HomeMy WebLinkAbout1100 Logan Heights Cir solar panels (a)SITE DET41 LS PROPERTY OWNER NAME: LOGAN HEIGHTS PROPERTY ADDRESS: 1000 LOGAN HEIGHTS CIRCLE, SANFORD, FL 32773 DESIGNERS INFORi`�4T10N COMPANY NAME: EMPIRICAL DESIGN, LLC REGISTERED ADDRESS: 149 OAK VIEW CIRCLE, LAKE MARY, FL 32746 PHONE: (407) 848-7877 GENER4L NOTES SCOPE OF WORK THIS SET OF PLANS DETAILS THE INSTALLATION OF A 162,180W GRID INTERACTIVE, SOLAR PHOTOVOLTAIC SYSTEM ON THE ROOF OF THE EXISTING PROPERTY DETAILED BELOW. CONTRACTOR 1NFORM.4TION CONTRACTOR COMPANY NAME: GOLD IN SOLAR, LLC CONTRACTOR REGISTERED ADDRESS: 3447 PERCIVAL AVENUE MIAMI, FLORIDA 33133 LICENCE NUMBER: CVC 5&(E65 NAME OF LICENSE HOLDER: DAREN GOLDIN PHONE: (305) 4(oS 9-190 UNLESS OTHERWISE NOTE (U.O.N.) ON PLANS OR IN THE SPECIFICATIONS, THE FOLLOWING GENERAL STRUCTURAL NOTES SHALL APPLY TO THIS PROJECT. I. ABBREVIATIONS NOTED ON THE DRAWINGS OR SPECIFICATIONS ARE THOSE COMMONLY USED. UPON REQUEST, THE ENGINEER WILL DEFINE ANY ABBREVIATION THAT IS QUESTIONED BY THE CONTRACTOR- 2. ONTRACTOR2. QUALIFICATION OF SUB -CONTRACTORS: ALL SUB -CONTRACTORS SHALL BE LICENSED BY THE STATE OF FLORIDA. 3. PROTECTION: PROTECT THE EXISTING BUILDING AND ADJACENT PROPERTIES FROM DAMAGE. 4. THE ARCHITECT/ENGINEER DOES NOT HAVE CONTROL OR CHARGE OF, AND SHALL NOT BE HELD RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES OR SAFETY PRECAUTIONS, AND PROGRAMS IN CONNECTION WITH THE WORK* NOR FOR THE ACTS OR OMISSIONS OF THE CONTRACTOR, SUB -CONTRACTOR OR ANY OTHER PERSONS PERFORMING THE WORK. THE ARCHITECT/ENGINEER DOES NOT GUARANTEE PERFECTION IN HER PLANS AND SPECIFICATIONS, NOR DOES GUARANTEE THAT A SATISFACTORY AND/OR FLAWLESS BUILDING WILL RESULT FROM HIS WORK. 5. EXISTING CONDITIONS: CONTRACTORS SHALL VISIT THE SITE PRIOR TO SUBMITTING A BID AND/OR BEGINNING ANY WORK, TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS OF THE SITE. SUB -CONTRACTORS SHALL BE HELD RESPONSIBLE FOR HAVING EXAMINED THE SITE, VERIFIED THE LOCATION OF ALL PROPOSED WORK AND FOR HAVING SATISFIED THEMSELVES FROM THEIR OWN PERSONAL KNOWLEDGE AND EXPERIENCE OR PROFESSIONAL ADVISE AS TO THE CHARACTER, LOCATION OF THE SITE, THE NATURE OF THE EXISTING CONDITIONS, LOCATION OF THE EXISTING UTILITIES AND ANY OTHER CONDITIONS SURROUNDING AND AFFECTING THE WORK, ANY OBSTRUCTION, THE NATURE OF THE EXISTING CONSTRUCTION, AND ALL OTHER PHYSICAL CHARACTERISTICS OF THE SITE SO THEY MAY INCLUDE IN THEIR INITIAL BID ALL COSTS FOR THE SATISFACTORY COMPLETION OF THE JOB. SUCH COST SHALL INCLUDE THE REMOVAL, RELOCATION OR REPLACEMENT OF ANY OBJECTS OR OBSTRUCTIONS THAT MAY BE ENCOUNTERED IN DOING THE PROPOSED WORK, ALL CONTRACTORS SHALL BE REQUIRED TO FIELD CHECK AND VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS. NOTIFY THE ARCHITECT/ENGINEER IF ANY DISCREPANCY EXISTS. COMMENCEMENT OF WORK SHALL CONSTITUTE FULL ACCEPTANCE OF SITE CONDITIONS. DISCREPANCIES, OMISSIONS OR VARIATIONS NOTED ON THE DRAWINGS DISCOVERED DURING THE BIDDING OR CONSTRUCTION PERIOD SHALL BE IMMEDIATELY COMMUNICATED IN WRITING TO THE ARCHITECT/ENGINEER, 6. DO NOT SCALE THE DRAWINGS. IF THERE ARE ANY DISCREPANCIES BETWEEN THE DRAWINGS AND FIELD CONDITIONS, STOP WORK AND NOTIFY IN WRITING THE ARCHITECT/ENGINEER IMMEDIATELY FOR CLARIFICATION. 7. FIRE PROTECTION NOTE: ALL PENETRATIONS OF FIRE RESISTANT ASSEMBLIES (I.E. RECESSED LIGHT FIXTURES, PIPE OR CONDUIT PENETRATIONS, HVAC PENETRATIONS, OR DEMOLITION, ETC.) SHALL BE PROTECTED AS TO NOT DECREASE THE FIRE RESISTANCE OF SUCH ASSEMBLIES. & ALL NEW MATERIALS AND FINISHES TO MATCH EXISTING, UNLESS OTHERWISE NOTED. 9. ALL NEW FINISHES, MATERIALS, PAINTS AND COLORS SHALL BE APPROVED BY THE OWNER PRIOR TO INSTALLATION. 10. ALL WORK SHALL BE PERFORMED IN A MANNER CONSISTENT WITH THE BEST PRACTICES FOR THE R175PECTIVE TRADES AND QUALITY SPECIFIED. II. CUTTING OR DRILLING OF ANY STRUCTURAL MEMBER IS NOT PERMITTED WITHOUT PRIOR APPROVAL OF THE ARCHITECT/ENGINEER. 12. NO WORKS WILL BE MADE IN THE CITY RIGHT OF WAY W/ INCLUDE APRON AND SWALE. 13. TAKE PRECAUTIONS AS NECESSARY TO CONTROL EXCESSIVE DUST AND NOISE, 14. DO NOT CONCEAL ANY WORK UNTIL ENGINEER AN BUILDING DEPARTMENT INSPECTOR APPROVE INSPECTION WORK 15. ANY AND ALL ITEMS REQUIRED TO FURNISH A COMPLETE CONSTRUCTION, BUT NOT SPECIFICALLY SHOWN OR SPECIFIED ON THESE DRAWINGS SHALL BE FURNISHED AND INSTALLED IN CONFORMANCE WITH 2017 FBC, 6TH EDITION AND LOCAL ORDINANCES AND, GOOD WORKMANLIKE MANNER. 16.THE CONTRACTOR SHALL COORDINATE ALL PARKING, STORAGE, TRASH REMOVAL, ETC. WITH THE OWNERS AND THE CITY OF ORLANDO. I-1. SECTIONS AND DETAILS SHOWN TYPICAL ON THE DRAWINGS MAY NOT BE SPECIFICALLY NOTED AT EACH LOCATION. HOWEVER, THESE DETAILS MAY BE APPLICABLE OR MAY BE REQUIRED IN MORE THAN ONE LOCATION. 18. SUPPORTING ROOF STRUCTURE SHALL BE VERIFIED FOR PROPOSED PANEL LAYOUT 19. EXISTING CONDITIONS DEPICTED REPRESENT CONDITIONS OBSERVED/ASSUMED ON FIELD VISITS BY THE ENGINEER IS NOT WARRANTED THAT CONDITIONS SHOWN ARE REPRESENTATIVE OF ACTUAL EXISTING CONDITIONS. CONSULTING ENGINEER ASSUMES NO RESPONSIBILITY FOR EXISTING CONDITIONS. THEY ARE SHOWN ONLY FOR REFERENCE. PV NODULES DESIGN CRI TER 14 4ND IN6T4LL4T I ON. I. DETAILS SHOWN ON THESE PLANS ARE PART OF THE SNAPNRACK PV MOUNTING SYSTEMS, SERIES 100 ROOF MOUNT, STRUCTURAL REPORT AND CALCULATIONS, ISSUE BY NORMAN J. SCHEEL,P.E. LICENCE No. 15002, STATE OF FLORIDA, DATED NOV. 11, 2015, AND ARE SHOWN AS REFERENCE ONLY. UPON REQUEST A FULL REPORT CAN BE PROVIDED. 2. SOLAR MODULES USED: a) MUST BE LISTED AND MUST BE IDENTIFIED AS CLASS C (IEC(o1730) BY AN APPROVED TESTING AGENCY. SEE ATTACHED MANUFACTURER SPECS. b) MUST WITHSTAND A MINIMUM WIND LOAD OF 33.0 PSF. SEE ATTACHED MANUFACTURER SPECS. c) MUST BE LISTED AND LABELED IN ACCORDANCE WITH UL 1103 (TYPE 1) AND WILL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. d) MUST COMPLY WITH SECTION 1509.1.0 OF THE 2017 FBC, 6TH EDITION. 3. MUST BE INSTALLED FOLLOWING THE MANUFACTURER'S RECOMMENDATIONS IN THE INSTALLATION AND OPERATION MANUAL. STRUCTURAL DESIGN CRI TER 14 I. ALL REFERENCED CODES AND SPECIFICATIONS SHALL BE LATEST EDITION AT TIME OF PERMIT 2. THE GOVERNING BUILDING CODE FOR THIS PROJECT IS THE 2017 FBC, 6TH EDITION TO THE BEST OF OUR KNOWLEDGE, THIS DESIGN COMPLIES WITH THE REQUIREMENTS OF THE GOVERNING BUILDING CODE. 3. WIND LOAD CRITERIA AS PER ASCE 7-10, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES: a) BASIC WIND VELOCITY:1 35 MILES PER HOUR b) EXPOSURE: C c) BUILDING CATEGORY: II 4. SUPERIMPOSED LOADS (PSF), EXISTING STRUCTURE, TO BE USED UNLESS OTHERWISE NOTE ON PLANS: a) DEAD LOAD ROOFING: 25 + 10 =35 b) LIVE LOAD ROOF: 30 zoo PERMIT # ��� PERMIT PERMIT # PERMIT #. l P- 4 L t o - PERMIT # �-- qZ (I PERMIT # " ci I, s PERMIT # V 7-11 � PERMIT PERMIT # 2, (L PERMIT # (� - ((/I PERMIT # _ 4­ZZ0­. , PERMIT # IJ- qLZ/ PERMIT# PERMIT # If - 4 LZ3 SANFORD BUILDING DIVISION A PERMIT ISSUED SHALL BE CONSTRUEi D TO BE A LICENSE TO PROCEED WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE TECHNICAL CODES. NOR SHALL iSSLIANCE OF A PERIv11T PPEVENT THE BUILDING OFFICIAL FROM THE.;=iEAFTEF RE01TRIN G A CORRECTION OF EPoROR3 IN i-)LANS, CONSTRUCTION OR VIOLATIONS OF THIS CODE SI Trz PL4N (E<VCH 1/64"= l '-0" VOTE: - SITE PLAN AERIAL BASED ON SATELLITE IMAGE FROM PROPERTY APPRAISER, TO BE FIELD VERIFIED. T�� '•\�F �t�'. , '`�,C '`moo. 1 sl U w D O BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: S-1 SHEET NUMBER: 3OF21 may. a m o � m appp,, o w V y w Of C U w D O BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: S-1 SHEET NUMBER: 3OF21 ROOF PLANE #1 49'-4" poor- fmLAN. ImHOT0v01.T,4IC 1" IODULAS L414rOUT SCALE: 3/16"=l' -O" NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #1 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) - 88% LOCATED IN ZONE 1 - 12% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 5'-0" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. ROOF PLANE #2 48'-8" R001: PL -4& PHOTOVOLT,41G 1 10DULSS L4Y0UT SCALE: 3/16"=l' -O' NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #2 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) - 98% LOCATED IN ZONE 1 - 2% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 5'-0" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. 2'-0" 2'-0" (TYP. ) Roo;: RL.AN. 4TTACH1" EMIT LAYOUT SCALE: 3/16"=l' -O" NOTE: - REFER TO SHEET 8-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN A55UMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK 2'-0" 2'-0" (TYP.) moor- PLAN. 4TTAGHMENT L41*700UT SCALE: 3/16"=1'-0" NOTE: - REFER TO SHEET 6-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK. CK )FF 3 (2) 2.5" w 0 BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: S-2 SHEET NUMBER: 4OF21 ROOF PLANE #3 10'-9" 22'-3" 13'-9" 8001= fi=1.4N. PHOTOVOLT,41C 1`10DULES LAYOUT SCALE: 3/16"=l' -O' NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #3 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) - 78% LOCATED IN ZONE 1 - 22% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 5'-5" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. 48'-11" ROOF FOLm 4N. PHOTOVOLTAIC "ODULES L44rOUT SCALE: 3/16"=1'-0" NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #4 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) - 95% LOCATED IN ZONE 1 - 5% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 5'-0" ROOF PLANE #4 NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. 2'-0" 2'-0" (TYP.) ROOF F=L,4N. ATTACHMENT L4YOUt SCALE: 3/16"=l' -O" NOTE: - REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK fi�'00� �'L4N. ,4TT4C�1" ��NT L,4YOUT SCALE: 3/16"=l' -O" NOTE: - REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK. U W C) BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: S-3 SHEET NUMBER: 5OF21 ROOF PLANE #5 52'-4" ROOF PLAN. PHOTOVOLTAIC MODULES LAYOUT SCALE: 3/16"=1'-0" NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #5 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE PANEL LOCATION TYPE #2 (WORST CONDITION) - 88% LOCATED IN ZONE 1 - 12% LOCATED IN ZONE 2 23'-6" CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 4'-10" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. ROOF PLANE #6.1 24'-4" 25'-6" ROOF PLAN. PHOTOVOLT41C MODULES LF4YOUT SCALE: 3/16"=l' -O" NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #6.1 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) - 92% LOCATED IN ZONE 1 - 8% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 5'-l" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. 2'-0" 2'-0" (TYP.) ROOF PLAN. 4TT,41SHMENT L04104OUT SCALE: 3/16"=l' -O" NOTE: - REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WOR< 2'-0" 2'_0" (TYP. ) ROOF PLAN. Alrmr 4CHMENT LA14rouT SCALE: 3/16"=l' -O" NOTE: - REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK. U W O BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: S-4 SHEET NUMBER: 6OF21 47-2" ROOF PLANE #6.2 19'-10" ROOF PLAN. PHOTOVOLTAIC MODULES ODULES L041rOUT SCALE: 3/16"=l'—O" NOTES: — ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. — EXISTING AREA OF WORK: -- ROOF PLANE #6.2 — TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. — CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. — EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 — 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) — 38% LOCATED IN ZONE 1 — 629 LOCATED IN ZONE 2 23'-6" CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 — ASSUMED DISTANCE, A = 5'—l" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. ROOF PLANE #6.3 24'-4" 25'-6" ROOF PLAN. PHOTOVOLTAIC MODULES L,4YOUT SCALE: 3/16"=l'—O' NOTES: — ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. — EXISTING AREA OF WORK: -- ROOF PLANE #6.3 — TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. — CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. — EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 — 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) — 62% LOCATED IN ZONE 1 — 38% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 — ASSUMED DISTANCE, A = 5'—l" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. 2'-0" 2'-0" (TYP. ) ROOF PLAN. ATTACHMENT Lp4YOUT SCALE= 3/16"=1'-0" NOTE: - REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK. 2'-0" 2'-0" (TYP. ) ROOF PLAN. ,41T,4cHtvlE mr LAYOUT SCALE: 3/16"=1'—O" NOTE: - REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EX15TING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BECsINNING OF WORK BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: S-5 SHEET NUMBER: 7 OF 21 ROOF PLANE #6.4 50'-8" ROOF FLAN. PHOTOVOLT,41C MODULES L414rOUT SCALE: 3/16"=l' -O' NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #6.4 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE PANEL LOCATION TYPE #2 (WORST CONDITION) - 88% LOCATED IN ZONE 1 - 12% LOCATED IN ZONE 2 23'-6" CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 4'-11" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. ROOF PLANE #7.1 24'-4" 25'-6" ROOF PLAN. PHOTOVOLT41C MODULES L,4YOUT SCALE: 3/16"=1'-0" NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #7.1 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) - 88% LOCATED IN ZONE 1 - 12% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 5'-l" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. " i � 2'-0" 2'-0" (TYP.) ROOF PL4N. 4TT,4CH1" «NT LA*rOUT SCALE: 3/16"=1'-0" NOTE: - REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WOR< ROOr- PLAN. ,4TT,4CH1„['ENT L414rOUT SCALE, 3/16"=1'-O" NOTE- - REFER TO SHEETS -3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK. H U W O Of cl- BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: S-6 SHEET NUMBER: 8OF21 47'-2" ROOF PLANE #7.2 ROOF PLAN. PHOTOVOLTAIC MODULES LAYOUT SCALE: 3/16"=1'-0" NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #7.2 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) - 38% LOCATED IN ZONE 1 - 62% LOCATED IN ZONE 2 23'-6" } CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 5'-1" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. DENO --T— Tvnir AI fklAn\InArV ROOF PLANE #7.3 J, * # r 24'-4" 25'-6" ROOF PLAN. PHOTOVOLT4IC MODULES LF4YOUT SCALE: 3/16"=l' -O' NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #7.3 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) - 88% LOCATED IN ZONE 1 - 12% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 5'-l" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. I � 1 2'-0" 2'-0" (TYP. ) ROOF PL4N. ATT,4CHMENT L,4YOUT SCALE: 3/16"=1'-0" NOTE: - REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN A55UMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK. 2'-0" 2'-0" (TYP. ) ROOT PLAN. ,4TT,4CHMENT L,,YOUT SCALE: 3/16"=1'-O" NOTE- - REFER TO SHEET 6-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK H U W O Of cl- BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: S-7 SHEET NUMBER: 9 OF 21 ROOF PLANE #7.4 50'-8" RoorPL.AN. PH OTO\/OLtA f C MODULAS L,4YOUT SCALE: 3/ 16 "=1 '-0" NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #7.4 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE PANEL LOCATION TYPE #2 (WORST CONDITION) - 95% LOCATED IN ZONE 1 - 5% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 4'-10" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. 50'-8" ROOF PL -AN. PHOTOVOLT41C MODULUS L41'OUT SCALE: 3/16"=l' -O' NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #8.1 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) - 88% LOCATED IN ZONE 1 - 12% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 5'-0" ROOF PLANE #8.1 NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. 1 2'-0" 2'-0" (TYP. ) Root- PLAN.4TT4cH1" r;Nlm L.41'OUt SCALE: 3/16"=1'-0" NOTE: - REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK 2'-0" 2'-0" (TYP. ) ROOF PLAN. 40rT,4CHMENT 1.44r oulr SCALE: 3/16"=l' -O" NOTE: - REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK H U W O BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: SHEET NUMBER: 10 OF 21 ROOF PLANE #8.2 66'-2" 24'-3- - 28'-3" i. .4 24'-3- 1 ROOF PLAN. PHOTOVOLTAIC I" IODULES LAYOUT OUT SCALE: 1/8"=J' -O" NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #8.2 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) - 88% LOCATED IN ZONE 1 - 12% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 4'-11" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. 50'-8" ROOF PL4N. PHOTOVOLT41C t' IODULES LP4YOUT SCALE: 3/16"=l' -O' NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #8.3 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) - 98% LOCATED IN ZONE 1 - 2% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 5'-0" ROOF PLANE #8.3 NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. Roo;: PL4N. ATT,4r.H INT L,4YOUT SCALE: 1/8"=l' -O" NOTE- - REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK 2'-0" 2'-0" (TYP.) ROOF PLAN. ,4TT,4r.H rmNT LAYOUT SCALE: 3/16"=1'-0" NOTE- - REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK. U W O cl- BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: S-9 SHEET NUMBER: 11 OF 21 ROOF PLANE #9.1 50'-8" Roo;: PL.4N. PHOTO\/OLT'41C 1" iODULAS LAYOUT SCALE: 1/8"=l' -O" NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #9.1 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE PANEL LOCATION TYPE #2 (WORST CONDITION) - 88% LOCATED IN ZONE 1 - 12% LOCATED IN ZONE 2 66._2. CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 5'-l" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. ROOF PLANE #9.2 ,1 24,_3. i 28'-3" 1 24,_8„ �` MOOR F=LAN. F'HOTOyOL.T,41C MODULES L.04YOUT SCALE: 1/8"=l' -O" NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #9.2 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) - 88% LOCATED IN ZONE 1 - 12% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 4'-9" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. I � 2'-0" 2'-0" (IYP.) WOOF F L.AN. ATTACHMENT L.'4YOUT SCALE: 1/8"=l' -O" NOTE: - REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR 5EGINNINC-4 OF WORK. RICOF PL.AN. ATTACHMENT LAYOUT SCALE: 1/8"=l' -O" NOTE- - REFER TO SHEET 6-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: S-10 SHEET NUMBER: 12 OF 21 ROOF PLANE #9.3 50'-8" ROOF PL4N. PHOTOVOLT,41C MODULES LAYOUT SCALE: 1/8"=l' -O" NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #9.3 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE PANEL LOCATION TYPE #2 (WORST CONDITION) - 98% LOCATED IN ZONE 1 - 2% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 5'-l" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. 49'-1" ROOF PLAN, PHOTOVOLT41C MODULES LF4YOUT SCALE: 1/8"=l' -O" NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #10 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) - 88% LOCATED IN ZONE 1 - 12% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 5'-l" ROOF PLANE #10 NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. 21-0" 2'-0" (TYP.) ROOr- PLAN. ATTACHMENT LAYOUT SCALE: 1/8"=l' -O" NOTE: - REFER TO SHEET 8-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK nCAln TCC TVnIf AI f\IA ll Lll']A�v 2'-0" 2'-0" (TYP. ) ROOD PLAN. ATTACHMENT LAYOUT SCALE: 1/8"=l' -O" NOTE: - REFER TO SHEET 8-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK U W O BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: S-11 SHEET NUMBER: 13 OF 21 ROOF PLANE #11 50'-9" ROOF FLAN. PHOTOVOLTAIC 1" ODULAs L4Y0UT SCALE: 1/8"=l' -O" NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #11 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) - 95% LOCATED IN ZONE 1 - 5% LOCATED IN ZONE 2 22'-0" CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 5'-2" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. ROOF PLANE #12 24'-8" 23'-2" ROOF PLAN. PHOTO�OLTA I C t*10DULrms LAYOUT SCALE: 1/8"=l' -O" NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #12 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) - 50% LOCATED IN ZONE 1 - 50% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 5'-0" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. 2'-0" 2'-0" (TYP. ) ROOD PLAN. ATT4cHMENT L,4YOUT SCALE: 1/8"=l' -O" NOTE: - REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK. nCkl CC TVMIr Al rkl—krlA— ROOD RL;4N. 4TTACI-O' MNT L,4Y0UT SCALE: 1/8"=l' -O" NOTE: - REFER TO SHEET 8-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK. BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: S-12 SHEET NUMBER: 14 OF 21 ROOF PLANE #13 22'-0" 1 24'-8" '� 23'-2" ROOF 10LAN. PHOTOVOLTAIC 1 IOMULSS LA*rOUT SCALE: 3/16"=l'—O" NOTES: — ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. — EXISTING AREA OF WORK: -- ROOF PLANE #13 — TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. — CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. — EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 — 100% LOCATED IN ZONE PANEL LOCATION TYPE #2 (WORST CONDITION) — 98% LOCATED IN ZONE 1 — 2% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 — ASSUMED DISTANCE, A = 5'—l" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. 49'-4" ROOF FLAN. PHOTOVOLT,4f C MODULES L414rOUT SCALE: 1/8"=l'—O' NOTES: — ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. — EXISTING AREA OF WORK: -- ROOF PLANE #14 — TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. — CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. — EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 — 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) — 98% LOCATED IN ZONE 1 — 2% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 — ASSUMED DISTANCE, A = 4'-11" ROOF PLANE #14 NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. d � 2'-0" 2'-0" (TYP. ) Roo;: PLAN. AmrorACH1" «NT L044rOUT SCALE: 1/8-=l'—O" NOTE: — REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. — LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK- 2'-0" ORK 2'-0" 2'_0" (TYP. ) ROOK PL4N. 4TT4CHt «NT L4YOUT SCALE: 1/8"=l'—O" NOTE: — REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. — LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: S-13 SHEET NUMBER: 15 OF 21 ROOF PLANE #15 22'-0" 24'-8" '� 23'-2" ROOF F=L -ANI. PHOT OVOLT,41 G twlODULES LAYOUT SCALE: 3/16"=l' -O' NOTES: - ROOF DIMENSIONS BASED ON FIELD VISIT AND SATELLITE IMAGE FROM SEMINOLE COUNTY PROPERTY APPRAISER. - EXISTING AREA OF WORK: -- ROOF PLANE #15 - TYPE OF EXISTING STRUCTURAL ROOF DECK: 2" X 4" WOOD TRUSSES AT 24" O.C. - CONDITION OF THE ROOF ASSEMBLY, EXISTING ROOF (NO CHANGE TO ROOF ASSEMBLY) FIRE RATING OF THE EXISTING ROOF ASSEMBLY SHALL BE MAINTAINED. - EXISTING ROOFING MATERIAL USED FOR THE ROOF ASSEMBLY: PANEL LOCATION TYPE #1 - 100% LOCATED IN ZONE 1 PANEL LOCATION TYPE #2 (WORST CONDITION) - 98% LOCATED IN ZONE 1 - 2% LOCATED IN ZONE 2 CODE ASCE: 7-10 = 135 MPH STRUCTURE CATEGORY: II EXPOSURE CATEGORY: C STRUCTURAL TYPE = BUILDING BUILDING TYPE = ENCLOSURE ROOF TYPE = GABLE ROOF SLOPE = 4:12 - ASSUMED DISTANCE, A = 5'-0" NOTE: REFER TO STRUCTURAL CALCULATIONS FOR WIND ZONE VALUES AND APPROPRIATE APPLICATION OF SAID VALUES. nCAlf)TCf TVr)If AI CAIAI]Aln Ary 2'-0" 2'_0" (nP•) iR00F PLAN. 4TTo4CHI «NT Lo4YOUT SCALE: 1/8"=l' -O" NOTE: - REFER TO SHEET 5-3 FOR TYPICAL INSTALLATION DETAILS. - LOCATION OF EXISTING STRUCTURAL MEMBERS HAVE BEEN ASSUMED AND MUST BE FIELD VERIFIED PRIOR BEGINNING OF WORK. U w 0 a_ BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: S-14 SHEET NUMBER: 16 OF 21 L Sne Nviack MAN"gtan. < SCALE-- ART tUM ER: GE8 FTIO : Q �0 ' �$l� `' TYPICAL LAYOUT HEbCiblaelAlsc®,.m . �;TE.- 12011 (1-30 ft. Roo,"'HI-eight Tablelk,Ra]]Span fln)for Roofa V l . g A110 115 a < 1. <. 16 -9 18 A 2 0,f.0, 2 T th _,lY 2?,9 28 A 30-7 3«.. .0 tl. 44, 6 .,... 0. -,2!J.` �F1.r ��i� �� ��K� � F °a ax:, dWY.:� f ,.ttY.> ■.® Eis,: , s-<,�:i,:... ... .. ✓..:c i ..Y:: r3 �;;, .m .5ti;' e''1* is ,N'. S. t .,. ,,....... t.. .. ... .... ......E ,.. ,� � � 3 A: > ,:3 :4 ,. ,. lx.. .... ,« � >._ ,,. - ..._.. --. '£.. ,.. �.. , _. .- - - •-E ,... >, ! 'v�,z-`. h s ..,.,1`., f s r < .. ,ro -> .. ,, ...:>:, 5< ... 4 ',. ,., .<, ,� f �r:._ � ^« zk'A e, Y..,s e..t• Wiz. ... 'a3,.a. -- c - �.. r... .S. ,3 a'�xi <: es:. ; :, ,,, .. .�iT^ . z4.,. d, i , sx*.• .N..: i' .. - .a l.: ro.':.. >,." ... .az.: -?� >y,,:ia - !: E N ,.Y > Pep,, 4 \ .€ E ? ; f y � s � it< r 20 15 r � � F r, z- a , .,.:: ,.>s,:red fl ',; a�... a. �,... rod' .. .« >.. .-¢.a „' >.,..k,d > ,,; .� .r .. ,,._�, t. �... a .,.•,. �. ,3"< : >r- a 3 a- E R. �'`3kRr , ts�; v, , , b i < Y, x s < i b6 66 �.$.i ��•y� r. �a �`r� i� <a`?:. a 50 '.319 - - x.1-4. 10 1 G0 0 � � =� � 0 2 s 4465 ` e - '55 . s. r $a , A ms ma ri s <s � w '55 m ,� gn.marEd ,' ? 