HomeMy WebLinkAbout819 E 1 St Ste 6 18-4391 Plans interior remodelDESIGN CRITERIA COMi'LIANCE PER FBC 2017 - ASCE 7-10 COMPLIANCE PER NEC 2014 BUILDING DESIGNED AS FULLY ENCLOSED STRUCTURE FACTOR ,18 WINDOW PROTECTION REQUIRED WIND SPEED 160 MPH, Vult 124 MPH, Vasd EXPOSURE CATEGORY D RISK CATEGORY II OCCUPANCY GROUP B - BUSINESS CONSTRUCTI❑N TYPE V - UNPROTECTED TABLE 600 FIRE RESISTANCE RATINGS INTERI❑R BEARING WALLS 0 COLUMNS 0 BEAMS/GIRDERS/TRUSSES/ARCHES 0 FL❑❑R/CEILING 0 ROOF/CEILING 0 EXTERIOR BEARING WALLS 15' MIN, - 0 TABLE 503 MAX, NUMBER OF STORIES MAX, HEIGHT IN FEET AREA ALLOWABLE 3 40' UL LIVING LANAI ENTRY GARAGE TOTAL ROOF DESIGN CRITERIA: PER ASCE 7-10 TOP CHORD, LIVE LOAD - 0/12-4/12 = 20 PSF 4/12-12/12 = 16 PSF TOP CHORD, DEAD LOAD - 12 PSF (SHINGLES) 20 PSF (TILE) BOTTOM CHORD, DEAD LOAD = 4 PSF BOTTOM CHORD, DEAD LOAD/STORAGE = 30 PSF BOTTOM CHORD, LIVE LOAD = 10 PSF 50.1# WINDL❑AD ACTUAL 1 18' 1350 SQ. FT 126 • ' 194 ' ' 576 2246 SQ, FT, CONTRACTOR TO VERIFY ALL DIMENSIONS AND CONDITIONS PRI❑R TO STARTING ANY CONSTRUCTION. IN THE EVENT ANY DISCREPANCIES OCCUR THAT AFFECTS CONSTRUCTION, NOTIFY THE ARCHITECT OR ENGINEER FOR CLARIFICATION, c1\users\ jim\documents\ebs\commercial\david casteel\david casteel int renovation, wg OCT 3 0 2018 TERIOO R RE OO VATIOO VICINITY MAP Sanford Museum Fort Mellon Park } t 819 bast 1 it Strut 2 A Seminole +� 1ipCtOf- Sal ars .11 SDA Church t a � i m III 1 PROJECT SITE PROJECT LOCATION - 1 it i 1 FRI t n� INDEX TO DRAWINGS MARK DESCRIPTION PRODUCT APPROVAL U Z J J q C 1 COVER B 1 EXISTING FLOOR PIAN Pa(U B 2 PROPOSED FLOOR PIAN B 3 EXISTING BAR JOIST LAYOUT \ C/)p W ROOF PLAN WALL SECTIONS, DETAILS LJ Iz=3 Lja: B 4 REFECTED CEILING PLAN M 1 HVAC PLAN CL —X >0U M 2 PLUMBING PLAN E 1 ELECTRICAL PLAN it LS 1 EGRESS PLAN wQ.a La fOUNMU PA=M U W?U 60 <Z Srj. Ci z Pa P7 ¢ HOJZ„Z_, OFFICE r ViL�J 1 y--< '1 WQMF-}� zOzN Q O P4 f/1 ,-. J } w .U-�g +v LLI2�SF-O� PERMIT F- L)XwSf\ WL, F- Cl) S 1 NOTES, DETAILS S 2 NOTES, DETAILS E-1257 V) z pp J O H ON z Z Li O _ Z Z W O f= O cn m p-- �- LL. Z owU) z O m D - rl� O U W m Ma_U LU Lli -4Ucn C14 3 M00 cc LU N N NQooO z � N O Z J 00 LL- LL W Q F-. p (n O D O Z (n W mN Q LU 0 rY M =w Z � J 0 Q Q U Z J J q O Pa g Y U JQaW ED Pa(U W J n~ W W QL , o X¢ U ��� Wa 6 -waw \ C/)p W S¢a = QUy QZ= WWF LJ Iz=3 Lja: 30 3 Ld p ECJ w=QW3 > CL —X >0U J.~-.-.ZF (� �UZ o3QM �aW ZID it Q zQ-1 Z}L,J YJ�q¢¢Q wQ.a La fOUNMU PA=M U W?U 60 <Z Srj. Ci z Pa P7 ¢ HOJZ„Z_, r ViL�J 1 y--< '1 WQMF-}� zOzN Q O P4 f/1 ,-. J } w .U-�g +v LLI2�SF-O� (L000 F- L)XwSf\ WL, F- Cl) WDW¢ 0C3F- ❑CL.Z-<DL0 SA�z F-Wx0<10 Q Lu CC '2 a w 00 W <L W Z Z o r N QN 0o Li I� ^ z 0 W :3 w z X LLJ Z J V O� o cl� L� LL a o 00 QUi o x o W W0 m 09 LL N h fY p o ^ Li a � 0 U 0~ O Pa g Y U .� N Z , o \ C/)p W Qa pcl > A W A it z H 1� <L W > Li z � LLJ J cl� L� � (4 Q ❑_ tY Li = � W W i- o- z Z > z �Q ❑ A U z °-\ d raj J Q W y IN si\commerc1at\dav1d casteel\david casteel Int renovation,dwg ELEC. LOCATI LOCATI EXISTING FLOOR PLAN SANITARY CA. SCALES 3/16' = 1'-0' E-1257 OD Z pp J O H OD N Z Z_ O Z OZ U Z two F O (!) m F o w � W 0 a. (1) Z a& O m 5 o UWmaCL0 O U �V) 18 lei 3 M 00 U) Q N N 0 O ixUz O Z Ir o N I Q N L1L. m Q WAX U p Q p (D/)2 D U z 0) m N Q W0 m OD 0 0 U LL Q OD yW J O Q Z J J A m � CD CD CL U a= p IN tU Z N LLJ LJ LL. H Vlad}aW p A WV14 fL 0. (/) W 4 xCcLu x A U (n AZx W W ►- 18 lei Wa3 �����¢ Ax �'"J z a. >6LLa �w2�3ai ixUz p 3 U W y g Z UJM(4 Q ZQ J W CL WAX U p Q LLJ U17AV i SUPPORT EXISTING BAR JOISTS REMOVE MASONRY UNDER FORME] AND POURED BEAM, CONSTRUCT 8'x16' MASONRY COL ADJACENT TO POURED COLUMNS INSTALL CONCRETE PRESTRESS', UNDER POURED BEAM AND ONT❑� NEW MASONRY COLUMNS GROUT ABOVE PRESTRESS TO OPTION: FORM AND POUR CONC, CONCRETE BEAM UNDER EXISTING EXIST, POURED BEAM TO REMAIN SEE DETAIL SHEET B2 o+ i co N U Fi STOREFRONT, BLOCK UP `sa'NT RY OPENING WITH MASONRY LEAVING C'0' IMPACT GLASS OPENING FOR WINDOW AS SHOWN PROPOSED FLOOR PLAN SCALE, 3/16' = F-0' si\commerclal\david casteel\david casteel Int renovation,dwg DESIGN CRITERIA- COMPLIANCE PER FBC EXISTING 2017 - ASCE 7-10 EXISTING BUILDING - INTERIOR RECONFIGURATION ALTERATION - LEVEL 3 COMPLIANCE PER NEC 2014 OCCUPANCY GROUP B BUSINESS OCCUPANCY GROUP B BUSINESS SCOPEI 1, REPLACE EXISTING Cl ROOF DRAINS WITH PVC, 2. SHIFT MAIN ROOF DRAIN DOWNSPOUT TO THE LEFT 2 FEET TO ACC❑MIDATE PROPOSED HALL 3, OPEN FLOOR AND INSTALL NEW SANITARY WASTE LINES TO NEW PLAN, 4, CUT FLOOR TO ACCOMIDATE ROLL IN ADA SHOWER WHERE SHOWN, 5, MODIFY EXISTING MASONRY WALLS AS SHOWN, NOTE ONLY CENTER WALL, PERPENDICULAR TO BAR JOISTS IS LOAD BEARING 6. CONSTRUCT NEW INTERIOR PARTITIONS AS SHOWN 7. REMOVE AND REPLACE EXISTING ROOF TOP A/C SYSTEM WITH EQUIPMENT SHOWN. 8. COMPLETE BUILD -OUT AS SHOWN 9, BUILDING CURRENTLY HAS 4 WATER METERS, REMOVE 3 METERS AND REPIPE SUPPLY LINES UTILIZING ONE (1) 1,5' EXIST, METER 10, INSTALL NEW TP❑ ROOF WITH SLOPE TO EXISTING ROOF DRAINS, 11, REMOVE EXISTING (4) ELECTRICAL SERVICES AND PANELS AND INSTALL ONE NEW 400 AMP SERVICE. LOCATION TO BE ON WALL NEAREST TO EXISTING ELECTRICAL TRANSFORMER, DRAB BAR L+ 36' A.F.F. UF'LRA 11NG LL VLR 19 40' A.F.F. E-1257 o, Ld Z J L_ Ld LO Q azo Aa•�t W CL O a N z co 0 N 00 >- z z yW d Q apJq_j A LL 02 z z jsw0 F— u zmU gC-C °-�- a:ao�ac CD ir 0 W C3 0O z Om57(r0 ~WWWVH U w m o a U =! w7_ Lllx_►Z'=¢ Vo =a�j EXISTING PARAPET WALL TO REMAIN. FLASH AND COUNTER FLASH, METAL CAP TO BE INSTALLED ON TOP OF PARAPET, NEW TPO ROOF WITH RIGID INSULATION TO SLOPE TO ROOF DRAINS. NOA TO BE PROVIDED PRIOR TO INSTALLATION EXISTING ROOF DECKING TO REMAIN EXIST. BAR .JOISTS TO REMAIN R-30 MULATION IN ROOF VOID NEW TPO ROOF WITH RIGID