DB VVB 58.0 / 57.0 F
Coil ADP ___ ------------------------- .............. 55.2 F
Bypass Factor --------------------------------------- 0.100
Resulting RH ------ ----------------------------------------- 53
Design supply temp. 58.0 F
Zone T-stat Check ------------------------------------------------- 0 of I OK
Max zone temperature deviation 0.2 oF
Load occurs at.-------.------.----------------.-.------------_ Des Htg
BTU/(hr-ft') - - __ - ------------------------------ ---------------------------------- 10.9
Ent. DB / Lvg DB ------------------------------- ----------------- _ . 59.4 174.3 'F
Fan motor BHP _ -------------- ---------------- _ ------------ 0.00 BHP
Fan motor kW ---------------------------- _ ---- - ------ ---- 0.00 kw
Fanstatic - - - - -- --- ------------------------------------------------------------ _ 0.00 in wg
CFM/person 17.64 CFM/person
Hourly Analysis Program v4.50 Page 1 of 1
Zone Sizing Summary For RTU-4
roject Name: 18340 Learning City Daycare - Sanford 10/15/201
repared bv: Loucks Engineering, Inc. 01:16P1
Air System Information
Air System Name --------- --- ------------ __......... - RTU-4
Equipment Class .------------------------ . UNDEF
Air System Type -- -- - ------ - SZCAV
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ------------- --- ... Sum of space airflow rates
Space CFM Individual peak space loads
Zone Sizing Data
Number of zones
Floor Area -- -
Location ------------------------------ -
Calculation Months _..._.._-------
Sizing Data ----------------------- ---- -
1
1306.0 ft2
Miami AP, Florida
Jan to Dec
Calculated
Maximum Design Minimum Time Maximum Zone
Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name MBH) CFM) CFM) Load MBH) ft2) CFM/ft2
Zone 1 16.3 889 889 Jul 1500 4.5 1306.0 0.68
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Zone Name /
Space Name Mult.
Cooling
Sensible
MBH)
Time
of
Load
Air
Flow
CFM)
Heating
Load
MBH)
Floor
Area
ft2)
Space
CFM/ft2
Zone 1
2 yrs 1 1 12.0 Jul 1500 654 2.2 770.0 0.85
Toilet (2yrs) 1 1 0.4 Jul 1300 23 0.2 43.0 0.54
Back Hall 1 3.9 Jul 1500 212 2.0 493.0 0.43
Hourly Analysis Program v4.50 Page 1 of 1
Project Name: 18340 Learning City Daycare -Sanford
Ventilation Sizing Summary for RTU-4
Prepared by: Loucks Engineering, Inc.
1. Summary
Ventilation Sizing Method ---------- ._--------------- ___-------- __Sum of Space OA Airflows
Design Ventilation Airflow Rate ---- _--------- ___---------- _---- -___ 388 CFM
2. Space Ventilation Analvsis Table
Zone Name / Space Name Mult.
Floor
Area
ft2)
Maximum
Occupants
Maximum
Supply Air
CFM)
Required
Outdoor Air
CFM/person)
Required
Outdoor Air
CFM/ft2)
Required
Outdoor Air
CFNI)
Required
Outdoor Air
of supply)
Uncorrected
Outdoor Air
CFM)
Zone 1
2 yrs 1 1 770.0 22.0 653.8 10.00 0.18 0.0 0.0 358.6
Toilet (2yrs) 1 1 43.0 0.0 23.4 0.00 0.00 0.0 0.0 0.0
Back Hall 1 493.0 0.0 212.1 0.00 0.06 0.0 0.0 29.6
Totals (incl. Space Multipliers) 889.4 388.2
10/15/208I 0`f:16R, Hourly
Analysis Program v4.50 Page
1 of 1
10 Air System Design Load Summary for RTU-4IProjectName: d 8340 Learning City Daycare - Sanford 10/15/2018
I Prepared k y: Loucks Engineering, Inc. 01:16PM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500
COOLING OA DB / WB 91.0 °F / 77.0 °F
HEATING DATA AT DES HTG