51 70 54 51 51 151 1 80 62 4H 4 sil Ills 4,ills 48 48 4H 48 48 M I 43 .4 4 _� 43 41 43 4,43.4 43 4:x,343 11 4,0 40 XJ RLV F Mounting System Layout Overview Nerles 100 Wind :lige ASCE 740 o nipol e n and Cladding.Roof 7 'to 27 degree for 6063 AdJoy RaA Components and Cladding Low -Rise. i Buildings ASCE 7-10 3Q4-11, 1 ill ? (3c 6--1 yrs Fid.30.4-2B Slop._. zo[Ic I, . . ne 2 ...ne 3 t,2,3 3 2 vi Rool'slopeyfi,me 0' to 45 a d' 41 a Gust L < - s � al4) Bcmed on, an area ucif Ld U U U� cn 1 1 I LLJ =z� Q 0 o < ry �D o 0 � 0< BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: D-1 SHEET NUMBER: 17 OF 21 Ut)101ft and Structural Attachment Notes Notes For Installation: 1. Roof Structure consists of Wood Rafters - 2" x 6" at 24" O.0 2. Structural Attachments to be located no more than 48" O.C. along the Mounting Rail. 3. Structural Attachment to be made directly to rafter using two 5/16" lag bolt with minimum 2)/2 Of penetration per attachment point. 4. Module Overhang to be 12" - Manufacturer Suggests less than 19.5" CLAMPSNAPNRACK STANDOW BOLT MOD SPLIT WASHER s 1 N 1 • r # �! ••rUE ALL -07 H&qMME TO t SILVER 10-16 ,C r�AAtaim �. *r •'� ' r I RE/ USERMS 100 1 LEVMNG STANDOFF" FLASHING HiSTALLED ' �: i PER 1 1 ENSTRUCRyNS ON LOW -SLOPE Ri 1 1 1PlIll "TC -91, ar Il FT $ik 11 of r :,*• '•O �• N. DESMFnON: ON PEN DETAIL 06, HD STAMOFF `o��tttrrr����° % ,J� ON r 1 r � • 7f r • Q; ASV -%"7% 11t W J U U V) U) V W LLJ /Q `/ Q Q (J_ �� O I. V O O O O < U W O tY rZ BY: B D D DATE: 8/29/2018 REVISION: SHEET TITLE: D-2 SHEET NUMBER: 18 OF 21 Mountmin Mountmin Svstem Com onent Overview System Bill of Materials Module Clamp (End) • Snap -N -Rack Bonding Adjustable X -End Clamp, 1.49" - 2.00" Clear •• UL2703 Listed - Approved to Bond Modules to Rail System •• Manufacturer Part Number: 232-02066 Module Clamp (Mid) • Snap -N -Rack, Bonding Mid Clamp, 1.31" - 1.77", Clear •• UL2703 Listed - Approved to Bond Modules to Rail System •• Manufacturer Part Number: 232-02051 DC Optimizer Attachment Clamp • Snap -N -Rack, Optimizer Attachment Kit W/ Weeb •• Manufacturer Part Number: 242-92091 Module Mounting Rail • Snap -N -Rack Standard P100 Mounting Rail, Clear - 162" Each •• Manufacturer Part Number: 015-09852 Module Mounting Rail Splice • Snap -N -Rack Standard Rail Splice, Clear •• UL2703 Listed -Approved to Bond Adjacent Rails to Each Other •• Manufacturer Part Number: 242-04014 Rail to Roof -Structural Attachment • Snap -N -Rack, Bonding HD Standoff •• UL2703 Listed - Approved to Bond to Rail System •• Manufacturer Part Number: 242-02722 Rail Grounding Lug • Snap -N -Rack, Ground Lug Assembly, 6-12 AWG •• UL2703 Listed -Approved to Connect Rail to EGC •• Manufacturer Part Number: 242-02101 m" x 2.75' (TYP.) s S. SOLT SPL1T LOCA( WASHER X 2.750 (TYP.) S.S. BOLT WITH SPUT L.00 ( WASHai aiX'-*-C-;:- t Me---IRf • " LAG BOLT Wrr H WASHER SNAPNRACK STANDARD RAIL SPUCE INSERT SNAPNRACK STANDARD RAIL SPLICE BASE BOLTS SK1T LOCK WASHERS (3 PER i i �►,�94APNRACK STANDOFF CLAMP Q • WITH SPLrr LOCKWASHER COLLARSNAPNRACK RAIN STANDOFF1� - 0 SNAPNRACK 1. f wrrH,---A SYSTEM SHOWNN 'i f"MOUNTING SPLTT LOCK - COMPATIBLE WITH ALL ROOF USE FLASHED L FOOT FOR FASTER INSTALLATION ON4 COMPOSrnON SHINGLEROOFS ww ypg� ........ ,�►,.P.. ;�" wfi rDRAFTM � ogle 1211113 $1W D04 SE#�1E31�NT END CLAMP AMP � TOP F �u tr4"u r...—, M011 21 No ...Am .,rF,.i11 • "y i • 1' r $1Qtb c>1tt I BERES M OVERVIEWON FLASHEI)' L*MET e``eeeet�ttt��� 0 2 =_ F � *- '78W — 'I't S ©N 4.41 L J U OfU 0 w rN W = =Q� 0o Q O 0 CD Oil- �0< U W C) BY: B D D DATE: 8/29/2018 REVISION: SHEET TITLE: D-3 SHEET NUMBER: 19 OF 21 Rail and Module Attachment Specification Detail Series 100 IUD P"r+f-t for _ .ILM Rai I Properties for Duwnw arty Loads Section Properti es in :.34 n' I 0.46 ins Stresses A 15,2 k 1= v 152 ksli E 10000 k-si valwt 6.38 Rai I 'rop rtit-� for Up,--. d L (xids Sectilon Properties 41 iW in, i NIft OL11 in, k rn Roof Height t b LID M ft Stresses Fh 152 ksl ti, 15 .2- ksl L E 10000 k:- A 3.84 -n N 1S d Rafl �°rstl 4,.16 k 606.E .bra't � L x a-.1r'ffwdI- &Iinej r. ch for 17 rr�"the2 7 a .) Pi y rep rpt h Baa *q 6063 AtRoy Rea PV panelCa"latkim & Component and Cladffing Forces PV Panel Calcu Iaton s for 39,' x ,' Panel Connccd ans Fart Width P ,,ngtb Pawl Wright P it rvc I Area 65 " rty P a ry 3°x.0 65:0 7 G. Aa 17.6 Wiffid ED, .; r;; ASCE 7 -1000mponent arxi Cladding Arind Sid I, L0 t) P 0 ri EXPDSIrr Car. C Ips Roq atop ej fro. M 0 to 4 5 " 2) Wrrd Iria r g jt"ram I10 :,h to t ) rrap. 6 3-4 Gery,t. . x) Ewe Jit m cw a •- 0.1 4 LD11tLva w l;Abri=1eataI Lrrwy-isi on) hiding Zcvw E Zaw 2 7-0 i : 3 Zclmcs 1.. 2. -Lki.. 5 Max -22.96 -3 A , -30.7 L 68.51 Min -7tx21 428.5 -19 7.H-5 12.64 Ips Roq atop ej fro. M 0 to 4 5 " 2) Wrrd Iria r g jt"ram I10 :,h to t ) rrap. 6 3-4 Gery,t. . x) Ewe Jit m cw a •- 0.1 4 LD11tLva w l;Abri=1eataI Lrrwy-isi on) 0 Ar wk i 4 mm era fxP Vjxama to r cd I mw nmY h) iv d t: bra as �:a a t! tta r'rxa '''a a' as a'��rataaa� > raa�G� ) Zraw 2 men- air fir, mu ? le pass kicacq arra thi,r.zrmav Universal End Clamp a X-cl R _ " w U ry U U C -D w rN W = =z LZ Q 0 0 Quo C -D o LL - 0 0< U w O n BY: B D D DATE: 8/29/2018 REVISION: SHEET TITLE: D-4 SHEET NUMBER: 20 OF 21 tzadin z Cn c 1 bre 3 1, 2, & 3 Ckbrnp -:=35 t ~ 471 3,02 tri. Clam -?? L —1 L3 2 VA 603 0 Ar wk i 4 mm era fxP Vjxama to r cd I mw nmY h) iv d t: bra as �:a a t! tta r'rxa '''a a' as a'��rataaa� > raa�G� ) Zraw 2 men- air fir, mu ? le pass kicacq arra thi,r.zrmav Universal End Clamp a X-cl R _ " w U ry U U C -D w rN W = =z LZ Q 0 0 Quo C -D o LL - 0 0< U w O n BY: B D D DATE: 8/29/2018 REVISION: SHEET TITLE: D-4 SHEET NUMBER: 20 OF 21 C 0[)timizer Attachment Method Detail Grounclin Lua Attachment Method Detail w U U (J� C/-) = U � W = =z� Q c� o Quo CD o 1 ooz o< BY: B D D DATE: 8/29/2018 REVISION: SHEET TITLE: D-5 SHEET NUMBER: 21 OF 21 it -is 4 PHOTOVOLTAIC POWER SOURCE /A WING. DVAS wouvEgsovacy WARNING � I WARNING � �.�� 1}1IARNING � .: � . • - SECI'llt�NQ SOiJRCE IS PV SYSTEM • . CLEC T RIC ALL SHOCK HAZARD �< ELE TR CAL a HOOK HAZARD . Ic�1 r Ur, : _I n9.r L � ...._:: • PHOTOVOLTAIC POWER SOURCE IF AGROUND �=,�JUT 1,i,NDIfCAIE � _m"fNAi.S ON Ri TH N!7A ML �ti,,.� � t i',PMAI I �.R-O' LINDE � 1".+.3NDLICTORS ;�?.�: SIDFS t. ;Y rig FNEnCI E wm u. l_ L a ,t,. f E LIPv{.%ai''NDED.+"�ND ENFRC5IZED r5i IDF Ie YBE FNFOCAUTION- SOLAR CIRCUIT # CAUTION - - # i rENI CIRCLIJ 5R�EAKER k£ SACKFED • • ' ' • ' a f k # 2 Full 9 WARNING: WARNING FwAl Q NOT DISCONNECT � � • � � TURN OFF PHOTOVOLTAIC � �� I'wICAL SHOCK HAZARD UNDER LOAD • : � - TV AC DISCONNECT PRIOR TO JO NOT TOUCH TERIVI'NALS, • WORKING INSIDE PANEL. � WARNING � PHOTOVOLTAIC AC DISCONNECT ERPIINALSONSOTh INE AND r c t .� _ .AD Si DES MAY ENERGi2ED —.wPHOTOVOLTAIC AC DISCONNECT # # ELF,—_�RiCAt�E{ti T1a ci t- P _�:� I 1 -• - f • r '� �'a �- U FAULT ICS IN DICaTE D. r A NING. WARNING FAI TURN OFi` PHOTOVOLTAIC ' . • • * • * A DISCI tgNECT PRIOR TO THE cC����1� It • • • :. • . 1f4dC}RIGING INSIDE PANEL P�4010,V00,41C - C tV" BE ENEPvIZED WARNING J ,&j F PHOTOVOLTAIC WARNING FAJ CAUTI€31. DC DISCONNECT ,"opklmv, SOLAR, ELECTRICSYSTEM CONNECTED memo HE �}(`1liF�iL�'.;RI$il"�t'�1ti,1 �'`L Iz'U �`" LAI a ANL? klAY Si FNIFR ni _F i� s ° f ,0 r MAIN PV SYSTEM WARNING U1 WARNING �uAL���Easc�u�rl: PV SYSTEM DC DISCONNECT AC DISCONNECT ELECTRICAL SHOCK HAZARD SECONCt dURCE i5 PV SYSTEFh APERAT_t T TOUCH TERMINALS. V WARNING* " 0r ?`RAT}1ti.- i'^a T � .i" � s ., # r R SG�ES N'AY BE 7RiER�?:izEc� 4ALS ON e0fli LINE AND ELECTRICAL SHOCK HAZARD ® # CTAC,i THE OPEN POS171iON DO NOT TOUCH TERA#INALS "FRMINALSON BOTH LINE AND ` HOR, CzRCUJ C ..RRR N, � • �� LOAD SIDES MAY BE ENERC4L � " � • i - . - • • • - CAUTION. IN rxE OPEN V05ITiON # SOLAR ELECTRIC SYSTEM CONNECTED 6C VOLTAGE IS ALWAYS PRESENT # FAI WARNING: WHEN SOLAR MODULESPHOTS VOLTA C ARE EXPOED TO SUNLIGHT ��vEry 17-j: +7 1111M TUP%i OFF PHOTOVOLTAIC �'M L _ AC Gt SIC.- NNECT = AC DISCONNECT PRIOR TO �:- SOLAR UISCONNECT! # WORKING INSIDE PANEL FAI WARNING MAIN Pel SYSTEM »...._.� ! _�-. gym. _ •"•� � f�c •. f . #r ��, ECSHO �_ELL I _KICAL SHOCK HAZARD. __ rx>ueLTAtC AC DISCONNECT DISCONNECT VA tDONC i 0ICHTER&Ai._ TERMINAL ON 80T} LINE AND Site Condition Assumptions Conductor Schedule E -1a Conduit Schedule Circuit Reference ID Circuit Description Conductor Type Conductor Material Conductor Size Design g Current OCPD Type OCPD Rating Conduit Schedule No. of Current Carrying Conductors Conduit Type Conduit Size and QTY Interconnection Frequency 60 Hz Voltage - Line 1 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC Voltaeg - Line 2 to Neutral 120 V CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A CO -2 3 CarFlex %4' Voltage - Line 3 to Neutral (If Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 16 A D.P.C.B. 20A Voltage - Line 2 to Line 3 - V EQ -3 EQ -4 EQ -6 EQ -1, EQ -2 CO -1 C�-2 CI -3 CI -4 CI -2 Junction Integrated Box Disconnect DC AC Optimized String of 15 Modules ----- ------ ------ ------ Inverter EQ -5 The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an "Optimized String of Modules". EQ2 12 EQ2 C12 Component ID Description EQ -1 Solar PV Module P300 Power P300 Power Optimizer Optimizer V EQ -2 DC Optimizer EQ C11 EQ I_,I EQ -3 DC Junction Box EQ -4 Integrated Disconect Solar Solar EQ -5 Inverter Photovoltaic Photovoltaic Module Module EQ -6 New Circuit Breaker Enclosure EQ -7 Existing Electrical Service EQ -8 Existing Meter Enclosure EQ -9 Insulation Piercing Splice Connector EQ -8 EQ -7 C�-2 CI -4 New Rated Breaker Enclosure Equipment Schedule Model Manufacturer Number QCell QPRO-265 SolarEdge SE P300 N/A N/A SolarEdge N/A SolarEdge SE38000-US GE TQL100REP N/A N/A N/A N/A NSI IPSC4002 Existing Meter EQ -9 ExistingService Electrical Service Notes See Module Information See DC Optimizer Information NEMA 311 - Outdoor Rated Disconnect Integrated with Inverter See Inverter Information See Page EQ4 for Detailed Specs 150A Main Breaker- NEMA 3R Meter to be Replaced with Bi -Directional Net Meter After Installation See Page EQ5 for Detailed Specifications Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information Manufacturer Name: QCell Module Model Number: Q.PRO-G3 265 Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent -Voltage -0.28% per oC Temperature Coefficent - Current 0.03% per oC Temperature Coefficent - Power -0.38% per °C Specifications at STC MPP Power - Pmp 265 W MPP Current - Imp 8.69 A MPP Voltage - Vmp 30.79 V Short -Circuit Current - Isc 9.28 A Open-Circuit Voltage - Voc 38.52 V Temperature Adjusted Vmp - Min 30.35 V VOC - Max 39.60 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P300 Rated Input DC Power: 300 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A Maximum Output Current: 15 A NOTE. SolarEdge Power Optimizers ONLY to be used with SolarEdge Inverter, as specified in this drawing. The following string limitations apply, based on the Inverter Selected. Inverter Input Bus Voltage at Specified Interconnection Voltage: 350 V Maximum Power Per String: 5250 W Minimum Optimizers Per String: 8 Inverter Information Manufacturer Name: Solar Edge Module Model Number: SE 38000 -US Nominal Power Output 3800 W Maximum AC Power Output 4150 W Maximum Continous Output Current at Specified Interconnection Voltage: 16 A Iff a 0 W CL W cl- BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E -1a SHEET NUMBER: 2 OF 38 for the environment." IFC 605.11.1. E • . .* o "AE awva WARNING e NI FWIWARNING- I WARNING �'�! DO MOT DISC`:ONNEC�T T(I i"v O PHOTOVOLTAIC _�. ._ � ! ISA ... 1.JNDE E__OAC AC CIISGOI T snit TO • �... �i. � —K NG IN IDS PAN1 WARNING WNK 6903VI WN0. 5%-n% R)R MARMQ SACICt3P SYMMS Part No. 596.00240 rr rr• 5oov 111 (fteftective Material Re crtretf} z PER NEC 110.27(0)&05HA MO PartNo. 596-=35 PER NEC 890-35(F)1 Pat No. 595.0(}258 ��I I IIIII�I)I CAUTION: �II Main ServiceDisconnect *(Reflexive Material Required) PER NEC, 69D.14C IFC 6M 11,1, IK 605:11.1.4 NEC 690.15 & NEC 690.53 I Pat No 5%40245 � 5(01 Pat Na5%-00234MAIN P II r9� rY WARNING WARNING L T AC DISCONNECT PER NEC705.12(DX4)PRNE0690.64 Part No, 596-00231 PEIt h EC 1 t C j I1 C x{}5.11:1, IFC 605.11.1 A ICK 590, i 5 &NEC 690.53 Part No. 596.0(1143 15A' s � .�I w PEFiNE059411(4jlPeriNB AC Disconnect 1 Baker f Points of Connection"� 'R lg NEC 6%,531 Part No. 595-{1<i241 t 7.57 300V1 , iat PER IFC 605.11.1, IFC E NfC 690.14{1 �NIA b; NEC 690,531 PartNo. 596-x(1253 1201240V "NK 690-14(CXZ IFC M.11.1,1FE 605.11,1.4, I Irlllliltll� �i 60 Hz NEC 690.15&NECK 531 Pat No. 596.045 TURN OFF PHOTOVOLTAI(1- 3,OOOW 12.5A SOLAR# 17 PER !FC 60511,1.1 Part No, 5%-00246 20A PERNE0 110.27(C)&OSHA 191a145M(7) PER NEC 690..52 PartNo. 596.00252 AIN P � * Amt Flo, 5%V SYSTEM DISCONNECT -00235 IIID �I III I 20A 12o/24oV PER NEC M, I*C)(21 we 605. 11, 1, t IFC 605.11 .4� 1 690.53 PER NEC 69014(CX2)1 PartNo. 5 -=39 -00243 Bu'ild'ing #2_ TO BE INSTALLED ON CIRCUIT BREAKER ENCLOSURE: THIS EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES, EXCLUDING MAIN OVERCURRENT DEVICE, SHALL NOT EXCEED AMPACITY OF BUSBAR. BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-2 SHEET NUMBER: 3 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency Circuit Noof Current q Y 60 Hz . Conductor Conductor Conductor Design OCPD OCPD Conduit Conduit Conduit Size Reference Circuit Description Carrying Voltage - Line 1 to Neutral 120 V Ip Type Material Size Current Type Rating Schedule Conductors Type and QTY Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC 3/4' Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A Co -2 3 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D.P.C.B. 20A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Module Model Number: Q.PRO-G3 265 EQ -3 EQ -4 EQ -6 Existing EQ -7 Meter Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent -Voltage -0.28% per oC EQ- 1,EQ-2 CO -1 CO -2 CO -2 Temperature Coefficent - Current 0.03% per oC CI -3 CI -4 CI -4 EQ -9 Temperature Coefficent - Power -0.38% per oC CI -2 Junction Integrated Specifications at STC Box Disconnect MPP Power - Pmp 265 W New ExistingSolar Electrical MPP Current - Imp 8.69 A DC AC Service Service MPP Voltage - Vmp 30.79 V Optimized String of 10 Modules Short -Circuit Current - Isc 9.28 A --------.--- ------ ------ Open-Circuit Voltage - Voc 38.52 1 V I Temperature Adjusted Inverter Vmp- Min 30.35 V VOC - Max 39.60 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P300 EQ -5 Rated Input DC Power. 300 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 1 A "Optimized String of Modules". NOTE: SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ2 12 EQ2 C12 Component Model string limitations apply, based on the Inverter Selected. ID Description Manufacturer Number Notes Inverter Input Bus Voltage at EQ -1 Solar PV Module QCell QPRO-265 See Module Information 350 V P300 Power P300 Power Specified Interconnection Voltage: Optimizer VOptimizer EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ I C11 EQ I-1 EQ -3 DC Junction Box N/A N/A NEMA 3R - Outdoor Rated Minimum Optimizers Per String: 8 EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Inverter Information Solar Solar Photovoltaic Photovoltaic EQ -5 Inverter SolarEdge SE3000U-US See Inverter Information ••• Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 30000 -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker- NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 3000 W EQ -8 Meter After Installation Maximum AC Power Output 3300 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A Building #2- 8 D Z o 31 U W O BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E -2a SHEET NUMBER: 4 OF 38 00m, w o . C Adhesive Fastened igns �11 Adhesive fastened signs may be acceptable if properly adhered. Vinyl signs shall be weather resistant. lFC 605.11.1.3 SECOND SERVICE DISCONNECT ON NORTH SIDE OF BUILDING w e FAI WA NTNG �► WARNING j� PHOTOVOLTAIC POWER SOURCE � 1l�lARNIN�'.� n WARNING DOM POVVFR UR(F • � . • �� � � � f� SECOND si3(JfZCE IS PV SYSTEM _LLt,'Tk'IG LSFOCK14 ,AI_�L3 EI.rcrx4.Al , Hap;Pt •, . •. �• - a111IX S"QNV �RgOF II; Ef AG,'OUNOFAUEII,&INDI��TED,,N E � � tih;L . ��� ti+11MIA E_5 ON SOTS{ LINE AN11) o€40TOVQ 1AiC $,YSIE k4ARE LI i!GR0UIN0EI1 NORMALLY GROLINLIE D #,0PdDJC-10k'!3 I-0,0 E7 SIDE=S f41AY BE E"Nt RGI Ff3 k,ND NIV14 bt, UZERIAZEUA (34 T.INGROI i,dDEO AND ENERGIZE 0 ! - � C - 46 IN THE iJPN POSITIONCAUTION: $ALAR CIRCUIT 11 CAUTION 11 •• 1/ FV 5Y5TEM CIRCUIT BREAKER l5 6AC KIFED WARNING�r •' n 1 WA "�%iIN RAO DO NOT DISCONNECT . � • TURN OFF PHOTOVOLTAIC _.' C I RI AL SH C� I_IAZARD LINDER LOAD - . • :. - AC C}ISCONNECT PRIOR TO DO NOT TOUCH TERN'iiNALS. . � • PHOTOVOLTAIC AC DISCONNECT 7 RNUNAL S ON ISCITH LIRr AND � Y+IORFLING INSIDE PANEL WARNING %�►� � i�p D 1Y BE ENERGIZED t i Yat - =,Fi.� ., t., :,; ,..�..k r,IS >l-;i�2gy.st ' i.{J/'....,+v�'"E 4J§�k �'�f�3 liE� L. t'.iE=E'1�;.;3L'p.LiJ _...___ 1N TLIt- OPEN POSITION PHOTOVOLTAIC AC DISCONNECT f Ti UI N FAVO IS'Raul _ zkT D, .7wk Nt�4ai�ALLt Y.�'S"3'��IC�i=t �>',�.'C�•�.4i�i�;�;� ! i1 _ • . a •. R i �� 'IWARNING: : rAj WARNING FA • TURN OFF PHOTOVOLTAIC • i . • j • • • AC DISCONNECT PRIOR TOrLtE+CFE X k�I�� Dc uc�c�L�:T,T Or,a KS 3 . f • ' • • • . • . , WORKING INSIDE PANEL. Pr[LTtiVOi,TAICwx.,TE-tIAPE UNGROUNDED NC, ENER;3EbE 1lV�iRtrIING ,IcTovr�.T�.IC •, CAUTION.. � B D D r L E Z ,�C-C K BAR LAR Y N DC �iSC+�I'�1NiECT � �.�, _ �� � � S�9ELECTRIC S SiEMC�IN ECTEC (� IFIF 0 L-t2NDiUCT�RS OF -THIS _ �� tL77k`.VCX TAs=.SVS?T-�'>4TARE UNGY�O NONE O NO 011 D8/29/2018 rANR T.IAY ER�,r .D i R.,� .. 1 r , MAIN Phi SYSTEM kA WARNING ►50 awl off& V SYSTEM DC DISCONNECT WARNING EWAL ;'OWFR SOURCE REVISION: SECOND SURGE IS PV SYSTEEVI1�1� DISCONNECT LFGTRICAL SHOCK HAZARD G PAF41 7FERkTIN CLif2RENT. Nr.7� L)C I IE RtilINK AN PIEsA 'IN 4'CiLFAi3F • a a LO 4NIC7E MAY F3F EVER( 17 ELECTRICAL SHOCK HAZARD 1 t:1. ; MAXiMLIPA SY�STIFNI VOL_TAG-=- 11 . 4 IN THE )PEN PgS3T1 N DO NOrTOUC tl TERMINAE S. 1i Tr.RMJNAtS ON sorli LINE AND gHORT. (,FRGUIT (;URRc.-NT � p� ry LOALI,8IEWS MAY ENLRUVE� 4 Q 7 � 1 � : teA�TI4. N; " ! �a ! t r IN Tft OPEN POSI IION � r . . 1A � SOLAR ELECTRIC SYSTEM CONNECTED DC VOLTAGE IS ALWAYS PRESENT I,4k Y AR N I N G: WHEN SOLAR MODULES � PHOT V� � .T�6 �rc }���4����'�tt� UTIII„ � so= 1 ' ARE.F-xr"OSED TO SUNLIGHT fit {z G"e�tt� l'4ii1'��l? � �r 1 LL1 �I MUM q ?�15.rq L�L�.i �l i7ti'v l iw l'u� � 4 • i1 TURN OFF PHOTOVOLTAIC AC DISCONNECT kRIMI �IACP 8 . 111 AC DISCONNECT PRIOR TO SOLAR DISCONNECT t ' ` 1 �IANLYA CU? EN' � WORKING INSIDE PANEL � E GOPERA ICU'CI RENT u'r^r1 •. 1 h RREI�� 'I� 14EET TITLE: Building #3_ ' SHEET NUMBER: 5 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency Circuit Noof Current q Y 60 Hz . Conductor Conductor Conductor Design OCPD OCPD Conduit Conduit Conduit Size Reference Circuit Description Type Material Size Current Type Rating Schedule Carrying Type and QTY Voltage - Line 1 to Neutral 120 V ID Conductors Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 4 PVC %4" Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A CO -2 1 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 25 A D.P.C. B. 30A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Module Model Number: Q.PRO-G3 265 EQ -3 EQ -4 EQ -6 Existing Maxium Series Voltage Allowed: 1000 VDC CO -1 CO -2 EQ -7 Meter Temperature Coefficent - Voltage -0.28% per oC EQ- 1,EQ-2 CI -2 CI -3 CO -2 CI -4 EQ -9 Temperature Coefficent - Current 0.03% per oC CI -4 Temperature Coefficent - Power -0.38% per oC Junction Integrated Specifications at STC Box Disconnect MPP Power - Pmp 265 W Optimized String of 11 Modules New Existing ElectricalSolar MPP Current - Imp 8.69 A DC AC Service Service 1 MPP Voltage - Vmp 30.79 V Optimized String of 12 Modules Short -Circuit Current - Isc 9.28 A �_--- ---♦-- ------ ------ Open-Circuit Voltage - Voc 38.52 V I I Temperature Adjusted Inverter J, Vmp - Min 30.35 V VOC - Max 39.60 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P300 EQ -5 Rated Input DC Power: 300 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE. SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ2 12 EQ2 C12 Component Description Manufacturer Model Notes string limitations apply, based on the Inverter Selected. ID Number Inverter Input Bus Voltage at EQ -1 Solar PV Module QCell QPRO-265 See Module Information 350 V P300 Power P300 Power Specified Interconnection Voltage: Optimizer Optimizer EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ C11 EQ EQ -3 DC Junction Box N/A N/A NEMA 311 - Outdoor Rated Minimum Optimizers Per String: 8 EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Inverter Information Solar Solar Photovoltaic Photovoltaic EQ -5 Inverter SolarEdge SE600OU-US See Inverter Information ••• Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 6000U -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker- NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 6000 W EQ -8 Meter After Installation Maximum AC Power Output 6000 W EQ -9 Insulation Pie Ging Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current 25 A at Specified Interconnection Voltage: Building #3- ZQK 344 cc a � D m o W W g BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E -3a SHEET NUMBER: [. 1 ,�`"'�t d4�. with, 44V f' r bci requh-ee tr THIS PANEL FEI FROM INV1 t tdn k€ [ r rt tT � wit r tf iE 41 c=i i F € No, fir. _ -.. ;a *NEC 230.27(E), NEC 230 72(A) I Pat No. 55&OG309 MAX AVAILABLE FAULT CURRENT DATE 2115/12 'NEC 110r24(A) I Part No. 558-00309 z PHOTOVOLTAIC POWER SOURCE T,�i 1Nr4�'NING �� � � WARNING , r� � I LILL TRICAL SHOCK NAZAF CD U0 NC)T TOUCH r==Rt'ANALS This" D> "Otic . u TORS 0� T'r:15 PHOTOVOLTAIC PCVVER S '77P%AiNALS ON SOTN L NE ANCA 'HOT: 1vOl TAV,' ',,YS 10,4 A9E L1NGRa( -:NL-E PER NEC 0035(F)I Part No, 5146-00258 NEC 694 531 Pat N o 5%-00241 FQR MARKING BACKUP SYSTEMS Pat No, 5%-00240 PER NEC 6%4fl 1 Par€No 596.00257 a PHO"'TOVOLTAIC iiii.iiiiii.ABELING REQUIREMENTS NEC 2011 Article 690 and /FC 2012 Adhesive Fastened Signs Adhesive fastened may signs be table � Y acceptable if properly adhered. Vinyl signs shall be weather resistant. IFIC 605.1 1.1.3 The markings shall be of sufficient durability to withstand the environment involved. NEC 110.21 * The materials used for marking shall be reflective, weather resistant and suitable far the environ ment." lFC 60 5.1 1,1.1 CjBreaker Panel I Pull Boxes PER NEC 6%3.5(C) I Pat No 5%-00234 PER NEC 7E1512(E3O) & NEIL 690,64 Pat No, 596.00231 Part No 596-002316- DISOONNET _L=r�T�ICAL St-�C:1�I°i NA�AF�C} l3N DSR LCiAD ^�T TUGTERS.PER NEC 6.0 596-00244 #>Hr3Tta'VCt!_FxtIC AC t}iSCONNE�T T Rfv'1��A� � �� 3�TH � tiE Af�� PER ME( 69) 54 Part Na 5%-00239 PERNEC 6%11�4`�Jj P30o 59 -0023 120/240V PER NEC 690 5A Part No. 596-00239 Irs;' THE f�PEN Pc76sTI�N PHa�TiZ�fCJLTAtG AC �t�Gf3NNECT � V�ARNI[�+ reg wAR�IN� r�� TURN OFF PIIGTDVCiLTAfC, Production Net MetelAC3ISC3NNECT RRItOR TC}' Tz Na€�F Teir NSIf*(Reflective Nfatefiai 3E PANEL-�.€r1EUNc�Ur� fi^dC �1r�' �> EVE�izalw Required)---, 41 CAUTI4N� SOLAR ELI:C3RIC SYSTE4 CN4IECTEI Service ► . nnect *(RefiectiveMaterial Required) 605,11 NEC 6190 15 & NEC 690 531 Part No. 5%--00245 ARNtNt� S t Nig SOURCE IS PV SYSTEM � A DI ,f%(�K I &1 E(^'r � ELECTRICAL S�-(C)�K hiAZAR(? 00 NIOT TOUC,,1 TERNItNAL'S TERMINAL: )N e0TIJ LIN E,SNL) "• �� • LOAD SIEDES RViAYSE ENERGIZED IN TH7 OPEN POSIT ON i $► 11 • . • CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED WARNING - PHOTOVOLTAIC 1lilARNINt�.. TLIRIV OFF PHOTOVOLTAIC AC DI COhI ISI ECT Edi}; , t �' AC DISCONNECT PRIOR TO �°� I„ RRNT SOLAR DISCONNECT' WORKING INSIDE PANEL �e rrU WARNING IN ' • MAIN PV SYSTEM LLECIRICAL SHOCK I IAZARD PHOTOVOLTAIC AC: DISCONNECT - - DISCONNECT iVEYT TOUCH f EEai;tiNAL& €ERMIN14,8 ON B TF LIGE AND � ,.• DSIDES MAY BE ENERGIZE .+ ,•� IN HE OPEN POSITIaN Building #4. TO BE INSTALLED ON CIRCUIT BREAKER ENCLOSURE: THIS EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES, EXCLUDING MAIN OVERCURRENT DEVICE, SHALL NOT EXCEED AMPACITY OF BUSBAR. C, •" 02 ST �,fe'I1j111l►►►►��� .UjLyj 1)n- ? rJAY ;3r.- tret_�u TIC -go CAUTION: SOLAR CIRCUIT laic, _ Its I HE OFPE N P061 2 • 11►1 WARNING: :3 ,a TURN OFF PHOTOVOLTAIC a AC DISCONNECT PRIOR TC3 WORKING INSIDE PANEL � WARNING 1.5 m r� G* ,OUND i AUL` 1`3 INWC.ATEti. Nt7n ALLY GR_riJWk:D =_ v^EDUCT` P ,, I." + (jN6ROUNDE€7ANDENERGIZ;-1G Q w o. Qf 6 ' •s • 3 I► • :• WARNING FAI WARNING �_:,� ��-;3_,z , -,k�, PHOTOVOLTAIC F - s- � ��� t_ _ , � . A LYf3,R UU%)F S lNDLIT 0 NtT��A�L�<�Ft4�E1�€3LETrtt�NOLIt:TElP6 DC DISCONNECT ' MN, PELlNG1=OUNDEDANDENERG[17EV - ``iii sr. fur;p.n E.71=1✓ . �.;� ....