INSULATION TO SLOPE TO ROOF DRAINS, NOA TO BE PROVIDED PRIOR TO INSTALLATION EXISTING ROOF DECKING TO REMAIN PARTITION WALLS EXISTING BOND BM, NEW FORMED AND POURED BEAM I 0 A z 3 WINDOW M.O. DETAIL: NEW WINDOW OPENING SCALE, 1/2' = F-0' EXISTING BAR JOISTS SCALD iie' ■ I --a ci\users\JIm\documents\ebs\commercial\do.vid casteel\david casteel Int renovation,dwg EXISTING REMOVE E SCH. 80 P' REPLACE E DRILL & EPDXY #50 INTO EXIST, BOND BM. MIN. 4' CUT OPENING IN EXISTING WALL TO 8' MIN. LARGER THAN THE M.O. NEEDED FOR THE WINDOW, DRILL AND EPDXY #50 VERT. INTO EXISTING SLAB, FORM & POUR NEW OPENING W/ 3000 PSI CONC, CUT VERT, SLOT IN BLOCK TO RETROFIT #50 VERT, DRILL 3/4' X 6' DP, HOLE IN EXISTING SLAB CARE TO BE TAKEN TO THOROUGHLY CLEAN OUT DEBRIS PRIOR TO ADDING EPDXY SET REBAR IN APPROVED EPDXY ALLOW TO CURE FOR THE SPECIFIED TIME PRIOR TO APPLYING ANY LOAD DO NOT DISTURB OR LOAD THE ANCHOR UNTIL IT IS FULLY CURED FORMED AND POURED BEARING BEAM TO REMAIN, u r.a NG IN EXISTING WALL TO THAN THE M.O. NEEDED FOR DRILL AND EPDXY #50 0 EXISTING SLAB, FORM & OPENING W/ 3000 PSI .L 3/4' X 6' DP. HOLE :XISTING SLAB TO BE TAKEN TO THOROUGHLY CLEAN DEBRIS PRIOR TO ADDING EPDXY REBAR IN APPROVED EPDXY 3W TO CURE FOR THE SPECIFIED : PRIOR TO APPLYING ANY LOAD NOT DISTURB OR LOAD THE ANCHOR UNTIL IT IS FULLY CURED DETAIL -i NEW PATHWAY INTERIOR OF BLDG, SCALEi 1/2' = V-0' EXISTING ROOF DRAIN PLAN WITH NOTED MODIFICATION SCALES 1/W = 1I -V E-1257 V) z 00 J O F N co >- O zz OW� U Z z > �i W O O tnmr- 00 a 9 oz OmOUjJYO U W m a a-0 U o_ V) N 00 uiN N N 0 0 Q o Z w NO 00 ono^ U z v N m LUo m ~� aW01 � U QMJJJ Q -�Qai o O as WJJF W� �QU Wdd>-dW a z v1 Uy W WaOa3 10.7,~�~~a Z..iJ (n SW Wf-gW3 Woz G N Z.0 Z)-Q W YJg41E �Q �1—O IO�A�U � z j Z �av�Qi a~ .. =H Zqq Q yC3-JZA "'c ^ Q (Z*'6 !-aL)(46i r! - =►Wr F- T J FL! L) (4 6 WMWQ h -U W=^ LJZI+HM 0C3 WW(4m �v� 04cIn n ►=-aa}ia l M .- a w L- 00 Z Z N0 04 ir- z N w fn M v a a3Lj- �o Z �o W N 00 N aw 0m W I0 co U. O N n G iii. v � U oO A \ N z v1 \ y� O (n 7 N A N q yyi NEW WINDO s►\commercial\david casteel\david casteel Int renovation,dwg ✓I\ PROPOSED REFLECTED CEILING PLAN E-1257 V) z Do J O F N >- z z L` O Z U FRO z OZ � wo F O cn m F o:00=) p W (N a.cn9woz o m 5 o UwmoaU o (n N M 00 N N Q 0 0 N O -1 m N W U-) 1- n O N O i— U W N QT- 14- o m M LJ � O a �a yWLLJa d A m N ¢OJOJJ CL � o z N WJ•U�'W� oau o W w-4 LJ � Q co F-aWQUy •>y� WZ.~r 0 W W�x�=a 0 ~ � ~ iS M CL J J�~rZ�3fh CL LLI W HU� �UZ C3 Q Z Z ¢~ ]CJ -Mama 2GUfAC3U Q QUO UU U liU IXUQ Woe M 4c z A A a Q J Z F-OJzz L6 J H""" .c1,4 Wap�gF'>-v z0ZIl a G aQZVUI W'U'S}(xv 01 FZ-V"z„W^ = La OW WL . Cl) aa�a�v� (4Cla -Q =a>y-z 1-(4XW<in z F --c0 LdMM 1.� T a; w H J 00 w ., Z Z Tr 04 Q N0 V 2 Z m 0 N T 'a , Vw (A M v q Q F— w opoz O 0 C4 Lid I— Q t 04 W0m LU J L� � w0 Q 0 am g � O U m N Z o W w-4 LJ � Q pp}�� _ � •>y� iS OC Z Q J Z a F- F- z Q L,J W H J O z � I-- H W LJ _j U LL. q Q F— w L,J O u W Lid I— 0� LL_ Z , J L� � •—+ 00 Q 0 L,J ry W q9 W N st\commercia(\david casteel\dav(d casteet Int renovatlon.dwg Lmi OgA 9 '- -� r --o- n rl ri 0 `4 \ EXIT PROPOSED ELECTRICAL PLAN NO CHANGES OR MODIFICATIONS THIS SIDE LEGEND 2 TUBE LED FLOUR FIXTURE 0 EXH.FAN EX, FAN 50 CFM DUPLEX OUTLET ® SPECIAL PURPOSE OUTLET EMERGENCY LIGHT SWITCH EXHAUST FAN SCHEDULE SYMBOL MANUFACTURER CATELGG # CFM VOLT/O/HZ REMARKS EF -1 BROAN OZ>$iz HD -50 50 120/1/80 112 ACCESSORIESi 1. PROVIDE WITH BACKDRAFT DAMPER, PLUG IN DISCONNECT AND VIBRATION ISOLATION 2. FAN TO BE OPERATED FROM WALL SWITCH. SWITCH BY ELECTRICAL CONTRACTOR. E-1257 m LJ V) z 00 O N Q O C9 Q -1'J0 A Y u-. O Z OZ>$iz z a ~ FOtnmF U. Z U O O0 D Q �z CL V) O m O Ir O U W m 0 a U W I- U V) 04 3 M 00 N W N Q N � O Ld Mpo p � U p Z W N O N u -Lo W Lo F- n Q oc p U) o --� D U w v N aUViV =1.4WMWQ m N Q W o m m LJ � U a �¢ dJ Q -1'J0 A Y CLV a= W (U p Z N W J F- W LL.0. �' Q QQ i Q mzx ~�,,�WWU(y WZI.- W�Hz=Q Wa3 W�z�3 WUZ p 3 U c y 2 Z a J W YaQQAa Ld Mpo p � U p Q W zoecjm a�`icn.,QQz4c z W c HOJzZQ C4 0-4 Wa�t-�-� Q Z01� Q z2 �L) aUViV =1.4WMWQ z ^ py�fQAQ1In V10HggqqZZ Lel F=QV}1¢ ■ M a: w 00 w . z Z - N ,. O 2� z -' 04 a 0 W L.� ED v a) a 41 x a 3� U vz� � Z O oz Z z _ . (n 0 p OD N a o W W U m coI W oC p 0 W �a v � U dJ ON. Y (U Z Q M q VI ae 0 Q W z W Q Q' J z Lel J O Lw L.� ED �-- w U � Z Li z 00 Q a. J Ld I�— W /201 rn N PROVIDE 6' DEEP INSULATION AND 16 GAGE SHEET METAL TOP PROVIDE FLEX CONNECTOR AT OVER CURB ASSEMBLY, TOP TO DUCT & ELECTRICAL CONNECTIONS PITCH IN ALL DIRECTIONS FOR (TYPICAL) PROPER DRAINAGE. PAINT METAL 14' ROOF CURB BY TOP TO MATCH ROOF COLOR. �AC UNIT MFR. UNIT MFG. SEAL & CONTINUOUS CURB ISOLATION PROTECTION OUTSIDE AIR INTAKE RETURN AIR DUCT CONN. SIZE AT UNIT CONN, SIZE I SUPPLY DUCT I_. I DUCT SMOKE DETECTOR 1 ROOF SEE DETAIL CIF REQUIRED) � PROVIDED BY DIVISIONI6. FILL INSIDE OF CURB W/ SOUND BATT INSULATION & LIGHTWEIGHT INSULATING CONCRETE NOTEi PIPE CONDENSATE FROM UNIT USING CONNECTION SIZE (3' MIN.) TO NEAREST ROOF DRAIN. PROVIDE 'P' TRAP AT UNIT. 5 TON, 14 SEER UNIT ROOF TOP A/C UNIT N.T.S. NOTE+ SECURE UNIT TO ROOF TOP PER MANUFACTURERS SPECIFICATI❑NS, NEW WINDOW PROPOSED ROOF TOP PACKAGE 2 INITS, CARRIER MODEL 50KC-AO6A2B5-OAOAO 208/240 VOLT 3 PHASE 14 SEER MANUAL OUTDOOR FRESHAIR VIA LOUVER ON UNIT HEAT CR HEATER 104BO❑ (7,9 - 10,0 KW) si\commerclal\david casteel\david casteel Int renovatlon,dwg WINDOW PROPOSED HVAC PLAN E-1257 N Z 0p O F 7-0' ABOVE ROOF 00 N >- Z Z � MINIMUM HEIGHT OZWO �W U Z W- L'JU. FOR O.A. INTAKE OUTSIDE AIR INTAKE RETURN AIR DUCT CONN. SIZE AT UNIT CONN, SIZE I SUPPLY DUCT I_. I DUCT SMOKE DETECTOR 1 ROOF SEE DETAIL CIF REQUIRED) � PROVIDED BY DIVISIONI6. FILL INSIDE OF CURB W/ SOUND BATT INSULATION & LIGHTWEIGHT INSULATING CONCRETE NOTEi PIPE CONDENSATE FROM UNIT USING CONNECTION SIZE (3' MIN.) TO NEAREST ROOF DRAIN. PROVIDE 'P' TRAP AT UNIT. 5 TON, 14 SEER UNIT ROOF TOP A/C UNIT N.T.S. NOTE+ SECURE UNIT TO ROOF TOP PER MANUFACTURERS SPECIFICATI❑NS, NEW WINDOW PROPOSED ROOF TOP PACKAGE 2 INITS, CARRIER MODEL 50KC-AO6A2B5-OAOAO 208/240 VOLT 3 PHASE 14 SEER MANUAL OUTDOOR FRESHAIR VIA LOUVER ON UNIT HEAT CR HEATER 104BO❑ (7,9 - 10,0 KW) si\commerclal\david casteel\david casteel Int renovatlon,dwg WINDOW PROPOSED HVAC PLAN E-1257 ae¢ N Z 0p O F 00 N >- Z Z � L` O Z OZWO �W U Z W- L'JU. = Q C9 cr �— Z O U jr EL -J V) z om51Feo 0~��¢ aI fx- _j>6W UwmoaU J:It►~rZW3 O UN F- W M 04 0! Q C3 C4 )%0 Z Z< _j W 0. A YaAQQa 00 LuN N Q N O Vu i _____ r HOT WATER SUPPLY COLD WATER SUPPLY WATER LINE si\commercial\daviol casteel\david casteel int renovatlon.dwg PLUMBING PLAN E-1257 a z 00 -.4 O N z z Oz LL. 02 FX U z jd N W O Oyf- it ZmF � O O¢QQ D W o LO z om5mmo 0wmoaU o LU 04 Z r+ -� o N N a N 0 4mu%o Z YJpV1aa oO ZOf N O 00 zo 000 N E2 LO n Q p Cn O ^ r- L6 -00 C.CZ U xW c N Q m T- Q Luo m a � U �a 00 Wwwo Q J J A Y CO aVa= G N .r ZN WJJ~WW CL O¢QQ wnLCLMCL 0 V/ �W� x¢a HWWQ=UVI azx WZN N Z r+ -� Z W U p3cC3 4mu%o Z YJpV1aa Z< _j W 0.04z4 WOZ MF -o zo 000 Q W�U L6 -00 C.CZ W xW c 0""<�Zi� VZl�y, Li M 4c ZJ�1�1 0 ¢ 0 o-Ui�y► t*, OWWJ.fQ(4Q.1 NOFW-a W Z L.P M 00_"-CMu) xa -z 1--(4xW-CLn J 0 I d LL- M a w E3 00 Lu z ., Z Z W ,. N W ZM LL LV (n Z x Q � 3 n 9 C�W L z Q N Q N W W um 00 LL C4 In a° C) CL.. .�on� � U 00 Q Y N z W C V/ M CI N Z a H Q W > W p Z I— W J J LL- E3 �-' z H rV W � o H pq W LL Z H W W n 9 N 9 .�on� � s • J� �6 EGRESS PLAN sI\commercial\davld casteel\david casteet Int renovation.dwg VY EXIT EMERGENCY LIGHT E-1257 cn z 00 -10 EN Q cc O Z U U z O z Ma o POcnmF �-CC �OO� N a. N W 0 z Om 0 m 0 U W m a a. U � O V) N co N N Q NOf O I J pp N LL- N O (n O f— U W N Q m � U OD 1-1 O WW LLJ o d Z -jA IN N 1-1 aca�a= o zN W V) OC Wa-aCL C'pmgalL Li LL. (� y W 4i�� Lda3 Xa Lj= OC >r J.~iZW3f+f' H WV p Q yqU� ZZz zQJ W ac CL YOJ.QQQQ W QUO L) C3 U V�CKVQ 0 W U I_1 iR,?, 6.Cg OVfmmmaIc =y C �-- 0 J .-. WLL. 1 0 04 " 4c � WQ�►-}w J zozr a o aau y`~"v aCuc4u =�W�WnWQ F -L) WSJ yaF- WZIi1-(w) a CL <:) WLai V1Q = >/I In W FX Q LU� W M a w W w Z ., Z Z .- N04 r LD W 9 2t Z N fn M v 41 4C w W 0 � z z 0 ■ cn d p N Q I W w00 0 m - � LL C-4 to N \\ Q cc ��1111111���\ H`J� ��•• 2 / Ii C) v � U OD 1-1 O IN N 1-1 Z O V) _ N Z a H Q W W 0 W �-- 0 J Q LL- J CL� W ED C-10) W LL- W Z Q� z �-, 00 Q LD W 9 w W rn 0/0/ 0 - � A. ZD�� f N \\ ��1111111���\ H`J� ��•• N GENERAL STRUCTURAL NOTES: 1. THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE DRAWINGS OF ALL OTHER DISCIPLINES AND THE SPECIFICATIONS. THE CONTRACTOR SHALL VERIFY THE REQUIREMENTS OF OTHER TRADES AS TO SLEEVES, CHASES, HANGERS, INSERTS, ANCHORS, HOLES, AND OTHER ITEMS TO BE PLACED OR SET IN THE STRUCTURAL WORK, 2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH ALL SAFETY PRECAUTIONS AND REGULATIONS DURING WORK. THE ENGINEER WILL NOT ADVISE ON NOR ISSUE DIRECTION AS TO SAFETY PRECAUTIONS AND PROGRAMS. 3. THE STRUCTURAL DRAWINGS REPRESENT THE FINISHED STRUCTURE AND DO NOT INDICATE THE METHODS OR MEANS OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY GUYING AND BRACING REQUIRED TO ERECT AND HOLD THE STRUCTURE IN PROPER ALIGNMENT UNTIL ALL STRUCTURAL WORK AND CONNECTIONS HAVE BEEN COMPLETED, THE INVESTIGATION, DESIGN, SAFETY, ADEQUACY, AND INSPECTION OF ERECTION BRACING, SHORING, TEMPORARY SUPPORTS, ETC., IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR. 4. THE ENGINEER SHALL NOT BE RESPONSIBLE FOR THE METHODS, TECHNIQUES AND SEQUENCES OF PROCEDURES TO PERFORM THE WORK. THE SUPERVISION OF THE WORK IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR. 5. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION, WHERE CONDITIONS ARE NOT SPECIFICALLY SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED, SUBJECT TO APPROVAL BY THE ENGINEER. 6. LOADING APPLIES TO THE STRUCTURE DURING THE PROCESS OF CONSTRUCTION SHALL NOT EXCEED THE SAFE LOAD- CARRYING CAPACITY OF THE STRUCTURAL MEMBERS, THE LIVE LOADING USED IN THE DESIGN OF THIS STRUCTURE ARE INDICATED IN THE 'DESIGN CRITERIA NOTES'. DO NOT APPLY ANY CONSTRUCTION LOADS UNTIL THE STRUCTURAL FRAMING IS PROPERLY CONNECTED TOGETHER AND UNTIL ALL TEMPORARY BRACING IS IN PLACE, 7. ON COMMERCIAL JOBS, SUBMIT SHOP DRAWINGS IN THE FORM OF TWO BLUE -LINE PRINTS AND ONE SEPIA. IN NO CASE SHALL REPRODUCTION OF THE CONTRACT DRAWINGS BE USED AS SHOP DRAWINGS. AS A MINIMUM, SUBMIT THE FOLLOWING FOR REVIEWt A. CONCRETE MIX DESIGNS INCLUDING MASONRY GROUT. B. MASONRY CONSTRUCTION MATERIAL CERTIFICATES. C. MATERIAL TEST REPORTS FOR MASONRY UNIT STRENGTH f'm. D. REINFORCING STEEL SHOP DRAWINGS. E. STRUCTURAL STEEL SHOP DRAWINGS F. POST -TENSIONED SLAB -ON -GRADE SYSTEM SHOP DRAWINGS. (w) G. PRE -CAST HOLLOW CORE SLABS. (w) H. PRE-ENGINEERED WOOD TRUSS SYSTEM. (0 SEE NOTES) ITEMS MARKED (a) SHALL HAVE SHOP DRAWINGS AND CALCULATIONS SIGNED AND SEALED BY A FLORIDA REGISTERED ENGINEER. SITE PREPARATION NOTES: 1. THE BUILDING SHALL BE PREPARED AND TESTED IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE SOILS ENGINEER. 