HEATING OA DB / WB 46.0 °F / 38.6 °F
ZONE LOADS Details
Sensible
BTU/hr)
Latent
BTU/hr) Details
Sensible
BTU/hr)
Latent
BTU/hr)
Window & Skylight Solar Loads 48 ft2 631 48 ft2
Wall Transmission 324 ft2 1184 324 ft2 960
Roof Transmission 1306 ft2 4220 1306 ft2 1523
Window Transmission 48 ft2 556 48 ft2 956
Skylight Transmission 0 ft2 0 0 ft2 0
Door Loads 0 ft2 0 0 ft2 0
Floor Transmission 1306 ft2 0 1306 ft2 506
Partitions 214 ft2 526 214 ft2 526
Ceiling 0 ft2 0 0 ft2 0
Overhead Lighting 1286 W 3779 0 0
Task Lighting 0 W 0 0 0
Electric Equipment 385 W 1232 0 0
People 22 4182 2640 0 0 0
Infiltration 0 0 0 0
Miscellaneous 0 0 0 0
Safety Factor 0%/0% 0 0 0% 0 0
Total Zone Loads 16311 264.0 4471 0
Zone Conditioning 17921 2640 4340 0
Plenum Wall Load 0% 0 0 0
Plenum Roof Load 0% 0 0 0
Plenum Lighting Load 0% 0 0 0
Return Fan Load 889 CFM 0 889 CFM 0
Ventilation Load 388 CFM 6006 11964 388 CFM 9958 0
Supply Fan Load 889 CFM 0 889 CFM 0
Space Fan Coil Fans 0 0
Duct Heat Gain / Loss 0% 0 0% 0
Total System Loads 23927 14604 14299 0
Central Cooling Coil 23927 14605 0 0
Central Heating Coil 0 14299
Total Conditioning 23927 14605 142991 0
Key: Positive values are clg loads
Negative values are htg loads
Positive values are htg loads
Negative values are clg loads
Hourly Analysis Program v4.50 Page 1 of 1
Air System Sizing Summary for RTU-5
3ruject Name: 18M0 Learning City Daycare - Sanford 10/15/201!
repared by: Loucks Engineering, Inc. 01.16PA
r
Air System Information
Air System Name .-- ---- .................. _-------- - --- -_ ----- RTU-5
Equipment Class -- - -- ---.-.- ------------------- ...... ..... ... UNDEF
Air System Type --------------------- --------------------------- - SZCAV
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM .....__.------------------ Sum of space airflow rates
Space CFM._-------------------- Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load ...------------ ---------------------------------- ........._...-....2.7 Tons
Total coil load ----------------------------- --------- --- - --- 32.2 MBH
Sensible coil load ._._. 18.9 MBH
Coil CFM at Jul 1500---------------------------------------------------------- 664 CFM
Max block CFM------------------------------------- --_.... _..... 664 CFM
Sum of peak zone CFM ._-_------------ ----------------- 664 CFM
Sensible heat ratio .................................... ...... 0.587
ftZ/Ton ---- ---- ---- - -- -- 303.0
BTU/(hr-ftZ) ------ - _ ----- ... ........ ..---- - - --- -------- 39.6
Water flow @ 10.0 °F rise ----- ...___._..___-... 6.44 gpm
Central Heating Coil Sizing Data
Max coil load - ------------------------------------ 11.2 MBH
Coil CFM at Des Htg _._._------.._..._.-........_.._........___......664 CFM
Max coil CFM ..... ------------------------------------------------------- 664 CFM
Water flow @ 20.0 °F drop. 1.13 gpm
Supply Fan Sizing Data
Actual max CFM------------- ------------------ 664 CFM
Standard CFM---------------------------------------- ---- 663 CFM
Actual max CFM/ftZ _.._....... 0.82 CFM/ftZ
Outdoor Ventilation Air Data
Design airflow CFM----------------------- ----------- --------------- .-..--- 359 CFM
CFM/ftZ .. ..- -_ - --------- --------------------- ...-.- 0.44 CFM/ftZ
Number of zones ------ ......
Floor Area ............ ._ .......__.