+. .. .,. PER NEC 0035(F)I Part No, 5146-00258 NEC 694 531 Pat N o 5%-00241 FQR MARKING BACKUP SYSTEMS Pat No, 5%-00240 PER NEC 6%4fl 1 Par€No 596.00257 a PHO"'TOVOLTAIC iiii.iiiiii.ABELING REQUIREMENTS NEC 2011 Article 690 and /FC 2012 Adhesive Fastened Signs Adhesive fastened may signs be table � Y acceptable if properly adhered. Vinyl signs shall be weather resistant. IFIC 605.1 1.1.3 The markings shall be of sufficient durability to withstand the environment involved. NEC 110.21 * The materials used for marking shall be reflective, weather resistant and suitable far the environ ment." lFC 60 5.1 1,1.1 CjBreaker Panel I Pull Boxes PER NEC 6%3.5(C) I Pat No 5%-00234 PER NEC 7E1512(E3O) & NEIL 690,64 Pat No, 596.00231 Part No 596-002316- DISOONNET _L=r�T�ICAL St-�C:1�I°i NA�AF�C} l3N DSR LCiAD ^�T TUGTERS.PER NEC 6.0 596-00244 #>Hr3Tta'VCt!_FxtIC AC t}iSCONNE�T T Rfv'1��A� � �� 3�TH � tiE Af�� PER ME( 69) 54 Part Na 5%-00239 PERNEC 6%11�4`�Jj P30o 59 -0023 120/240V PER NEC 690 5A Part No. 596-00239 Irs;' THE f�PEN Pc76sTI�N PHa�TiZ�fCJLTAtG AC �t�Gf3NNECT � V�ARNI[�+ reg wAR�IN� r�� TURN OFF PIIGTDVCiLTAfC, Production Net MetelAC3ISC3NNECT RRItOR TC}' Tz Na€�F Teir NSIf*(Reflective Nfatefiai 3E PANEL-�.€r1EUNc�Ur� fi^dC �1r�' �> EVE�izalw Required)---, 41 CAUTI4N� SOLAR ELI:C3RIC SYSTE4 CN4IECTEI Service ► . nnect *(RefiectiveMaterial Required) 605,11 NEC 6190 15 & NEC 690 531 Part No. 5%--00245 ARNtNt� S t Nig SOURCE IS PV SYSTEM � A DI ,f%(�K I &1 E(^'r � ELECTRICAL S�-(C)�K hiAZAR(? 00 NIOT TOUC,,1 TERNItNAL'S TERMINAL: )N e0TIJ LIN E,SNL) "• �� • LOAD SIEDES RViAYSE ENERGIZED IN TH7 OPEN POSIT ON i $► 11 • . • CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED WARNING - PHOTOVOLTAIC 1lilARNINt�.. TLIRIV OFF PHOTOVOLTAIC AC DI COhI ISI ECT Edi}; , t �' AC DISCONNECT PRIOR TO �°� I„ RRNT SOLAR DISCONNECT' WORKING INSIDE PANEL �e rrU WARNING IN ' • MAIN PV SYSTEM LLECIRICAL SHOCK I IAZARD PHOTOVOLTAIC AC: DISCONNECT - - DISCONNECT iVEYT TOUCH f EEai;tiNAL& €ERMIN14,8 ON B TF LIGE AND � ,.• DSIDES MAY BE ENERGIZE .+ ,•� IN HE OPEN POSITIaN Building #4. TO BE INSTALLED ON CIRCUIT BREAKER ENCLOSURE: THIS EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES, EXCLUDING MAIN OVERCURRENT DEVICE, SHALL NOT EXCEED AMPACITY OF BUSBAR. C, •" 02 ST �,fe'I1j111l►►►►��� U w D O r BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-4 SHEET NUMBER: 7 OF 38 laic, :3 ,a a N Cz4 1.5 m QILI- Q w o. Qf U w D O r BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-4 SHEET NUMBER: 7 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency q Y 60 Hz Circuit Reference ID Circuit Description Conductor Type Conductor Material Conductor Size Design Current OCPD Type OCPD Rating Conduit Schedule . Noof Current Carrying Conductors Conduit Type Conduit Size and QTY Voltage -Line 1 to Neutral 120 V Voltaeg - Line 2 to Neutral 120 V CIA PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %4' CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A co -2 3 CarFlex 3/4" Voltage -Line 3 to Neutral (If Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D.P.C.B. 20A Voltage - Line 2 to Line 3 - V EQ -3 EQ -4 EQ -5 CO -1 CO -2 EQ -1 EQ -2 C1-3 C1-4 E-1,EQ-2 C1-2 Junction Integrated Box Disconnect DC ACService Optimized String of 9 Modules ----- ---♦-- ------ ------ Inverter EQ -5 The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an "Optimized String of Modules". EQ2 12 EQ2 Component C12 ID Description EQ -1 Solar PV Module P300 Power P30C Power Optimizer Optimizer V EQ -2 DC Optimizer EQ C1,1 EQ EQ -3 DC Junction Box EQ -4 Integrated Disconect Solar Solar Photovoltaic Photovoltaic EQ -5 Inverter • • • Module Module EQ -6 New Circuit Breaker Enclosure EQ -7 Existing Electrical Service Existing Meter Enclosure EQ -8 EQ -9 Insulation Piercing Splice Connector EQ -9 EQ -7 CO -2 C1-4 New Equipment Schedule Model Manufacturer Number QCell QPRO-265 SolarEdge SE P300 N/A N/A SolarEdge N/A SolarEdge SE3000U-US GE TQL100REP N/A N/A N/A N/A NSI IPSC4002 Existing Meter EQ -9 Existing trical Service Notes See Module Information See DC Optimizer Information NEMA 311 - Outdoor Rated Disconnect Integrated with Inverter See Inverter Information See Page EQ4 for Detailed Specs 150A Main Breaker - NEMA 3R Meter to be Replaced with Bi -Directional Net Meter After Installation See Page EQ5 for Detailed Specifications Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information Manufacturer Name: QCell Module Model Number: Q.PRO-G3 265 Maxium Series Voltage Allowed: 1000 VDC Coefficent - Voltage -0.28% per oC Temperature Coefficent - Current 0.03% per oC Temperature Coefficent - Power -0.38% per oC Specifications at STC MPP Power - Pmp 265 W MPP Current - Imp 8.69 A MPP Voltage - Vmp 30.79 V Short -Circuit Current - Isc 9.28 A Open-Circuit Voltage - Voc 38.52 V Temperature Adjusted Vmp - Min 30.35 V VOC - Max 39.60 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P300 Rated Input DC Power: 300 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A Maximum Output Current: 15 A NOTE: SolarEdge Power Optimizers ONLY to be used with SolarEdge Inverter, as specified in this drawing. The following string limitations apply, based on the Inverter Selected. Inverter Input Bus Voltage at Specified Interconnection Voltage: 350 V Maximum Power Per String: 5250 W Minimum Optimizers Per String: 8 Inverter Information Manufacturer Name: Solar Edge Module Model Number: SE 3000U -US Nominal Power Output 3000 W Maximum AC Power Output 3300 W Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A Bu'ild'ing #4. U w 0 BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E -4c SHEEP NUMBER: 8 OF 38 �g \ \ Y \� � � �. � � r� � tet• a" +•y��Iy Is \ \ ✓ter j I! at \" \\\\ s .ate X t V . z v8 t • . `• • •• •i .• lu s a • - � w � • w � a M a • a • a• � w � • � a I fa a a a a s a . • • � w� a • a a • a !� PHOTOVOLTAIC POWER SOURCE ° WARNING OIJAL N)WER SOURCE • : ` • • 0 ARNING F " WARNING � � WARNING LLLCTRICAL SHOCK H.A2AR®HOCK SECOND SOURCE IS PV SYSTEM . T T Ewe, T 9 a r _ CON t, FHOTOVOLTAIC POWER SOURCE �� a GRt7UND F JLT IS ; v�1�1�T��. i P" d1 S 0,14 SOTN "ter;"RIS; ,LLQ". G OLIN QED CL.==NDJC711DRS LOAD fii MAY .. FIEF � E P,w x = e" ;� wt� € , k IJf GRQ,'- NDF ; AIND CAUTION: SOLAR CIRCUIT _ �.�._ CAUTION • � i IN IHE,DFEN POSI TION � ! • � • � � • � ♦ , .+• •. •• 41 V 5YSTEM URCUJ SKkAKER 15 SACKFER il ! i 2 9 F1 WARNING: + • • • • WARNING DO NOT DISCONNECT • � • • � TURN OFF PHOTOVOLTAIC LCTRICAL SHOCK HAZARD UNDERLOAD AC DISCONNECT PRIOR TO DU NOT TOUCH TER "INALS. WORKING INSIDE PANEL � WARNING A&PHOTOVOLTAIC Ac DISCONNECTt� T-�INALS ON BOTH LINE AND LOAD Si DES L'AY BE DWRIGIZED li �t E OPEN POSITION PHOTOVOLTAIC AC DISCONNECT FAV, TIS INDICATED, _ ., s s �WARNING FAI TURN OFF PHOTOVOLTAIC j • • % . ♦ • AC DISCONNECT PRIOR TO E LX. C- N SHOCK CIO S00 Ii- i i 0 • G INSIDE PANEL PH0701,101-TAIC SYSTELIAREUNCACAWDED A" ,�,NV kli 9E ENERGIZED WARNING v WARNING F PHOTOV'OLTAI� . riYj 4�. j CAUTION: ;r i fl ars �Ty �. SOLAR ELECTRIC SYSTEM CONNECTED i 11 DG L7�IS�OIVIVEI�T � F r "�1 � �����.�� �= c.� t�t��. �c��10 IL GIn N • • PHOTCVCIIAsWill e x-A� � � UN i € LiTvUEU ♦ • If ♦ 1 _ • *� , WARNING DUAL POWZR OURCE MAIN PV SYSTEM Ul WARNING PV SYSTEM DC DESGC)NtVEGT SECOND SOURCE IS PV SYSTEM AC; DISCONNECT ELECTRICAL SHOCK HAZARD � 0PCRkT t>G "L V4 DaT DO NOT TOUCH 7 FR10i;yAL.S WARNING " !_ , OPERATING TACE � � r +. ! � • -��- - .! TtR�il :7,1 .S OA' SE E LIME —7E ELECTRICAL SHOCK HAZARD OBJ, ��^EGA AN' �� EUERt iZEb _._........ _ _ -- VIAXAALi;" SYSTi~! VCi,Taf', . !! .► +' .+t 1 '"Ei [?'i` Pi1 ,�tiaN no Nor TOUCH TERiAkNlkLS '7ERMNALS'ON MTM LINE AND SHORT CRC Uff CllF.R;-;N i WAD SIDUS8AAY.UC ENER ED � : CAUTION: IN14F-c,r~ro I cs,r-asp , ! SOLAR ELECTRIC SYSTEM CONNECTED WARNING ��� �'s D VOLTAGE t ALWAYS PRESENT "AYYAR� I NI � V WHEN SOLAR MODULES PHOTOVOLTA �y' 1iJjAj1) � ll!�IGL !'! � ! ARE EXPOSED TO SUNLIGHT > � -� `,* � 5�i. � �� V � �?F � C����S "� •! • T�RN OFF PHOTOVOLTAIC _ d _ AC DISCONNECT "1n' ?v ��5� :!! AC DISCONNECT PRIOR TO ` SOLAR DISCONNECT , a WORKING INSIDE PANEL. SHEET TITLE:Zs € � T, � �� •���� WARNING� MAIN PV SYSTEM ATEHHOi- CIRC01FCURRENi ELLCTRIC;ALSHOCK HAZARU PHOTOVOLTAIC AC DISCONNECT DI OhtNEC 1 TERMINALS M, 3OTV LINE AND -5 I -OA D SiDES NIAY 13E ENEr't ,ti ECI IN 1-E OPEN 1l()S(T ON , . • � Bu'ild'ing #5 SHEET NUMBER: 9 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency 60 Hz Circuit g No. of Current Conductor Conductor Conductor Design OCPD OCPD Conduit Conduit Conduit Size Reference Circuit Description Type Material Size Current Type Rating Schedule Carrying Type and QTY Voltage - Line 1 to Neutral 120 V ID Conductors Voltaeg - Line 2 to Neutral 120 V CIA PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC 3/4' Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A co -2 3 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 16 A D. P.C.B. 20A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Existing Module Model Number: Q.PRO-G3 265 EQ -3 EQ -4 EQ -6 Meter EQ -7 Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent -Voltage -0.28% per oC CO -1 CQ -2 CO -2 Temperature Coefficent - Current 0.03% per oC CI -3 CI -4 CI -4 EQ -9 Temperature Coefficent - Power -0.38% per °C EQ -1 EQ -2 CI -2 Junction Integrated Specifications at STC Box Disconnect New Existing MPP Power - Pmp 265 W Solar Electrical MPP Current - Imp 8.69 A DC AC Service Service MPP Voltage - Vmp 30.79 V Optimized String OF 38 Modules Short -Circuit Current - Isc 9.28 A Open -Circuit Voltage - Voc 38.52 V I Temperature Adjusted Inverter .� Vmp - Min 30.35 V VOC - Max 39.60 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P300 EQ -5 Rated Input DC Power: 300 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE. SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ2 12 EQ C12 Component Model string limitations apply, based on the Inverter Selected. ID Description Manufacturer Number Notes Inverter Input Bus Voltage at P300 Power EQ -1 Solar PV Module QCell QPRO-265 See Module Information 350 V P300 Power Specified Interconnection Voltage: Optimizer Optimizer EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ C11 EQ 1.1 EQ -3 DC Junction Box N/A N/A NEMA 3R - Outdoor Rated Minimum Optimizers Per String: 8 EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Inverter Information Solar Solar Photovoltaic Photovoltaic EQ -5 Inverter SolarEdge SE38000-US See Inverter Information ••• Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 38000 -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker - NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 3800 W EQ -8 Meter After Installation Maximum AC Power Output 4150 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current 16 A at Specified Interconnection Voltage: Bu'lld'lng BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E -5a SHEET NUMBER: 10 OF 38 3'* r A'S \ H? A A w 4 v � 4 R� 41 IIII 7 � � f O igu i ! '� ! •a i a .; � • i a i ai 0 a a ! ai i ! • � i• • , �# •• a a a a! s s ! ! • ! • a WARNING �� WARNING � ` PHOTOVOLTAIC �c�wE� sf� ��� WARNING �� GOND SWARNIOURCE AL V SYSWFIR TEM • : A w • 1 — ECCiVii 5C3URCE IS PV SYSTEM LLECTRICAL SHOCK HAZARD �� � t,l� sit ,. � .. • i L)C, f,407 To! Cr, i ERh I` ALS, ESOURCE IF AGROUND FAULT IS iNDi ATED, -I2t, l S 01 S"T" of - s`,'TI_i PHt TJ', L.$ _ S} ": 4=` ?I?S I CPQ[ 4_RNIALLY GROUNDED CL'IdLDJ 70RS # Lt: AU SSIi���; #.IAY HE I-,NERG E>D W L e �t?Id�U � .. '.I,;Y IBE UN(3R0,VNDEI�AN EN`F GIZ E� • � � : � CAUTION: SOLAR CIRCUIT CAUTION . PYSYS T6ht41 t"I$i7iTSKEFtISBACKFE • • ' ' • ` n ? sk WARNING: � • .. • • � WARNING /i1 DO NOT DISCONNECT • � • � TURN OFF PHOTOVOLTAIC ELE-CTRICAL SHOCK HAZARD UNDER LOAD � . � • : � . • AC DISCONNECT PRIOR TO � L)0 N10F TOUCH TF_RN'lINIALS � � # WORKING INSIDE PANEL WARNING .� PHOTOVOLTAIC �� DISCONNECT �RNII �ES Nv 0TH �E AMD p#it3TOVOLTAIC AC DISCONNECT IN T`H7 0=177, DOSITIt 'l . i• N A ROUND FADE. I' INDttaTED Mill NORMALLY" GROUNDEC C�Iv�Lt�Tt>�� � • •# r •• # � ' � MAY PF LN'GRGUNDEDAND ENERC,17 ED • .• • W"WARNING.FAI WARNING %,A' TURN OFF PHOTOVOLTAIC cLEeiRiC S-40_Iz I n4Rc 6 • 7 • • 1 AC DISCONNECT PRIOR TO THeccW)NDU IORISOPTHIS, 3 • : • . , • . , + ; • . - . UVC3f KfNG INSIDE PANEL R L, GV0LTAIesY8P_7UAREUN ROLNDED F NU Me'W BE UNERCIZED C 11 PHOTOVOLTAIC "A WARNING FAI. ?j WARNING � DATE: t £ � � � ,> �� � � CAUTION: , II=ACIROJt�ltidAU TISIl'dCICAT ID, t r c � �. > x HAz D DISCONNECT � � a�� � I�� � ����� v>�� c � ���ta� � � � SOLAR ELECTRIC SYSTEM CONNE TE�J ��} - - � rHE C N C ,;~RS SIF Alas A, I:I ur I t aL c �I�c I � l f� RE UNOgOONV �U ' 047i HA0Imac Phi SYSTEM D DISCONNECT � s�U�c� MAIN PV SYSTEM WARNING S CDND SOURCE IS Pv SYSTEM! AC DISCONNECT ELECTRICAL SHOCK HAZARD YARNING FAM ti � ,, ,, �,►� ZON6qOTHLtNE AND ELECTRICAL OiK A AR €I. CVOLIAG # � t CiA[7 5`. DEQ I�IAa E3T EIS.IERi i7Ein 1!7 OPEN �01,;17iON 04 NOT TOUCH Tr -R -MI iAI S i TERMINALS 014 BOTH L114 ANDeta .iFe£ a=RC'4.IITC.tRri=W, Q pry. ... _.,... LOAD SINES MAY 6E EHERGIZEG tJ ' 1 • i • • ! t • • CAUTION. • 1 IN THE OPEN POS.TItUN • #+� SOLAR ELECTRIC SYSTEM CONNECTED �^► DC VOLTAGE IS ALWAYS PRES17NT WHEN SOLAR MODULES PHOTOVOLTAIC �i�� 1l!/ARIUI N V . , � ARE EXPOSED TO SUNLIGHT R _ TURN OFF PHOTOVOLTAIC AC DI Oi'iiN E T ' - AC DISCONNECT PRIOR TOSHEET TITLE: I ; ��'�TSYDLTA�'G. _ � ,E � SOLAR DISCONNECT V114fZKING INSIDE PANEL �[ 3i RATED AC s� WARNING A . .n� � � t � �ri�� � � " } �• . , MALI PV SYSTEM K E ES;IK'I"ALSHOCK HAZARD <.H DI C{�h+1NEST 6 F#CTt>Vil iA9C ext DISCONNECT E- VAXtkl V S 10XTAGE J0 NOT T000fi TERMINALS_ TERMINALS OV BOTP LINEANC ! . a OAD SIDES MAY VE ENEf2�tZED r # I�TOtE ttVF_# .� .� Bumildiong #6 I SHEET NUMBER: 11 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency q Y 60 Hz Circuit Reference ID Circuit Description Conductor Type Conductor Material Conductor Size Design Current OCPD Type OCPD Rating Conduit Schedule . Noof Current Carrying Conductors Conduit Type Conduit Size and QTY Voltage - Line 1 to Neutral 120 V Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %11 Voltage - Line 3 to Neutral (If Applicable) V CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A CO -2 3 CarFlex 3/4" CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A CO -3 Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D. P.C.B. 20A CO -4 Voltage - Line 2 to Line 3 - V EQ -3 EQ -4 EQ -6 EQ -1, EQ -2 CO -1 CO -2 CI -3 CI4 CI -2 Junction Integrated Box Disconnect DC AC Optimized String of 9 Modules ----- ---+-- ------ ------ Inverter EQ -5 The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an "Optimized String of Modules". EQ2 12 EQ2 C12 Component ID Description EQ -1 Solar PV Module P300 Power P300 Power Optimizer VOptimizer EQ -2 DC Optimizer EQ IC11 EQ I.1 EQ -3 DC Junction Box EQ -4 Integrated Disconect Solar Solar Photovoltaic Photovoltaic EQ -5 Inverter ••• Module Module EQ -6 New Circuit Breaker Enclosure EQ -7 Existing Electrical Service Existing Meter Enclosure EQ -8 EQ -9 Insulation Piercing Splice Connector EQ -8 EQ -7 CO -2 CI4 :A New Service Equipment Schedule Model Manufacturer Number QCell QPRO-265 SolarEdge SE P300 N/A N/A SolarEdge N/A SolarEdge SE3000U-US GE TQL100REP N/A N/A N/A N/A NSI IPSC4002 Existing Meter EQ -9 Exis tingSolar Electrical Service Notes See Module Information See DC Optimizer Information NEMA 3R - Outdoor Rated Disconnect Integrated with Inverter See Inverter Information See Page EQ4 for Detailed Specs 150A Main Breaker- NEMA 3R Meter to be Replaced with Bi -Directional Net Meter After Installation See Page EQ5 for Detailed Specifications Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information Manufacturer Name: QCell Module Model Number: Q.PRO-G3 265 Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent - Voltage -0.28% per oC Temperature Coefficent - Current 0.03% per oC Temperature Coefficent - Power -0.38% per oC Specifications at STC MPP Power - Pmp 265 W MPP Current - Imp 8.69 A MPP Voltage - Vmp 30.79 V Short -Circuit Current - Isc 9.28 A Open-Circuit Voltage - Voc 38.52 V Temperature Adjusted Vmp - Min 30.35 V VOC - Max 39.60 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P300 Rated Input DC Power: 300 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A Maximum Output Current: 15 A NOTE. SolarEdge Power Optimizers ONLY to be used with SolarEdge Inverter, as specified in this drawing. The following string limitations apply, based on the Inverter Selected. Inverter Input Bus Voltage at Specified Interconnection Voltage: 350 V Maximum Power Per String: 5250 W Minimum Optimizers Per String: 8 Inverter Information Manufacturer Name: Solar Edge Module Model Number: SE 30000 -US Nominal Power Output 3000 W Maximum AC Power Output 3300 W Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A Building #6_ ON o. F OR _ d I U W O Cl - BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: I SHEET NUMBER: WK11M i. • • e •� • ell stir, • 0 ex 4 i w s. • wIII ! w ! w • • i • ! • 1 + w ♦ i i! i w • ! � • • � 1 • w s FA1 WARNING A" " WARNING FAj PHOTOVOLTAIC POWER SOURCE � WARNING WARNING OUAI-POWFRSIOURCS • � . • - SECOND SOURCE IS PV SYSTEM ELLCTRIC AL SHOCK I V\2ARDE, ECT RCSHO�'x KAZARLI - • oc� N 3 r �;a^x TER ,NAL � THEMCCONC .��,�s�F HIS PHOTOVOLTAIC PCW -111,, SCURCE IF AGROUND FAULT IS iN DICATED, f i C RCTN d', "! Nf?Tut�• tAi 4Y i "FR E QNGRL)UNDED . NORI 40" GROUNDED CON UC 0 ,!-01t€ zICI=� VlIkr 1iE ENE RG ,AND MAY aE LNIER�IZEl� t�9r^Y E -E LINGRO UNEIF0 AND I NERD Z a • CAUTION: SOLAR CIRCUIT CAUTION IN TEIE F F RC>ZI7lOGAR(;Ut T 6REAKER IS &AcxFF. • - • ' - • : r &I WARNING: l�! VVARNiNG /A C?Ci NC)T DISCONNECT . • TURN OFF PHOTOVOLTAIC � ELE IRICAL SHOCK HAZARD UNDER LOAD • :. - �' AC DISCONNECT PRIOR TO �Du NOT TOUCHTPR41jRALS,� � PHOTOVOLTAIC AC DISCONNECT C3RkING INSIDE PANEL WARNING TE>Qr 1I�hLSc�IuBCTIIL=I�EAIvD ifv iI?E OPEN POSITION LOAD-SiDE, %E ENERGIZED PHoTovntTAIC AC DISCONNECT _ ...•F:[t«il. +if'ki.�L.�1tid F@`L: _ 1 C�-,OLIND FAULT IS INDir-ATED, QRMALLYGROUNDF0 CONDUCTORS !A� W WAhNING. WARNING TURN LIEF PHOTOVOLTAIC ELilCTR S*-i'Kit,w::hRG • • • r r • ,AC DISCONNECT PRIOR TO TPE CI :�������s("T� rHIIS M 11 • • . . . : • r • WORKING INSIDE PANEL Tj OT ICSYS3TECI.AREUNGRsb NLXD � I ANO %cIk4YE ENERGIZED • PHOTOVOLTAIC WARNING �� "A WARNING "A E:C.TTaIO�AL HQC* H.V11RD • CAUTION: W A L ROUN D FAuLl IS 1NDlo ATEO� x . YST— EMCON+€IE�TfvNSOLAR ELEMI 9CC DISCONNECT ,� RI �L IvcT CONDUCToRs, • • D 'a;?E� ING3iOUNLcCAN E cR€ZEO v AD 8/29/2018 PV SYSTEM DC DISCONNECT WARNING DUAL POWER SOURCE MAIN PV SYSTEM WARNING fA DA `,lP Fi�ti.3c... �.`v,t6 �: %. •,�.. ., . I=I I=GcTRICA('LESc1H�cqCCx }H++(��ry �sEcono SOURCE IS PV SYSTEM AC DISCONNECT C NOT TOUCH ERMINALS. OWARNREVISION: WARNING ING ! nINALs(�)V50rFLINE AND i.VNt ELECTRIC AI< SHOCK HAZARD � tk,(MJ �fnsT f °y i roc=: . + , 1.- OPEN POSITION no Nor TaucO TERMNALS_ Jill TERMINALS ON Bt1FN LINE AND ,"a3"ORT z iRCUJ CURRENT, LOAD SIDES MAY BE ENERGIZE .0 t a x � off • • r CAUTION: IN, Tft 01EN POSITION +-� SOLAR ELECTRIC SYSTEM CONNECTED DC VOLTAGE IS ALWAYS PRESENT x ,�+ q� � WARNING: WHEN SOLAR MODULES PHOTOVOLTAIC m�#�� �ANORGE ARE EXPOSED TO SUNLIGHT �� ;�n� F� i�fER �v?�� r � iI(� i��` �� � � "" v _�� �' ' 1 • + -?���ER-PMGE x O _I«. see TURN OFF PHOTOVOLTAIC AC DISCONNECT �����i��.��,�f SOLAR DISCONNECT �KING INSIDE PANEL AC DISCONNECT PRIOR TO JAIRSTtCrAT �� '` wivll";�IGILTAIG� Aiiiiiiiiiiii WARNING MAIN PV SYSTEM RATED "" (T CURREN ELECI-RICALSHOCKHAZARL) PHCITOV LTAIC AC DISGONNECT , DISCONNECT MA IIIJ Sy`STEV VOL7154GE T < 1 I rERl��ln rEI � In I TF� LIJJI �.. r . _L POS T ION_ + E-7 ,+ Building #7 SHEET NUMBER: 13 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency Circuit Noof Current q Y 60 Hz . Conductor Conductor Conductor Design OCPD OCPD Conduit Conduit Conduit Size Reference Circuit Description Type Material Size Current Type Rating Schedule Carrying Type and QTY Voltage - Line 1 to Neutral 120 V ID Conductors Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %4' Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A Co -2 3 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 21 A D.P.C. B. 30A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Module Model Number: Q.PRO-G3 265 EQ -3 EQ -4 EQ -6 Existing EQ -7 Meter Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent - Voltage -0.28% per °C EQ- 1,EQ-2 CO -1 CO -2 CO -2 Temperature Coefficent - Current 0.03% per OC CI -3 CI -4 CI -4 EQ -9 Temperature Coefficent - Power -0.38% per °C CI -2 Junction Integrated Specifications at STC Box Disconnect New Existing MPP Power - Pmp 265 W Solar Electrical MPP Current - Imp 8.69 A DC AC Service Service MPP Voltage - Vmp 30.79 V Optimized String of 19 Modules Short -Circuit Current - Isc 9.28 A ----- ---♦-- ---_-- ------ Open -Circuit Voltage - Voc 38.52 V I Temperature Adlusted Inverter Vmp- Min 30.35 V VOC - Max 39.60 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P300 EQ -5 Rated Input DC Power: 300 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE. SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ2 12 EQ2 C12 Component Description Manufacturer Model Notes string limitations apply, based on the Inverter Selected. ID Number Inverter Input Bus Voltage at EQ -1 Solar PV Module QCell QPRO-265 See Module Information 350 V P300 Power P300 Power Specified Interconnection Voltage: Optimizer Optimizer EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ C111 EQ I.1 EQ -3 DC Junction Box N/A N/A NEMA 3R - Outdoor Rated Minimum Optimizers Per String: $ \�__c EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Inverter Information Solar Solar Photovoltaic Photovoltaic EQ -5 Inverter SolarEdge 50000 -US See Inverter Information ••• Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 5000U -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker- NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 5000 W EQ -8 Meter After Installation Maximum AC Power Output 5450 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current 21 A at Specified Interconnection Voltage: Bu'ild'ing BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E -7o SHEET NUMBER: 14 OF 38 ON NORTH SIDE OF E •NFC ;i! )tF1 NFC 710 7XA1 f PxtNPS 55R ffi� a 1 REQUIREMENTS NEC 2011 e 690 and IFC 2012 PER NEC 690 17(4) 1 Pat No, 5P%-002313 w Building I Structure CAUTION `~MiS..NtilY+44 6V Ft fliMp.'a x: r PERNECf .56(B)IPatNo:558-00350 PER NEC f Y;,." i F) I Part No 511-00258 AVft 3 DC Disconnect/ a . :. "A WARNING ,�� �NC►TC►�I.''OL.TAIC FLECTRIC SN(iQKH HAZARD CIC DISCONNECT,. THE DG CON-E)UGTORS OF 7(AF V'3K)R)',,'OLTlIC SYSTE'kMAP%C, UNC�R()UNIL)C) + + AND MAY RE FNEW117 D A PERNEC6903W)j PartNo, 59-6-00258 NEC 690 531 Part N o. 596-00241 NEC 690 53 ( Part No, 596-00253 PER NEC 690.31(EX3) & 1FC 60511.1 2, 605.11 1.A Parc No. 5%-00247 Inverter PER NEC 690.5(0I Part No. 5'x-00234 Aft • Production J Net Meter ry .^f?J+CIflV vi L474CfYRCR Ly tiRf.:4iPtL� 0.. Pat No- 596-0023 a AF N1Nta� [A� Do NOT DISCONINECT rLc i IGAL NaGK I{El1At'[� !UNDER LOAD gar au�f rf�1 L.PER NEC , PHt7Tt3Vt?ETAIC AG 011.11410 VT TpI"gF�RrrlyyryryAk_ ♦�♦kdLR3iy�Tf�-^i L�fE tp�f�L}ry YIN TfiE" OPEN Ft�liiCiPl PHOTOVOLTAIC ACDISCONNECT PER NEC 690, 1 A4)1 Part No. 596-00233 PER NEC 690,5411 Part No 596-OD239 PER NEC 690,541 Part No 0239 nn tt t 0 T�I�N oar ��{caT�vaLT�lc Production Net Meterac �iscolvNr �ro� Ta (Bi-directional) WORKING INSIDE PANEL Nl l{1Rlost R•wdPart No. Ii 10 258 CAt�TIDN- Main €i rpt f�f�3.� r,rNtf� rfz SLfLECTRIC SYSTE1GQf�IVECTED Service Disconnect R"?� f31�c`f? }lfdflELifv[ FPvf ft�lit)PER NEC 690 14CY2), IFC 605 11, 1, 1FC 60 PE a NEC •i0. XC)ParNo, �RNII�IV GU'AIPQYdEFtSC1Uft�f ��'•[�N �"� W I 'tri 1 Ir.+i:l PER NEC s�c�N� $��� f �� °rsTl:r� AC Ci1�CCENN ECT D.. NEC 690164 Part No 96-00 0 605,1114, NEC 15 &NEC 690,53: IFC • 596-00243 PER NEC 690, 17(4)1 Part No, 596-00233 AC Disconnect/ Breaker/ Points of Connection SOLAR ELECTRIC SYSTEM C{}NNECTED PHOTOVOLTAICilVll�1 ilt li�U �4v LC+Pu'� ' . s� AC C)ISCONNECT %4A0,11,J14AC Eh l�AXIINki CL EN SOLAR DISCONNECT ., 9 tOe'ER EErDFJCE-RATI�a11i FI.r� YI�1LE yiET' .+ Part MAIN ��► s�r�T�n� LLLCI KICALSHOCK li ARI) Iri, ��.r�. �.or n,� .�,.•.. � r rrr+n E ��r►�r PER NEC 69014(0: ) I Part No 5146-002339 Building #8- PER NEC 690.14(01 FC 6015.11.1, 'r( 60511.1 4 NEQ,690, 15 0690.53 Far t� -00243 TO BE INSTALLED ON CIRCUIT BREAKER ENCLOSURE: THIS EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES, EXCLUDING MAIN OVERCURRENT DEVICE, SHALL NOT EXCEED AMPACITY OF BUSBAR. BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: AnFknh Ha E-8 Appy PPIE RecpA i•nW M�-•evi bx HwY .� .JrCYAxaKka�sl Yt<w• �" twei "M�kW�N,fl4g h .'rV4e,.Re: MO WR..�sL ..w..