2. IF THE SITE PREPARATION REQUIREMENTS ARE NOT SPECIFIED BY A GEOTECHNICAL REPORT THE FOLLOWING PROCEDURES SHOULD BE USED AS A MINIMUMi A. WITHIN AN AREA A MINIMUM OF 5 FEET BEYOND THE BUILDING LIMITS, EXCAVATE A MINIMUM OF 4' OF EXISTING SOIL. REMOVE ALL ORGANICS, PAVEMENT, ROOTS, DEBRIS AND OTHERWISE UNSUITABLE MATERIAL. B. THE SURFACE OF THE EXPOSED SUBGRADE SHALL BE INSPECTED FOR POCKETS OF SOFT OR UNSUITABLE MATERIAL. EXCAVATE UNSUITABLE SOIL AS DIRECTED BY THE GEOTECHNICAL ENGINEER/TESTING AGENCY. C. FILL ALL EXCAVATED AREAS WITH APPROVED CONTROLLED FILL. PLACE IN 8 -INCH LIFTS AND COMPACT TO A MINIMUM OF 95% OF THE MAXIMUM DRY DENSITY BASED ON THE MODIFIED PROCTOR TEST. D. ALL CONTROLLED FILL MATERIAL SHALL BE A SELECT GRANULAR MATERIAL FREE FROM ALL ORGANICS OR OTHERWISE DELETERIOUS MATERIAL. E. PROVIDE FIELD DENSITY TESTS FOR EACH 1,500 S.F. OF BUILDING AREA FOR EACH LIFT OF CONTROLLED FILL. -1 - CENTERLINE OF PROPERTY LINE 6' MIN. SWALE DEPTH FIN. FLP. 6' PREFERRED FIN. FLR. ---I I 1 7I COMMON SWALE (NTS) SLAB ON GRADE NOTES,, 1, PROVIDE CONCRETE SLABS OVER A MINIMUM 6 MIL POLYETHYLENE VAPOR BARRIER, PROPERLY LAPPED AND TAPED, 2. IF SPECIFIED, SLABS SHOULD BE CURED WITH A SEALING AND CURING COMPOUND AS SOON AS POSSIBLE. REFER TO SPECS FOR CURING COMPOUNDS. 3. WALKWAYS AND OTHER EXTERIOR SLABS ARE NOT INDICATED ON THE STRUCTURAL DRAWINGS. SEE THE SITE PLAN AND ARCHITECTURAL DRAWINGS FOR LOCATIONS, DIMENSIONS, ELEVATIONS, JOINTING DETAILS AND FINISH DETAILS. PROVIDE 4' WALKS REINFORCED WITH 6X6 - WI .4XWI .4WWF UNLESS OTHERWISE NOTED. 4. SLABS TO BE PERMANENTLY EXPOSED TO WEATHER SHALL BE AIR ENTRAINED (2 TO 3%) WITH AN ADMIXTURE THAT CONFORMS TO ASTM C- 260, 5. ALL CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF ACI 301, 'SPECIFICATION FOR STRUCTURAL CONCRETE BUILDINGS'. GUIDE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION' ACII 302. HOT WEATHER CONCRETING SHALL BE IN ACCORDANCE W/ ACI 306. 6, SLABS SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE FOLLOWING FLATNESS/ LEVELNESS REQUIREMENTS SLAB CATEGORY SPECIFIED LOCAL MINIMUM FLAT Ff=35 Ff=23 F1=13 CAST -IN-PLACE CONCRETE N❑TES., U 1, CONCRETE MIXES SHALL BE DESIGNED PER ACI 301, USING PORTLAND CEMENT CONFORMING TO ASTM C-150, AGGREGATE CONFORMING TO ASTM C-33, AND ADMIXTURES CONFORMING TO ASTM C-494, C-1017, C-618, C-989 AND C-260. CONCRETE SHALL BE READY -MIXED IN ACCORDANCE WITH ASTM C-94. aVa= 0 c1' M 2. CONCRETE SHALL CONFORM TO THE FOLLOWING COMPRESSIVE STRENGTH, SLUMP AND WATER/CEMENT RATIO REQUIREMENTS• ae aNI` 00 TYPE MIN. f'c (28 DAYS)SLUMP W/C RATIO AGG, SIZE COLUMNS 3000 PSI 3' to 5' .46 #57 ELEVATED SLABS 3000 PSI 3' to 5' .46 #89 FOOTINGS 3000 PSI 3' to 5' .50 #57 SLABS -ON -GRADE 3000 PSI 3' to 5' .50 #57 TIE BEAMS 3000 PSI 4' to 6' .50 #89 BOND BEAMS 3000 PSI 8' to It' .50 #89 AT CONTRACTOR'S OPTION, AN APPROVED ADMIXTURE (SUPER PLASTICIZER) MAY BE USED TO PRODUCE FLOWABLE CONCRETE. MAXIMUM SLUMP SHALL NOT EXCEED 8 INCHES. ON COMMERCIAL JOBS, THE CONTRACTOR SHALL SUBMIT TEST RESULTS OF THE PROPOSED CONCRETE MIXES ALONG WITH THE MANUFACTURER'S TECHNICAL DATA FOR APPROVAL PRIOR TO POURING CONCRETE, 3. ALL CONCRETE WORK SHALL CONFORM TO THE REQUIREMENTS OF ACI 301, 'SPECIFICATION FOR STRUCTURAL CONCRETE BUILDINGS'. HOT WEATHER CONCRETE SHALL BE IN ACCORDANCE WITH ACI 305. 4. ALL REINFORCED STEEL SHALL CONFORM TO ASTM A-615, GRADE 40. ALL WELDING OF REINFORCING STEEL SHALL BE IN ACCORDANCE WITH AWS DI.4, 5. ALL WELDED WIRE FABRIC (WWF) SHALL CONFORM TO ASTM A-185 (FLAT SHEETS ONLY). 6. ALL REINFORCING STEEL SHALL BE SET AND TIED IN PLACE PRIOR TO POURING OF CONCRETE, EXCEPT THAT VERTICAL DOWELS FOR MASONRY WALL REINFORCING MAY BE 'FLOATED' IN PLACE, 7. REINFORCING STEEL, INCLUDING HOOKS AND BENDS, SHALL BE DETAILED IN ACCORDANCE WITH ACI 318. ALL REINFORCING STEEL INDICATED AS BEING CONTINUOUS (CONT) SHALL BE LAPPED 48 X BAR DIAMETER. LAP CONTINUOUS BOTTOM BARS OVER SUPPORTS, LAP CONTINUOUS TOP BARS AT MID -SPAN UNLESS OTHERWISE NOTED, 8. UNLESS OTHERWISE NOTED, THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR REINFORCEMENT, A. CONCRETE EXPOSED TO WEATHERi #6 THROUGH # 18 BARS - 2' #5 BAR, W31 OF D31 WIRE & SMALLER - 2' B. CONCRETE NOT EXPOSED TO EARTH OR WEATHER, BEAMS AND COLUMNS - 2' C. FOUNDATIONS EXPOSED TO EARTH - 3' 9. BAR SUPPORTS AND HOLDING BARS SHALL BE PROVIDED FOR ALL REINFORCING STEEL TO INSURE MINIMUM CONCRETE COVER. BAR SUPPORTS SHALL BE PLASTIC TIPPED OR STAINLESS STEEL. 10. ALL EDGES OF PERMANENTLY EXPOSED CONCRETE SURFACES SHALL BE CHAMFERED 3/4' UNLESS OTHERWISE NOTED. 11. FORMWORK SHALL REMAIN IN PLACE UNTIL CONCRETE HAS OBTAINED AT LEAST 90% OF ITS 28 DAY COMPRESSIVE STRENGTH. THE CONTRACTOR SHALL PROVIDE ALL SHORING AND RESHORING. DRILL 3/4' X 8' DP. HOLE IN SLAB, SPECIFY 04 OR #5 REBAR CARE TO BE TAKEN TO THOROUGHLY CLEAN OUT DEBRIS PRIOR TO ADDING EPDXY SET REBAR IN APPROVED EPDXY ALLOW TO CURE FOR THE SPECIFIED TIME PRIOR TO APPLYING ANY LOAD DO NOT DISTURB OR LOAD THE ANCHOR UNTIL IT IS FULLY CURED 4' . 6 d. OLD FTG NEW FTG . ' • d.. OLD FTG NEW FTG DETAIL.- REBAR RETROFIT MONOLITHIC POUR mll DETAIL= REBAR RETROFIT STEM WALL MASONRY NOTES: 1. MASONRY CONSTRUCTION SHALL CONFORM TO THE REQUIREMENTS OF THE 'SPECIFICATION FOR MASONRY STRUCTURES (ACI 530.1-99)', PUBLISHED BY THE AMERICAN CONCRETE INSTITUTE. SEE 'TESTING AND INSPECTION NOTES' FOR ADDITIONAL INFORMATION. 2. HOLLOW LOAD-BEARING MASONRY UNITS SHALL CONFORM TO THE ASTM C-90, AND BE MADE WITH NORMAL WEIGHT AGGREGATE. UNIT COMPRESSIVE STRENGTH OF 1900 PSI ON NET SECTION TO PROVIDE A MINIMUM NET AREA COMPRESSIVE STRENGTH OF MASONRY (f'm) OF 1,500 PSI, AS AS DETERMINED BY THE STRENGTH METHOD OF ACI 530.1 3. FILL 4tL BOND BEAMS AND REINFORCED CELLS SOLIDLY WITH GROUT. GROUT SHALL CONFORM TO ASTM C-476 AND SHALL OBTAIN A MIN. 28 DAY COMPRESSIVE STRENGTH OF 3000 PSI, 8-11' SLUMP, TESTED PER ASTM C-1019 EACH 5,000 S.F. GROUT STOPS ARE TO MESHED OR SCREEN TYPE, FELT PAPER IS NOT ALLOWED. 