Location ._------------------- -------
Calculation Months -----------------
Sizing Data----- ------------------------
1
813.0 ftZ
Miami IAP, Florida
Jan to Dec
Calculated
Load occurs at ------ -- .- -- ------ ---------- -- ----I Jul 1500
OA DB / WB - - --- .... ---------------------------------- 91.0 / 77.0 F
Entering DB / WB ------------ -------- - ......................... 84.4 / 71.9 F
Leaving DB / WB..---------------------------------------- 58.0 / 57.0 F
Coil ADP - - ---------- ------ ------ .-------------------------------------- 55.1 F
Bypass Factor... --.--- 0.100
ResultingRH ------------------------------ ...................................... 54
Design supply temp. -- - - -- - 58.0 F
Zone T-stat Check ---------------- ---- ----------------- 0 of 1 OK
Max zone temperature deviation _- ------ 0.1 F
Load occurs at ..----------------------- ---------------- Des Htg
BTU/(h r-ftZ)---------------- - - 13.8
Ent. DB / Lvg DB -------------------- -.._. 57.0 / 72.7 F
Fan motor BHP ------------ - ------ -- 0.00 BHP
Fan motor kW .- -- ----------------------------------- 0.00 kW
Fan static -- - - ---- - -- - 0.00 in wg
CFM/person 16.30 CFM/person
Hourly Analysis Program v4.50 Page 1 of 1
t Zone Sizing Summary for RTU-5
Pioject Name: 18340 Learning City Daycare - Sanford
Prepared, by:`Loucks Engineering, Inc.
10/15/2018
01:16PM
Air System Information
Air System Name ------- ---------------------------------------- --- RTU-5
Equipment Class --- - - - - --.---------- ... ................... UNDEF
Air System Type -------------- --- --------.--._------ - ------- - -- SZCAV
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM Sum of space airflow rates
Space CFM . Individual peak space loads
Zone Sizing Data
Number of zones . ................... ...... - - - ..............._..1
Floor Area --.------------------------ .._._.....--------------------------- 813.0 ft2
Location .._______----- -------------- ---------- ---- ._ Miami IAP, Florida
Calculation Months ------------ ............................Jan to Dec
Sizing Data ---------- - ---.----_----------- --- ---------------------- Calculated
Maximum Design Minimum Time Maximum Zone
Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name MBH) CFM) CFM) Load MBH) ft2) CFM/ft2
Zone 1 12.2 664 664 Jul 1300 2.0 813.0 0.82
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Zone Name /
Space Name Mult.
Cooling
Sensible
MBH)
Time
of
Load
Air
Flow
CFM)
Heating
Load
MBH)
Floor
Area
ft2)
Space
CFM/ft2
Zone 9
2 yrs 2 1 11.9 Jul 1300 649 1.9 770.0 0.84
Toilet (2yrs) 2 1 0.3 Jul 1300 14 0.1 43.0 0.33
Hourly Analysis Program v4.50 Page 1 of 1
r
Project Name: 18340 Learning City Daycare -Sanford
Ventilation Sizing Summary for RTU-5
10/15/2018Preparedby: Loucks Engineering, Inc.
01:/26PM
1. Summary
Ventilation Sizing Method ------------
Design Ventilation Airflow Rate.
2. Space Ventilation Analvsis Table
Sum of Space CA Airflows
359 CFM
Zone Name / Space Name Mult.
Floor
Area
ft')
Maximum
Occupants
Maximum
Supply Air
CFM)
Required
Outdoor Air
CFM/person)
Required
Outdoor Air
CFM/W)
Required
Outdoor Air
CFNI)
Required
Outdoor Air
of supply)
Uncorrected
Outdoor Air
CFM)
Zone 1
2 yrs 2 1 770.0 22.0 649.2 10.00 0.18 0.0 0.0 358.6
Toilet (2yrs) 2 1 43.0 0.0 14.3 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 663.5 358.6
nouny r+ndrysis rrogram v4.5u
Page 1 of 1
e
Air System Design Load Summary for R U-5
Project Name: '18340 Learning City Daycare - Sanford 10/15/2018
Prepared by. Loucks Engineering, Inc. 01:16PM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500
COOLING OA DB / WB 91.0 °F / 77.0 °F
HEATING DATA AT DES HTG
HEATING OA DB / WB 46.0 °F / 38.6 °F
ZONE LOADS Details
Sensible
BTU/hr)
Latent
BTU/hr) Details
Sensible
BTU/hr)
Latent
BTU/hr)
Window & Skylight Solar Loads 0 ft2 0 0 ft2
Wall Transmission 248 ft2 912 248 ft2 735
Roof Transmission 813 ft2 2627 813 ft2 948
Window Transmission 0 ft2 0 0 ft2 0
Skylight Transmission 0 ft2 0 0 W 0