� Y: +ii"r� :L usiigyvc: *3aA�rw•xxT•tlu MR *-NK We 11016 and NFf rtkie 130 5(CX11( ),(-i) Pat No 55, 00330 Adds, \\ gip,\ ON NORTH SIDE OF E •NFC ;i! )tF1 NFC 710 7XA1 f PxtNPS 55R ffi� a 1 REQUIREMENTS NEC 2011 e 690 and IFC 2012 PER NEC 690 17(4) 1 Pat No, 5P%-002313 w Building I Structure CAUTION `~MiS..NtilY+44 6V Ft fliMp.'a x: r PERNECf .56(B)IPatNo:558-00350 PER NEC f Y;,." i F) I Part No 511-00258 AVft 3 DC Disconnect/ a . :. "A WARNING ,�� �NC►TC►�I.''OL.TAIC FLECTRIC SN(iQKH HAZARD CIC DISCONNECT,. THE DG CON-E)UGTORS OF 7(AF V'3K)R)',,'OLTlIC SYSTE'kMAP%C, UNC�R()UNIL)C) + + AND MAY RE FNEW117 D A PERNEC6903W)j PartNo, 59-6-00258 NEC 690 531 Part N o. 596-00241 NEC 690 53 ( Part No, 596-00253 PER NEC 690.31(EX3) & 1FC 60511.1 2, 605.11 1.A Parc No. 5%-00247 Inverter PER NEC 690.5(0I Part No. 5'x-00234 Aft • Production J Net Meter ry .^f?J+CIflV vi L474CfYRCR Ly tiRf.:4iPtL� 0.. Pat No- 596-0023 a AF N1Nta� [A� Do NOT DISCONINECT rLc i IGAL NaGK I{El1At'[� !UNDER LOAD gar au�f rf�1 L.PER NEC , PHt7Tt3Vt?ETAIC AG 011.11410 VT TpI"gF�RrrlyyryryAk_ ♦�♦kdLR3iy�Tf�-^i L�fE tp�f�L}ry YIN TfiE" OPEN Ft�liiCiPl PHOTOVOLTAIC ACDISCONNECT PER NEC 690, 1 A4)1 Part No. 596-00233 PER NEC 690,5411 Part No 596-OD239 PER NEC 690,541 Part No 0239 nn tt t 0 T�I�N oar ��{caT�vaLT�lc Production Net Meterac �iscolvNr �ro� Ta (Bi-directional) WORKING INSIDE PANEL Nl l{1Rlost R•wdPart No. Ii 10 258 CAt�TIDN- Main €i rpt f�f�3.� r,rNtf� rfz SLfLECTRIC SYSTE1GQf�IVECTED Service Disconnect R"?� f31�c`f? }lfdflELifv[ FPvf ft�lit)PER NEC 690 14CY2), IFC 605 11, 1, 1FC 60 PE a NEC •i0. XC)ParNo, �RNII�IV GU'AIPQYdEFtSC1Uft�f ��'•[�N �"� W I 'tri 1 Ir.+i:l PER NEC s�c�N� $��� f �� °rsTl:r� AC Ci1�CCENN ECT D.. NEC 690164 Part No 96-00 0 605,1114, NEC 15 &NEC 690,53: IFC • 596-00243 PER NEC 690, 17(4)1 Part No, 596-00233 AC Disconnect/ Breaker/ Points of Connection SOLAR ELECTRIC SYSTEM C{}NNECTED PHOTOVOLTAICilVll�1 ilt li�U �4v LC+Pu'� ' . s� AC C)ISCONNECT %4A0,11,J14AC Eh l�AXIINki CL EN SOLAR DISCONNECT ., 9 tOe'ER EErDFJCE-RATI�a11i FI.r� YI�1LE yiET' .+ Part MAIN ��► s�r�T�n� LLLCI KICALSHOCK li ARI) Iri, ��.r�. �.or n,� .�,.•.. � r rrr+n E ��r►�r PER NEC 69014(0: ) I Part No 5146-002339 Building #8- PER NEC 690.14(01 FC 6015.11.1, 'r( 60511.1 4 NEQ,690, 15 0690.53 Far t� -00243 TO BE INSTALLED ON CIRCUIT BREAKER ENCLOSURE: THIS EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES, EXCLUDING MAIN OVERCURRENT DEVICE, SHALL NOT EXCEED AMPACITY OF BUSBAR. BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-8 SHEET NUMBER 15 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency Circuit Noof Current q Y 60 Hz . Conductor Conductor Conductor Design OCPD OCPD Conduit Conduit Conduit Size Reference Circuit Description Carrying Voltage -Line 1 to Neutral 120 V ID Type Material Size Current Type Rating Schedule Conductors Type and QTY Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %11 Voltage - Line 3 to Neutral (if CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A co -2 3 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 1.5 A D. P.C.B. 20A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - I V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Module Model Number: Q.PRO-G3 265 EQ -3 EQ -4 EQ -6 Existing EQ -7 Meter Maxium Series Voltage Allowed: 1000 VDC CO -1 CO -2 CO -2 Temperature Coefficent - Voltage -0.28% per oC Temperature Coefficent - Current 0.03% per oC EQ -1 EQ -2 CI -3 CI -4 CI -4 EQ_g Temperature Coefficent - Power -0.38% per oC CI -2 Junction Integrated Specifications at STC Box Disconnect MNew ExistingPP Power - Pmp 265 W Solar Electrical MPP Current - Imp 8.69 A DC ACService Service MPP Voltage - Vmp 30.79 V Optimized String of 9 Modules Short -Circuit Current - Isc 9.28 A —____ ___�__ ______ ______ Open -Circuit Voltage - Voc38.52 V Temperature Adjusted Inverter Vmp - Min 30.35 V VOC - Max 39.60 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P300 EQ -5 Rated Input DC Power: 300 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE: SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ2 12 EQ2 C12 Component Model string limitations apply, based on the Inverter Selected. 350 V P300 Power P300 Power ID Description Manufacturer Number Notes Inverter Input Bus Voltage at EQ -1 Solar PV Module QCell QPRO-265 See Module Information Specified Interconnection Voltage: Optimizer Optimizer EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ C11 EQ I-1 EQ -3 DC Junction Box N/A N/A NEMA 311 - Outdoor Rated Minimum Optimizers Per String: 8 EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Inverter Information Solar Solar Photovoltaic Photovoltaic EQ -5 Inverter SolarEdge SE3000U-US See Inverter Information ••• Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 3000U -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker - NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 3000 W EQ -8 Meter After Installation Maximum AC Power Output 3300 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A Building #8- U W 0 a_ BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: SHEET NUMBER: 16 OF 38 F'asha`K1infrr7atonnAIab�Inqfor the environment." IFC 605.1 �. :• • 4 1 ivi I• • t• C• PHOTOVOLTAIC POWERPSOURCE .31 auAt POWF;Z1 uRc • : t • /A WARNING ►� WARNING PHOTOVOLTAIC 1NARNING SECONE7 SC}URCE IS PV SYSTEIN .. ♦ . . CLLCTRICAL SHOCK HAZARD SHOCIHAZARDIt • DO INOT TCIJC�I TERIOINALS. HE DC>_essta,. Te, S OF THIS + PHOTOVOLTAIC POWER SOURCE _.AGROUND FAJLr IS 1NOICATED, 'rF!R1v1j14ALS ON BOTH ILiNS AND i 4'.,11,A-0LTAiC SY$TPIAARE UNGROUNDED . ��.u, •�,�..:a NORMALLY GROUNDED CONDUCTC)RS ANO h�'.At BE UNERCIZEC MAY FF UN(C IROU iDFD !�sND FNFR('i1?E13. • � � : � LC?Af��IL3ES p�ta� �� �N�1�c�Iz�o CAUTION: SOLAR CIRCUIT: � � CAUTION IN THE OPEN POSITION ff 'i I liff iii, 10 1111 PV SYSTEIaT CWU€ T 9REIAKER IS ERCKFED • • ♦ ♦ • r 101 WARNING: � • .. WARNING ;� DO NICHT DISCONNECT • • • 46 TURN OFF PHOTOVOLTAIC S _., C IRICAL SHUCK HAZARD UNDER LOAD . ♦ • : ♦ . AC DISCONNECT PRIOR TO DGS NOT TOUCH TERMINALS.� illlARN1NG F� PHOTOVOLTAIC AC DISCONNECT TI�IILI�TI1_tvrvC L 1�ORKINGINSIDEPANEL L0, AD �'i InFLlA°RE E NFCIF D n IN THE CPPB S1TlitirJ PHOTOVOLTAIC AC DISCONNECT NORMALLY GROLI DED CON U: t •• 1i WARNING JAFj " TURN OFF PHOTOVOLTAIC � EL TRIC SSI CK HAZ5Re 6 • s 0 % / •a AC DISCONNECT PRIOR TO HE M, CONLAX TORS OF Tr+ WORKING INSIDE PANEL PP1107 (Yt'(XTAICSYSTEMAREUNCROUNDED _e AND MAY 13E ENERGIZED "'WARNING � j� #3i;a R PHOTOVOLTAIC FAI WARNING FA►� , ��*7 YMI ELECfRi"AL to k t .> f? a� _. IF A ROLUNc rAU T r ►t r CAUTION' F.FCT�I�".7rse tnx ? DC DIS+'ONNECT NORMALL L c'(,JNVUP(tA{L�CI�Tc� S SOLA(�ELi�.�R��i5YSTEi1�CO�iNEC�D �� - - R THE DC GCi t1GTt)R TH1S M,,A' FF [INGF:,DDN QED AND ENER61Z"EL ' YSiEPOAIRE iNQsAOUNiiED AND Ft ,4Y PF FNPPC 14 •, • t MAIN PV SYSTEMWARNING FAI pv SYSTEM DISCONNECT WA N P G DUAL POW R SOi Com£ SECOND SOURCE IS PV SYSTEM A�.r DISCONNECT G'4►T ELI^CTRICAL SMOCK HAZARD �P�R�aTit��cc ����T: � � �,, 1 : 1 �} �± 00 NOT TOUCH TERN I � � • WARNING Com! � � � �� TERM,LiNAis L" N dOTt1 LINEANIL) 18 OPFRAAT INC ` OIL P ,C E 1 ELECTRICAL SHOCK HAZARD " 11 } Lc�aa iDES MAY epi- S7!0s�izRD _,____ _ — — MXXI UTA ��STF I1 01TA�`F 11 ` ' I TF OPEN >� �;T= T;LNor To""I I TFRMINAI S. Id1AeS Ciel BOTH LINE AND SHOW ' I`QUIT r_LRRE,,r Q LOAD SIDES MAY BE EfiiE IGUER 8 ! 11 . . ! CAUTION: Ir,E raw roslrlt>u SOLAR ELECTRIC SYSTEM CONNECTED DC VOLTAGE IS -ALWAYS PRESENT � . « , € trr � i 1 ' �WARNING: WHEN S6LAR MODULES PHOTOVOLTAIC ���I 4 �iI ����v1 r�G�.. B ARE EXPOStO TO SUNLIGHT - � 1111110� TURN OFF PHOTOVOLTAIC•s Cul�l P�h'�r iP �`'LEA c A DISCONNECT � 1,,k%MA � �R 111 AC DISCONNECT PRIOR TO k'WRILVACCLI�'RRIEVri SOLAR DISCONNECT WORKING INSIDE PANEL ;i. 7, E -D AC, U'RER J NG t��t�`.k�RRE[I$i i i IE U"1Tt� �� p �j t �}�_ , • 1 +« kRX V=E4RCURR 7 j�^Kj' T��V !»t4h �{ I F w iaC �€if?.S�Olr1•IRRENT �¢"�• YilS.iiLRTwUQ,R.:N C i L71 `l . sYUUiir. `"tai/t� �LPY s t t 'r i.. �. * �... •. !S1_LED . WARNING II AIN PV SYSTEM R TEDSH0 = 0R UR CI RE ® Lti (I ICAL SHOCK HAZARD PHOTOVOLTAIC AC (DISCONNECT DISCONNECT 1V1A 1%1Uk1 SVSTE MiV0liArEn NOT TOUCH TERMAIN LS. ,..,�.,.;_,. �.. r�•�,���F TITLE: TERMINALS ON BO k' LINE AND LOAD ,&DES MAY LE ENERGIZED 1 • 1 • , IN THE OPEN POSITION r« • SHEET NUMBER: 17 OF 38 *jt:UUNU bt,t' VIIL t:1JISL;VNNt:UI The markings shall be of sufficient ON NORTH SIDE OF BUILDING diwrawshowAhn this p+ svi is an 1.:+(EXt 4tr,1,,1 L f durability t� withstand the tI�s1T c teas 113€0 T turn torr 1),] Tv ibel seeded wii , - baszed on h rE:, eco cL :e ax. dE� t3d.� ), �. _ ...: � �5%00300environment involved. IEC 110.21 with. R!for���r.����u�.�.�� THIS PANEL FED FROM INV1 MAX AVAILABLE FAULT CURRENT* 46,552 AMPS tTE EIectric: Swa ise eWipn ent muLtbeh�d Marked p'_ lie, lcy i1� r btH1di,�l �P(,raethan 'k�t,_a0�• (IPart Nta 55�,.,L?1341 DATE 211.5112 * The materials used for marking shall be r�t1 � Ing un its) iic�t��i��e_.���.� aseietrlcgrata}aPvSys_terniThsindudes *NEC 110.24W113artNo,558003 reflective, weather resistant and suitable F'asha`K1infrr7atonnAIab�Inqfor the environment." IFC 605.1 �. :• • 4 1 ivi I• • t• C• PHOTOVOLTAIC POWERPSOURCE .31 auAt POWF;Z1 uRc • : t • /A WARNING ►� WARNING PHOTOVOLTAIC 1NARNING SECONE7 SC}URCE IS PV SYSTEIN .. ♦ . . CLLCTRICAL SHOCK HAZARD SHOCIHAZARDIt • DO INOT TCIJC�I TERIOINALS. HE DC>_essta,. Te, S OF THIS + PHOTOVOLTAIC POWER SOURCE _.AGROUND FAJLr IS 1NOICATED, 'rF!R1v1j14ALS ON BOTH ILiNS AND i 4'.,11,A-0LTAiC SY$TPIAARE UNGROUNDED . ��.u, •�,�..:a NORMALLY GROUNDED CONDUCTC)RS ANO h�'.At BE UNERCIZEC MAY FF UN(C IROU iDFD !�sND FNFR('i1?E13. • � � : � LC?Af��IL3ES p�ta� �� �N�1�c�Iz�o CAUTION: SOLAR CIRCUIT: � � CAUTION IN THE OPEN POSITION ff 'i I liff iii, 10 1111 PV SYSTEIaT CWU€ T 9REIAKER IS ERCKFED • • ♦ ♦ • r 101 WARNING: � • .. WARNING ;� DO NICHT DISCONNECT • • • 46 TURN OFF PHOTOVOLTAIC S _., C IRICAL SHUCK HAZARD UNDER LOAD . ♦ • : ♦ . AC DISCONNECT PRIOR TO DGS NOT TOUCH TERMINALS.� illlARN1NG F� PHOTOVOLTAIC AC DISCONNECT TI�IILI�TI1_tvrvC L 1�ORKINGINSIDEPANEL L0, AD �'i InFLlA°RE E NFCIF D n IN THE CPPB S1TlitirJ PHOTOVOLTAIC AC DISCONNECT NORMALLY GROLI DED CON U: t •• 1i WARNING JAFj " TURN OFF PHOTOVOLTAIC � EL TRIC SSI CK HAZ5Re 6 • s 0 % / •a AC DISCONNECT PRIOR TO HE M, CONLAX TORS OF Tr+ WORKING INSIDE PANEL PP1107 (Yt'(XTAICSYSTEMAREUNCROUNDED _e AND MAY 13E ENERGIZED "'WARNING � j� #3i;a R PHOTOVOLTAIC FAI WARNING FA►� , ��*7 YMI ELECfRi"AL to k t .> f? a� _. IF A ROLUNc rAU T r ►t r CAUTION' F.FCT�I�".7rse tnx ? DC DIS+'ONNECT NORMALL L c'(,JNVUP(tA{L�CI�Tc� S SOLA(�ELi�.�R��i5YSTEi1�CO�iNEC�D �� - - R THE DC GCi t1GTt)R TH1S M,,A' FF [INGF:,DDN QED AND ENER61Z"EL ' YSiEPOAIRE iNQsAOUNiiED AND Ft ,4Y PF FNPPC 14 •, • t MAIN PV SYSTEMWARNING FAI pv SYSTEM DISCONNECT WA N P G DUAL POW R SOi Com£ SECOND SOURCE IS PV SYSTEM A�.r DISCONNECT G'4►T ELI^CTRICAL SMOCK HAZARD �P�R�aTit��cc ����T: � � �,, 1 : 1 �} �± 00 NOT TOUCH TERN I � � • WARNING Com! � � � �� TERM,LiNAis L" N dOTt1 LINEANIL) 18 OPFRAAT INC ` OIL P ,C E 1 ELECTRICAL SHOCK HAZARD " 11 } Lc�aa iDES MAY epi- S7!0s�izRD _,____ _ — — MXXI UTA ��STF I1 01TA�`F 11 ` ' I TF OPEN >� �;T= T;LNor To""I I TFRMINAI S. Id1AeS Ciel BOTH LINE AND SHOW ' I`QUIT r_LRRE,,r Q LOAD SIDES MAY BE EfiiE IGUER 8 ! 11 . . ! CAUTION: Ir,E raw roslrlt>u SOLAR ELECTRIC SYSTEM CONNECTED DC VOLTAGE IS -ALWAYS PRESENT � . « , € trr � i 1 ' �WARNING: WHEN S6LAR MODULES PHOTOVOLTAIC ���I 4 �iI ����v1 r�G�.. B ARE EXPOStO TO SUNLIGHT - � 1111110� TURN OFF PHOTOVOLTAIC•s Cul�l P�h'�r iP �`'LEA c A DISCONNECT � 1,,k%MA � �R 111 AC DISCONNECT PRIOR TO k'WRILVACCLI�'RRIEVri SOLAR DISCONNECT WORKING INSIDE PANEL ;i. 7, E -D AC, U'RER J NG t��t�`.k�RRE[I$i i i IE U"1Tt� �� p �j t �}�_ , • 1 +« kRX V=E4RCURR 7 j�^Kj' T��V !»t4h �{ I F w iaC �€if?.S�Olr1•IRRENT �¢"�• YilS.iiLRTwUQ,R.:N C i L71 `l . sYUUiir. `"tai/t� �LPY s t t 'r i.. �. * �... •. !S1_LED . WARNING II AIN PV SYSTEM R TEDSH0 = 0R UR CI RE ® Lti (I ICAL SHOCK HAZARD PHOTOVOLTAIC AC (DISCONNECT DISCONNECT 1V1A 1%1Uk1 SVSTE MiV0liArEn NOT TOUCH TERMAIN LS. ,..,�.,.;_,. �.. r�•�,���F TITLE: TERMINALS ON BO k' LINE AND LOAD ,&DES MAY LE ENERGIZED 1 • 1 • , IN THE OPEN POSITION r« • SHEET NUMBER: 17 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule of Current Interconnection Frequency 60 Hz Circuit Conductor Conductor Conductor Design OCPD OCPD Conduit No. Conduit Conduit Size Reference Circuit Description Carrying Voltage -Line 1 to Neutral 120 V ID Type Material Size Current Type Rating Schedule Conductors Type and QTY Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A C01-1 2 PVC %11 Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A Co -2 3 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D.P.C. B. 20A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Module Model Number: Q.PRO-G3 265 EQ -3 EQ -4 EQ -6 Existing Meter Maxium Series Voltage Allowed: 1000 VDC EQ -7 Temperature Coefficent - Voltage -0.28% per oC CO -1 CO -2 CO -2 Temperature Coefficent - Current 0.03% per oC CI -3 CI -4 CI -4 EQ -9 Temperature Coefficent - Power -0.38% per °C EQ-1,EQ-2 CI -2 Junction Integrated Specifications at STC Box Disconnect MPP Power - Pmp 265 W New Existing Solar Electrical MPP Current - Imp 8.69 A DC AC Service Service MPP Voltage - Vmp 30.79 V Optimized String of 12 Modules Short -Circuit Current - Isc 9.28 A ----- --- --- ------ Open-Circuit Voltage - Voc 38.52 V Temperature Adjusted Inverter Vmp- Min 30.35 V VOC - Max 39.60 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P300 EQ -5 Rated Input DC Power: 300 W Maxlum Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE: SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following Component Model string limitations apply, based on the Inverter Selected. EQ 12 EQ C12 D Description Manufacturer Number Notes Inverter Input Bus Voltage at P300 Power EQ -1 Solar PV Module QCell QPRO-265 See Module Information 350 V P300 Power Specified Interconnection Voltage: Optimizer Optimizer EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ C11 EQ 1_1 EQ -3 DC Junction Box N/A N/A NEMA 3R - Outdoor Rated Minimum Optimizers Per String: 8 EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Inverter Information Solar Solar Photovoltaic Photovoltaic EQ -5 Inverter SolarEdge SE3000U-US See Inverter Information ••• Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 3000U -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker- NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 3000 W EQ -8 Meter After Installation Maximum AC Power Output 3300 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current at Specified Interconnection Voltage:.B 12.5 A u'l I d'i #9- BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: SHEEP NUMBER: 18 OF 38 Arc Flash and Shock Hazard Appmp6obe PPE RegWred ep LABELING ZC A7 T71 Aitidf� 130 REQUIREMENTS NEC 2011 Article 690 and IFC 2072 M 4 LLJ Of L.Lj cr� Adhesive Fastened Signs [I - Adhesive fastened signs may be acceptable if properly adhered. Vinyl signs shall be weather resistant. IFC 605.11.1.3 Epp, SECOND 5ERVICE D15CONNECT The markings shall be of sufficient ON NORTH SIDE OF BUILDING durability to withstand the z S�v pam o urnber rd ty pt 'NEC 230,2(E) 558-00309 the project sco,pe and NEC 230 72(A) Part Nk ed- mr6 1 "for environment involved. NEC 110.21 THIS PANEL FED FROM INV11 MAX AVAILABLE FAULT CURRENT: 46,552 AMPS DATE 2/15/12 ,quiprn.eRt mu�t be 1164 markt per the * The materials used for marking shall be ont In a building ot%tiuctxe (otNr 0 -on %EC4CkIR4(01,�artNo 5% -CC`. ; ............ 71 by tmcre than,.ve 'IeNce prNder ii e, G24(A) Pa -0009 ,t6city and a PV System). TN s indudei, *NEC 11 I rt No 558 3 reflective, weather resistant and suitable at laW- Ing for the environment." IFC 605 MMEEM FAI WARNING' W FAI WARNING FAI PHOTOVOLTAIC POWER SOURCE FAI WARNING a WARNIN6 DUAV POWER SOURCE SECOND SOURCE IS PV SYSTEM LLLCTRICAL SHOCK HAZARD .. . .... ........ ..... CL EC'FRIC SHO : HkZARD ELECTRICA; �$HO-CK HAZARD DO NOT. 10JCH TERMINALS, THEE CONDLI,'CTORS OF THIS IIHOTOVOLTAIC POIATP �OURC IF AGROUND �'ZLI` IS INOICATED, 77IRMI NALS Oq ROTH LINF7 AND PHOTOVOLTAK�,- $YSTEk,,1 ARE LINGROUNDED NORMALLY GROUNDED CONDUCTORS LOAD SIDES MAY BE ENERGIZED �E ER'� NEIZEU MAY CAUTION: SOLAR CIRCUIT BE ILINGROUNDIED AND ENERGIZED CAUTION v W MTHE 0,PEN F0,91TION PV SYSTEM CIRCUIT BREAKER 15 SACKFIED 641 WARNING: 21 FAIL WARNING kil,DO ]IT NOT DISCONNECT TURN OFF PHOTOVOLTAIC ELECTRICAL SHOCK HAZARD UNDER LOAD AC DISCONNECT PRIOR TO DO NOT TOUCH TERMINALS. WORKING INSIDE PANEL PHOTOVOLTAIC AC DISCONNECT TERMINALS ON BOTH LINE AND FA&I WARNING FAI LOAD SIDES klAY BE ENERG12ED FLTRICAt IT.'7H7 OPFN POStTJOI, PHOTOVOLTAIC AC DISCONNECT SH01K HAZAki, • IF A GROI,, i NC,4 DFAUL, IS INDITLD, NoRfAALLY GROONDED CONDUCTOR* •of . ......... . . . . .. . ......... ... 14AW BE, UNGROUNDED AND FNEPCIZED "A WARNING: FAR WARNING FA TURN OFF PHOTOVOLTAIC ELECrRf�; SHOCK HAZ' ARD 6 D ri n TSITA -01 rn-4 a LTA - 7 0 0 0 AC DISCONNECT PRIG To I HE EX CON DUCTO RS OF THIS • WORKING INSID 'HOTOVOLTAW SYSTEM ARE UNCROUNDEL, 3 :GNU MAY BE ENEnIZED A" FAI rA PHOTOVO WARNING WARNING FAJ t' LEC f RI(;A!- �HCXX HAZARD IF A GROUND FAuLT I$ I,,,;DICATEDz CAUTION: BY: BDD ELECTRIC SHOCK t-(AZARD DC, DISC INECT. NORMALLY OROUNDED 12C.NDUCTORS SOLAR ELECTRIC SYSTEM -�Y00ftQINNEICTED 0 THE OG CONGUCTORS OF TNI MAS FA,- AND ENERGIZED r40T0,VOL'rAIc,SvSTE1,I ARE UtiGR00NDED AND, MAY RF DATE: 8/29/2018 ".400111aft— WARNING rkl ■ WARNING 04JAL POWER MAIN PV SYSTEM 1115*1 PV SYSTEM DO DISCONNECT SECOND SOURCE 19 PV SYSTEM AC DISCONNECT FLECTRICAL SHOCK HAZARD REVISION: MKIM OPZRATIN' CURRCNT� DO NOT IOUCH TERMINAL -S, •T ERfVItNAL$ OIN aOT11 LINE AND WARNING WIL OP E RA T I I,4'C�' VC) L T A C- F LOAD SIDES LIAY BE ENERGIZE,,-) ELECTRICAL SHOC'K-HAZ,AR'D IN THE OPEN POSI-7ION MkK Al t Y"A SY STE INI VOt- TAG F 00 NOr TOUCH TERMINALS TERMIINALS ON ROT" LINE AND -11nF_T CURRQN"! J-OAD SIPES MAY SE ENERGIZED 8 oil, . IN.1*11L OPEN fL)5jfION •SOLAR ELECTRIC SYSTEM CONNECTED DCVOLT/�GE IS ALWAYS PRESENT . ...... .. FAI WARNING: WHEN SOLAR PHOTOVOLTAIC V� IBM 417M 63POSED TO SUNLIGHT i-Eir� JRK%' INTRE TURN OFF PHOTOVOLTAIC C ISCONNECT AC DISCONNECT PRIOR TO kAkX1)&`rII,;YFEM `,IQLT��E 11111111OW111111111 111 AC, CDUERB"T 111111111ZI11111111 SOLAR DISCONNECT WORKING INSIDE PANEL RIVEN RATED AC OPEWING CURREtJ SKR'�V'JRNITC`�URRE.%U �Ilw 01`,'ER,1Vt1FRE1`J1 )EVICE RATING: kli'�X FATE SaXPRITCURRENTOF T RAT ED AC OPERATI NG'VOLTAC-E Hl: N� R' T N!4 RATE14C CrrERA7150LTAGE WARNING MAIN PV SYSTEM RATED IORTCIRUF CORRENT ELECTRICAL SHOCK HAZARD PHOTOVOLTAIC AC DISCONNECT DISCONNECT MAXIMUM SYSTEM V0054GE 11111111111111111111111110 DO NOT TOUCH TERIV11NALS, TERMINALS ON, BOTIA, LINE AND LOAD SOES MAY bE ENERGIZEDD IN THE OPEN POSITION SHEET NUMBER: 19 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Circuit Reference ID Circuit Description Conductor Type Conductor Material Conductor Size Design Current OCPD Type OCPD Rating Conduit Schedule . Noof Current Carrying Conductors Conduit Type Conduit Size and QTY Interconnection Frequency q Y 60 Hz Voltage -Line 1 to Neutral 120 V Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %11 CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A co -2 3 CarFlex 3/4" Voltage - Line 3 to Neutral (If Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D.P.C.B. 20A Voltage - Line 2 to Line 3 - V EQ -8 EQ -3 EQ -4 EQ -6 EQ -7 CO -1 co_2 co -2 EQ- 1,EQ-2 CI -3 CI -4 CI -4 CI -2 Junction Integrated Box Disconnect New DC AC Service Optimized String of 9 Modules ----- ---♦-- ------ ------ Inverter EQ -5 The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an "Optimized String of Modules". Equipment Schedule EQ2 12 EQ2 C12 Component Model ID Description Manufacturer Number EQ -1 Solar PV Module QCell QPRO-265 P300 Power P300 Power Optimizer Optimizer EQ_2 DC Optimizer SolarEdge SE P300 EQ Cl1 EQWI_� EQ -3 DC Junction Box N/A N/A EQ -4 Integrated Disconect SolarEdge N/A Solar Solar Photovoltaic PEQ-5 Inverter SolarEdge SE3000U-US • • • Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP EQ -7 Existing Electrical Service N/A N/A Existing Meter Enclosure N/A N/A EQ -8 EQ -9 Insulation Piercing Splice NSI IPSC4002 Connector Existing Meter EQ -9 ExistingSolar Electrical Service Notes See Module Information See DC Optimizer Information NEMA 3R - Outdoor Rated Disconnect Integrated with Inverter See Inverter Information See Page EQ4 for Detailed Specs 150A Main Breaker- NEMA 3R Meter to be Replaced with Bi -Directional Net Meter After Installation See Page EQ5 for Detailed Specifications Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information Manufacturer Name: QCell Module Model Number: Q.PRO-G3 265 Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent - Voltage -0.28% per oC Temperature Coefficent - Current 0.03% per oC Temperature Coefficent - Power -0.38% per °C Specifications at STC MPP Power - Pmp 265 W MPP Current - Imp 8.69 A MPP Voltage - Vmp 30.79 V Short -Circuit Current - Isc 9.28 A Open-Circuit Voltage - Voc 38.52 V Temperature Adjusted Vmp - Min 30.35 V VOC - Max 39.60 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P300 Rated Input DC Power: 300 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A Maximum Output Current: 15 1 A NOTE: SolarEdge Power Optimizers ONLY to be used with SolarEdge Inverter, as specified in this drawing. The following string limitations apply, based on the Inverter Selected. Inverter Input Bus Voltage at Specified Interconnection Voltage: 350 V Maximum Power Per String: 5250 W Minimum Optimizers Per String: 8 Inverter Information Manufacturer Name: Solar Edge Module Model Number: SE 3000U -US Nominal Power Output 3000 W Maximum AC Power Output 3300 W Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A Bu'ild'ina #10 BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E -10 a SHEET NUMBER: 20 OF 38 'am", ?I+ i Ow, as as U ty,�.' U, on th? proje 01, -,7ccyne, W'd 0s ith AH'Jfo,, kx--.� reQ1U111-er11k1t1*f, letit must be b elld mart., -A per Itle Circuits / Enclosures PER NEC 690 17(4) 1 Part No, 596-00233 CAUTION PE R N EC 690 56(B) I Pat W, 558-00350 PHOTOVOLTAIC SYSTEM. 11111111111110A4� BE Ll N G *NEC Artrllje 11716 atidWA2012 Pif! No, R E Q U I R E M E NTS NEC 2011 Article 690 and IFC 2012 X c Adhesive Fastened Signs Adhesive fastened signs may be acceptable if properly adhered. Vinyl signs shall be weather resistant. IFC 605,11.13 V I14LJ or-mv 11,60r- LJI0%.0VN [Art..* 1 I T The markings shall be of sufficient ON NORTH SIDE OF BUILDING 411 : I durability to withstand the *NEC 2h0,2(E), NEC 230 72(,A) I PartkR4 55, PANEL FED environment involved. NEC 110.21 ,OM INV1 MAX AVAILABLE FAULT CURRENT: 46,552 AMPS DATE 2115112 0 1 Part W,)55,PX�313 The materials used for marking shall be , *NEC 11024(A) I PartNo 558-00309 reflective, weather resistant and suitable for the environment." IFC 605.11. 1.1 PER NEC 690,35(F) I Part No, S96.00258 PER NEC 110,27(C) &OSHA 1910,145(f)(7) Part Na. 5%-00235 () DC Disconnect / Breaker / Recombiner Box PER N E C 690 3 5(F) I Par t N o, 595-00258 PER NEC 690 17(4)1 Par tNo. 596-00232 FOR MARKING BACKUP SYSTEMS Part No, 5%-00240 t PER IFC 6075.11.1, IFC 605 11 1A NEC 690.15 & NEC 00.14(C)(2)i PartNo, 596.00238 NEC 690.531 Part No596-00241 NEC 690.53 1 Part No. 596-00253 4 . . # 9 1 F TMO MIFA0 I PHOTOVOLTAIC POWER SOURCE Ir F,&I ,A WARNINGMAL POWFR SOURCF WARNING FAMSECOND SOURCE IS PV SYSTEM PHOTOVOLTAIC POWER SOURCE IF A GROUNI) FAULT IGNNCATED, NORMALI-V GR—OUNDEDt�ONDUCTORS CAUTION- SOLAR CIRCUIT' NIA V ef', UNGRC)1JNDL-,'0 ANS ENER61ZED CAUTION PV SYSIVOGIRCV, I SREAKF>i as 5ACKFEO FAWN WARNING FAi DO NOT DISCONNECT ILLPCTRICAL SHOCK I " IAZARD UNDER , 19-A D-..- Im 00 NOT TOUCH TF-RNIP PHOTOVOLTAIC AC D'ISCONN99T TERMINALS ON BOTH LIN�IAND FAI WARNING F,&I LOAD SIDES MAY BE ENERGiZEC) PNC3TOVOLTAIC AC DISCONNEC7 HA2A,NC tl , 1�!,��-4_ " 1!_1 IN n ir, OPEN POSITION 'r'=` NN(,ATED ORMALLi `-�ROUNDLC CONCUCI'ORS '%FRIC1717r, zue FAMA R N I N G: WARNING FA TURN OFF PHOTOVOLTAIC 7 ELLCTRI�, 3�iLKK HA�,4RL� AC DISCONNECT PRIOR TO !HE IX CC%0U(-'T0RS0r'U+• S a WORKING INSIDE PANEL PH010VGLTAJ0,,Y1-,'[EUARF UNGROLNDED • ANUS MAY 9E ENER(r LZETJ WARNING w-'" W-0 )UND FAULT IS IN01 SOLAR ELECTRIC SYSTEM CONNECTED —1. BDD NOPMALIN(�,ROUNVED W%` MAY OF It INCK01 �N])` ED AND • TE: /2/2 MAIN PV SYSTEM 1541 WARNING P DA89018 WARNING DUAL POWER SOURCE FLECTRICAL, SHOCK HA7ARD SECOND SOURCE IS PV SYSTEM AC DISCONNECT 00 NOT TOUCH TERfOlfAALS, REVISION: T�.RNIINALS ON 50TH UNE,"D 1 OAr) ST)C-S %1AY P7 1-NJF-RG127P7D IN *Tlit- OPEN PC'' -:04 CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED .,# I FAMARNING: PHOTOVOLTAIC""' frOfii'.INALOPE,RATINGACFREI,IUE,V,"tom t TURN OFF PHOTOVOLTAIC AC DISCONNECT N1k\!