4. REINFORCING STEEL SHALL BE IN ACCORDANCE WITH ASTM A-615, GRADE 60. SHOP FABRICATE REINFORCING BARS WHICH ARE SHOWN TO BE HOOKED OR BENT. DOWELS SHALL HAVE STANDARD 90 DEGREE HOOKS AND LAPPED WITH FIRST LIFT OF REINFORCING. PROVIDE A MINIMUM LAP OF 48 WITH A MINIMUM LAP OF 26' FOR #5 REBAR AND GREATER, 5. MORTAR SHALL CONFORM TO ASTM C-270, TYPE M, S, OR N. ALL MORTAR SHALL MEET THE 'PROPORTION SPECIFICATION' OF ASTM C-270 AND EVALUATED IN ACCORDANCE WITH ASTM C-780. 6. UNLESS OTHERWISE INDICATED, ALL WALLS SHALL BE LAID IN RUNNING BOND. BOND CORNERS AND INTERSECTIONS OF ALL LOAD BEARING WALLS. INTERSECTING NON-LOADBEARING WALLS SHALL BE CONNECTED BY PREFABRICATED TEE AND CORNER HORIZONTAL JOINT REINFORCEMENT 2 16' D.C. 7. PROVIDE VERTICAL REINFORCING BARS OF THE GIVEN SIZE AND SPACING AS INDICATED. PROVIDE BARS AT ALL WALL CORNERS, INTERSECTION AND OPENING EDGES. PROVIDE CLEANOUTS FOR EACH GROUT POUR EXCEEDING 5FT, 8. PROVIDE PRE -CAST LINTELS ABOVE ALL WALL OPENINGS INCLUDING HVAC DUCTS. SEE DRAWINGS FOR LOCATIONS OF ALL OPENINGS. UNLESS OTHERWISE ON PLAN PROVIDE PRE -CAST LINTELS BELOW AS A MINIMUM. • OPENINGS LESS THAN 6FT = 8' PRE -CAST U -LINTEL W/1-#5 & 8' KNOCK -OUT COURSE W/1-#5 (TYPICAL PERIMETER BOND BEAM 16' TOTAL DEPTH) • OPENINGS GREATER THAN 6FT, = SEE DRAWINGS. PROVIDE ONE REINFORCED CELL EACH SIDE OF OPENING W/ 8' LINTEL BEARING. cI\users\,jim\documents\ebs\commercial\david casteel\david casteel int renovotion.dwg BLOCK CONSTRUCTION X 6' SUB FASCIA .UM. FASCIA :NTED ALUM SOFFIT rRUCTURAL SHEATHING 1BLE END TRUSS X 4' STIFFENER EA. VERT. TRUSS MEMBER E DETAIL TRAP SCHEDULE B 24' O.C. BOND BM, SIMPSON SP -1 OR EQUAL STUD TO PLATE CONNECTION XF(3() 2' X 6' SUB FASCIA f ALUM. FASCIA VENTED ALUM SOFFIT NAILS 2' X 4' BRACING 8'-0' O.C. STRUCTURAL SHEATHING SECURE TO TRUSS W/ 2' X 4' RAT R 8 8'0' O C 8d NAILS AT 4' O.C. ALL WOOD TO SOOD GABL c SECURE ETO FRAME WALL W/ Il oir.-12d NAILS 8' O.C. NAILS (3) 6d NAILS\"-'�' 5/8' DRYWALL E CLG.---" (OPT. 1/2' CLG. BD.) 2' X 6' STUDS Q 24' O.C., 8,-0& 5/Er A.B. Q 12' E.LATE W/ C. SIMPSON HETA 20 OR EQUAL EACH STUD (24' mm) 1/2' DRYWALL P.T. 1' X 2' FURRING STRIPS Q16'OC. -SIMPSON HETA 20 OR EQUAL a 24' O.C. ---CONC. BOND BM.W/ 5/8' x10' ANCHOR BOLTS e 12' O.C. INSTALL 3'(MIW WASHER UNDER NUT. MASONRY WALL WITH VERTICAL RODS FRON FTG. TO BOND BEAM 2 48' O.C. BLOCK CONSTRUCTION/SCISSOR TRUSS POUR REINFORCED CELLS SOLID W/ CONC. (3) 16d NAILS 2' X 4' BRACING 8'-0' O.C. 2'X4, RAT 88'-V0. 0 I ;t • 0 I (3) 16 d NAILS y 5/8' DRYWALL ! CLG (OPT. 1/2• CLG. BD.) SIMPSON SP -2 8'-0' STUD TO PLATE 2' X 6' SUB FASCIA ALUM. FASCIA -VENTED ALUM SOFFIT - STRUCTURAL SHEATHING SHTG. TO RUN CRIT. OVER FRAMING .DINTS - GABLE END TRUSS - 2' X 4' STIFFENER 1p1 yEE�A, ,{VEp�RT. �TREUSDSETMEMBER SECURE' TO %bSS WA�L12d NAILS a a, a.C. (3) 16d NAILS 24' GALV. STRAP FROM STUD TO VERT. TRUSS MEMBER 0 48' O.C. 'DBL.TOP PL. STUDS a 16' O.C. FRAME CONSTRUCTION SIMPSON SP -2 TOP PLATE TO STUD X 6' SUB FASCIA .UM. FASCIA ENTED ALUM SOFFIT PL. AILS 'RAMS WALL FROM FLOOR TO E OF ROOF SHEATHING rRUCTURAL SHEATHING 4TG. TO RUN CONT, OVER LAMING ,JOINTS t 16, O.C. FRAME CONSTRUCTION/SCISSOR TRUSS BALLOON FRAME GABLE END. VERTICAL TRUSS MEMBER4 70" RTICAL TRUSS MEMBER 2 24' O.C. 4' O.C. 2 X 4' STIFFENER a EA X 4' STIFFENER 11 EA VERT.' TRUSS MEMBER VERT. TRUSS MEMBER NAILED TO TRUSS MEMBER NAILED TO TRUSS MEMBER TRUSS STIFFENER DETAIL OPTIONAL DETAIL NOTEi NO DIAGONAL BRACING REQUIRED WHERE TRUSS VERTICAL IS LESS THAN 48' GABLE END FRAMING DETAILS N.T.S. WOOD FRAMING NOTES: 1. WOOD CONSTRUCTION, CONNECTIONS AND NAILING REQUIREMENTS SHALL CONFORM TO THE 'FLORIDA BUILDING CODE, 2017'. 2. ALL WOOD FRAMING MATERIAL SHALL BE SURFACED DRY AND USED AT 19% MAXIMUM MOISTURE CONTENT. 3. ALL LOAD BEARING WALL FRAMING SHALL BE NO, 2 GRADE SOUTHERN PINE OR SPF. 4. ALL JOIST AND RAFTER FRAMING SHALL BE NO. 2 GRADE, SOUTHERN PINE OR HEM -FIR. 5, ALL FRAMING EXPOSED TO THE WEATHER OR IN CONTACT WITH MASONRY OR CONCRETE SHALL BE PRESSURE -TREATED IN ACCORDANCE WITH THE AMERICAN WOOD PRESERVERS ASSOCIATION SPECIFICATIONS. 6. BOLTHEADS SHALL BE CAREFULLY CENTERED AND DRILLED NOT MORE THAN 1/16' LARGER THAN THE BOLT DIAMETER. BOLTED CONNECTIONS SHALL BE SNUGGED TIGHT BUT NOT TO THE EXTENT OF CRUSHING WOOD UNDER WASHERS, 7. PREFABRICATED 'MICRO -LAM' LUMBER HEADERS AND BEAMS SHALL AS MANUFACTURED BY 'TRUSS JOIST Macrdllan CORP.' BOISE, IDAHO OR APPROVED EQUAL, DO NOT CUT OR NOTCH MICRO -LAM MATERIAL WITHOUT THE MANUFACTURER'S APPROVAL, 8, PREFABRICATED METAL JOIST HANGERS, HURRICANE CLIPS, HOLD-DOWN ANCHORS AND OTHER ACCESSORIES SHALL BE AS MANUFACTURED BY 'SIMPSON STRONG TIE COMPANY', OR EQUAL. INSTALL ALL ACCESSORIES AS PER THE MANUFACTURE'S REQUIREMENTS. ALL STEEL SHALL HAVE A MINIMUM THICKNESS OF 0.04 INCHES (PER ASTM A446, GRADE A) AND BE GALVANIZED (COATING G90). PRE-ENGINEERED WOOD TRUSS NOTES: 1. ROOF WOOD TRUSS SYSTEMS SHALL BE DESIGNED BY THE MANUFACTURER TO SUPPORT THE FOLLOWING LOADS, A. ROOF TRUSS GRAVITY LOADING CASE TOP CHORD, LIVE LOAD - 0/12-4/12 = 20 PSF 4/12-12/12 = 16 PSF TOP CHORD, DEAD LOAD - 12 PSF (SHINGLES) 20 PSF (TILE) BOTTOM CHORD, DEAD LOAD = 4 PSF BOTTOM CHORD, DEAD LOAD/STORAGE = 30 PSF BOTTOM CHORD, LIVE LOAD = 10 PSF DEAD LOAD - 5 PSF FOR 1/2' CD GYPSUM B. ROOF TRUSS WIND LOADING CASE TRUSSES ARE TO BE DESIGNED FOR WIND LOADING AS SHOWN ON DESIGN ANALYSIS, USE FACTOR 1=1-0, UPLIFT SHALL DEDUCT 2/3 OF DEAD LOADS. 2. WOOD TRUSSES SHALL BE DESIGNED BY THE MANUFACTURER IN ACCORDANCE WITH THE APPLICABLE PROVISIONS OF THE LATEST EDITION OF THE 'NDS' NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION ANSI/AF&PA AND THE NATIONAL DESIGN STANDARD FOR METAL PLATE CONNECTED WOOD TRUSS CONSTRUCTION 'ANSI/TPI'. 3. WOOD MATERIALS SHALL BE SOUTHERN PINE, DOUGLAS FIR OR LARCH AND SHALL BE KILN DRIED AND USED AT 19% MAXIMUM MOISTURE CONTENT. PROVIDE GRADE NO. 2 OR BETTER REQUIRED TO SATISFY STRESS REQUIREMENTS. 