Do,or Loads 0 ft2 0 0 ft2 0
Floor Transmission 813 ft2 0 813 ft2 269
Partitions 0 ft2 0 0 W 0
Ceiling 0 ft2 0 0 ft2 0
Overhead Lighting 1040 W 3055 0 0
Task Lighting 0 W 0 0 0
Electric Equipment 385 W 1232 0 0
People 22 4182 2640 0 0 0
Infiltration 0 0 0 0
Miscellaneous 0 0 0 0
Safety Factor 0%/0% 0 0 0% 0 0
Total Zone Loads 12008 2640 1951 0
Zone Conditioning 13352 2640 1952 0
Plenum Wall Load 0% 0 0 0
Plenum Roof Load 0% 0 0 0
Plenum Lighting Load 0% 0 0 0
Return Fan Load 664 CFM 0 664 CFM 0
Ventilation Load 359 CFM 5558 10642 359 CFM 9293 0
Supply Fan Load 664 CFM 0 664 CFM 0
Space Fan Coil Fans 0 0
Duct Heat Gain / Loss 0% 0 0% 0
Total System Loads 18911 13282 11246 0
Central Cooling Coil 18911 13283 0 0
Central Heating Coil 0 11246
Total Conditioning 18911 13283 11246 0
Key: Positive values are cig loads
Negative values are htg loads
Positive values are htg loads
Negative values are clg loads
Hourly Analysis Program v4.50 Page 1 of 1
Air System Sizing SU0nnlary for RT[1'6
rro]octvwame 1834oLearning City Daycare Sanford piepare4by'
Loucks Engineering, Inc. 1V/
15/2810 Air
System Information a|
raystemwame—-- Equipment
Clas——— nTu-
6 umoEr
szcAv
Sizing
Calculation Information Zone
and Space Sizing Method: ZoneCFM--_----—
aumofypoona|mmwramu Space
CFM . Individual peak space loads Central
Cooling Coil Sizing Data Total
coil load .... ---'——---- ------ ... ... ............ nJ Too, Total
coil load ......... ---------------------------------------- s.e MBy Sensible
coil load ------ ----- —----'' —--' 25.8 mBn Coil
oFmat Jul 1000--------------- ---------- ----------- en3 orm Max
block orm------------------------------ ---- ---------- enz Cnw Sum
ofpeak zone cFm------------------------ --- nua CFw Sensible heat
ratio ----- _------------- —............. o.00r W/on---------- —---- —-..... --- —.
29a.0 sTu/(xpn')--.................... ---- ---------------
4n.1 Central Heating
Coil Sizing Data Max coil
load -------- --- ------- -------------------------------------- —--- 1s.s mBn Coil cnwatDes
VW oon CFm Max coil CFM--------- --------------- ----------------------- ---------- —
yon nrM Supply Fan Sizing
Data AnmalmaxcFM_--- StanuardCFM-----' mct"
a|
maxoFMm`_—'
Outdoor Ventilation Air
Data Design airflow oFM---- --------- --
yno npm eon
oFM 4ns
onN Numbernfzones, -------- ------------------ ----- ---------- --------------------
I Floor
Area —---- ---- --------------- ---- ------------------------------------ -moz.o
n` Calculation MonSizing Data ths
Jan mDecCalculated
Load occurs at ---------- --------------------- ----- ------- ------------------
Jul
1soo oaoo/vve ---- o1.n/
77.n F Entering oB/mB ------ --- -------- o4.
4/rty r Leaving o13/vvB--- —------- 58.
0/57o F Coil ADP ... ..... --------------------------------- --------------- on.1
F Bypass Factor ----------- ------------- ---------------------------- 0.100
Resulting Rn------------------------------ —_------ a4 m
Design supply temp.— --' -- so.
o F Zone T-statCheck ------------ ----- ------------------------------------------- nof1
OK Load occurs at uru/(hpu')--------- ---- --- --- ---.....
Fan motor BHP --_------- ------ —_'
mmmmo,Nw
Des mg 1^.
1 o7.
o/7z.
y `F
o.on BHP 0.00
Nm Hourly Analysis
Program v4.50
Page 1of1
Zone Sizing Surnmary for RTU-6
Project Name:'18340 Learning City Daycare - Sanford 10/15/201
Prepared by: Loucks Engineering, Inc. 01:17PP
Air System Information
Air System Name .---------------- ---- ------------------- --_---- _. RTU-6
Equipment Class --- ----- ------ ----------------_-------- ------ UNDEF
Air System Type .....--------------------- ------ --- ---- SZCAV
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM------ ------- ---------- Sum of space airflow rates
Space CFM . ----- Individual peak space loads
Zone Sizing Data
Number of zones - ----------------------- -----
Floor Area-, - - - - - --- ---- ------ ------------1093.0 ftZ
Location -.-.- . --.--------------- .---- ___----- Miami IAP, Florida .