%W ACIPUVER Kam AC DISCONNECT PRIOR TO AR DISCONNECT MANUM AC CAREN'T WORKING INSIDE PANEL WO`EE RURENT DDICERAT L MUWARNING I&I �ORAC%1011FIRIOEJION MAIN PV SYSTEM SHEET TITLE: LLLICTRICAL SHOCK HAZARL) . .. ..... . PHOTOVOLTAIC AC 01'§CONNEIbT DISCONNECT JF RMHALS','V, [3011LINEAND LOAD --�!OES NIAY Off-, ENERGIZED IN Tf�F` OPEN POSITION Bu'ild'ing #11 SHEET NUMBER: 21 OF 38 z M Lij LLJ Of 4 . . # 9 1 F TMO MIFA0 I PHOTOVOLTAIC POWER SOURCE Ir F,&I ,A WARNINGMAL POWFR SOURCF WARNING FAMSECOND SOURCE IS PV SYSTEM PHOTOVOLTAIC POWER SOURCE IF A GROUNI) FAULT IGNNCATED, NORMALI-V GR—OUNDEDt�ONDUCTORS CAUTION- SOLAR CIRCUIT' NIA V ef', UNGRC)1JNDL-,'0 ANS ENER61ZED CAUTION PV SYSIVOGIRCV, I SREAKF>i as 5ACKFEO FAWN WARNING FAi DO NOT DISCONNECT ILLPCTRICAL SHOCK I " IAZARD UNDER , 19-A D-..- Im 00 NOT TOUCH TF-RNIP PHOTOVOLTAIC AC D'ISCONN99T TERMINALS ON BOTH LIN�IAND FAI WARNING F,&I LOAD SIDES MAY BE ENERGiZEC) PNC3TOVOLTAIC AC DISCONNEC7 HA2A,NC tl , 1�!,��-4_ " 1!_1 IN n ir, OPEN POSITION 'r'=` NN(,ATED ORMALLi `-�ROUNDLC CONCUCI'ORS '%FRIC1717r, zue FAMA R N I N G: WARNING FA TURN OFF PHOTOVOLTAIC 7 ELLCTRI�, 3�iLKK HA�,4RL� AC DISCONNECT PRIOR TO !HE IX CC%0U(-'T0RS0r'U+• S a WORKING INSIDE PANEL PH010VGLTAJ0,,Y1-,'[EUARF UNGROLNDED • ANUS MAY 9E ENER(r LZETJ WARNING w-'" W-0 )UND FAULT IS IN01 SOLAR ELECTRIC SYSTEM CONNECTED —1. BDD NOPMALIN(�,ROUNVED W%` MAY OF It INCK01 �N])` ED AND • TE: /2/2 MAIN PV SYSTEM 1541 WARNING P DA89018 WARNING DUAL POWER SOURCE FLECTRICAL, SHOCK HA7ARD SECOND SOURCE IS PV SYSTEM AC DISCONNECT 00 NOT TOUCH TERfOlfAALS, REVISION: T�.RNIINALS ON 50TH UNE,"D 1 OAr) ST)C-S %1AY P7 1-NJF-RG127P7D IN *Tlit- OPEN PC'' -:04 CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED .,# I FAMARNING: PHOTOVOLTAIC""' frOfii'.INALOPE,RATINGACFREI,IUE,V,"tom t TURN OFF PHOTOVOLTAIC AC DISCONNECT N1k\!%W ACIPUVER Kam AC DISCONNECT PRIOR TO AR DISCONNECT MANUM AC CAREN'T WORKING INSIDE PANEL WO`EE RURENT DDICERAT L MUWARNING I&I �ORAC%1011FIRIOEJION MAIN PV SYSTEM SHEET TITLE: LLLICTRICAL SHOCK HAZARL) . .. ..... . PHOTOVOLTAIC AC 01'§CONNEIbT DISCONNECT JF RMHALS','V, [3011LINEAND LOAD --�!OES NIAY Off-, ENERGIZED IN Tf�F` OPEN POSITION Bu'ild'ing #11 SHEET NUMBER: 21 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency Circuit Noof Current q Y 60 Hz . Conductor Conductor Conductor Design OCPD OCPD Conduit Conduit Conduit Size Reference Circuit Description Carrying Voltage -Line 1 to Neutral 120 V ID Type Material Size Current Type Rating Schedule Conductors Type and QTY Voltaeg - Line 2 to Neutral 120 V CIA PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %4" Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A co -2 3 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D.P.C. B. 20A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Module Model Number: Q.PRO-G3 265 EQ -3 EQ -4 EQ -6 Existing Maxium Series Voltage Allowed: 1000 VDC EQ -7 Meter Temperature Coefficent - Voltage -0.28% per oC CO -1 co -2 co -2 Temperature Coefficent - Current 0.03% per oC CI -3 CI -4 CI4 EQ -9 Temperature Coefficent - Power -0.38/ per oC EQ -1, EQ -2 CI -2 Junction Integrated Specifications at STC Box Disconnect MPP Power - Pmp 265 W New Existing MPP Current - Imp 8.69 A DC AC Solar Service MService I PP Voltage -Vmp 30.79 V Optimized String of 8 Modules Short -Circuit Current - Isc 9.28 A _— -- — Open -Circuit Voltage - Voc 38.52 V Temperature Adjusted Inverter Vmp - Min 30.35 V VOC - Max 39.60 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P300 EQ -5 Rated Input DC Power: 300 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE., SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ2/C12 EQ2 Component Model string limitations apply, based on the Inverter Selected. C12 ID Description Manufacturer Number Notes Inverter Input Bus Voltage at EQ -1 Solar PV Module QCell QPRO-265 See Module Information 350 V P300 Power P300 Power Specified Interconnection Voltage: Optimizer VOptimizer EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ C11 EQ 1.1 EQ -3 DC Junction Box N/A N/A NEMA 3R - Outdoor Rated Minimum Optimizers Per String: $ :C Elm. - EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Inverter Information Solar Solar Photovoltaic Photovoltaic EQ -5 Inverter SolarEdge SE3000U-US See Inverter Information ••• Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 3000U -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker- NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 3000 W EQ -8 Meter After Installation Maximum AC Power Output 3300 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 AJ__ F Building #1 1 W to BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E -11a SHEET NUMBER: 22 OF 38 *NEC 2330 2tNEC 230,72(A) 7 art N 553.00309 ATHIS PNEL FED environment involved. ITEC 110.21 FROM INV 1 MAX AVAILABLE FAULT CURRENT. 46,552 AMPS quipmrrit mustbe hdd r��ir�. p1 l tl DATE 2115712 d rtinabuildinj,<� �f��t�,��<<��t ��t �,-NEC 55���� 3, The materials use or marking shall be a>> by mfx P thin ��i� e��srs ����s�i�r t� e_ :., .......�,,..,..., ik xem)TNLinclud� *NEc11L,�a(��ParthJc�55������ reflective, weather resistant and suitable for the environment." IFC 605.1 1.1.1 AM WARNING An WARNINGPHOTOVOLTAICPOWER SOURCE ® WARNING U11,1ARNING► DUAL POWER SOURCE • . • LLLGTRICA. L SHOCK IHAZARD -a SECOND SOURCE i � PV SYSTEM - • . _._ CLL RI(; kit�C.h H t7 i ELECTRICAL $HOCK HAZARD - UO NOT I&xll tl TERMINALS, THE PC COUIDUCTORS'.1F 11I 16 PHOTOVOLTAIC PO ER SOURCE IR AGROUND FAULT IS INLIC;ATED, s 77PNIINALS ON rCTH LINE.AND t�dH0tJt�'OLTACSYSTEM ARE LINGR'01jNDE ��a>�: �_� �fdP'kALL1 �3F (� Jl�� C� �.C7�LLIC: I:�RS LOAD SIDFS MAY dE FNERGIZED AND Nita BE ENEKI<EE CAUTION- SOLAR CIRCUIT MAYBE UNGROUNDED AND FNFR � EU CAUTION • - � : � i IN THE OPEN ROSITJUN *I • - • • i . � . , +� PV SYSTEM CIFtGUI r BREAKER IS BAGtCEEi! • • ' -` • r i l�� WARNING: G ; � � • - - - 2 • • 5 WARNING � DO NOT DISCONNECT � � • � TURN OFF PHOTOVOLTAIC LLLCI'RICAL SFiOCK HAZARD UNDER LOAD • : . AC DISCONNECT PRIOR TO DO NOT TOUCH TERMINALS, � • WORKING INSIDE PANELFAI WARNING �� �,�,�; .._;4h�=,E LOAD SIDES WAY BE ENE RE RNii �r PHOTOVOLTAIC AC DISCONNECT TERNINIALS ON BOTH LIN €v'CIZECT PHOTOVOLTAIC AC DISCONNECT Et E= Ti(+': ri,FEG3%I4HAZARD >:aM �, �g a; :, rr ����:, IN n -IE OPEN POSITION � 0=1 GROUND FAULT 15INDtI ATED, N F2,©i.INfi?ED C�tvQ€.tCTGlR�� 'ttY E3E LI Rt7LINDFD AI D ENER0717C, �• f FAI WARNING 10 TURN OFF PHOTOVOLTAIC ELECTRIC SHOCK HAZARD 6 • 7 " • • • AC DISCONNECT PRIOR TO I HF DC COND'UCTORS,oPTHS • t� , _ • • : • . • WORKING INSIDE PANEL RHOTcs�����LTAICSY�:TEMAREUNGR L D AND MAY BE EINERGIZZED PHCTCiVtaLTAIC ® WARNING % A WARNING CAUTION: • D D DC DIS+ C ► INEGT I A ROI-INDFA= L ISNDIGATED THECIC < , � ,� ,-��� OF THI'� _ ��r�,� I)� RO�NVEr� CU,NC�iICTt�E2 . SIO%AR �LEICTRIC SYSTEM CONNECTED MAYBE l.l„C..I%iJUND D AND ENERGIZEi, - - F -Ot�7s'OLTAKC ,. � c S'S k,n tJN R� tl LO I •DATE: 8/29/2018I AND 6iA° RF ENFRO€ FE . 1� MAIN PV SYSTEM WARNING A PV SYSTEM DC DISCONNECT WARNING DUAL POWSR S0,L)RC EC_I TRIAL SHOCK HAZARD REVISION: SECOND SOURCE IS PV SYSTEM AC DISCONNECT, �PEPATING RREt T: 1��/�A�t /� LIQ NTTU�HTFR�tINAL�. 11 RN NG ►aae f "- y TEf��JINlEL;� 4�hi SCI'TFI LINE Ai'�;� 1PERATI C, VCLTACE ' LCJRCi $!DES k1AN" RE ENFRO17ED ELECTRICAL SHOCK HAZARD M kX1.%4 A SYSTEM V0,1 T:.i :- � � Ire rHT ,* PEN PO$1 10,N ©O NOT TOUCH TTLIs TERMINALS ON garH a� LINENE AND v►±iSRi „sR,CUfT RPrN" LOAD SIDES MAY BE ENERC4ZED 8 CAUTION: IN THE OPEN 110511 ION SOLAR ELECTRIC SYSTEM CONNECTS[' DC VOLTAGE IS ALWAYS PRESENT `0 WA NTNG: WHEN SOLAR MODULeS PHOTOV LTAIC 01KAL OPERATIINUAC I'QL AG �— ARE EXPOSED TO SUNLIGHT , RPIE��.1 XiXp r1 �# 1( y l Lvi � N0MIN 0P�T1NCAC`FRE4 ``�`- •' I �� TURN OFF PHOTOVOLTAIC i��C��E r� 11P1I I �see DI CONNEMAXI AICPkf ACDISCONNECT PRIOR TO, 'YF&lh1 h�wE I MAX1MUMA C RENT SOLAR DISCONNECT.WORKING INSIDE PANEL OPERATING CURRENT ���� OVERS �t TDE';, ATs SRK1101, ROTERON 1;HEET TITLE: XRATIG101 TAG �AWARNING F0 MAIN PV YSTEMN'.X RAEcD AC D ERAT,N,D,G ' RATED SHORT CIRCUIT CURRENT L LCTRICAI SHOCK HA.ZARC) PHOTOVOLTAIC AC DISCONNECT E?IIJ' SV' STEM VLd NOT TOI�II TIfllA DISCONNECT TERMINALS ON EI{` TU LINE iN€3 • .AD50ESMAY EE ENERGIZEDE- 12 • IN THE L PIN PLYS -K' N IET NUMBER: 23 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency Circuit Noof Current q Y 60 Hz . Conductor Conductor Conductor Design OCPD OCPD Conduit Conduit Conduit Size Reference Circuit Description Carrying Voltage -Line 1 to Neutral 120 V ID Type Material Size Current Type Rating Schedule Conductors Type and QTY Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %4" Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A co -2 3 CarFlex 3/4" Applicable) - V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D.P.C. B. 20A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Module Model Number: Q.PRO-G3 265 EQ -3 EQ -4 EQ -6 Existing EQ -7 Meter Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent -Voltage -0.28% per oC CO -1 CO -2 CO -2 Temperature Coefficent - Current 0.03% per oC CI -3 CI -4 CI -4 EQ -9 Temperature Coefficent - Power -0.38% per oC EQ -1 EQ -2 CI -2 Junction Integrated Specifications at STC Box Disconnect MPP Power - Pmp 265 W New Existing Solar Electrical MPP Current - Imp 8.69 A DC AC Service Service MPP Voltage - Vmp 30.79 V Optimized String of 10 Modules Short -Circuit Current - Isc 9.28 A ----- ---♦-- ------ ------ Open-Circuit Voltage - Voc 38.52 V Temperature Adjusted Inverter Vmp - Min 30.35 V VOC - Max 39.60 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P300 EQ -5 Rated Input DC Power: 300 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE: SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ2 12 EQ2 C12 Component Description Manufacturer Model Notes string limitations apply, based on the Inverter Selected. ID Number Inverter Input Bus Voltage at 350 V P300 Power EQ -1 Solar PV Module QCell QPRO-265 See Module Information Specified Interconnection Voltage: Optimizer P300 Power Optimizer EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ C1,1 EQ EQ -3 DC Junction Box N/A N/A NEMA 3R - Outdoor Rated Minimum Optimizers Per String: 8 EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Solar Solar Inverter Information Photovoltaic Photovoltaic 71 EQ -5 Inverter SolarEdge SE3000U-US See Inverter Information • • • Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 3000U -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker- NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 3000 W EQ -8 Meter After Installation Maximum AC Power Output 3300 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A Building #12 - U W 0 CL BY: BDD DATE: 8/29/2018 REVISION: SHEEP TITLE: E -12 a SHEET NUMBER: 24 OF 38 e�.>> O N �i a� F�� 4 ' ���p.�'•.'��0R1rJ;�' 14e, FPV' Aft 0 01 . . . . . . . . . . . . . . . . . . . o 4At An 4 011 .6 � J MIN 1 i i • ! i i • M I 1 /A 3 WARN INta ��> ���, PHOTOVOLTAIC POWER SOURCE ��� WARNING ",& WARNING D4.IAI_ POWFR S CFARIFAMSECOND SOURCE IS PV SYSTEML"LL�.,I RIGAL'I IOCK HAZARD R: • • — Eii i .ire A4iLI ELEC'TRi,::A, �N 3si H�kZAR � t ! •t e __. z7v one 00 NOT TOUCa . *rRfigTINALS, itIE D CONDUCTORS O_'THIv> �. tt !, PHOTOVOLTAIC POWER SOURCE IEA GROUND FAULT IS INOtCt�T�D, 'TERMINALS ONSOT41LSt*IEANL} PHO PAA)LT.A�(w1$YSTEP,4ARE(NCROUNDEU ..,; .,-.. Nl7ttMALLYSt;OUNDED "{IND ICi4"R •< tt - I_GAD SIDS MAY 4 ENE GIZEt) . AND NIAY BE ENERGIZED � 4A,' PE UN(dRQUNDE0AND ENERGIZED • ! IN INE OPEN POW !ON � CAUTION: SOLAR CIRCUIT' .. 4t CAUTION .rwsysrEM��cv,r�R±wxxt�t>y�ntE��� • • • � � • i !E t 10 ilil'ARN1NG: F0 WARNING kO DO NoT biscONNECT . � • � TURN OFF PHOTOVOLTAIC RICAL. SHO I [AZARD tJt DER LOAD • . • � • AC DISCONNECT PRIOR TO DO NOT TQLJCI4 TLIR INAL S. - • PHOTOVOLTAIC AC DISCONNECT TERNWALE ON S�')Tfi LINE AND WORKING INSIDE PANEL WARNING �.`� � LOAD SIDLE WAY BE ENERGIZED PHOTOVOLTAIC AC DISCONNECT IN TFIE OPEN POSITION . �� •. , � � � !�' A � F C)tRNiT Ft�t:ilaHAZARD� • ! FAI WARNING- ,,�� .�! � WARNING JFAJ TURN DIFF PHOTOVOLTAIC LLLKTkk� Sr4(_1CK RAZARu • .. . i 0 • 0 AC DISCONNECT PRIOR TO THE DC tt`NDL3CT;tf SOrTHIS 1� 11 • • • • . ; . • - • tl1fC RKING INSIDE PANEL PLI010V TAI YSJEMAPE UIN OMDE-0 • NL' WNL° DLNSlvl PHOTOVOLTAIC � WARNING WARNING FAJ ELL( I���i �� ������� HA E) _ _. vCll€ TE: CAUTION: T _ DC C�f:SC0t''JECT NORMALLY r.R()LsNc�FDL;�r�DUCT��RS SCLAR ELECTRIC SYSTEM CONNECTED �(} rNE Iry � ON U" rCRS OF THI � MAY BE 1IN�..faC"�UNDED,AND ENEROZ 1 PJ,f0T0V0L1A1 SYSTE d1 ARE UNC.ROUNV3 -t, ,1Boni 4 �# . tt �' i • i r• , WAI`NII DUAL POWER SOURCE MAIN PV SYSTEM An WARNING PV SYSTEM DC DISCONNECT /� �y�y �j,�*� ,r� SECOND SOURCE IS PV SYSTEM /� C �s C N �+� Fl F%,TRiG�iL SHOCK ,Hr�'.AR[ /""{ I N 1 �! 171 �i� OPERATING i�URRCH-1 Ji^'I 5.+° D I +A:i {. r N !'ll E 4rT � �� I)L7 !NC�T T(Tk!lC;M T Ffc�iP�GtAI ,* ELECTRICAL SHOCK -HAZARD !OPE RA TIrjG VOL T AC, L Lc�AnSIDES7 MAY E�� ENEPOSITION t _. .... -.. kiA�S.I�,9Llta,31��TEh1'��4"�LT&f rt•t .�! (N'-1� tEi� POSITI�i°d TrRMiNAC-9 ON-RgTH LINR VND i i{_1LiY C: RCUI f ' Lai si± N I + CAUTION: • t. LOAD SID" MAY CSL EN( RGIZ� D {� i • : - • • • • IN 144 OPtrs i'()'SlI!ON SOLAR ELECTRIC SYS iEh4 CONNECTED WARNING: A plat t�[ �^+ DC VOLTAGE IS ALWAYS PRESENT .+-y �ryy � �y �� `u Y i AR N I Iii V WHEN SOLAR MGt�iiJlLES PHOTOVOLTAIC Z..i`LTAIC 1� 1! OPFRATIt�v� LTAG`. M= ARE E?tPfiSEr3 iit SUNLIGHT �{ "� E r ' •. ti ON11 1i 0P4 TJ1iGACFRv0i'c Y� TURN OFF PHOTOVOLTAIC AC DISCONNECT AC DISCONNECT PRIOR TO ? 1�d Yui t��uT MAXI UMCCI E T SOLAR DISCONNECT' WORKING INSIDE PANEL RATEUACOPERATING �URi I�T ,HQRT^1RfU1T^UJ T Airs C IRRT �1�A RTCCA- , PL}TR FR,u "z#Gi E P�iGti t � �. •. tt W ED AC OPPATINGkOLTAGE ?Ia. r'T�. ma T a �tT!u1j�� T N WARNING MAIN PV SYSTEM E II IL SHOCK LR PHOTOVOLTAIC C DISCONNECT T DISCONNECT f,101MUM SYSTEM VOLTA c 00 NO, I TOUCH I ERMINALS, f ERMINALS ON C OTO LINE AND LOAD SICES'MAYPEEENERGIZF0 t IN t F O "I N P4"TS.TK)14IF � t. � .,• tt � � i♦ NUMBER:SHEET 25 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency Circuit Noof Current q Y 60 Hz . Conductor Conductor Conductor Design OCPD OCPD Conduit Conduit Conduit Size Reference Circuit Description Voltage -Line 1 to Neutral 120 V ID Type Material Size Current Type Rating Schedule Carrying Conductors Type and QTY Voltaeg - Line 2 to Neutral 120 V CIA PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC 3/a" Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A co -2 3 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 16 A D.P.C.B. 20A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Module Model Number: Q.PRO-G3 265 EQ -3 EQ -4 EQ -6 Existing Meter Maxium Series Voltage Allowed: 1000 VDC EQ -7 Temperature Coefficent - Voltage -0.28% per oC CO -1 CO -2 CO -2 Temperature Coefficent - Current 0.03% per oC CI -3 C1 -4C14 EQ -9 Temperature Coefficent - Power -0.38% per oC EQ -1 EQ -2 CI -2 Junction Integrated Specifications at STC Box Disconnect MNew Existing PP Power - Pmp 265 W Solar Electrical MPP Current - Imp 8.69 A DC AC Service Service MPP Voltage - Vmp 30.79 V Optimized String of 17 Modules Short -Circuit Current - Isc 9.28 A —____ ___}__ ______ ______ Open -Circuit Voltage - Voc 38.52 1 V I Temperature Adjusted Inverter m6 Vmp - Min 30.35 V VOC - Max 39.60 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P300 EQ -5 Rated Input DC Power: 300 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE. SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ 2 12 EQ C12 Component Model string limitations apply, based on the Inverter Selected. ID Description Manufacturer Number Notes Inverter Input Bus Voltage at 350 V P300 Power P300 Power EQ -1 Solar PV Module QCell QPRO-265 See Module Information Specified Interconnection Voltage: Optimizer Optimizer EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ C11 EQ I.1 EQ -3 DC Junction Box N/A N/A NEMA 311 - Outdoor Rated Minimum Optimizers Per String: I 8 EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Solar Solar Inverter Information Photovoltaic Photovoltaic EQ -5 Inverter SolarEdge SE38000-US See Inverter Information Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 38000 -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker - NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 3800 W EQ -8 Meter After Installation Maximum AC Power Output 4150 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current 16 A at Specified Interconnection Voltage: Bu'ild'ina #13 U W 0 a BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E — 13a SHEET NUMBER: 26 OF 38 r Box / Circuits / Enclosures F) I Part 6 PEF, CSK 4v 'y PER NE'11- I I 027(Q & DSHA 191014W0 Part No 5,96-002— PE R N E C 6(k, 56(B) I P ar t No 5-11- OC13 DC Disconnect / Breaker 1 Recombiner Box PERIFC 605 11 1, IFC. 605,11 1 4, NEC 6-A,) 15& NEC 090 14K)"-1) I Part No. 59f)1 Q38 PER NEC 690,39(F) IPart No 5%-00258 NEC 690,53, 1 PA No, '59,65-00241 FOP, MAKKING BACKUP SYSIEMS Part N o, 596-00240 Z PHOTOV06"LTARO.", REQUIREMENTS NEC 2011 Article 690 and IFC 2012 Adhes'I've Fastened Signs Adhesive fastened signs may be acceptable if properly adhered. Vinyl signs shall be weather resistant. IFC 605.11.1.3 !, n m o c m ir mo m & i o voix, n n MORTH SIDE OF BUILDING TO BE INSTALLED ON CIRCUIT BREAKER ENCLOSURE: THIS EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES, EXCLUDING MAIN OVERCURRENT DEVICE, SHALL NOT EXCEED AMPACITY OF BUSBAR. BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: 111@00to"If5,A f4 IF,',605,11,1,4.,N 1 6% 53 RE R N EC 6 9D, 14(CX 2) j Part No. 596- W39 .00243 -14 X" E Bu'ild'ing #14 SHEET NUMBER: 27 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency Circuit Noof Current q Y 60 Hz . Conductor Conductor Conductor Design OCPD OCPD Conduit Conduit Conduit Size Reference Circuit Description Type Material Size Current Type Rating Schedule Carrying Type and QTY Voltage - Line 1 to Neutral 120 V ID Conductors Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %11 Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A Co -2 3 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D.P.C.B. 20A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Module Model Number: Q.PRO-G3 265 EQ -3 EQ -4 EQ -6 Existing EQ -7 Meter Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent - Voltage -0.28% per oC CO -1 CO -2 CO -2 Temperature Coefficent - Current 0.03% per oC CI -3 CI -4 CI -4 EQ -9 Temperature Coefficent - Power -0.38% per oC EQ -1 EQ -2 CI -2 Junction Integrated Specifications at STC Box Disconnect MNew ExistingPP Power - Pmp 265 W Solar Electrical MPP Current - Imp 8.69 A DC AC Service Service MPP Voltage - Vmp 30.79 V Optimized String of 10 Modules Short -Circuit Current - Isc 9.28 A ----- --- --- -----_ Open -Circuit Voltage - Voc 38.52 V Temperature Adjusted Inverter lip Vmp - Min 30.35 V VOC - Max 39.60 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P300 EQ -5 Rated Input DC Power: 300 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE: SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ2/C12 EQ2 Component Model string limitations apply, based on the Inverter Selected. C12 ID Description Manufacturer Number Notes Inverter Input Bus Voltage at EQ -1 Solar PV Module QCell QPRO-265 See Module Information 350 V P300 Power P300 Power Specified Interconnection Voltage: Optimizer VOptimizer EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQC11 EQ 1_1 EQ -3 DC Junction Box N/A N/A NEMA 311 - Outdoor Rated Minimum Optimizers Per String: 8 EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Inverter Information Solar SolarEQ-5 Inverter SolarEdge SE3000U-US See Inverter Information Photovoltaic Photovoltaic Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 3000U -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker - NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 3000 W EQ -8 Meter After Installation Maximum AC Power Output 3300 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A Bu'lld'ing ° 'CON,fl• �- •' �GE:N loo e m ' �- a .� r o.��5 :e gyp'•• 'tOR;rJ�;:' '•'•....,.s•'' XV 0 //llllll�` BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E -14c SHEEP NUMBER: 28 OF 38 • • v Aft, ! 0 aQ �v MI°�V`v` f 1 41 \ WWI 4 MENUr- 2 lr �I v � v • W j ,re �. �� j� a s i a •i i i �` � '-� .i � o • •• i• a i i • i s � � .. > ..rte` t z .., '� i � � • � a ■ ., i i • W, i . a• ! . i . i i a a i • iwiiirALc. i • • • i f PHOTOVOLTAIC POWER SOURCE' WARNING DUAL POWER SOURCE FA om"RgING /AA JAFJ WARNING WARNING %'l • : • t • - SECOND SOURCE IS PV SYSTEM - ELECTRICAL SHOCK HAZARD EL �f IIIc ��� ��A�A�� e � • DC.I NOT TOUCH TERk°it ,� cs, THE DC CONVU1, zORS OF TI-a2i N4,070 VOLTAIC POWEP SOURCE GROO ND FAULT IS iNOICATED, � iE7RIOINALS0�•BbTJALjN7.44Z"I PH0T0t+OJAICSY$TFNIARE UN£_ROUNDED:�ELV i;')UNDEDCONDLIf TORS L .AD SIDESfa14� E3F'F`gFRGi/~D AND Vk)ILSEENERGIZ7Ei CAUTION: SOLAR CIRCUIT •, MAY PI uNCiROUNDEDtNNDENEFGI ED CAUTION IN THE OREN Pi aTIQN • - t : - � FV 5YSTEM CIRGJtT SREAKER IS 13ACKFED • • • • • • • i / WARNING: WARNING 141 DO NOT DISCONNECT . • . i TURNS OFF PHOTOVOLTAIC LLECTRICAL SFiQCK HAZARD UNDER LOAD • AC DISCONNECT PRIOR TO 1-10 NOT TOUCH TERMINALS_ f •• Ii - lA � �N� INIS IDE P. i SEL Wr AI wA r it G A PHOTOVOLTAIC AC DISCONNECT TER3IINAL i ON BOTH LINE AND i3 • , , . ­_ LOAD SIDES klAY BE ENE R�i�C3 • .. TAIG AC DISCONNECTFL E 7,1Rlt�Al. $i��f�L.K HAe RL) . £ � � m x� �m�u �r. � a�c . Re THE C -P-FN POSITI.O�! PHQTC3VC7L M A Dti L7 FAUL 15 INDICATED, NORMALLY GR'?i.(P DC D CONCUCTORS r - 1-94Y' RF LsNGROUNDEE3;cND FNERhI?EI: + r ti •� WARNING: FVJ WARMING �,�►� TURN OFF PHOTOVOLTAIC • • i /� . • * ELECTRIC SHOCK ZARD AG DISCONNECT PRIOR TO tHL CC,0n�.T�)RsOF I 4 1� ! • ' _ • • :. . f WORKING INSIDE PANEL PHUT %f0LTA0.'S STE��l�.RELIa��>ROUNDED � • - AND MAYBE ENERGIZED • PHOTOVOLTAIC "A WARNING FAI rA WAoR %It�G �i�^* ,�^. 4U 1,1 L C TRK A �,H, � ��,ATAR CAUTtON1: • IF L/ti✓ �IS �T 4Gci ,I0FAUL, , NDICATED ELE£TRC SH(N.. HAZARD NOR!I Al L`:' GROUNDED €. ,NBLII Tci� SOLAR ELECTRIC SYSTEM CONNECTED C.C1NDLICTORS OF TFI ED l0 ONGROUND. • • 1a1r1t` f E ill i i LAIf 1i AND Edi F::.` i l l T,iE OC rf • MAIIti! WARNING PV SYSTEM FAQFAI 1A 8/29/2018 PV SYSTEM DC DISCONNECT WARNING DUAL POWER sc�ua p ,�+ �^+ SECtiNO SOURCE IS PV SYSTEM /�-�+r�IS�.r►ONN ECT ELECTRICAL SHOCK HAZARD _ LCD NOT TOUCH TERMINAL REVISION: WARNING �''± RAT1t� CLlF�rz6LdT_ 7�Yf"' RNING � TEI�i3•`1INALS ON 50TH LIN Ef NL) RATING VOL � .• r • � LOAD $IBES %lAY DE ENERGIZED ELECTRICAL SHOCK HAZARD gIL4'A rE%1= T. G • . IN Tri- OPEN ap Nor TOUCH TERMINALS. r� TERMINALS ON BOT" LINE AND ," URRI SN' LOAD SIDES MAY BE ENERGtZEV Il i € . 1 • - :T 0 1 CAUTION: IN THE OPEN PUSII iUN SOLAR ELECTRIC SYSTEM CONNECTED DC VOLTAGE IS ALWAYS PRESENT� WARNING: �y WHEN SOLAR MODULES PHOTOVOLTAIC �t��It�tr �P �t,4�TIII?�w�IG� (�i�� • '' ARE EXPOSED Tb SUNLIGHT 4_� , 'isl 4 I T � `'w 6� �4Ii�,r P lVtjl�l v 6� L � • �� RAX �t'E P i i'lf ;yu TURN OFF PHOTOVOLTAIC AG DISCONNECT IJANMUM AC P lif AC DISCONNECT PRIOR TO �,IIII Y,TE�� T�`°x �� • . P.i 1 l� CCURRE � � SOLAR DISCONNECT WORKING INSIDE PANEL II','�UR E T„1111101111111rr1 i ER RENT {i E 1 i� '� E ROTE�I( a�.�,�T� rg E k,I4, � ' ,Ai ED OPERATING \10L AGGE �R�� f F 4 ry E �; n( •WARNING [� • MAIN IAV SYSTESHEET TITLE: M 1tt{tl� LICti'tt11� I�LI.ALR`� �•i . r o>r �� was R4TE`D H�'TC[RCU�TC RRENT� ELECTRICAL'SHOCKHAZARD PHOTOVOLTAICACDISCONNECT DISCONNECT ,,{{yy�� ,l %I ^Ssrb ;;A r}L, -{fry`s DO NC�T TOU.C-I TERMINALS, .���"SI i�iR � v..E{ i�.�`i'�Vi� TERMINALS t* BOA! LINE AND � � • i � 11• . LOAD SIDES MAl+"Cas_ EM1JE€i(aIZEG r4 • 1ON E - 15 • • •r ia1 f 1'� i�lE OPEN F`CISi.Tt 4 Bu'ild'ing #15 SHEET NUMBER: 29 OF 38 ON 0 t GENy �o: 117�7 1�3 N111 - IL i r o tiv,- �. own - 2 1y .. Sti r r a r i r • i i ! i! a t FAI WARNING FAR A WARNING FAI tC PQ'4{'ttERWARNING ' 4��1��E iRNING OuAt. POWER SOURCE • ' ! • i /"� SECOND SOURCE IS PV SYSTEM L LLLC-fRICASHOCK HA AR[� � • • • • _ ELECTRIC i>rt. _ �_ -'s r; F`sC� + c .,LiT£:TRICAL:`a}-1CCK HAZAR€� � D(D NOT TOJCi i TERMINALS, 1'HL DC CCNU TCHS O THI S C POWER SOL W AGROUND FAULT IS !NDiCATED, Irrmtv!1NAES ON ROTH 111Nt_ ATS PHOK)VOLG (:� SYST ?#ARE t.I�li<;t2OUWII€;L�; �s��� �,e��; ���� � ., �y ��� �.�«c N�F�RMA11_l'' GROUNDED iMOCd DLIC' i�tfi'� I..;)AD `SIDES fltAY RP t=P1t=:i rI E%3 At'40 Wri' BE ENEf GIZZEt �S1,�i'` E 1:: 4lN{.i�0.�JNt3f::�� =r�N(:° F.. 7t..�(�I.'