4. CONNECTOR PLATES SHALL BE NOT LESS THAN 0.036 INCHES (20 GAUGE) IN COATED THICKNESS, SHALL MEET OR EXCEED ASTM A653 GRADE 33 OR HIGHER AND SHALL BE HOT DIPPED GALVANIZED ACCORDING TO ASTM A-525 (COATING G90). 5. THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY AND PERMANENT BRACING AS REQUIRED FOR SAFE ERECTION AND PERFORMANCE OF THE TRUSS. THE GUIDELINES SET FORTH BY THE TRUSS PLATE INSTITUTION PUBLICATION 'HIB -91, COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLING AND BRACING METAL PLATE CONNECTED WOOD TRUSSES' SHALL BE A MINIMUM REQUIREMENT. 6. TRUSS MEMBERS AND COMPONENTS SHALL NOT BE CUT, NOTCHED, DRILLED NOR OTHERWISE ALTERED IN ANY WAY WITHOUT THE WRITTEN APPROVAL OF THE TRUSS MANUFACTURER'S ENGINEER. 7. SUBMIT COMPLETE SHOP DRAWING FOR ALL WOOD TRUSSES SHOWING MEMBER SIZES, SPAN, DIMENSIONS, CHORD PITCH, LOADING AND REACTIONS. SHOP DRAWINGS SHALL BE SUBMITTED TO THE ENGINEER AND SHALL BEAR THE SEAL OF A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA 8. IF THE NET UPLIFT FORCES SHOWN ON THE FINAL ENGINEERED TRUSS CALCULATIONS ARE GREATER THAN THE CAPACITY OF THE SPECIFIED CONNECTORS, THE CONTRACTOR SHALL SUPPLY CONNECTORS TO MEET THOSE UPLIFT FORCES AS A MINIMUM. SIMPSON RSP4 OR EQUAL BOTH SIDE DBL. STUD (P.T. STU] AGAINST MASONRY EX WA SIMPSON RSP4 OR EQUAL BOTH SIDE S_ E 16'O.0 ALTERNATING SIDES MIXED CONSTR. DETAIL NOT TO SCALE IG SIDES IP PL. BEARING STUD WALL A.B. E 24' O.C. VERT. A-307 ANCHOR BOLT (5/8'DIA. X 10', W/3' X 1/8' WASHERS) 2 32' O.C. MAX (12' FROM CORNERS.) ALTERNATE METHOD- 5/8' X 6' POWER RAWL 'LOK-BOLT OR EQUAL SLEEVE ANCHORS e 32' O.C.> ELECTRICAL NOTES: 1. ALL EXTERIOR OUTLETS TO BE WP-GFI 2. ALL GARAGE, KITCHEN COUNTER, AND BATHROOM VANITY OUTLETS TO BE GFI. 3. ALL BEDROOM OUTLETS TO BE ARC -FAULT INTERRUPTER PROTECTED, 4. SERVICE OUTLET TO BE LOCATED WITHIN 10' OF A/C. 5. SMOKE DETECTORS TO BE HARD WIRED INSIDE ALL BEDROOMS AND ONE WITHIN 8' OUTSIDE OF BEDROOM. SMOKE DETECTORS WITH CO2 DETECTION AS REQUIRED 6. SMOKE DETECTOR TO BE AT ALL ENCLOSED STAIRWELLS. 7. ALL ELECTRICAL TO BE ABOVE FPE. (EXCEPTIONi ONE SWITCH AT 42' FOR EXIT LIGHT TO BE GFI PROTECTED.) 8, AFCI OUTLETS REQUIRED - ALL CIRCUITS E-1257 V) z IID O F N O Z �w U Z O Z > .8 a z = Q Z O U c? 0: 0: aN-jWoz O m O a ER O c>wmoa.5 W F- U a V V) yW Ljj G ¢ ¢p"IgJJ A Y aVa= 0 c1' M c Z(U �.H�WLL. ae aNI` 00 W N Q _ ¢ N N O Qz= WW,=a oo WLj ., 03 ZNO Z "ZW 1 N �0 z DO U) J ►~ Y CL � M C3 >-zL) ox ZL) 2C uu i0=CZ G0q ¢a p (n O aQ� c) w zcz1- �►V.,Sy1.4 Ld °: N Ni W L.1- OaaZ+¢In =q>Z N Q H ¢ to ¢ W M a w 00 m ~a U a OD yW Ljj G ¢ ¢p"IgJJ A Y aVa= 0 (U c Z(U �.H�WLL. ae aNI` WC% I Q 14 _ ¢ Qz= WW,=a WLj ., 03 rt; -1 _w�ZW> Z "ZW ¢www W WUZ ¢ �0 z J ►~ Y CL � M C3 >-zL) ox ZL) 2C uu i0=CZ G0q ¢a ¢~~o H 4 aQ� y`"~a`�^ ¢ as w zcz1- �►V.,Sy1.4 a uc4u h=-V„Z�W2.-*t JLd Ni W L.1- OaaZ+¢In =q>Z I- (4 m y ¢ In H ¢ to ¢ M a w 00 Lu 6�W� Z 0 04 LLL o N n TZ i V +t' N - ('3 W_ V) M °% 0 a- x LL. E V Oc z o z 00 WQ N a 0m W w 00 LL N ,1 PX oC p g ^ G li v U OD O Y (U Z \0 F I Q 14 N j to Of Z O � � J QLj W > t�� W H 4 aQ� w wz� JLd Q 6�W� (� LLL o LL_ w Z f- a H L L W 0 a- E (fin^ V J W 9 ,1 PX �Q7•• m• '�� ^ m= 2 X 4' SOLID BLK. 2 X 8' STRUTS W/ (4)#12 X 2 1/2' WOOD SCREWS J ` -P.T. 2 X 8' W/ 1/4' X 3' TAPCONS E 12' D.C. 2 X 8' STRUTS W/ (4)#12 X 2 1/2' WOOD SCREWS P.T. 1 X BUCK MASONRY OPENING 1/4' PLYWOOD 1/2' CDX PLYWD. SHTG. 2 EXT. DETAIb ALT, FRAMING FOR ARCH TOP IN MASONRY OPENING 2 X 4' SOLID BLK, 2 X 8' STRUTS W/ (4)#12 X 2 1/2' 1� WOOD SCREWS / -P,T. 2 X 8' W/ 1/4' X 3' TAPCONS B 12' O.C. 2 X 8' STRUTS W/ (4)#12 X 2 1/2' WOOD SCREWS P.T. 1 X BUCK MASONRY OPENING 1/4' PLYWOOD 1/2' CDX PLYWD. SHTG. 2 EXT. DETAILt ALT, FRAMING FOR CIRCLE TOP IN MASONRY OPENING 41 '�`—'� ROOF EDGE W ' A ROOF EDG 4' Iy ZONE 11 8d RING SHANK NAIL 2 4. O.C. AT SUPPORTED PANEL EDGES AND 4' D.C. 2 FIELD ZONE 21 8d RING SHANK NAIL 2 4' D.C. AT SUPPORTED PANEL EDGES AND 4' D.C. 2 FIELD (OPTIONAL - 1.31 GUN NAIL) ROOF SHEATHING NAIL ZONE c1\users\,pm\documents\ebs\commercial\davld casteet\david casteel Int renovation.dwg 2 X 4' SOLID BLK. 2 X 8' STRUTS W/ (4)#12 X 2 1/2' WOOD SCREWS J ` •P.T.2X8'W/1/4'X3' TAPCONS 2 12' O.C. 2 X 8' STRUTS W/ (4)#12 X 2 1/2' WOOD SCREWS P.T. 1 X BUCK MASONRY OPENING 1/4' PLYWOOD 1/2' CDX PLYWD. SHTG. a EXT. DETAIb FRAMING FOR ARCH TOP IN MASONRY OPENING 2 X 4' SOLID BLK, 2 X 8' STRUTS W/ (4)#12 X 2 1/2' 1� WOOD SCREWS / -P.T. 2 X 8' W/ 1/4' X 3' TAPCONS 2 12' D.C. 2 X 8' STRUTS W/ (0#12 X 2 1/2' WOOD SCREWS P.T. 1 X BUCK MASONRY OPENING 1/4' PLYWOOD 1/2' CDX PLYWD. SHTG. a EXT, DETAIU FRAMING FOR CIRCLE TOP IN MASONRY OPENING SINGLE NAIL EDGE SPACING WALL SHEATHM NAIL SPACING NAILING AT T13P PLATE - 8d ! 4' O.C. PLYWOOD/GYPBOARD SHEATHING NOTES: 1, ALL PLYWOOD CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE AMERICAN PLYWOOD ASSOCIATION (APA) SPECIFICATIONS. 2, ALL ROOF PANEL SHEATHING SHALL BE 15/32' (1/2' NOM.) EXPOSURE -1 APA RATED SHEATHING. SUITABLE EDGE SUPPORT SHALL BE PROVIDED BY USE OF PANEL CLIPS OR BLOCKING BETWEEN FRAMING. SEE NAILING SCHEDULE. NO BLOCKING OR EDGE BLOCKING SUPPORT REQUIRED AT RIDGE , ZONE 2 IF NOT SPECIFIED, CONNECT ROOF SHEATHING WITH 8d RING SHANK NAILS AT 4. O.C. AT SUPPORTED PANEL EDGES AND 4. O.C. INTERMEDIATE SUPPORTS. NOTE 4' O.C. NAILING PATTERN WITHIN 48' OF ALL ROOF EDGES, RIDGES AND HIPS. OVER 1/2' NOMINAL PLYWOOD, 3, INSTALL ALL PLYWOOD SHEATHING WITH THE LONG DIMENSION OF THE PANEL ACROSS SUPPORTS AND WITH THE PANEL CONTINUOUS OVER TWO OR MORE SPANS, STAGGER PANEL END JOINTS. ALLOW 1/8' SPACING AT PANEL ENDS AND EDGES UNLESS OTHERWISE RECOMMENDED BY THE SHEATHING MANUFACTURER. 