Calculation Months ----------- ___..-------------------------- Jan to Dec
Sizing Data _------------------- Calculated
Maximum Design Minimum Time Maximum Zone
Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name MBH) CFM) CFM) Load MBH) ftZ) CFM/ft2
Zone 1 16.6 903 903 Jul 1300 2.8 1093.0 0.83
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Zone Name /
Space Name Mult.
Cooling
Sensible
MBH)
Time
of
Load
Air
Flow
CFM)
Heating
Load
MBH)
Floor
Area
ftZ)
Space
CFM/ftZ
Zone 1
3 yrs 1 16.3 Jul 1300 889 2.7 1050.0 0.85
Toilet (3yrs) 1 0.3 Jul 1300 14 0.1 43.0 0.33
Hourly Analysis Program v4.50 Page 1 of 1
Ventilation Sizing Summary for RTU-6 r,
Project Name: 18340 Learning City Daycare - Sanford 10/15/2C', 8
Prepared by: Loucks Engineering, Inc. 01:1_7PM
1. Summary
Ventilation Sizing Method Sum of Space CA Airflows
Design Ventilation Airflow Rate __......_......_... 489 CFM
2. Space Ventilation Analysis Table
Zone Name / Space Name Mult.
Floor
Area
ftz)
Maximum
Occupants
Maximum
Supply Air
CFM)
Required
Outdoor Air
CFM/person)
Required
Outdoor Air
CFM/ft2)
Required
Outdoor Air
CFM)
Required
Outdoor Air
of supply)
Uncorrected
Outdoor Air
CFM)
Zone 1
3 yrs 1 1050.0 30.0 888.9 10.00 0.18 0.0 0.0 489.0
Toilet (3yrs) 1 43.0 0.0 14.3 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 903.3 489.0
Hourly Analysis Program v4.50 Page 1 of 1
It,
L
Air System Design. Load Summary for R iU-6 — ---
Project Name: 1`8340 Learning City Daycare - Sanford 10/15/2018
Prepared by: Loucks Engineering, Inc. 01:17PM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500
COOLING OA DB / WB 91.0 °F / 77.0 °F
HEATING DATA AT DES HTG
HEATING OA DB / WB 46.0 °F / 38.6 °F
ZONE LOADS Details
Sensible
BTU/hr)
Latent
BTU/hr) Details
Sensible
BTU/hr)
Latent
BTU/hr)
Window & Skylight Solar Loads 0 ft2 0 0 ft2
Wall Transmission 354 ft2 1301 354 ft2 1048
Roof Transmission 1093 ft2 3532 1093 ftZ 1275
Window Transmission 0 ft2 0 0 ftZ 0
Skylight Transmission 0 ft2 0 0 ft2 0
Door Loads 0 ft2 0 0 ft2 0
Floor Transmission 1093 ft2 0 1093 ft2 460
Partitions 0 ft2 0 0 ft2 0
Ceiling 0 ft2 0 0 ft2 0
Overhead Lighting 1404 W 4124 0 0
Task Lighting 0 W 0 0 0
Electric Equipment 525 W 1680 0 0
People 30 5703 3600 0 0 0
Infiltration 0 0 0 0
Miscellaneous 0 0 0 0
Safety Factor 0%/0% 0 0 0% 0 0
Total Zone Loads 16341 3600 2783 0
Zone Conditioning 18183 3600 2785 0
Plenum Wall Load 0% 0 0 0
Plenum Roof Load 0% 0 0 0
Plenum Lighting Load 0% 0 0 0
Return Fan Load 903 CFM 0 903 CFM 0
Ventilation Load 489 CFM 7576 14509 489 CFM 12679 0
Supply Fan Load 903 CFM 0 903 CFM 0
Space Fan Coil Fans 0 0
Duct Heat Gain / Loss 0% 0 0% 0
Total System Loads 25759 18109 15465 0
Central Cooling Coil 25759 18110 0 0
Central Heating Coil 0 15465
Total Conditioning 25759 F 18110 15465 0
Key: Positive values are clg loads
Negative values are htg loads
Positive values are htg loads
Negative values are clg loads
Hourly Analysis Program v4.50 Page 1 of 1
Air System Sizing Summary for RTU-7
1 Project, Name: 'I8340 Learning City Daycare - Sanford
Preparerd by. Loucks Engineering, Inc.