��7 • r � i r i CAUTION: SOLAR CIRCUIT CAUTION IN THE OPEN POSITION • FIV SYSTEM CIRCUIT ISREAKE�< fS EIACKfED • � • ' � • • • i Ir�1 WAitiNI�IG. _ ►A1 WARNING F'• i DQ NOT DISCONNECT TURN OFF PHOTOVOLTAIC - LECTFRIC AL SHOCK HAZARD UNDER LOAD � � • • C C • � n AC DISCONNECT PRIOR TO DID NOT TOUCH TERMINALS. WORKING INSIDE PANEL r,&j WARNING PHOTOVOLTAIC Ac c�+scaN TERMINALS ItgALS{ A c Tr 1_It AND LOAD SIDES WAY BE ENERGIZE IN THE OPEN POSITION PHOTOVOLTAIC AC DISCONNECT RICD tit i -1 im't11 t 1 L" I _TL? , •• +. t �_i ! 4-x.7 oµ -rAi;E � � S p^{ p� pry pa p� g^' �^'(� �* � f MAY Sf,,-.1.1NI.. (it UN, t��i D, AND �.D. Ela C. R7GI717 f) es WARNING. FAI WARNING FAI TURN CFF PHOTOVOLTAIC 6 • . 7 • . • AC DISCONNECT PRIOR TO THE C���a��a����, ��� TI�7�: • w ! • ' - . . : • . . Vt1ORKING INSIDE PANEL PHOTO> OLTA� ,YIS TEM.kK'E LNGROMDE L • AND MAY RE ENERGQED PHOTOVOLTAIC WARNING �� WARNING F . (,fR �� �I � K IIA �� CAUTION HA7AR0 CTC DISCONNECT �1�t����LLa, �F� �rl1f �,�� .€�€�� Sof-Ah EL GTRI�SY5TE �0NNE TED $ ,itl L iF t-'�Nz�i1 tcA'ab lfia . Mai°" BE Fft,E'OU.'aJ.b�.f.3 E- RGI7 E[) vv i�p PV SYSTEM DC DISCONNECT SECOND DUALP04YERSOURCE MAIN PV SYSTEM G� WARNING SEGONCS SOURCE IS PV SYSTEM AC DISCONNECT FLECTRICAL SHOCK HA7ARD WARNING �"FiATitlt3i..i1i RER _ + � TER4�IN,,ALS ON OIti 111""h" DF RATINIO V01_TAGE + LOAD S IDES MAY BL- rt E i ELECTRICAL SHOCK HAZARDE1Ak.ih9t1iLi5Y TE".ti'C31TAc=,- .�� ,+ ,• •+ er�7Hr- O'ENPOSDO NOT TOUCH TF RMINAL& ?It21� TERMINA1L3 ON ROTH LINE AND SfiOR f DiRCUI t CURRE,N7 +�4 LOAD SIDES MAY 6E ENER(AZLIi � �Y � r . : CAUTIO IO 1N THEO ENF . SOLAR ELECTRIC SYSTEM Ct?NNECTEIJ �� p XLTAIGE IS ALWAYS PRESENT FAR WARNING. WHEN SOLAR MODULES PHOTOVOLTAIC0M!�AL'En;R 13G CbOC GE ROM � AyeEXPOSED TO SUNLIGHT QMIRAL C TURN OFF PHOTOVOLTAIC AC DISCONI N�CT L1114GP 6ftr SOLAR DISCONNECT AC DISCONNECT PRIOR TO MK�9,01 VFEMVOLKE . I � i1 CURSE �- �hCR-1 IK,UFCCURRE T WORKING INSIDE PANEL RfiIEDA OPERATI CLIRREN - S I C� iii E F S ISBN II,,K R z-ED)U � PLI iRRENT Of { R 00 LEER TECCTUDI � r� T ELS AC EATIG i'tl �,; 4 �_ FIRM: G,TR� E l ifs .M::LEtt WARN I G R ..SHEET TITLE: E �,RAT_Ct i."NER �NGtQJ4 ® MALI PV' SYSTEM W1EID T [RCUITCURRtRT LLLLCIRIL.AL SHOCK RAZ -ARID PHOTOVOLTAIC AC DISCONNECT DISCONNECT MAXIMUM TE VOLTAGE DONCI TOUCHTERMINALS, 'I ERMINALS ON BOTH I-IKE AND LOAD SIDES t0AY BE h* RGIZED + �q , •! INTHEOPENPC-, "ION Clubhouse SHEET NUMBER: 31 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency Circuit Noof Current q Y 60 Hz . Conductor Conductor Conductor Design OCPD OCPD Conduit Conduit Conduit Size Reference Circuit Description Type Material Size Current Type Rating Schedule Carrying Type and QTY Voltage - Line 1 to Neutral 120 V ID Conductors Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.28 A N/A N/A CO -1 2 PVC Y4if Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A Co -2 7 x 3 PVC 3 x 1-1/2" Applicable) 120 V CI -3 Inverter Input Circuit THWN - 2 Cu #8 AWG 45 A N/A N/A CO -3 3 PVC 31' Voltage - Line 1 to Line 2 208 V CIA Inverter Output Circuit THWN - 2 Cu #8 AWG 40 A T.P.C.B. 50A Voltage - Line 2 to Line 3 208 V CI -5 Service Feed Conductors THWN - 2 Cu 2 x #2/0 AWG 280 A T.P.C.B. 400A Voltage - Line 3 to Line 1 208 V EQ1 EQ2 Co Environmental Assumptions Optimized String of 14 Modules Bo ner EQ3 Minimum Annual Temperature 20 C Optimized String of 14 Modules Maximum Annual Temperature 35 C Optimized String of 15 Modules PV Module Information Combiner EQ3 Optimized String of 14 Modules Box Manufacturer Name: QCell j Optimized String of 14 Modules I Module Model Number: Q.PRO-G3 265 Optimized String of 15 Modules Maxium Series Voltage Allowed: 1000 VDC — Combiner— Box EQ3 I I Optimized String of 14 Modules I I Temperature Coefficent - Voltage -0.28% per oC Optimized String of 14 Modules I I Temperature Coefficent - Current 0.03% per oC I I Optimized String of 15 Modules Temperature Coefficent - Power -0.38% per °C III CI -3 CO -3 Combiner EQ3 Box III EQ -10 CI -5 Specifications at STC Optimized String of 14 Modules I I I CO -1 EQ -8 MPP Power - P m p 265 � � / Optimized String of 14 Modules I VV r— DC Wireway MPP Current - Imp $ 69 /► Optimized String of 15 Modules — ---- J i I !'1 r Existing MPP Voltage - Vmp V Combiner EQ3Meter 30 • �� Optimized String of 14 Modules EQ -9 Short -Circuit Current - Isc 9.28 A Optimized String of 14 Modules I Ili I I I I Open -Circuit Voltage - Voc 3$.52 V Optimized String of 15 Modules I I I I Inverter I Inverter I Inverter I Inverter I Inverter I Inverter I Inverter I I I I I I CO -2 Existing Temperature Adjusted Electrical Combiner EQ3 i I i i i i i i i C I -4 service Box Vm - p Min 30.35 V Optimized String of 14 Modules Optimized String of 14 Modules I I DC AC DC AC DC AC DC AC DC AC DC AC DC AC VOC - Max 39.60 V I I I I I I I I I I Optimized String of 15 Modules I I Integrated I Integrated I Integrated I Integrated I Integrated I Integrated ( Integrated I EQ -7 DC Optimizer Information —------� i Disconnect i Disconnect i Disconnect i Disconnect i Disconnect i Disconnect i Disconnect Combiner EQ3 New Box solar Optimized String of 14 Modules I Service Manufacturer Name: Solar Edge i Panel Optimized String of 14 Modules AC WI reway Module Model Number: SE P300 Optimized String of 15 Modules Rated Input DC Power: 300 W ------J I Maxium Input Voltage 48 V EQ -10 Z EQ -6 Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Equipment Schedule Power Optimizers to form what is otherwise referred to as an Component Model Maximum Output Current: 15 A "Optimized String of Modules". Description Manufacturer Number Notes NOTE. SolarEdge Power Optimizers ONLY to be used with EQ -1 Solar PV Module QCell QPRO-265 See Module Information SolarEdge Inverter, as specified in this drawing. The following string limitations apply, based on the Inverter Selected. EQ2\\[/C12 EQ2 C12 EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Inverter Input Bus Voltage at EQ -3 DC Junction Box N/A N/A NEMA 3R - Outdoor Rated 350 V P300 Power P300 Power Specified Interconnection Voltage: Optimizer Optimizer EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Maximum Power Per String: 5250 W EQ C11 EQ 1-1 EQ -5 Inverter SolarEdge SE14.4k-US See Inverter Information Minimum Optimizers Per String: $ \;:EQ -6 New Solar AC Combiner GE See Page EQ5 for Detailed Specs Inverter Information Solar Solar EQ -7 Existing Electrical Service N/A N/A 400A Main Breaker - 3PH 120 - NEMA 3R Photovoltaic Photovoltaic Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Manufacturer Name: Solar Edge Module Module EQ_8 Meter After Installation Module Model Number: SE 3000U -US EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ6 for Detailed Specifications Connector Nominal Power Output 3000 W EQ -10 New Wireway N/A N/A NEMA 3R - 10" x 10" Maximum AC Power Output 3300 W Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A Clubhouse- C3 d J U w 0 Of Cl - BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-1 6a SHEET NUMBER: 32 OF 38 Existmin Service Detail Connection to Existing Electrical System via insulation piercing splice connectors. `,se4;tOND a�lrrrri.,s d U W U n BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-17 SHEET NUMBER: 33 OF 38 New Solar Service Eauipment Specifications Prid uct #: TM1212RCU SPECIRCADONS C. at egckry Sft le Ph as e - U SA 1,2" Space Feed Door G S-A, C o m p h a c e imfpzll�� Standard 22 125A ain Breaker List Price 5512 LLJ D CD Of a_ BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: Z at, E-18 a� �A IJV o �U z LLJ LLJ LLJ D CD Of a_ BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-18 SHEET NUMBER: 34 OF 38 I �777777,3 i .:toutput Al 77 -is 1.1 :.J-0 i i �x T ,' WT do XX UJ m m n C, I °i Pm I w �g r.«. .,...n.�.� _.._ .....ate. ��.«...� - to, ow AQ W «. c 3 mr Al 77 -is 1.1 :.J-0 i i �x T ,' WT do XX UJ m m n C, I °i Pm I m N •. P-7 �0 � •'•1•reurr' �G\� 4dV' I E - 19 c a � CQ V) I m N •. P-7 �0 � •'•1•reurr' �G\� 4dV' U W D O r BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: Z E - 19 c a � CQ V) 0 o z 0 D U W Q W �q o Of Cl- .9 " Pcl U W D O r BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E - 19 SHEET NUMBER: 35 OF 38 DC Opt111 imizer Specifications tom• ,�dg�l P300 / P400 / P405 ModuleAdd-On Z 3. For NorthAmerica .awwo INPUT� _. a. �......... __.__ �. a Rated InpUt DC P(Ylver,' 300 400 405 W Absolute Maximum Input Vo Cage � U ('j ( j° �'` P300a1+1 1 1rt4.+� ( E" � L LLJ ............., .... ,..�...... ,........ .......... ,...��,............. ...`4�d�.... . MPPTperaCig R•angE 8-i -80 10 1 Maxiiinum short circuit CurrentAdc Max rturn DC Input Cum ............................. 12.5 Adc maxulm mcienc r ............................. .......................... ... 993 ...........,.................................... ' .... . Chrerv&ta a ate r + wm.__ II OUTPUT DURING ITPEItATii I I E I R OP __..._-_....- MI2ER CONNECTED TO 0 jERATING Sl�LARE GE Nta.xqnum Output Current15 ............ .............. ............ ...... ..........., ..... ....... ... ..95 ....... .... AdC kvaxArurtt output vo4tage 6 Vdc OUTPUT OURINOG STI D!! POWER OPT] NIIZER DISCONNECTED FRO W SOLAREDGE INVERTER OR SOLAREDGE INVERTER OFF) Safet � qui � e er �+e�` � tiiaer �Vdc STAiNADARD COMPLIANCE v �,.. EMC ECSC Part15 ClaSS B, IEC61 -6x v IEC610 iti-5-3 -t fclass. tl 3 f t IJt.1741 R.OHS - _ _ ___.._ W.... ___.__.._..____....___._.._._ ______.................____........_.....__....___._..._..__ . . ___. _ __.____.__.....__._.__.____._.. ___._.. _..... _._... _._ _ ___....._.._______ ... _... INSTALLATION SPECIFICATtONSa _ �_. � .__,. uo d4\ ` ` Maximo 'i A.w ..... ... .`..... '..'.._.' ;.....�� .� 1000 ...... .......... .............. .......... c ,' " PXXX-2 series 141 x 212 x 40-5 5.55 x 8-54 x 1.59 mm / in Dimensions (xLxH) i Pxxx-5 sues,mm/in 128x152x2F..5,� 128x152x35/ 128x152x49rr 597.it.ldll3. ............. 5x597x1_37 5x5,.�7x1..8`9 weight (including cables) . , .Pxxx 5 series .... . .11-7 ...........I . .........930 2.05........... I.......—.93012-05.......... f l lb ..�iput -pn ctur MCMI C r>n ... ...... ............ .... ................ )utpii mire'T.ype / Conrkectw Doi isle Insulat=ed; MC4 Comp i :pimp tWireteng rh............. S;?'.3. ........... ... ............................ ' , ... cpeti Tepeeatre Bair......# - - +185..? .� ., . Pxxx-2 series IP65 / NEPA" Pf0te4_tk0 akin......, 9P3l'xx-5 senes, .. . IP 68 I NEMA6P Up to 25% more sneer tolefaiKe topartial sMdirkg Flexible sWtvn design for rrk&ximum soace utilizzaboon Fast instaRation with a sagle bolt lex n . tion mainteflance with module lvP I mthnitoring liod le -l' l vultage -s dokevn for Orvqsaller and firefigh'te'r saf e USA - GERMANY - ITALY - FRANCE - JA _ CHINA - ISRAEL. - AUSTRALIA It,ftad STS J* arup to ls� #flo , PV SYSTEM DES FGN USING A SOLAREDGE INVERTEFM hf,,, i urn :String Length (,PoweT,Opr izer:sl Maximum String Length Mrrii�ti per Strt.................. . ................... ... ParailIel Strings of Different Lengths 60h Isom 0406d tam&Ta i SINGLE PHASE I THREE PHASE 206V' THREE PHASE s 18 25 25 50 5250 6000 12754 W yes 28 S/0'M tttt U W D O C*rl Cl - BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-20 SHEET NUMBER: 36 OF 38 Z 3. .awwo a co pa U U L LLJ a w o. a U W D O C*rl Cl - BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-20 SHEET NUMBER: 36 OF 38 �;_ to] ft a-* IT Wim U54"k •- G E R N ANY - ITA L- E A Ci -E -> PAN -CHINA - A S R A .IA -~ "1 H E T HE R L NDS -ISRAEL Inverter Specifications www.solaredge.us I ng le Phase Invene rs for North America sold.r =4" SE3000A- US/ SE 38GOA-US/ SE50GOA-US / S E,60GOA-US 5E j A"15 ll5 ; 5E2�� 5 SEII) CJS 5E11 US _ __- ® .m..m......�." �,�,,,�,. ..."..... ....�."m... ......... ......... UTP Nominal r Output 3 76W 114M 'VA Maxx AC PowerClutput 33= 41505400 8350 22M VA ..<.,..<...,.....>...............<....,..,.,.I..I......1.,...,,.,,....,... .........,. . .,.. ..,.... � 5r1.5CI � I �# A GutPut Voltage ink. -Nom. -Max -01 183 - 208 - 229 Vac AC Output Voltage titin-Nc .Wax 211 2 -264 Vac E fr ter - lctrrt 4204 5'9-3- WS (with KI t,ntr , ,:, ?. „,.. .... 16 ax.Cont Continuous crt rt 12.5 �. ...,.. ....<. ...,<....�._...., 25 32 �� ..,.. ....,....�. �5 A ....., 2 '��' ld 21 2� 42 GFDL Threshold ............ < . ...... .. ......... ... , . .... . 41�ttir nr"Irr -..sb4hreshald reqs .. ra sci r u d` ,..,..<. ........ >... .......,....., ......... ItaI��. Input age 50D We ,MoT_DCIMptit ' .. ............. 325 # Z08V,I 3W 4(1 j.... , flak. . . am InpEut Currentu1 9 5 33 � - Is Z'3 � ( 3� 5 Adc . . Iax" Input 51ho rt Circa rt Cu rrent 45 Adc R r'. pi!$flasrt f atact n ....................... .. we's < .,...., .......... Grour E ai t Isolati s Detection Setns Maximum Ilr r r Efficiency <.. <..... 7.,a..... 31t��.,.. 9,9..3..... 92.3..<.. ..<. ..,... 9�, ... <. ��..... = �Vtighted EfEciency 97.5 975 97- 97-5 .......,.... <. ... ..<<. .. ... .. .. .. .><.. ., ,. ... .. .. ... .. ... .... ... ,. ... ., .. E..... <.. ,. ..,. ... ... .. <,.. .... .. ,.. .<. >. .. ., .... >..< <. .. .. .. .. ,. .... 2_5 e A W DDITIONAL FEATURES ... pported Cwnmunic2tionl r .�. 9 2 E&,e et Zi _....._...._.. ei�enue Grade Date ANSI C.2 1 < on; �zp�,d 5hutda n— NLEC 20,14 690.12 functiorR,21ienable when Sola -Edge maid shoi3own ki'tisimst2liedW STANDARD COta1PU' NC; Safety UL174L WISM, U1.1998, CSA 22.2 ncJ rrtariri rests tEI 15 Emiss .... , IN LLAN SPECIFICATIONS A r�ricrt r Is t e� r e 3, 1 AWG 3,a' mi i um /8-3 AWG DC input conduit size it of stringy 3,,W miniir� / 1: 2 strings j 16-6 AWG 3/47 urs , 14 strings j 14-6�i.41 Uimen s write Said Switch3 ,5 X 12 5 x ilk 5 in . I'ss U is .5 �r 7.2 / z 315 z l 5 3/ 5x2€rt _.. gA de let rthSafttti5s tfix 5L21232 ....,.....,.,.,.,..5&7j2* 1.....,...,. s is ,<. Natural convection Cooling Natural CoaveutioR � and internal E Faris fuse bie): ianfuser ..........................................<.....,......,.,.,.. ..male,,...,.... Nail 425 t 50 d&A Mire. -Max.. Operating Temper _ 13to+1 C-25toi ( to +60 f vers p it Fop` Protection Pad% NEMA. 3R M i mW be WtoNUA 4 A ta- ,� ✓ •� v 100 %2�0 F�0RtCP�' U W D U BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-21 t 4 � CV �n O r m �U U t] Uj Q a_ �.w .. ra U W D U BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-21 SHEET NUMBER: 37 OF 38 Insulation Piercin Documents Wire size: /0-3 G (Main) 2-10 AWG Amperage Rating., i 190 (CU gimps) - 150 ,L ,imps Dimensions: Im Connector Sr)ecifications No need to strip wire - No tape or :over needed - Exclusive turbo spacer Deeps tap side open while main conductor is being tightened Splice, Tap Power Connectors Thermal P''Ia tic Fiber Reinforced Thermal P'l a sti c Mounting: Camp Te rater Rating: Environ mental and n M UL4,068 Listed U W O n BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-22 SHEET NUMBER: 38 OF 38 Zer IM, ke a CQ 0 �o z 2 U W PQ Q a - W � .� PC U W O n BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-22 SHEET NUMBER: 38 OF 38 `ems r'r E t °•'� V. , / a, L A4 0 ,,., -C� r !b✓6: ice.-.: �0 Y.. Rl Heiier-mbw3nhTVbr u e +� u., 2 i r +J A I C P3 LT/ -k y u:WF' {K' A +E Oma r. S"STE M v "A tau /W"� ML�DPQ f Narci =. PPE Re uitet# "''yam/O/O/// +M M y — Q N NW Mut°' v7 t 1 rr J 3r'FF,+_. • r R _ IJV >'OV �+;'> QUIREMENTSz NEC1 Article 690 IFC 2 °pQ P, r l/9 Fastened aw ,adhesive fastened signs may be acceptable if properly adhered. Vinyl Signs shall be weather resistant. IFC 605,1 1.1..3 ar NE ittC X61 °moi // / /f �✓ % !�10 los SECOND SERVICE DISCONNECT ���s,/, The markings shall be of sufficient ON NORTH SIDE OF BUILDING Tt dppra � io'oxn 'Yt th r,o-te ar it tJ ttat UJB =1x /- i o :� ;,%hoto w} tr iat—Pkr.x nanrn rhe a je . r i f,q F ?3Q }NEC2 2i 5 349 durability to withstand the !_2f!abet t"!e='�*ded I�sit7',�Ft'i baq_ --d o the pr: ea "cope. argl Ji_;. ,.,.... ,, ,.....-. , N iii. A) I PartNo 5&00 r Y,i11r��rzrr,w:x.,.n THIS PANEL FEC► environment involved. NEC 110.21 FROM INV I MAX AVAILABLE FAULT CURRENT, 46.552 AMPS *NOTE Ele t11rujl Serric,� equiPrnent rniu t be fi�,d rn'x .(j per ttr DATE 2115112 : ('eEC� ire,,0, 1t E1�,rv�f'{";i,�ri �l%tIa"�JIr�.1 �.�C if��rti,Re fC:�.+'r,-r 7f,,:ir1 `t'dEl_ -t':)?S.0) 1 Part ir(o 55� C-'d.i�_: � The materials used for marking hall be 7 . ..,...., «.,,.,, .,... di^411nctgpl u t 14 rrwjLr�m r.tr�ri iir a rrl,,Ar1 r e:, k },,.,�1�_»ilitie__ucha dk�itn(iryandaFosytcrj)TN,-indudi" � NEC11024(A)IPart No55&00300- reflectlVe, weather resistant and suitable nr� Pashan 'nfoi�r,. t,:;rt;r) ldb?hn4 it �F for the environment, IFC 605.1 1.1.1 Combiner Box / Circuits I Enclosures EMT/ Conduit Raceways '"(`/;' R ive Material Re uir ) ' Breaker Panel ! Pull Boxes ' o ' ' WARNINGSECOINO SOURCE IS PV S TO BE INSTALLED ON CIRCUIT WARNING4• NOISIAldPEPNE�C6%,31(E)(3)&IFC 615,111.2 � � w BREAKER ENCLOSURE:PER NEC 705.12(D)(4)& NEC 69064 Part Na 59F, X206 Pat Na. 596-00231 4 i ; . ,� THIS EQUIPMENT FED BY MULTIPLE PERNEC P IN THE QP[J-1 POSITION• NE.. 690 �t Na 596-4!32 7 . )I = SOURCES. TOTAL RATING OF ALL PER tJEC 6C) 35(F) I Far€No 59Fi 00255 _ PER NEC 690.5(C)I Pat Na. 596-00234 PER NEC J17(4)IPart No. 5 _c 2 PER NEC 6 i_ 1(E 3)&IFC6451I 12,605.11 14 PEF NE( 7a> 12(D)0)�&NEC 69064 OVERCURRENT DEVICES, Part No 596-00247 WARNING: Pat Na. 596-00236 EXCLUDING MAIN OVERCURRENT Building 1 Structure inverter " " r • • Ir DEVICE, SHALL NOT EXCEED TURN • PHOTOVOLTAIC ,� AMPACITY OF BUSBAR. oW. ER LOAD « « PER NEC 69t3.33(E}i) I Pert No 596-00244 CAUTION DISCONNECTAC ! PHOTOVOLTAIC ° DISCONNECT W W.�. WORKINSIDEING PANEL PHOTOVOLTAIC AC DISCONNECT Yh;iWN.ci'f t4wA WihY YIYVfN 16A : T PER NEC 11027(1) &OSHA 191(11450(7) 2aov 16A .. Par[ No. 5 t 23s PEER N€C 6'94.17(4) Part No, 596-002133 PER NEC 690 54 I Part No 5 -00239 I 240V moil PER NEC 690.541 Part No 596-00239 PER NEC 690 5(Q I Part No 5%-00234 . 0 PER NEr 56fE? I Part No. 55&-00350 , �j TURN •J t IC Production / Net Meter Production l Net Meter• DISCONNECT • ! PRIOR TO •LLJ DC Disconnect 1 Breaker / Rearm bi nes Box (Bi-directional) O + • . oAin WARNING FAI %Cir! tt tRequired)PER NEC 110.27(C?&OSHA 1910,1451 LL ,t LawPart No 5r -GOZ35 PE R NEC' 690.35(F)1 Pitt No. 5` 6.00258 0 A" WARNINin. FAI'll CAUTION: Trim B +. Main Service Disconnect*(Reffect+ue,V,,3-erra;Regts+rp-d) BY: BDD PER IFC 6051 1.1. IFC 605.11 1 4, NEC 690.15 & PER NEC 69014CM, IEC 60511 1, IEC 605 11 1 4, NEC 690.14(C)(2) 1 Part No. 596-0023 i _ NEC 690.15 & NEC 690 531 Part No 5%-00245 PE R N EC 690 5(C) i Part N o 5`36 -00234 PER NEC 690 35F) PatNo 5%-002 II SYSTEM III U II �Mi� Cpl Irl - " � 1 • �.I _ DATE: 8/29/2018 i PV i!I DISCONNECT ' AC i SECOND# + + SYSTEM DO NOT TOUCH TEWAINALS WARNING10 3A PEP NEC 705,1 (Gi(4;&NEC 69064 aoovISCONN,ECT Part No. 5'36-00231 PERK€C 690.14(CX2), IFC 605.11.1, a REVISION: SHOCKSIDES VAY BE LECTRICAL a ; IFC 605 11.1 4, NEC 690.15 & NEC 690,53 soov Pat Na 596-x00243 15A x PER.NEC69017(4)1PjtNo, 5%-00233 MAY UE ENERZED AC Disconnect/ Breaker Points of ConnectionCAUTION:'' 1 VOLTAGE'"S ' iti ALWAYS '' 4' NEC 690 531 Part Na. 596-00241 q is it WHEN SOLAR MODULIESr ie i 240V PER: NEC 69014tCk2L IFC 64}5) 1.1, IFC 605 ? 1 1 4, ?WARNING: ARE EXPOSED • 10.3A 60 Hz NEC 6�?15&NEC 690.531 Part No. 5%-OJ245 PER NEC 690 17(4)1 Partft _ 2 soov r i 380ow SII _DISCONNECT TURN OFF PHOTOVOLTAIC PRIOR TO )f . i1 # 15A _ PER IFC 60511 1, IFC 605.11.1 4, NEC 690115& 16A WORKING PANEL 16A NEC 691114(02)1 Part No. 596-00237 = PER IFC 605.11 11 Part Na. 5%-00246 \ I 16A PER POE( 110 27(1) & L35Hk 1910145(f}(7) 240V Part No '1%-X)235 PER NEC 6%_ 521 RitNo 51* -00152 � r► NEC 690,531 PartNa SWO025B31116111110W among PHOTOVOLTAIC AC DISCONNECT DISCONNECT SHEEP TITLE: 16A r.r r 600V s 16A FOR tv1AR�IN'� BACQ1 51 LEMS 2aov PER NEC 690.14(0(21 IFC 60511 1, S�►�1.EG i)Ii G D1k�1�i0Y� x ".M _._ IFC (40511.} 9 N 15&REC69053 PartNo 5%-00240 ? PER NEC_ 69014(CX2il Part No, 596-0`0239 iir7243 A PERMI-1" ISSI IED SHALL BE CONSTRUED TO BE A u. LICENSE TO PROCEED WITH THE WORK AND NOT AS PENCE 17(,1IPar€Ncr 5b 40233AUTHORITYE-1 ` v-_ TO VIOLATE, CANCEL, ALTER OR SET ISIDE= ANY OF THE PROVISIONS OF THE TECHNICAL OFFICE CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT THE BUILDING OFFICIAL FROM THEREAFTER PrOUIRING A CORRECTION OF ERRORS IN PLANS, CONSTRUCT ION OR VIOLATIONS OF THIS CODE SHEEP NUMBER: PERMIT #� „•,��-- �/eZ 0,� 1 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Circuit Reference ID Circuit Description Conductor Type Conductor Material Conductor Size Design Current OCPD Type OCPD Rating Conduit Schedule No. of Current Carrying Conductors Conduit Type Conduit Size and QTY Interconnection Frequency 60 Hz Voltage - Line 1 to Neutral 120 V Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %4' CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A Co -2 3 CarFlex Y4" Voltage - Line 3 to Neutral (If Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 16 A D.P.C. B. 20A Voltage - Line 2 to Line 3 - V EQ -3 EQ -4 EQ -6 EQ -1 EQ -2 CO -1 CO -2 CI -3 CI -4 CI -2 Junction Integrated Box Disconnect DC AC Optimized String of 13 Modules --------+--- ------ ------ Inverter EQ -5 The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an "Optimized String of Modules". EQ212 EQ2 C12 Component Description ID EQ -1 Solar PV Module P300 Power P300 Power Optimizer Optimizer V EQ -2 DC Optimizer EQ C11 EQ (_1 EQ -3 DC Junction Box \�__c EQ -4 Integrated Disconect Solar Solar Photovoltaic Photovoltaic EQ -5 Inverter ••• Module Module EQ -6 New Circuit Breaker Enclosure EQ -7 Existing Electrical Service EQ -8 Existing Meter Enclosure EQ -9 Insulation Piercing Splice Connector EQ -8 EQ -7 CO -2 CI -4 New Service Rated Breaker Enclosure 1 I Equipment Schedule Manufacturer Model Number QCell QPRO-265 SolarEdge SE P300 N/A N/A SolarEdge N/A SolarEdge SE38000-US GE TQL100REP N/A N/A N/A N/A NSI IPSC4002 Existing Meter EQ_g Existing Electrical Service Notes See Module Information See DC Optimizer Information NEMA 3R - Outdoor Rated Disconnect Integrated with Inverter See Inverter Information See Page EQ4 for Detailed Specs 150A Main Breaker - NEMA 3R Meter to be Replaced with Bi -Directional Net Meter After Installation See Page EQ5 for Detailed Specifications Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information Manufacturer Name: QCell Module Model Number: 315 G5DUO Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent - Voltage -0.28% per oC Temperature Coefficent - Current 0.04% per oC Temperature Coefficent - Power -0.37% per °C Specifications at STC MPP Power - Pmp 315 W MPP Current - Imp 9.55 A MPP Voltage - Vmp 32.98 V Short -Circuit Current - Isc 10.04 A Open -Circuit Voltage - Voc 39.87 1 V Temperature Adjusted Vmp - Min 32.06 V VOC - Max 40.42 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P320 Rated Input DC Power: 320 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A Maximum Output Current: 15 1 A NOTE: SolarEdge Power Optimizers ONLY to be used with SolarEdge Inverter, as specified in this drawing. The following string limitations apply, based on the Inverter Selected. Inverter Input Bus Voltage at Specified Interconnection Voltage: 350 V Maximum Power Per String: 5250 W Minimum Optimizers Per String: $ Inverter Information Manufacturer Name: Solar Edge Module Model Number: SE 380OH-US Nominal Power Output 3800 W Maximum AC Power Output 3800 W Maximum Continous Output Current at Specified Interconnection Voltage: 16 A BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-2 SHEET NUMBER: 2 OF 38 D .lts E S N4 OG E 3 ;07m. r .� U •• -_ W 1Q r r k / j �_� i a s s - � r � •� s Ak • • i • WARNING Fi a WARNING Fhl )HOTOVOLT IC POWERSOURCE' � l�iRNIN+�^u�'k nl POWER SOURCEWARNING • i � � • - SECOND SOURCE IS PV SYSTEM " = - � � • DO NOT TOUCH , ERViNALS. _� � ,� PHOTOVOLTAIC POWER SOURCE ROVNE, �A ULT IS INDI C Az E 'TPhlINALS ON ROT11[Lt GC7USC?EC; COND' J .4}AD SIDES MAY BE. ENE RG17F- ") i"N 0,ry,..4 GE...';i:..* E, `�.#P=,':'FFA. t4 ,�..1'twE'..;?'a�.r�., AND F`3t' ;-,- „ � ,:.�,; • � rl ��Pt�N; Si�LAI:t GPR��lIT CAUTION - #pI 111111 11 t RV srsat:Nl cr BREAKER IS BAFt) 46_ • • •• i k 10 WARNING: WARNING F�`#'� DQ NOT DISCONNECT i � • t TURN QEF PHOTOVOLTAIC I_ TRICAL SHOCK HAZARD UNDER LOAD . • 1' AC DISCONNECT 0 A �J0 NOT TOUGH TLRI 15 ;;." •, WC►RKING INSPDE PANEL a a PHOTOVOLTAIC DISCONNECT r0,7) V N I N G irl � r r� �� INS AG,61. ES VlAf B E"`.ilER 'Z(� ? PHC.)Ti' VnI.TAiC AC DISCONNECT FAUL7 Is .TI-17 C)PEN iNGPi'3`UNOFD.'AND E!'`:F"r<GZGB FR WARNIN �'a� WARNING �a1 TURN OFF PHOTOVOLTAIC ' r r • . • • AC DISCONNECT PRIOR TO I 0 r�r�n a 0R.s UHiS 1► t • ' _ . . : I, • WORKING INSIDE PANEL AIC 3E ENERGIZED PHOTOVOLTAIC a WARNING WARNING EL ]fflC;AL:,H(X;KHA2J11? DC DISCONNECT GROUNCED c= �,����� �� , SOLAR ELECTRIC SYSTEM CONNECTED 10 TNC i}C J" C}tJciC €>� rtli( I tF'fC Rah 3Li d E; h� Z='' e # t t 11 AND1JXfl ENERGI7Ft # ## PV SYSTEM > c DIs ll� lrcT 1�VARIdt�1 ¢ � ; r MAIN Pel' SYSTEM WARNING sEcoNo SCii�C4iii SYSTEM', AC DISCONNECT ELECT1C�iL�c HAZARD WARNINGF7aP,41ihSCU;�M,: t". DO t�i.,T Tr1,0CH ER{�, 4'HCf. [_CIAil Sir)ES k^A`( RtNEPG;ZED 1 ELECTRICAL SHOCK HAZARD „XIM} l5�TEN ,t _T ��4 p* INTIO NOT TOUCH TERMNALq t TEPMINALS ON BOTH LINE AND � /� p.