4. ALL NAILING SHALL BE CAREFULLY DRIVEN AND NOT OVERDRIVEN. THE USE OF STAPLES ARE PROHIBITED. 5. ALL EXTERIOR ROOF L WALL SHEATHING TO BE NAILED AS PER SHEAR WALL NAILING DETAIL SAFE LOAD TABLE FOR CAST -CONCRETE HIGH-STRENGTH PRECAST & PRESTRESSED U LINTELS LENGTH SAFE LOAD - POUNDS PER LINEAR FOOT UNFILLED FILLED 6 FT < PANEL WW a d cma A LENGTH <4 FT, 4' - 0' (48') 1,875 tbs. 6,408 tbs. 4' - 6' (54') 1,860 tbs, 4,815 tbs. 5' - 4' (64') 1,743 lbs. 4,615 tbs. 5' - 10' (70') 1,575 tbs. 3,744 tbs. 6' - 6' (78'> 1,565 lbs, 3,260 tbs. 7' -6' (90') 1,550 lbs, 2,887 tbs. 9' - 4' (112'> 1,025 lbs. 1,747 lbs. 10' - 6' (126') 922 tbs. 1,333 tbs, 11' - 4' (136') 800 lbs. 1,483 lbs. 12' - 0' (144') 750 tbs, 1,304 tbs. 13' - 4' (160') 651 lbs. 1,018 tbs. 14' - 0' (168') 585 tbs. 909 tbs. 14' - 8' (176') 563 lbs. 1,341 tbs. 15' - 4' <184') 510 tbs. 1,210 lbs. 17' - 4' <208') 387 lbs. 911 lbs. 19' - 4' (232') 289 lbs. 823 tbs, NOTES: 1. (FILLED s) ACTING AS A COMPOSITE BEAM TOTAL 16' ONE #5 BAR IN THE LINTEL, ONE #5 BAR IN KNOCK -OUT COURSE, WINDBORNE DEBRIS PROTECTION FASTENING SCHEDULE FOR WOOD STRUCTURAL PANELS I 1) FASTENERS SHALL BE INSTALLED AT OPPOSING ENDS OF THE WOOD STRUCTURAL PANEL 2) WHERE ANCHORS ARE INSTALLED IN MASONRY OR MASONRY/STUCCO, THEY SHALL BE VIBRATION RESISTANT ANCHORS HAVING A MINIMUM WITHDRAWAL CAPACITY OF 1500 LBS 3) ANCHORS SHALL PENETRATE THROUGH EXTERIOR COVERINGS, INTO BUILDING FRAME A MIN. 2'. 4) FASTENERS SHALL HAVE 2' EDGE DISTANCE IN CONCRETE OR CMU. NAILING AT BOTTOM PLATE - 8d ! 4. O.C. 3000 PSI CONC. FTG, W/<2>#5 CONT, 0 (U 16' RECESS @ GARAGE DOOR SEE PLAN 8' 3000 PSI CONT._;�4v • CD ; SHOWER RECESS P,C, LINTEL STRUCTURAL STEEL -NOTES: 1. ALL STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED IN ACCORDANCE WITH THE 'MANUAL OF STEEL CONSTRUCTION' OF THE AISC. 2, UNLESS OTHERWISE NOTED, ALL MATERIALS SHALL BE IN ACCORDANCE WITH THE FOLLOWING ASTM SPECIFICATIONS, MEMBER ASTM MIN. STRENGTH STRUCTURAL TUBING A500 (GRADE B) 46KSI STEEL PIPE A53 (TYPR E, GR.B) 35KSI OTHER SHAPES/PLATES A36 36KSI CONNECTION BOLTS A325 92KSI ANCHOR BOLTS A307 THREADED RODS A36 36KSI NON -SHRINK GROUT C1107 8000 PSI 3. ALL CONNECTIONS SHALL BE SHEAR TYPE CONNECTIONS AND DESIGNED BY THE FABRICATOR BASED ON THE AISC MANUAL PART 2 WITH REACTIONS FROM THE 'ALLOWABLE UNIFORM LOAD' TABLES UNLESS REACTIONS ARE SHOWN ON PLAN. SUBMIT SHOP DRAWINGS AND CALCULATIONS SIGNED AND SEALED BY A PROFESSIONAL ENGINEER. MINIMUM BOLT DIAMETER SHALL BE 3/4' SHEAR/BEARING TYPE BOLTS AND TIGHTENED BY THE 'TURN -OF -NUT' METHOD. 4. ALL WELDING SHALL BE IN ACCORDANCE WITH AWS D1.1 USING E70XX ELECTRODES. UNLESS OTHERWISE NOTED, PROVIDE CONT, MIN. SIZED FILLET WELDS PER AISC +< REQUIREMENTS. ALL FILLER MATERIAL SHALL HAVE MINIMUM YIELD STRENGTH OF 58 KSI. ALL WELDING SHALL BE DONE BY A CURRENTLY CERTIFIED WELDER IN ACCORDANCE WITH 'AWS'. 5. HOLES IN STEEL FOR OTHER TRADES SHALL BE DRILLED OR PUNCHED AND DETAILED ON THE SHOP DRAWINGS. ALL SLOTTED HOLES SHALL BE PROVIDEE WITH SMOOTH EDGES. BURNING OF HOLES AND TORCH CUTTING AT THE SITE IS NOT PERMITTED. 6. U.O.N. ALL STRUCTURAL STEEL SHALL BE SHOP PAINTED WITH ONE COAT OF TYPE I, RED OXIDE PRIMER PAINT, SEE SPECIFICATIONS. IF APPLICABLE, VERIFY THAT PRIMER COATINGS ARE COMPATIBLE WITH SPRAYED ON FIRE PROOFING. 7. COLUMNS, ANCHOR BOLTS BASE PLATES ETC, HAVE BEEN DESIGNED FOR THE FINAL COMPLETED CONDITION AND HAVE NOT BEEN INVESTIGATED FOR POTENTIAL LOADING ENCOUNTERED DURING STEEL ERECTION AND CONSTRUCTION, ANY INVESTIGATION OF THE COLUMNS, ANCHOR BOLTS, BASE PLATES, ETC. FOR ADEQUACY DURING THE STEEL ERECTION AND CONSTRUCTION PROCESS IS THE SOLE RESPONSIBILITY OF THE 4' TAPCONS STAGGERED 6�� MAXI 6' 2x8 P,T, BUCK ATTACH 1/4' TAPCONS MIN. 1.5' EMBEDMENT AT 16' MIN. (3) PER OPENING SECURE DOOR FRAME TO MANUFACTURERS SPEC'S ALTERNATE BUCK AT HEADER DETAIL RUNLERUNLESS SS OTHERWISE NOTED, ALL STRUCTURAL STEEL PERMANENTLY EXPOSED TO THE WEATHER, INCLUDING ALL BRICK SHELF ANGLES SHALL BE HOT -DIPPED GALVANIZED IN ACCORDANCE WITH ASTM A153. 9. PROTECTION COATINGS DAMAGED DURING THE TRANSPORTING, ERECTING AND FIELD WELDING PROCESSES SHALL BE REPAIRED IN THE FIELD TO MATCH THE SHOP APPLIED COATING. EXTERIOR WINDOWS, DOORS, CURTAIN WALLS NOTES- 1. ALL WINDOWS, DOORS, CURTAIN- WALL, AND STOREFRONT SYSTEMS SHALL BE DESIGNED BY A 'SPECIALTY' STRUCTURAL ENGINEER IN ACCORDANCE WITH THE GOVERNING BUILDING CODE FOR COMPONENTS AND CLADDING WIND LOADING. 2. REFERENCE ARCHITECTURAL SPECIFICATIONS FOR ADDITIONAL INFORMATION, MIN. EMBEDMENT FASTEN W/ 1/4' TAPCONS MIN. EMBED INTO CON(. 1.25' 8 24. O.C. WINDOW �— 2 X 4' P,T. BUCK DOOR FASTEN W/ 1/4' TAPCONS MIN./ EMBED INTO CONC. 1.25' 2 X 4' BEVELED P,T. BUCK ! 24. O.C. INDICATES 8' CMU WALL W/ FILLED CELLS, W/ #5 REBAR INDICATES 8' CMU WALL W/ FILLED CELLS, W/ #5 REBAR INDICATES 8' CMU WALL W/ FILLED CELLS, W/ #5 REBAR FASTEN W/ 1/4' TAPCONS THRU WINDOW FRAME AND BUCK INTO MASONRY, MINIMUM EMBEDMENT, 1-1/4' SEE WINDOW MANUF. SPECS FOR REQUIRED NUMBER OF FASTENERS THAN 1-1/2' X 4' BEVELED P.T. BUCK WINDOW DOOR r SIDE JAMB ONLY, NONE REQUIRED ! HEAD GARAGE DOOR F - z w P.C. LINTEL A INDICATES 8' CMU WALL W/ FILLED CELLS, W/ #5 REBAR 1 CELL FOR UP TO 910' DOORS 2 CELLS FOR DOORS OVER 910' 2 X 6' P.T. #2 PT YP BUCK FASTEN W/ 1/2' A.B. ! 24. O.C. (OPT. 5/8' X 6' POWER RAWL 'LOK-BOLT' OR EQUAL SLEEVE ANCHORS ! 