10/15/2018
01:17PM
Air System Information
Air System Name ---------- ---- ---------------------------------------- RTU-7
Equipment Class -------------------- ----------.------ -----------.- UNDEF
Air System Type, - __ - -------------------------- SZCAV
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM Sum of space airflow rates
Space CFM . Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load .. - ...... - ....... 3.2 Tons
Total coil load -- -------------------------------------------------- 37.9 MBH
Sensible coil load . 25.2 MBH
Coil CFM at Jul 1600........................__------.....__----------- 1014 CFM
Max block CFM ----- ----------------------------------------------- 1014 CFM
Sum of peak zone CFM ----- ___------ ------------- 1014 CFM
Sensible heat ratio ---------------------- 0.665
ft2/Ton ------------------- ------ --- ------------------ - - --- 237.1
BTU/(hr-ft2) -------------------------------------- --------------------- 50.6
Water flow @ 10.0 °F rise . 7.58 gpm
Central Heating Coil Sizing Data
Max coil load ---- -- - ---- ------- - -------------------------------- 14.9 MBH
Coil CFM at Des Htg . 1014 CFM
Max coil CFM -. 1014 CFM
Water flow @ 20.0 °F drop --- ------- _._----------- _____....... 1.49 gpm
Supply Fan Sizing Data
Actual max CFM-----------------------------..-------- --- -------------- 1014 CFM
Standard CFM .--- - ----------------------------------------- ----- 1014 CFM
Actual max CFM/ft2------------- ----- -------------- ------------------- 1.36 CFM/ft2
Outdoor Ventilation Air Data
Design airflow CFM--------------------------------------- ----------.-.._.. 327 CFM
CFM/ft2 ...----------- ------- --- -- - - ----------- -- - ...... 0.44 CFM/ft2
Number of zones . - ----------------...---------------------------------.1
Floor Area . - - -.------- .... ...... ----- -- - 748.0 ft2
Location .__.-_------------------- _____ Miami IAP, Florida
Calculation Months ---------------------------------- __--- -....._..Jan to Dec
Sizing Data --- --------------------- ---- ------------ ---------------------- Calculated
Load occurs at - ........ ----------------------------- ----------------------- Jul 1600
CA DB / WB ------_-------- — --- --...- 90.7 / 76.9 F
Entering DB / WB_..---------------------------------- 81.0 / 68.8 F
Leaving DB / WB-------------------------------------------- 58.0 / 57.0 F
CoilADP ------------- ------- - - ---------------------------------------------------- 55.4 F
Bypass Factor -------------------------- - - 0.100
Resulting RH . - -------------------------- ----- 52
Design supply temp.. ------------.._...__.-_ .. ................ 58.0 F
Zone T-stat Check ----------- -------------------------------------------------- 1 of 1 OK
Max zone temperature deviation --- _--- ----------------------------- 0.0 F
Load occurs at ------------------- -- Des Htg
BTU/(hr-ft2) .. _ ._...._ ---------------------- 19.9
Ent. DB / Lvg DB.------------------------- 62.0 / 75.6 F
Fan motor BHP --------------------- ---------------- 0.00 BHP
Fan motor kW 0.00 kW
Fan static ------- - -- - --------------------------- 0.00 in wg
CFM/person .-... 16.35 CFM/person
Hourly Analysis Program v4.50 Page 1 of 1
Zone Sizing Summary for RTU-7
Project Name: 18340 Learning City Daycare - Sanford 10/15/2018
IPrepare.d by. Loucks Engineering, Inc. 01:17PM
Air System Information
Air System Name - --. ----------------- - --- ----------------------_ RTU-7
Equipment Class .-- -------------- .-.---------- --- .......... UNDEF
Air System Type ------------ ------ -- - - - - - -. SZCAV
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ----------------------------- Sum of space airflow rates
Space CFM.__ - - - Individual peak space loads
Zone Sizing Data
Number of zones ---------- ----------------------------------------- - -----1
Floor Area - -- - ---------- ------------------ 748.0 ft2
Location ..-------------------- _-------------------- __.__ Miami IAP, Florida
Calculation Months ..................... ....___.___.._...._..Jan to Dec
Sizing Data ---,----- --------------------- .----------- ----------------------- Calculated
Maximum Design Minimum Time Maximum Zone
Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name MBH) CFM) CFM) Load MBH) ft2) CFM/ft2
Zone 1 18.5 1014 1014 Jul 1700 6.6 748.0 1.36
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this systern.