� LOAD MDES MAY EDS, ENERGIZED � � � . i � ' • � • CAUTION: IN 14L WEN 110$11, �U N � SOLAR ELECTRIC SYSTEM CONNECT11 DC VOLTAGE IS ALWAYS PRESENT 0>. _= a_ "A WARNING: WHEN SOLAR MODULES PHOTOVOLTAIC 1I!ik # ARE EXPOSED TO SUNLIGHT y��rEs `t� � �����1Y1� i` C� _ , d<� � • # TURN OFF PHOTOVOLTAIC # ��� r� Eel HER—POINT"i",I .� A C ISCONNE c DISCONNECT PRIOR TO �YFF:,PNLT�CjE111=111., ����G�'#t.� � SOLAR DISCONNECT _�'T �1�If AUT a I E �EDACQPER TNG IRRE., WORKING INSIDE E PANEL e 4° r ! f" SEI"^i IiD�E("h€I�.a�`�t� art E? RT s� 44TKAC, ERA E� Imo, iE i � WT AC ERRITIN VOLTAGE�� er � WARNINGRAIN P SYSTEM P RATE A, ARA7 G',10 JA � � # � � SHEET TITLE: ED? CIRCUITiRENT LLLQFRICAL SHOCK HIAZARL) PHOTOVOLTAIC � DISCONNECT I {N N EST MAXIMUM SYSTEM VOLTAGE a0 QCT TOUCH TERN Er ALl',3, HE#?iVIINALS 01% e+". Tti LINE AND _,AC3 &DE S MAY BE EtdER'Ca2Ei,; ., IN THE OPEN PfJediTCiiN . r 1 bill III E', a; oafs MFlwoftl SHEET NUMBER: 3 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency Circuit Noof Current q Y 60 Hz . Conductor Conductor Conductor Design OCPD OCPD Conduit Conduit Conduit Size Reference Circuit Description Carrying Voltage - Line 1 to Neutral 120 V ID Type Material Size Current Type Rating Schedule Conductors Type and QTY Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %4' Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A Co -2 3 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D.P.C. B. 20A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Existing Module Model Number: 315 G51DUO EQ -3 EQ -4 EQ -6 EQ -7 Meter Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent -Voltage -0.28% per oC EQ -1, EQ -2 GO -1 CO -2 CO -2 Temperature Coefficent - Current 0.04% per oC CI -3 CI -4 CI 4 EQ -9 Temperature Coefficent - Power -0.37% per oC CI -2 Junction Integrated Specifications at STC Box Disconnect Solar MPP Power - Pmp 315 w New Existing Electrical MPP Current - Imp 9.55 A DC ACS IF ervice Service MPP Voltage - Vmp 32.98 V Optimized String of 8 Modules Short -Circuit Current - Isc 10.04 A ----- ---• -- ------ ------ Open-Circuit Voltage - Voc 39.87 V I Temperature Adjusted Inverter qJr Vmp - Min 32.06 V VOC - Max 40.42 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P320 EQ -5 Rated Input DC Power: 320 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE: SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ2/C12 EQ2 C12 Component Model Notes string limitations apply, based on the Inverter Selected. ID Number Inverter Input Bus Voltage at Description Manufacturer EQ -1 Solar PV Module QCell QPRO-265 See Module Information 350 V P300 Power P300 Power Specified Interconnection Voltage: Optimizer Optimizer EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ C1,1 EQ l-,1 EQ -3 DC Junction Box N/A N/A NEMA 311 - Outdoor Rated Minimum Optimizers Per String: 8 EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Inverter Information Solar Photovoltaic Photovoltaic EQ -5 Inverter SolarEdge SE3000U-US See Inverter Information ••• Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 3000H -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker - NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 3000 W EQ -8 Meter After Installation Maximum AC Power Output 3000 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A UJ 0 Of 0 - BY: BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-4 SHEEP NUMBER: 4 OF 38 g � r 8, 6/0 NAL ��� 161EfI1 H`=Am-11er=MA&ANa"-nriW1 W 5 riV / j pyx i„ a Pk H' 0 0 1V0 L T All S Y S T Em M h IdC 18M4 O(it WBid z r ApproP +PisERt ttlited i / ca,.»«.,...a. a,•a. , ,D iimct 'RWfRar+ax«.ls•n.aw-ev wMry�.,rREQUIREMENTS ..,t�� 2012 y i NECArticle 690 and IFC 12 M �p L.Li W Adhesive Fa09 steriE.-d Signs ae Adhesive fastened signs may be acceptable 1/011 �W ° if properly adhered. Vinyl signs shall be V weather resistant. [FC 605.1 1.1.3 `r 'EC 4W, ) o N Pay No 55F,(Y9 SECOND SERVICE DISCONNECT ON NORTH SIDE OF BUILDING The markings shall be of sufficient ori photrcfvu ti.fic r3betffff i,vnarfr,. rfe nutrber a ! _q Q withstand durability t ithstand the atfat-f rPPded vAff .3rp ed n tfe prq f mpr rcpt_ a...,.�,..e. iEi NEC�Ii Partflllo5%00309 rpt.ta err ,�r,,t rr .,tF, .1uri�r�tr����,r , rr. environment involved. NEC 110.21 THIS PANEL FED FROM INV1 MAX AVAILABLE FAULT CURRENT; 46,552 AMPS 11-T1c4id ac 11 i1 :tl +ta fi , a C aii erg �Fr'1? DATE 2115112 F,�. feM� iltl r r r:,,drr. r rr , r f rr"rt,{r 'NEC 408,4(b) Patt No, 5 -00,1 � he materials used for marking shall be T r nrt r`' w:1 [,ry m x�, tik r � q E r idJ� r, puu4jCutill tlesst r�e4�r�� rjry,rdaPVSys,n)Ih:include *NEC 11024(A)IPart No5 . 3 reflective, weather resistant and suitable :err Flash and ir-4brrri.A,.;nal lakwlinq for the environment." IFC 605.1 1.1.1 PHOTOVOLTAIC POWER SOURCE WARNING` DVAI. POWER SOURCE WARNING WARNING WARNINGSYSTEM• . • LECTRIC� L HOC HAZARD SL��N� ��7u���E t �t o r4o'r TOUCH FERMINALS. rw t,)c (x,jvucrr*. PHOTOVOLTAIC POWEIR SOURCE Ar,rt0 U NZ r,A L '"SP%114ALS ON ROTA f IN17AAD PftiJ0VCLT,4i0 SYSTE MARE ''��F ",':ALL. , .ate It tE1� [� � i� <D _ C 0R, R e� MAY BE ENERGIZF-D AND rm^A'r LE ZNE?? t7EF1 CAUTION, SOLAR CIRCUIT , Mse ✓F UN(iFC-' ) AND , 11FR 7E,, • � � � � CAUTION • _ • � _ � • � � FJ TF►L PLP PC} IiiC>� PV 5Y' 1I EM GIR(,Ur 15REAKER IS iiRCKFED WARNING; ,. WARNING FA -1 DO NOT DISCONNECT � � • � � TURN OFF PHOTOVOLTAIC --I�fLCTRICAL SHOCK HAZARD UNDER t.�OAD � � • : � � n AC DISCONNECT PRIOR TO 30 NOT TOUCH T-LIRIVAIALS,. . WORKING INSIDE PANEL WARNING PHOTOVOLTAIC ;C DISCONNECT PrV,,NA= ON B Tr 14r All,,,') � z„r:;_ -., i.:, ,,_.a C539ESl,'1AyF jF$d.lZf F{Z t ¢ : f PHOTOV01, TAIL ASC DISCONNECT LFi r RIGA) 6JA A' i r y- F A aCit CID FAULT IS 1NDIF 4-F D, NORMALLY2R'XJNDFD t�.D'NVQCT',.7Rs s ' 1 • � gp.A"iBE UN(zF?.uUPv0,FD ANr^i cryFRC9ZE 1WARNING: # + FI WARNING 10 TURN OFF PHOTOVOLTAIC . • • AC IJISCONNECT PRIOR TO r U N DUC I OR'$ OP 114 11 II e ' - i • : • • a WORKING INSIDE PANEL P f<,) -r 00 `?.."Ar„SYS TELI AFE,.,t- 4J, , • G 'wig? 3E ENERGIZEDPHOTOVOLTAIC • WARNING FAI d #Jl r l w lr � s . CAUTION: SOLAR ELECTRIC SYSTEM C AN C 10 FL HAZARD DC DISCONNEC r G U I HE DIC, ONDIJfTOR`Q THiS 141GROiNDED ANG IF i'G7: - r e BY: BDD ANO LIMN SF FNEI? GB:17ED •MAIN PV SYSTEM � WARNIISG /A1 PV SYSTEM DC DISCONNECT WARNING F�����°� so�t�r.� DATE: 8/29/2018 00 NOT TOUCH TERNIIINIALS, WARNING '± SECOND SOURCE IS P'V SYSTEM A DI' CONN EC FI FCThICAL SHOCK HAZARD ELECTRICAL SHOCK HAZARD FATIPJC V`� rArat LOAD SIDES MAY S ENI PGIZED REVISION:T�.WJINALS ON 5CtTh LINE AK) DIS NOT TOUCI4 TERMINAL,,'. RMNALS ON BOTH LINE AND , Rf;UtT CL?PAiiNT i t • CAUTION: ., LOAD S9LYLS MAYMAYUL LNFI?C3tZi[3 + � • � f t IN , i UPEN PUrrrotw y SOLAR ELECTRIC YSTEM CONNECTED /� DC VOLTAGES !� �LWAi” a PRESENT FSI WARNING WHEN SOLAR MODULES PHOTOVOLTAIC � — A. EXPOSk TO SUNLIGHT r � �'� ®' ,„ � sf I =DR �ERt h C '.� TURA OFF PHOTOVOLTAIC AC DISCONNEC � AC DISCONNECT PRIOR TO � UN S Ei � TGE � ? SOLAR DISCONNECT � RTi �RvUffCURR T TA °ETIIRRE ,T WORKING ItdSIDE. PANEL €iP I ED AC OPERA, 9 I NG,7 ,IL'k.l AGE r i I%L � f s 4'I "A 'DARNING 0 ; MAIN Pel SYSTEM SHEET TITLE: RATEDSHORT [R UITCURR T�'� LI.L r I�ICr�L `al����� 19r L'�ii:?� PHOTOVOLTAIC AC DISCONNECT DISCONNECT TPERrvINA "it E 0TE ONE AND SHEET NUMBER: 5 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency 60 Hz Circuit g No. of Current Conductor Conductor Conductor Design OCPD OCPD Conduit Conduit Conduit Size Reference Circuit Description Carrying Voltage -Line 1 to Neutral 120 V Ip Type Material Size Current Type Rating Schedule Conductors Type and QTY Voltaeg - Line 2 to Neutral 120 V CIA PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 4 PVC %4" Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A co -2 1 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 25 A D. P.C.B. 30A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Module Model Number: 315 G5DUO EQ -3 EQ -4 EQ -6 Existing EQ -7 Meter Maxium Series Voltage Allowed: 1000 VDC CO -1 CO -2 Temperature Coefficent - Voltage -0.28% per oC EQ-1CI-2 CI -3 ,EQ -2 CO -2 CI -4 Temperature Coefficent - Current 0.04% per oC CI -4 EQ -9 Temperature Coefficent - Power -0.37% per °C Junction Integrated Specifications at STC Box Disconnect MPP Power - Pmp 315 W Optimized String of 10 Modules7 New Existing Solar Electrical MService PP Current - Imp 9.55 A DC AC Service 1 MPP Voltage - Vmp 32.98 V Optimized String of 9 Modules Short -Circuit Current - Isc 10.04 A �____ ___}__ ______ ______ Open -Circuit Voltage - Voc 39.87 V Temperature Adjusted Inverter Vmp - Min 32.06 V VOC - Max 40.42 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P320 EQ -5 Rated Input DC Power: 320 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE. SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ211C12 EQ Component Model string limitations apply, based on the Inverter Selected. ID Description Manufacturer Number Notes C12 Inverter Input Bus Voltage at EQ -1 Solar PV Module QCell QPRO-265 See Module Information 350 V P300 Power P300 Power Specified Interconnection Voltage: Optimizer Optimizer EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ Cl1 EQ I -,I EQ -3 DC Junction Box N/A N/A NEMA 3R - Outdoor Rated Minimum Optimizers Per String:T 8 EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Solar Solar Inverter Information Photovoltaic Photovoltaic EQ -5 Inverter SolarEdge SE6000U-US See Inverter Information ••• Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 5000H -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker - NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 5000 W EQ -8 Meter After Installation Maximum AC Power Output 5000 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current 21 A at Specified Interconnection Voltage: L n rw W 0 a - BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-6 SHEET NUMBER: 6 OF 38 SHEET NUMBER: 7 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule of Current Interconnection Frequency 60 Hz Circuit Conductor Conductor Conductor Design OCPD OCPD Conduit No. Conduit Conduit Size Reference Circuit Description Type Material Size Current Type Rating Schedule Carrying Type and QTY Voltage - Line 1 to Neutral 120 V ID Conductors Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %11 Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A co -2 3 CarFlex 3/4” Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D.P.C.B. 20A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Existing Module Model Number: 315 G5DUO EQ-3EQ-4 EQ -6 EQ -7 Meter Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent - Voltage -0.28% per oC CO -1 CO -2 CO -2 Temperature Coefficent - Current 0.04% per oC CI -3 CI -4 C14 EQ -9 Temperature Coefficent - Power -0.37% per oC EQ-1,EQ-2 CI -2 Junction Integrated Specifications at STC Box Disconnect MPP Power - Pmp 315 W New Existing Solar Electrical MPP Current - Imp 9.55 A DC AC Service Service MPP Voltage - Vmp 32.98 V Optimized String of 8 Modules Short -Circuit Current - Isc 10.04 A ----- ---+-- ------ ------ -1 Open -Circuit Voltage - Voc 39.87 V Temperature Adjusted Inverter Vmp - Min 32.06 V VOC - Max 40.42 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P320 EQ -5 Rated Input DC Power: 320 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE: SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ2 12 EQ2 C12 Component Description Manufacturer Model Notes string limitations apply, based on the Inverter Selected. D Number Inverter Input Bus Voltage at P300 Power EQ -1 Solar PV Module QCell QPRO-265 See Module Information 350 V P300 Power Specified Interconnection Voltage: Optimizer Optimizer V EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ C11 EQ EQ -3 DC Junction Box N/A N/A NEMA 311 - Outdoor Rated Minimum Optimizers Per String: 8 EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter S'l.r Solar Inverter Information olar Photovoltaic • • • Photovoltaic EQ -5 Inverter SolarEdge SE3000U-US See Inverter Information Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 3000H -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker - NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 3000 W EQ -8 Meter After Installation Maximum AC Power Output 3000 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A U W 0 BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: SHEET NUMBER: i 1 i SHEET NUMBER: milwoo Site Condition Assumptions Conductor Schedule Conduit Schedule Circuit Reference ID Circuit Description Conductor Type Conductor Material Conductor Size Design g Current OCPD Type OCPD Rating Conduit Schedule No. of Current Carrying Conductors Conduit Type Conduit Size and QTY Interconnection Frequency 60 Hz Voltage -Line 1 to Neutral 120 V Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %4" CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A co -2 3 CarFlex 3/4" Voltage - Line 3 to Neutral (If Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 16 A D.P.C. B. 20A Voltage - Line 2 to Line 3 - V EQ -4 EQ -6 EQ-3CO-1 CO -2 _\ CI -3 CI -4 EQ -1, EQ -2 CI -2 Junction Integrated Box Disconnect DC AC Optimized String of 13 Modules ----- ---}--- ------ Inverter EQ -5 The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an "Optimized String of Modules". EQ2/C12 EQ2 P3C12 Component ID Optimizer 00 Power Description P300 Power EQ -1 Solar PV Module Optimizer EQ -2 DC Optimizer E(QC11 EQ EQ -3 DC Junction Box EQ -4 Integrated Disconect Solar Solar Photovoltaic Photovoltaic EQ -5 Inverter Module Module EQ -6 New Circuit Breaker Enclosure EQ -7 Existing Electrical Service Existing Meter Enclosure EQ -8 EQ -9 Insulation Piercing Splice Connector EQ -8 EQ -7 CO -2 CI 4 New Solar Service I Equipment Schedule Model Manufacturer Number QCell QPRO-265 SolarEdge SE P300 N/A N/A SolarEdge N/A SolarEdge SE38000-US GE TQL100REP N/A N/A N/A N/A NSI IPSC4002 Existing Meter EQ -9 Existing Electrical Service Notes See Module Information See DC Optimizer Information NEMA 311 - Outdoor Rated Disconnect Integrated with Inverter See Inverter Information See Page EQ4 for Detailed Specs 150A Main Breaker - NEMA 3R Meter to be Replaced with Bi -Directional Net Meter After Installation See Page EQ5 for Detailed Specifications Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information Manufacturer Name: QCell Module Model Number: 315 G5DU0 Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent - Voltage -0.28% per oC Temperature Coefficent - Current 0.04% per oC Temperature Coefficent - Power -0.37% per oC Specifications at STC MPP Power - Pmp 315 W MPP Current - Imp 9.55 A MPP Voltage - Vmp 32.98 V Short -Circuit Current - Isc 10.04 A Open-Circuit Voltage - Voc 39.87 V Temperature Adjusted Vmp - Min 32.06 V VOC - Max 40.42 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P320 Rated Input DC Power: 320 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A Maximum Output Current: 15 A NOTE. SolarEdge Power Optimizers ONLY to be used with SolarEdge Inverter, as specified in this drawing. The following string limitations apply, based on the Inverter Selected. Inverter Input Bus Voltage at Specified Interconnection Voltage: 350 V Maximum Power Per String: 5250 W Minimum Optimizers Per String: 8 Inverter Information Manufacturer Name: Solar Edge Module Model Number: SE 380OH-US Nominal Power Output 3800 W Maximum AC Power Output 3800 W Maximum Continous Output Current at Specified Interconnection Voltage: 16 A UJ 0 BY: BDD DATE: 8/29/2018 REVISION: I SHEET TITLE: E-10 SHEET NUMBER: 10 OF 38 SHEET NUMBER: 11 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency q Y 60 Hz Circuit Reference ID Circuit Description Conductor Type Conductor Material Conductor Size Design Current OCPD Type OCPD Rating Conduit Schedule No. of Current Carrying Conductors Conduit Type Conduit Size and QTY Voltage - Line 1 to Neutral 120 V Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %11 Voltage - Line 3 to Neutral (If Applicable) V CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A CO -2 3 CarFlex 3/4" CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A CO -3 Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D. P.C.B. 20A C04 Voltage - Line 2 to Line 3 - V EQ -3 EQ -4 EQ -6 CO -1 CO -2 EQ -1, EQ -2 CI -3 CI -4 CI -2 Junction Integrated Box Disconnect DC AC Optimized String of 8 Modules ______ Inverter EQ -5 The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an "Optimized String of Modules". Component EQ2 12 EQ2 C12 ID Description EQ -1 Solar PV Module P300 Power P300 Power Optimizer Optimizer VEQ-2 DC Optimizer EQ C11 EQ 1_, EQ -3 DC Junction Box EQ -4 Integrated Disconect Solar Solar Photovoltaic Photovoltaic EQ -5 Inverter ••• Module Module EQ -6 New Circuit Breaker Enclosure EQJ Existing Electrical Service Existing Meter Enclosure EQ -8 EQ -9 Insulation Piercing Splice Connector EQ -8 EQ -7 CO -2 CI -4 New Solar Service Equipment Schedule Model Manufacturer Number QCell QPRO-265 SolarEdge SE P300 N/A N/A SolarEdge N/A SolarEdge SE3000U-US GE TQL100REP N/A N/A N/A N/A NSI IPSC4002 Existing Meter EQ -9 Existing Electrical Service Notes See Module Information See DC Optimizer Information NEMA 3R - Outdoor Rated Disconnect Integrated with Inverter See Inverter Information See Page EQ4 for Detailed Specs 150A Main Breaker - NEMA 3R Meter to be Replaced with Bi -Directional Net Meter After Installation See Page EQ5 for Detailed Specifications Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information Manufacturer Name: QCell Module Model Number: 315 G5DUO Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent - Voltage -0.28% per oC Temperature Coefficent - Current 0.04% per oC Temperature Coefficent - Power -0.37% per oC Specifications at STC MPP Power - Pmp 315 W MPP Current - Imp 9.55 A MPP Voltage - Vmp 32.98 V Short -Circuit Current - Isc 10.04 A Open -Circuit Voltage - Voc 39.87 V Temperature Adjusted Vmp - Min 32.06 V VOC - Max 40.42 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P320 Rated Input DC Power: 320 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A Maximum Output Current: 15 1 A NOTE: SolarEdge Power Optimizers ONLY to be used with SolarEdge Inverter, as specified in this drawing. The following string limitations apply, based on the Inverter Selected. Inverter Input Bus Voltage at Specified Interconnection Voltage: 350 V Maximum Power Per String: 5250 W Minimum Optimizers Per String: 8 Inverter Information Manufacturer Name: Solar Edge Module Model Number: SE 3000H -US Nominal Power Output 3000 W Maximum AC Power Output 3000 W Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A ao w J w 0 Of 0 - BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E- 12 SHEET NUMBER: 12 OF 38 ON D n o. �. 40 FOR (ill i/1111 �/ i /1, 0 Hellen"I"11-ann /�j/ `/ HOTOVOLTA A IC Y M g' LL s y ���, � �firPPEl�r iuUr>,t I ` NI'm Rw REQUIREMENTS Farr lig; S,r r ,:;'..� q NEC 2017 Article 690 and IFC2012 W� M • Adhes� f N L.L Adhesive fastened signs may be acceptable l if properly adhered. Vinyl signs shall be weather resistant. 1FC 605.11 1,3 S NEC 4 8,4fB f aft No: 5WVFX�9 SECOND SERVICE DISCONNECT The markings shall be of sufficient ON NORTH SIDE OF BUILDING 3f;� s} �r%$�r �r6afr: Irl ��ta �. rr;"1t,r � .+1 1tr"'rrar,:Jr,. 7r c,r-- irfyrir Irt��r`, fir--gavr,l o, Tfeo ber, d rl� *NECr�2 NECf� atLAo 55,&00309 durability OWI San e (Et, r r 7 )I P f�Ftzl �,rr,F _environment involved, NEC 110,1 e?r ?��.# t��t# V' ,rev i ,a- ? r tr t Cnrj ,,v d it-� - rFt�t {wr,`rriw n.,'st-_rr, �.<, �,f,Y1,.�«.F�r�,r<� THIS PANEL FED FROM INV 1' MAX AVAILABLE FAULT CURRENT. 46.552 AMPS N O, EPISI a6r1I_ !IlPtr,.rrri:aatr n it, r) raljt ,.a DATE 2/15112 The materials used for markingshall be NE )de , hpn .r �' . r, in a t a lint) r,r trurfuye (r tl r than '11EL. � � 4�� � P,)tt til `� _ �� , 6, PR .;.l,IFt.1 aYjt xted%Jrnor�thdn.:r�r;�_ P_b'- ,fo d�d a, publicuIdales-.t�-Ia_eE9t�;ryandaPV�y rn)T}ai anrdjde�� 'PdEC11024(A)1PattNo55Rt103t�9 reflective, weather resistant and Suitable r��; ",arn if--)Ir"aion,.Alab- 19 for the environment." IFC 605.11.1.1 Combiner Box / Circuits i Enclosures EMT 1 Conduit Raceways *(Reflective Material Required) Breaker Panel / Pull Boxes Biu it NI MSI � II II II IIIIII� i�o� I II IIII 1111111 1 I t � III lui li � i ul iii.Il a uii gi a ii �. � �, �r� � POWFIZ O ,,, IlAt�.�� .� ,� r�N WARNING e WARNING 4", TO BE INSTALLED ON CIRCUIT PER NEC 690.31(E)(3)&IFC 605.11 .2 BREAKER ENCLOSURE: PER NEC 70 12(DX4) & NEC 69{1.64 t Part No. s Pat No. 596-00231 LOAD 810�_-,S MAY BE F!',IFRGIZFD 'CAUTION: i N1 Ii! SOLAR !N _ -iii �i I �,�� THIS EQUIPMENT FED BY MULTIPLE IN THE OFEN FO�jITJQN PER I�Ec551tLll�rtia596a3z57 ' SOURCES. TOTAL RATING OF ALL PER NEC n��l: 11(4) I mart N�). 54f G°I233 PER NEC 600 35(F)1 Part No 596-50258 i PER NEC 6 31(E)(3) &IFC 605 i t 1 2, 605.11.1.- PER NEC 690.5(C) I Pat No. 595-00234 Part No £96 00247 PER NEC -05.12(0)(4) NEC64J64 OVERCURRENT DEVICES, WARNING: I I' 1111111 IIID All iI Part No. 596-00236 EXCLUDING MAIN OVERCURRENT Building i Structure FAM Inverter ` w s • r DEVICE SHALL NOT EXCEED TURN OFF PHOTOVOLTAIC UNDER"'' AMPACITY OF BUSBAR. AC CAUTION DISCONNECTPHOTOVOLTAIC AC DISCONNECT 1 PER NEC F,90.33(EX2) I Part No 596-0024 1 .. y WARNING ,.. ...," �asrWwanr,usarWev+nv+n ` 21A PHOTOVOLTAIC PER NEC 110.27(() &E SHA 1110.145(fX7) 240V 21A w Part t v 596-00235 PER NEC 690 541 Part No. 59b•00239 ? PER NEC 690.1 ?(4) I Part No 595-00233 240V , . PER NEC 650.541 Part No. 5145-1X5239 PER N Er 690 5(0 I Part No, 596-4)4234 WARNING: FIER NEC hQ ) 56(B) � Part Nei. 55$-00350 �WARNINGAML TURN Production / Net Meter Production I Net Meter • .. PRIOR :FF PNOTOVOLTAIC HE-tY-,� DC Disconnect I Breaker l Recom bi ner Box WORKING INSIDE o _ Are R N [ OSHA 910 Fps^ III Ni..WARNING IY ,.», ,.,_.i% 4 f! " PER tY€C 110.27(C) 1.Jr 'J Ji iM 131t�1�Jiti i) " j [Y i * Part Nr, 5 6-OW35 PER NEC 690,35(F) Part No 596-00253 E R, K;AL CAUTION: HAZARr .