24. O.C.) z' 'H LO STAGGERED 2x8 P.T. BUCK ATTACH WITH <8 HEADER AS PER 1/4' TAPCONS MIN, 1.5' EMBEDMENT AT 16' O.C. STAGGERED MIN. (3) PER OPENING SECTION VIEW SECURE DOOR FRAME TO 2x8 HEADER AS PER MANUFACTURERS SPEC'S E-1257 FASTENER SPACING FOR WOOD FRAMED STRUCTURES (IN.) FASTENER TYPE PANEL 4 FT < PANEL 6 FT < PANEL WW a d cma A LENGTH <4 FT, LENGTH <6 FT. LENGTH <8 FT. #8 WOOD SCREW BASED ANCHOR 0 V) O 0 W/2' EMBEDMENT LENGTH 16 10 8 #10 WOOD SCREW BASED ANCHOR W F- o W/2' EMBEDMENT LENGTH 16 12 9 1/4' LAG SCREW BASED ANCHOR M 00 W N �U¢ W/2' EMBEDMENT LENGTH 16 16 16 I 1) FASTENERS SHALL BE INSTALLED AT OPPOSING ENDS OF THE WOOD STRUCTURAL PANEL 2) WHERE ANCHORS ARE INSTALLED IN MASONRY OR MASONRY/STUCCO, THEY SHALL BE VIBRATION RESISTANT ANCHORS HAVING A MINIMUM WITHDRAWAL CAPACITY OF 1500 LBS 3) ANCHORS SHALL PENETRATE THROUGH EXTERIOR COVERINGS, INTO BUILDING FRAME A MIN. 2'. 4) FASTENERS SHALL HAVE 2' EDGE DISTANCE IN CONCRETE OR CMU. NAILING AT BOTTOM PLATE - 8d ! 4. O.C. 3000 PSI CONC. FTG, W/<2>#5 CONT, 0 (U 16' RECESS @ GARAGE DOOR SEE PLAN 8' 3000 PSI CONT._;�4v • CD ; SHOWER RECESS P,C, LINTEL STRUCTURAL STEEL -NOTES: 1. ALL STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED IN ACCORDANCE WITH THE 'MANUAL OF STEEL CONSTRUCTION' OF THE AISC. 2, UNLESS OTHERWISE NOTED, ALL MATERIALS SHALL BE IN ACCORDANCE WITH THE FOLLOWING ASTM SPECIFICATIONS, MEMBER ASTM MIN. STRENGTH STRUCTURAL TUBING A500 (GRADE B) 46KSI STEEL PIPE A53 (TYPR E, GR.B) 35KSI OTHER SHAPES/PLATES A36 36KSI CONNECTION BOLTS A325 92KSI ANCHOR BOLTS A307 THREADED RODS A36 36KSI NON -SHRINK GROUT C1107 8000 PSI 3. ALL CONNECTIONS SHALL BE SHEAR TYPE CONNECTIONS AND DESIGNED BY THE FABRICATOR BASED ON THE AISC MANUAL PART 2 WITH REACTIONS FROM THE 'ALLOWABLE UNIFORM LOAD' TABLES UNLESS REACTIONS ARE SHOWN ON PLAN. SUBMIT SHOP DRAWINGS AND CALCULATIONS SIGNED AND SEALED BY A PROFESSIONAL ENGINEER. MINIMUM BOLT DIAMETER SHALL BE 3/4' SHEAR/BEARING TYPE BOLTS AND TIGHTENED BY THE 'TURN -OF -NUT' METHOD. 4. ALL WELDING SHALL BE IN ACCORDANCE WITH AWS D1.1 USING E70XX ELECTRODES. UNLESS OTHERWISE NOTED, PROVIDE CONT, MIN. SIZED FILLET WELDS PER AISC +< REQUIREMENTS. ALL FILLER MATERIAL SHALL HAVE MINIMUM YIELD STRENGTH OF 58 KSI. ALL WELDING SHALL BE DONE BY A CURRENTLY CERTIFIED WELDER IN ACCORDANCE WITH 'AWS'. 5. HOLES IN STEEL FOR OTHER TRADES SHALL BE DRILLED OR PUNCHED AND DETAILED ON THE SHOP DRAWINGS. ALL SLOTTED HOLES SHALL BE PROVIDEE WITH SMOOTH EDGES. BURNING OF HOLES AND TORCH CUTTING AT THE SITE IS NOT PERMITTED. 6. U.O.N. ALL STRUCTURAL STEEL SHALL BE SHOP PAINTED WITH ONE COAT OF TYPE I, RED OXIDE PRIMER PAINT, SEE SPECIFICATIONS. IF APPLICABLE, VERIFY THAT PRIMER COATINGS ARE COMPATIBLE WITH SPRAYED ON FIRE PROOFING. 7. COLUMNS, ANCHOR BOLTS BASE PLATES ETC, HAVE BEEN DESIGNED FOR THE FINAL COMPLETED CONDITION AND HAVE NOT BEEN INVESTIGATED FOR POTENTIAL LOADING ENCOUNTERED DURING STEEL ERECTION AND CONSTRUCTION, ANY INVESTIGATION OF THE COLUMNS, ANCHOR BOLTS, BASE PLATES, ETC. FOR ADEQUACY DURING THE STEEL ERECTION AND CONSTRUCTION PROCESS IS THE SOLE RESPONSIBILITY OF THE 4' TAPCONS STAGGERED 6�� MAXI 6' 2x8 P,T, BUCK ATTACH 1/4' TAPCONS MIN. 1.5' EMBEDMENT AT 16' MIN. (3) PER OPENING SECURE DOOR FRAME TO MANUFACTURERS SPEC'S ALTERNATE BUCK AT HEADER DETAIL RUNLERUNLESS SS OTHERWISE NOTED, ALL STRUCTURAL STEEL PERMANENTLY EXPOSED TO THE WEATHER, INCLUDING ALL BRICK SHELF ANGLES SHALL BE HOT -DIPPED GALVANIZED IN ACCORDANCE WITH ASTM A153. 9. PROTECTION COATINGS DAMAGED DURING THE TRANSPORTING, ERECTING AND FIELD WELDING PROCESSES SHALL BE REPAIRED IN THE FIELD TO MATCH THE SHOP APPLIED COATING. EXTERIOR WINDOWS, DOORS, CURTAIN WALLS NOTES- 1. ALL WINDOWS, DOORS, CURTAIN- WALL, AND STOREFRONT SYSTEMS SHALL BE DESIGNED BY A 'SPECIALTY' STRUCTURAL ENGINEER IN ACCORDANCE WITH THE GOVERNING BUILDING CODE FOR COMPONENTS AND CLADDING WIND LOADING. 2. REFERENCE ARCHITECTURAL SPECIFICATIONS FOR ADDITIONAL INFORMATION, MIN. EMBEDMENT FASTEN W/ 1/4' TAPCONS MIN. EMBED INTO CON(. 1.25' 8 24. O.C. WINDOW �— 2 X 4' P,T. BUCK DOOR FASTEN W/ 1/4' TAPCONS MIN./ EMBED INTO CONC. 1.25' 2 X 4' BEVELED P,T. BUCK ! 24. O.C. INDICATES 8' CMU WALL W/ FILLED CELLS, W/ #5 REBAR INDICATES 8' CMU WALL W/ FILLED CELLS, W/ #5 REBAR INDICATES 8' CMU WALL W/ FILLED CELLS, W/ #5 REBAR FASTEN W/ 1/4' TAPCONS THRU WINDOW FRAME AND BUCK INTO MASONRY, MINIMUM EMBEDMENT, 1-1/4' SEE WINDOW MANUF. SPECS FOR REQUIRED NUMBER OF FASTENERS THAN 1-1/2' X 4' BEVELED P.T. BUCK WINDOW DOOR r SIDE JAMB ONLY, NONE REQUIRED ! HEAD GARAGE DOOR F - z w P.C. LINTEL A INDICATES 8' CMU WALL W/ FILLED CELLS, W/ #5 REBAR 1 CELL FOR UP TO 910' DOORS 2 CELLS FOR DOORS OVER 910' 2 X 6' P.T. #2 PT YP BUCK FASTEN W/ 1/2' A.B. ! 24. O.C. (OPT. 5/8' X 6' POWER RAWL 'LOK-BOLT' OR EQUAL SLEEVE ANCHORS ! 24. O.C.) z' 'H LO STAGGERED 2x8 P.T. BUCK ATTACH WITH <8 HEADER AS PER 1/4' TAPCONS MIN, 1.5' EMBEDMENT AT 16' O.C. STAGGERED MIN. (3) PER OPENING SECTION VIEW SECURE DOOR FRAME TO 2x8 HEADER AS PER MANUFACTURERS SPEC'S E-1257 �c Cn 00 _j O F_ N Q O O WW a d cma A �0z OZ�w0 L) z P: 0 V) O 0 (L(nOOZ C4La}aW n aP°a6 Q Uj O m O & O 0wOoon.0 W F- o 363 It Wa SW >o M 00 W N �U¢ N N 0 Q Z Y Q Z0_ W OC CL N O 00 n (11 N W w F- � Q F.. p ((n ., U W N (V as 0 -C a] Q W OII.- CO �c a cU WW a d cma A OD dVaW � 00 d'J Y o ZN CU C4La}aW n aP°a6 Q �fn Z �-_ C F- q L) (4 I.-�a�> W W F ==z 3 363 ��-F-►yea Z..,J xQoc Wa SW >o N �U¢ 33aWWt`') O OMU%D Z< Z Y Q W OC CL d C3 Q Q Q n (11 m= 6 L) >OL� WVzggum 00"S.cZ ., SVl p i-OJggZZa w-C-C=~Af},� }.. as 0 -C a] �- OII.- Ix--UZW= WzIiI-C$ 1 Q 0 cmin I-w5o<in Ld Ld iawz Q rn pW.' w � 0 W W n Z Z I N r_ 0 T (n J W to M .1 �; M _j < X Q 3 C? z 0.6 o z 0U ' N a I LUW 0 m 00 0 in O g L- M w CLI v � cU OD Q Y CU Z I.-�a�> N n (11 z ., OU 0 F- �- 1 Q LLJ Ld Ld Q � Q � W W z (n J r::) �-- I - Q (/)p Q 0U W O 0 w O L- w CLI Z N V / y� Ilil( 1 97 :m_ �<<i Illli� N