Space Loads and Airflows
Zone Name /
Space Name Mult.
Cooling
Sensible
MBH)
Time
of
Load
Air
Flow
CFM)
Heating
Load
MBH)
Floor
Area
ft2)
Space
CFM/ft2
Zone 1
4 yrs 1 18.0 Jul 1700 983 6.3 705.0 1.39
Toilet (4yrs) 1 0.6 Jun 1100 32 0.3 43.0 0.74
Hourly Analysis Program v4.50 Page 1 of 1
Project Name: 18340 Learning City Daycare - Sanford
Prepared by: Loucks Engineering, Inc.
1. Summary
Ventilation Sizing Method ------ -------------
Design Ventilation Airflow Rate .-..-...-
2. Space Ventilation Analysis Table
Ventilation Sizing Summary for RTU-7
Sum of Space OA Airflows
327 CFM
Zone Name / Space Name Mult.
Floor
Area
ftz)
Maximum
Occupants
Maximum
Supply Air
CFM)
Required
Outdoor Air
CFM/person)
Required
Outdoor Air
CFM/ft2)
Required
Outdoor Air
CFNI)
Required
Outdoor Air
of supply)
Uncorrected
Outdoor Air
CFM)
Zone 1
4 yrs 1 705.0 20.0 982.5 10.00 0.18 0.0 0.0 326.9
Toilet (4yrs) 1 43.0 0.0 31.7 0.00 0.00 0.0 0.0 0.0
Totals (incl. Space Multipliers) 1014.2 1 326.9
r
10/15/26"8isi
01-17PM I
Hourly Analysis Program v4.50 Page 1 of 1
F1 Air Systerin Design Load Surnmary for RTU.-7
Pr jec', Name: 18340 Learning City Daycare - Sanford 10/15/2018
Prepared by. Loucks Engineering, Inc. 0117PM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600
COOLING OA DB / WB 90.7 °F / 76.9 °F
HEATING DATA AT DES HTG
HEATING OA DB / WB 46.0 °F / 38.6 °F
ZONE LOADS Details
Sensible
BTU/hr)
Latent
BTU/hr) Details
Sensible
BTU/hr)
Latent
BTU/hr)
Window & Skylight Solar Loads 208 ft2 3150 208 ft2
Wall Transmission 858 ft2 3760 858 ft2 2541
Roof Transmission 748 ft2 2105 748 ft2 872
Window Transmission 208 ft2 1441 208 ftZ 2496
Skylight Transmission 0 ft2 0 0 ft2 0
Door Loads 0 ft2 0 0 ft2 0
Floor Transmission 748 ft2 0 748 ft2 681
Partitions 0 ft2 0 0 ft2 0
Ceiling 0 ft2 0 0 ft2 0
Overhead Lighting 955 W 2836 0 0
Task Lighting 0 W 0 0 0
Electric Equipment 353 W 1133 0 0
People 20 3855 2400 0 0 0
Infiltration 0 0 0 0
Miscellaneous 0 0 0 0
Safety Factor 0%/0% 0 0 0% 0 0
Total Zone Loads 18280 2400 6590 0
Zone Conditioning 20122 2400 6537 0
Plenum Wall Load 0% 0 0 0
Plenum Roof Load 0% 0 0 0
Plenum Lighting Load 0% 0 0 0
Return Fan Load 1014 CFM 0 1014 CFM 0
Ventilation Load 327 CFM 5039 10299 327 CFM 8344 0
Supply Fan Load 1014 CFM 0 1014 CFM 0
Space Fan Coil Fans 0 0
Duct Heat Gain / Loss 0% 0 0% 0
Total System Loads 25161 12699 14882 0
Central Cooling Coil 25161 12700 0 0
Central Heating Coil 0 14882
Total Conditioning 25161 12700 14882 0
Key: Positive values are cig loads
Negative values are htg loads
Positive values are htg loads
Negative values are clg loads
Hourly Analysis Program v4.50 Page 1 of 1