• ! Main Service disconnect *(RefleC'tive J11;a£eda; ,4et7u;red) PER QFC 605.11.1, IFC 605 tt 1.4, NEC 694.15& PER NEC 69014((X2}, IFC60511 1, IFC 605.11 1 4, BY: BDD NEC 690,14(C)(2)1 Part No- 5'36-002 3 NEC 6� 15 & NEC 690.531 Part No 596-00245 PER NEC 690 5(C)1 Part No 5%-00234 PER NEC 6%35(F) I Pati. No 5,A4025 Ir 111 II Q ��� I U pl I DISCONNECT °�� w5 III I r r b ' PV SYSTEM DC DATE: 8/29/2018 :..,� 4 AC t • ,,NP 12.6A PER NEC70512(DX4)&NEC 69G64 aoov Part No 5 154231 PER NEC 690.14(CX2),]F-605-111, REVISION: ` IFC 645 11.1.4, NEC 69015 & NEC 6�5 53 600V TERMINALSDO NOT T0I;CH Part No 596-0243 15A a PER NEC 690.170)1 Part No. 5%-00233 LOAD SIULS MAY BE, ENERGIZEDAC Disconnect I Breaker/ Paints of ConnectionCAUTION: ' DC VOLTAGE IS ALWAYS _ I IN Ift OPEN POSITION NEC 694.531 Part No. 596.00241 - �� '. '' II I�� VIII �I ill WHEN s '" i +>� +li 240V ESENT PER NEC 690.14(CX21 IFC 605 11 1, IFC 60511 1.4, � WARNING: ARE EXPOSED SOLAR TO NEC 69415&NEC 690.531 Part No 596- 45 60 Hz PER NEC 6A)17(4)1 PartNo 596-00252 400vL1 4010 5 000w TURN •PHOTOVOLTAIC . • DISCONNECT !" • 400V NNEC PER IFC 605 11 1, IFC 605.11 1A, NEC 69015& 21A � � � WORKING DPANEL 21A 15A NEC 640 14(02) 1 Part No. 596-00237 PER IFC 605.11 11 Pat No. -00246 21A PERNEC 11(}27(0)&OSHA 1910.145(#)(7) r ! ` 240V N/A Ix �� I� �� IA�� Pact No 596 00235 f .. PER NEC 690 52 Part No, 5 -OD2 2 io --%�4 NEC 00531 Partlia 546-00253 MAIN PV SYSTEM SHEET TITLE: PHOTOVOLTAIC DISCONNECT ism=i 600V FOR MARKING BACKUP S'6TEMS 240V = PER NEC 690.14(6}(21 tFC 605.11.1, PartNo T -X0,0240 IFC 605f1i1 NE X95& 069053 �RNEC 6901.14(0X2)1 PartNo, 5%(30239 �rt"<5%-0024? � C 69013( 1 Part No: 596-W22133 � � ' E-13 SHEET NUMBER: 13 OF 38 Site Condition Assumptions Interconnection Frequency 60 Hz Voltage - Line 1 to Neutral 120 V Voltaeg - Line 2 to Neutral 120 V Voltage - Line 3 to Neutral (If Applicable) - V Voltage - Line 1 to Line 2 240 V Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information Manufacturer Name: QCell Module Model Number: 315 G5DUO Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent - Voltage -0.28% per oC Temperature Coefficent - Current 0.04% per oC Temperature Coefficent - Power -0.37% per oC Specifications at STC MPP Power - Pmp 315 W MPP Current - Imp 9.55 A MPP Voltage - Vmp 32.98 V Short -Circuit Current - Isc 10.04 A Open -Circuit Voltage - Voc 39.87 V Temperature Adjusted Vmp - Min 32.06 V VOC - Max 40.42 V DC Optimizer Information Manufacturer Name: Solar Edge N/A Module Model Number: SE P320 Rated Input DC Power: 320 W iMaxium Input Voltage 48 V Maximum Short Circuit Current: 10 A Maximum Output Current: 15 A NOTE: SolarEdge Power Optimizers ONLY to be used with SolarEdge Inverter, as specified in this drawing. The following string limitations apply, based on the Inverter Selected. Inverter Input Bus Voltage at Specified Interconnection Voltage: 350 V Maximum Power Per String: 5250 W Minimum Optimizers Per String: 8 Inverter Information Manufacturer Name: Solar Edge Module Model Number: SE 5000H -US Nominal Power Output 5000 W Maximum AC Power Output 5000 W Maximum Continous Output Current at Specified Interconnection Voltage: 21 A Conductor Schedule Conduit Schedule Circuit Reference Circuit Description Conductor Conductor Conductor Design OCPD OCPD Conduit No. of Current Carrying Conduit Conduit Size SolarEdge SE P300 Type Material Size Current Type Rating Schedule N/A Type and QTY ID 50000 -US EQ -6 New Circuit Breaker Enclosure GE TQL100REP EQ -7 Existing Electrical Service N/A Conductors EQ -8 Existing Meter Enclosure CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC /4" CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A CO -2 3 CarFlex 3/4" CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 21 A D. P.C.B. 30A EQ -1 EQ -2 C r1 Q L_W-%J The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an "Optimized String of Modules". Equipment Schedule EQ2 12 EQ2 C12 ZZ P300 Power P300 Power Optimizer Optimizer EQ C11 EQ ____CI_� Solar Solar Photovoltaic Photovoltaic Module Module Component ID Description Manufacturer Model Number EQ -1 Solar PV Module QCell QPRO-265 EQ -2 DC Optimizer SolarEdge SE P300 EQ -3 DC Junction Box N/A N/A EQ -4 Integrated Disconect SolarEdge N/A EQ -5 Inverter SolarEdge 50000 -US EQ -6 New Circuit Breaker Enclosure GE TQL100REP EQ -7 Existing Electrical Service N/A N/A EQ -8 Existing Meter Enclosure N/A N/A EQ -9 Insulation Piercing Splice Connector NSI IPSC4002 EQ -9 Notes See Module Information See DC Optimizer Information NEMA 311 - Outdoor Rated Disconnect Integrated with Inverter See Inverter Information See Page EQ4 for Detailed Specs 150A Main Breaker - NEMA 3R Meter to be Replaced with Bi -Directional Net Meter After Installation See Page EQ5 for Detailed Specifications w 0 Of BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-14 SHEET NUMBER: 14 OF 38 l����1111rrrEs, OND O 0 1 s _ R e er ann/1 Jowl&O h 1 ov/ zHyyj� I w�< wF`HU`T0`V"0LTA1CSYSTEM /W :,,�A Im- GiHy M i PPF R trps# �4�q/� MCI '+tlkiMal.IM ML4 ce4 t`h+A i".iYVY,S' 3tM/iMwkJ H ecN •tl,liuitl{+WY• � / f �'j� 12 Part #`"'- $ �a '.;; 0 REQUIREMENTS /�NEC 2011 Article 690 and IFC 2012 � ON,, m t oOfW e Adhesive a.we%Signs /� // Adhesive fastened signs may be acceptable c if 1Kv1 HH���H properly adhered. Vinyl signs shall be weather resistant. lFC 605.1 1..1..3 �tiHH f' SECOND SERVICE DISCONNECT - The markings shall be of sufficient FI ON NORTH SIDE OF BUILDING xrr rrrsrr ,ttrr �� 4� �r a+stt flr� /, durability to withstand the fne G.IFGl7 i-E�JE j r } .i �rt ,✓ zi Y ,!�'7 t �- N r,r23021-13,NECLr RitNd rJ rekri cf perafie�ia r 'Cheavath AH) r r ura r r� rr „arre THIS PANEL FEU environment involved. NEC 110.21 777,7 77� . FROM INV 1 MAX AVAILABLE FAULT CURRENT; 46.552 AMPS *NOTE: Service>N, ir,'�d rna+xJ P� 6. DATE 2115f12 The materials used Or marking shall betE4i��irerlr prc;nn � h�lfir-�a crtructiirtfon `NEC408E}PartNo tyand aPVsy rt)Tht int11;1i NEC11024(A)1PartNo.55&003t reflective weather resistant and Suitable I ✓ in 977 } 4 for the environment. iFC 605.1 1.1.1 3q n Combiner Box /Circuits /Enclosures EMT/ Conduit Raceways *(Reflective Material quo -f � Breaker Panel /Pull Boxes �l III III IU MINI iii�pi I�II� IIl I LII 11 iii I II II !! ii III ii II ii Y III • � , II� !� SOUR CSWARNING G TO BE INSTALLED ON CIRCUIT I PER NEC 90.31(E} )&t10605.11.12 U* BREAKER ENCLOSURE. pl m I pl Iml p ! PER NEC 745.12(DX4) N NEC 69464 Part No. 596-00206 , I �N� I �- * • , 1 PSL No. 596-00231 I NII IIIII III I Illlllll��l �I ° THIS EQUIPMENT FED BY MULTIPLE CAUTION IHL PER NEC69ttaltE);fartse= �'`-OC}25i SOURCES. TOTAL RATING OF ALL PER. NEC 13140351F} ( Part No, 5%-00258 PER NEC 690. 5(C} j Part No. 596 X10234 P'PNEcF�")17 1P�a,"r"��,, C.00�z» PER NEC6 31(E)(3)&IFc601IT2,605.1114 PER NEC :o512(1)}(4) & NEC 690 64 OVERCURRENT DEVICES, Part No 596-00247 Pat5960' EXCLUDING MAIN OVERCURRENT &A WARNING: Building /StructureInverter +II • . r NNE& I DEVICE, SHALL NOT EXCEED TURNOFF r r «AIC UNDERLOAD AMPACITY OF BUSBAR. AC DISCONNECT PRIOTO 1,407 JOLIC-4 T=i-Rk�NAL CAUTION PHOTOVOLTAIC AC DISCONNECT ON 51"TH I, 1141r, D PER NEC 690.33(EX2)1 Pmt No 596-00244 ss: waxav WORKING L ..«, INSIDEUj PANEL WARNING 7 12.5A Y43✓tti.l.0 CY Ai AFMY - PHOTOVOLTAIC. DISCONNECT PER NEC 110.2711} &OSHA 1914.145(f}(7} 240V 12 5A w Part No. 59611235 PER NEC 65[1541 part N4. 596 (1Q239 PER NEC" 690" 1 A4)1 Part No. 596.00233 2aov i t„ PER NE( fly-#? 54 (Part No. 596-00239 .. ,.W� PER NEC 690 5(C) Part No 5916-41:3234A. 'I FAI WARNINGO TURN OFF PHOTOVOLTAIC i+ F- • Production / Net Meter Production/ Net Meter _ r • - +� DC Disconnect / Breaker / Recom bi ner Box (Bi-directional) I WORKINGPANEL CD { ., t...... laterialRequired) PER NEC 110.27(C) & OSHA 1910,14507)WARNIN � i MEWi ! i = Part No 5%-00235 CAUTION* ELFCTRICSHOCK HP Z,' 7M Illion a - Main Service Disconnect �R rtv� f t l Required) PER IFC 605 1 1 1, IFC 6051 ME DC CONDUCTOR-� OF TKS 1 14 NEC 690.15 & � PER NEC 69414(C 2), IFC 60511.1, IFC 605.11,1, 4, � .BY: BDD NEC 690,14(C)(2)1 Part No. 596 t}Q233 NEC 690.15 & NEC 690 53 I Part No 596.00245 IE R NEC 690 5(C) I Part No 596-00234 ,I �l " l�l! Isr DATE:_. PER NEC E9035(0 PartN65%-Q425 nW,l 8/29/2018PV SYSTEM C f 4 a l U01 9 AC DISCONNECT aoov REFtBdEC?{>51z( ENoNS i23 PF€ NEC 6k14(t 2),W605111, (�"Ili1l.11l+ + P�A11 � IT Ilfl 111 REVISION: �I'i . DJ • 60IN 7 H77 OPEN P05��io"4 Part No IFC 64511 I.A, NEC 69+1iNSi 010243 TFRWNA(,S ON _. 1-1 nONOrTOUCHTF1ROANALS 5A PER NEC 6�0.17(4)1 PartNr, 596 O(}233 • AC Disconnect / Breaker l Points of Connection NEC 600,531 PartNo. 5+6-00241 ! ! DC PRESENTP A WHEN SOLAR MODULES 4 MA �i w II III I II L_ I III _.II �Y=1=11111YI11• ..... ` FAI WARNING: I' ' I li ul 240V = PER NEC 6 .14(c X21 !FC 605 11 1, IFC 6x1511 1 4, ARE EXPOSED TO SUNLIGHT 6.3A 60 Hz N€ C 690.15 & NEC 690.531 Part No 59+5-00245 TURN OFF PHOTOVOLTAIC 400V 3,000W • s r PER NEC 691 17(4)1 Part No. 596.40232 ! ! I Ipl II DISCONNECT ! # =SOLAR 600V 12.5A C. • I 15A PER tFC 605 t t 1,1K60511 .1 4, NEC 690115 & • !PANEL 12.5A NEC 69014(02) I Part No 596-00237 PER IFC 605.11 11 Pat No. 59603246 12.5PER NEC 114 27(1) & OSHA 1910 145(9(7) A � ' • 240v "`A WARNING PER NEC %521 Part No 5%-OD25 Part No 596 0023s ,� SHEET TITLE: 11 NEC 6^Y053 1 PdtNo, 5146.00253 12.5APHOTOVOLTAIC AC DISCO14NECT DISCONNECT t 600V 12.5A 240V PER NEC 690.14(CX211FC 6051 T 1 FOR MARKING BACK'L1 P S'15TE M S E C 690.53 Par k No 596-00240 PER NEC 69t314(C2)I Part No, 596-0023; IFC 605 4 NE"lt� 00243 .. ... PER NEC 690171* I Part N4.596X233 s w� , %' " ` , „ E-15: SHEET NUMBER: 15 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency Circuit Noof Current q Y 60 Hz . Conductor Conductor Conductor Design OCPD OCPD Conduit Conduit Conduit Size Reference Circuit Description Carrying Voltage - Line 1 to Neutral 120 V Ip Type Material Size Current Type Rating Schedule Conductors Type and QTY Voltaeg - Line 2 to Neutral 120 V CIA PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %4" Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A co -2 3 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 1.5 A D.P.C.B. 20A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Existing Module Model Number: 315 G51DUO EQ -3 EQ -4 EQ -6 EQ -7 Meter Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent -Voltage -0.28% per °C CO -1 CO -2 CO -2 Temperature Coefficent - Current 0.04% per °C EQ -1 EQ -2 CI -3 CI -4 CI 4 EQ -g Temperature Coefficent - Power -0.37% per °C CI -2 Junction Integrated Specifications at STC Box Disconnect MPP Power - Pmp 315 W New Existing Solar Electrical MPP Current - Imp 9.55 A DC ACService Service MPP Voltage - Vmp 32.98 V Optimized String of 8 Modules Short -Circuit Current - Isc 10.04 A ----- ---+-- ------ ------ Open-Circuit Voltage - Voc 39.87 V I Temperature Adjusted Inverter 4 Vmp - Min 32.06 V VOC - Max 40.42 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P320 EQ -5 Rated Input DC Power: 320 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE: SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ2 12 EQ2 Component Model string limitations apply, based on the Inverter Selected. C12 Ip Description Manufacturer Number Notes Inverter Input Bus Voltage at P300 Power EQ -1 Solar PV Module QCell QPRO-265 See Module Information Specified Interconnection Voltage: 350 V P300 Power p g Optimizer Optimizer V EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ C11 EQ 1.1 EQ -3 DC Junction Box N/A N/A NEMA 3R - Outdoor Rated Minimum Optimizers Per String: 8 EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter 1 0-1- Solar Inverter Information Solar C Photovoltaic Photovoltaic EQ -5 Inverter SolarEdge SE3000U-US See Inverter Information Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 3000H -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker - NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 3000 W EQ -8 Meter After Installation Maximum AC Power Output 3000 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A w 0 BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-1 6 SHEET NUMBER: 16 OF 38 SHEET NUMBER: 17 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule of Current Interconnection Frequency 60 Hz Circuit Conductor Conductor Conductor Design OCPD OCPD Conduit No. Conduit Conduit Size Reference Circuit Description Carrying Voltage -line 1 to Neutral 120 V ID Type Material Size Current Type Rating Schedule Conductors Type and QTY Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %4" Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A co -2 3 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D.P.C. B. 20A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Existing Module Model Number: 315 G5DUO EQ -3 EQ -4 EQ -6 EQ -7 Meter Maxium Series Voltage Allowed: 1000 VDC CO -1 co -2 co -2 Temperature Coefficent - Voltage -0.28% per oC Temperature Coefficent -Current 0.04% per oC CI -3 CI -4 CI -4 EQ -9 Temperature Coefficent - Power -0.37% per oC EQ-1,EQ-2 CI -2 Junction Integrated Specifications at STC Box Disconnect MPP Power - Pmp 315 W New ExistingSolar Electrical MPP Current - Imp 9.55 A DC ACService Service MPP Voltage - Vmp 32.98 V Optimized String of 10 Modules Short -Circuit Current - Isc 10.04 A ----- ---�-- ------ ------ -� Open -Circuit Voltage - Voc 39.87 V I I Temperature Adjusted Inverter m6p Vmp - Min 32.06 V VOC - Max 40.42 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P320 EQ -5 Rated Input DC Power: 320 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE: SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ2 12 EQ2 C12 Component Model Notes string limitations apply, based on the Inverter Selected. ID Manufacturer Number Inverter Input Bus Voltage at P300 Power Description MftEQ-1 Solar PV Module QCell QPRO-265 See Module Information 350 V P300 Power Specified Interconnection Voltage: Optimizer Optimizer EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ C11 EQ EQ -3 DC Junction Box N/A N/A NEMA 3R - Outdoor Rated Minimum Optimizers Per String: 8 EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Inverter Information -S on I an rr Solar Photovoltaic Photovoltaic EQ -5 Inverter SolarEdge SE3000U-US See Inverter Information ••• Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 3000H -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker- NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 3000 W EQ -8 Meter After Installation Maximum AC Power Output 3000 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current 12.5 A at Specified Interconnection Voltage: L n rw 1 w 0 BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: SHEET NUMBER: 18 OF 38 r .� T A f+fill ill .t'�i rf//tl ►►►.-L.,,. h 00 IS x > A k PHO,�TOVOLTAIC SYSTEM w/�� „a , v" AppmprWo PPS Rectett H 7 A N �(��7 ��^n� J1 M �V o P�Fr,rrlrL,,11r33� ���fi1FPA2012 �iC/ a�� Pl , 115",3-00-11 1 REQUIREMENTS 11IS j N% NEC 2011 690 and IFC 2012 M U C) e Lk £ "i.w d . Signs F&_ w i If %;/ Adhesive fastened Signs may be acceptable m i0 ,% if properly adhered. Vinyl signs shall be LINV 1 weather resistant. IEC 605.1 1.1.3 �� r , y 'H *3*NEC 4084,(6) SECOND SERVICE DISCONNECT ON NORTH SIDE OF BUILDING The markings shall be of Sufficient irG{rr, hrr6sr r1 t`,rSf' rri'>' t r#trtr.ttr7t,nr I durability to withstand the ore phato,*o# x latent j l x r �srro, 7-te �u rol an l tYTV *NEC 30 Y oe-� . E0 230.72(A) I Prt1�o. 5%00309x1ra. rr1 � r/ �.� THIS PANEL FED environment involved. NEC 110.21 rel�'.e:i r r frCat ri,, s t,Fr_ �,JthJ 1 t ,« rF �_ rF^err:= FROM INV 11 MAX AVAILABLE FAULT CURRENT, 46.552 AMPS 1'd OTE,Ei�t1r �rJi �rultm -Ir ,�'k�fi`.i�r arF c DATE 2115112 r�Er ct { ,Er, e,(,[I, �r,a;,�lraarkr_cr rr r t;lrl,,ri `NEC408A(Es"))PartN�5583�" The materials used for marking Shad be dn"AI inn unit"') ) «�', 1 ed iw,(m t ,. than i «� J',A w fi frSd4ljp%r !. �, n> ..................... ,-- ua Cl;tlllle_ ,_d a � t�;, 11,,.PV,ystem)Th_-in u, , .NEC,�����EPa€tN�S��3� reflective, weather resistant and suitable r"+rc Nash .�ri�,i irf:�rrt»r}3r),�i �kririr for the environment." I1=C 605.1 1.1.1 Combiner Box / Circuits l Enclosures EMT f Conduit Raceways "(eftectllrMaterial Required) Breaker Panel / Pull Boxes R11 I IIIIIII U �plllu l 1 III IIII LI I Ili II UII II I I ILII IIII IIIII II III III I IIII I WARNING , -;I IIi4 t 4A WARNING FAI WARNING ! (IIIL III TO BE INSTALLED ON CIRCUIT► tsr SOURCE IS PV SYSTEM PER NEC 690.3103)&FC 605,11.12 C BREAKER ENCLOSURE. Part. No. 596-00206 i" '!�'i�i' i "i'lli ' "�'� ' ��Ii' s ' "" i :" ' PER NEC 705.12c1Pal t � NEC -00.34 P�No_ 596-00231 I h�IIII�I " IONyy'I THIS EQUIPMENT FED BY MULTIPLE �� SOLAR PER NEC 690.4(F)1 Part No 596-00257 ���� PER NEC 6 35(F)IPartNo 5 -0025 _ _ RNECr. s ,s ; F r PER NEC90.5(Q]PartNo.596-00234 SOURCES. TOTAL RATING OF ALL PEP NEC �9��17(4) 1 r���,. 233 FE,.¢aE� 0�I,1){F_.,05- f 12, 0J.t1.1 PER NEC 705,12(t��41)&NEC 69064 OVERCURRENT DEVICES, Part No 596-0024 i Part No, 596-00236 EXCLUDING MAIN OVERCURRENT Tj Building 1 Structure PHOTOVOLTAIC Inverter0 WARNING FAA Do +► r DEVICE, SHALL NOT EXCEED TURN OFF UNDER ';' AMPACITY OF BUSBAR. AC D , TOLICH y CAUTION y PER NEC9Q,33(E2) I Part. 596 0(1244 WORKING INSIDE W PANELWARNING PHOTOVOLTAIC AC DISCONNECT 12.5A Y■(*]1Rg6144Af W �Y]YHi1N PER NEC 114.27(C) &OSHA 1910145(fX7) = 24oV Past No. 596-00235 PER NEC 6% 1 A4)1 Part No, 596-00233 2aov PER NEC 690 541 Part No 5 X239 PER NEC 690.541 Part No. 596-OD239 PER NEC 690 5(C) I Part No 596-00234FAI WARNING: 0 PER i"1Gt: E59t3 56(R) I Part Nc S5 'it);�,0 ► f TURN OFF PHOTOVOLTAIC Production / Net Meter Production 1 Net Meter AC DISCONNECT PRIOR TO CONDLIC TOPS OF URS LLJ DC Disconnect/ Breaker/ Recom bi ner Box•. PANEL o (Bi-directional , f >._'Cl- :' 1at#s€/1t'�0 PER NEC 110, 27(i) &415##6 191Q.145(fi7)) I P ' � � at No 591 x1235 PER NEf 690.3fmt Nr. 596-00258 #FI WARNING r pr P CAUTION: _ y i i Iii IIt' :NOPVAi Vy fY Y Main Service Disconnect * Reflective Materiall Required? BY: BDD PER IFC 60511.1,1FC 605.11.1 �t NEC Ca90 t 5 & PER NEC 69014CX2), IFC 605.11 1,1FC 605,111A NEC 690.14(CX2) I Part No- 596-00238NEC 690-15 & NEC 690 531 Part No 596.00245 E PE R NEC 690 5(C)1 Part No 596-00234 " I II III I IIIAN WARNING PER NEC69035(F)1Par tNo,596-0025 i IIII �I II IIIIIII IIID II I " '�' �, .!� DATE: 8/29/2018 PV SYSTEM DC DISCONNECT ; r Ili �FLECTRICAL SHOCK AC HAZARD 6.3A PER NEC 70512((71(4)&NEC 69064 aoov Pat No 596-0023(RMNIAL�S ON IeOTH LINE AND 8 NEC 14(()(21, IFC 60511 1r REVISION: LOAD $1DES MAY S7 ` + 60oV IFC 6(15.1 t 14, NEC 69(`1.15 & NEC 69J 5377 - 00 NOT TOUCH TFRUINALS.i Pett No 596-OW43 _ . ON 15A = ' PER NEC69017(4)1 Part No. 5 6(X)2_' AC Disconnect / Breaker 1 Points of Connection CAUTION. IN 14F OPEN 11OSJiQN NEC 690.531 Part No. 596-00241DC VOLTAGE IS ALWAYS PRESENT • f , .. MODULES • ' I I 240V ? PER NEC 69(}.14(Cj{2 {fC t 05 1 +.1, IFC 50511 1A # ARE EXPOSEC TO SUNLIGHT NEC 69015 &NEC 690.531 Part No 596- X1245 4 TURNOFF"O O O i PEP, NEC 69017(4)1 Pat No 596-D1232 . E � 3,000w V T p I� III IIIII I� IIII IIII I N � , DISCONNECT -� sooSODISCONNECTI 15A12.5A PER IFC 645. 11, 1, [FC 60511.1.E NEC 69015 & WORKING INSIDE 12.5A NEC 69014(CX2) I PartNo, 596-40237 PER IFC 605,11 11 Pat No. 596-00246 12.5A PER NEC 110 27(C) & OSHA 1910145{O(7) 240V N/A Part No 596-W235 FWARNING PER NEC 690.521 Pat No 5%-01252 a NE SHEET TITLE: Part%. '0025s � : u, DISCONNECT 600V c 12.5A ' FOR MARKING BACKUP SYSTEMS 240V PER NEC 690 t 4{t�{2} IFC 605.11 1, Pat Mtn 596 0(1240 IFC 605 1 4 6iEt.6.15 & fEC b90 53 p PER NEC 69014(CX2) I Part No. 596-00239 �� � tNa,`�s-t71JZ4; .... � � PE€�:N1_C 69017% I Part No 5_00233 �. � � � g � : � E 19 SHEET NUMBER: 19 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Circuit Reference ID Circuit Description Conductor Type Conductor Material Conductor Size Design Current OCPD Type OCPD Rating Conduit Schedule Noof Current . Carrying Conductors Conduit Type Conduit Size and QTY Interconnection Frequency q Y 60 Hz Voltage - Line 1 to Neutral 120 V Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %4" Voltage - Line 3 to Neutral (If Applicable) V CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A co -2 3 CarFlex 3/4" CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D.P.C.B. 20A Voltage - Line 2 to Line 3 - V EQ -8 EQ -3 EQ -4 EQ -6 Existing EQ -7 Meter Q_1,EQ_2 CO-1CO-2 CO -2 CI -3 CI -4 CI 4 EQ -9 CI -2 Junction Integrated Box Disconnect New Existing Solar Electrical DC ACService Service Optimized String of 8 Modules Inverter EQ -5 The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an "Optimized String of Modules". Equipment Schedule EQ 2 12 EQ 2 Component Description Manufacturer Model Notes C12 ID Number P300 Power P300 Power EQ -1 Solar PV Module QCell QPRO-265 See Module Information Optimizer Optimizer EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information EQ CI1 EQ (_,l EQ -3 DC Junction Box N/A N/A NEMA 3R - Outdoor Rated EQ4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Solar Photovoltaic • • • Photovoltaic EQ -5 Inverter SolarEdge SE3000U-US See Inverter Information Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker - NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net EQ -8 Meter After Installation EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information Manufacturer Name: QCell Module Model Number: 315 G5DU0 Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent - Voltage Temperature Coefficent - Current -0.28% 0.04% per °C per °C Temperature Coefficent - Power -0.37% per oC Specifications at STC MPP Power - Pmp 315 W MPP Current - Imp 9.55 A MPP Voltage - Vmp 32.98 V Short -Circuit Current - Isc 10.04 A Open -Circuit Voltage - Voc 39.87 V Temperature Adjusted Vmp - Min 32.06 V VOC - Max 40.42 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P320 Rated Input DC Power: 320 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A Maximum Output Current: 15 A NOTE: SolarEdge Power Optimizers ONLY to be used with SolarEdge Inverter, as specified in this drawing. The following string limitations apply, based on the Inverter Selected. Inverter Input Bus Voltage at350 Specified Interconnection Voltage: V Maximum Power Per String: 5250 W Minimum Optimizers Per String: 8 Inverter Information Manufacturer Name: Solar Edge Module Model Number: SE 3000H -US Nominal Power Output 3000 W Maximum AC Power Output 3000 W Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A U W 0 BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-20 SHEEP NUMBER: 20 OF 38 ��LLb1EE9fffppp .'— 1 <g 0. � 6 ��A •y!•!lIYrY ��`V i ap Hy Fay Heller a CCr PHOTO'VOLTAIC !3YSTEKA 'OH' Are Rash and Hazard / Appropriate ISE fiequired a w t2 qk �n i.1 R.y+f+41 4i/%0%% / M•Mv.rfom C12 REQUIREMENTS0 110 16 andWA "T, fk J ,{r C 2011 Article 690 and IFC 2012 W Of Cl w o H adhesive fastened signs may be acceptable � �W if properly adhered. Vinyl Signs shall be weather resistant. IFC 605+1 1 .1.3 w j SECONDSERVICE DISCONNECT The markings shall be of sufficient ON NORTH SIDE OF BUILDING $:IhowwtWclateatr o?narrc7� r�urobet y)afy,p �*� durability to withstand the tat -1 nepr�vvrzt,,�ry ea -Priori the project nye 'ir_ _—_ .._...,.,,....., EC 23Q }, NEC 23d? 7ZA}( r?i cr. 553t'J?09 environment involved. ITEC 110.21 THIS PANEL FED FROM INV11 MAX AVAILABLE FAULT CUl411EEM 4$.552 AMPS 111TE equipment mi tbe f? Il rn.arhd pet t": DATE Z/15112 r.IES.�or,u4 �Er'sI _�r�h�aill,rranr>tri,�,a�c (o�.lt«r *NE,-4084(E�1Patt, �55r0��� � �.+..+...,++._ � The materials used for marking shall be —tiiik put4ic�uthte ss a e4&-tr,1ry and j �,; Tl,�In JJe, ��Cs102�IPart No 55&00reflective, weather resistant and suitable A„�_Flalt f infJTrnAi-�rJIab,ing for the environment." IEC 605.1 1,1 +1 t i i• ! 4 i i • • ♦ J • • r : i PHOTOVOLTAIC POWER SOURCE VtdARNINGI c�uALPc�Vvr saTsRc� • ` � • WARNING ��` � WARNING ,&j . ► T ARNING SECOND SOURCE IS PV SYSTEM LLL(; I HIC AL St 10,CK HAZARD DO NOT TOUCH FERVIINALS, THE ,_ PHOTOVOLTAIC P� GROG .e _{7htt kkIL3 N F0Ti-I .r4�4pQIJCXVAC, SyI"TA ARE V1,4G14e S.1,R !" R !• zP.�.'K .� f �] k..%l>! C, r {1 -1. �` J....e ;"OR'S ' f-0AF,',,1DF-9%1A''r 8F,FNF�iGIZED t`<Pi'DMA:i u,ESNEKtZEU '.IA' F'( ti^.Y,ir.,;i_'?r� 3; i [ ENFR''31ZF • � � � � CAUTION- SOLAR CIRCUITCAUTiQNIN It IL QIP�–'N RO-SITION _ ! PV SYS 1 EM CtiR' I r 5REAKER r;z EAGt4gED • • • j 2 iVARNIN FAI WARNING U DO NOT DISCONNECT • TURN CUFF PHOTOVOLTAIC EL1--`QjRICAL SHOCK HAZARD UNDER LOAD . .. • C : . L AC DISCONNECT PRIOR TO ' aJORKING INSIDE PANELMUM WARNING PHOTOVOLTAIC AC DISCONNECT RIVRJA S ON RUTLINE AN ) OA SDES F'Ar BE, ENERC 21�) ra � TRA rlg+IF,W' ..,_ • !._ �. -� 4 II; THC (OPEN PC)S3*°ai Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency Circuit Noof Current a v 60 Hz . Conductor Conductor Conductor Design OCPD OCPD Conduit Conduit Conduit Size Reference Circuit Description Type Material Size Current Type Rating Schedule Carrying Type and QTY Voltage - Line 1 to Neutral 120 V ID Conductors Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC Y4" Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A Co -2 3 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D. P. C. B. 20A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Module Model Number: 315 G5DUO EQ -3 EQ -4 EQ -6 Existing Maxium Series Voltage Allowed: 1000 VDC EQ -7 Meter Temperature Coefficent - Voltage -0.28% per °C CO -1 CO -2 CO -2 Temperature Coefficent - Current 0.04% per oC CI -3 CI -4 CI -4 EQ -9 Temperature Coefficent - Power -0.37% per °C EQ-1,EQ-2 CI -2 Junction Integrated Specifications at STC Box Disconnect MPP Power - Pmp 315 W New Existing Solar l Service MPP Current - Imp 9.55 A DC AC Service MPP Voltage - Vmp 32.98 V Optimized String of 8 Modules Short -Circuit Current - Isc 10.04 A Open -Circuit Voltage - Voc 39.87 V I Temperature Adjusted Inverter •l, Vmp - Min 32.06 V VOC - Max 40.42 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P320 EQ -5 Rated Input DC Power: 320 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE: SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ2 12 EQ2 Component Model string limitations apply, based on the Inverter Selected. C12 ID 350 V P300 Power P300 Power Description Manufacturer Number Notes Inverter Input Bus Voltage at EQ -1 Solar PV Module QCell QPRO-265 See Module Information Specified Interconnection Voltage: Optimizer Optimizer EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ EQ EQ -3 DC Junction Box N/A N/A NEMA 3R - Outdoor Rated Minimum Optimizers Per String: $ EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Inverter Information Solar Solar Photovoltaic Photovoltaic EQ -5 Inverter SolarEdge SE3000U-US See Inverter Information ••• Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 3000H -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker - NEMA 3R Nominal Power Output Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net p 3000 W EQ -8 Meter After Installation Maximum AC Power Output 3000 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-22 SHEET NUMBER: 22 OF 38 1W ,TALC EP, TO NEL 110.2ACE &O to 19E4.145(17) Part No, 596-00235 L -i P*06, 5S8 W35> Breaker l RecombinEer Box PER NEC 690.35(F)I Fart No. 596-00258 VV�1 L N aL Art ,IX;,'ES ARF F, < Ca;; t`t.r 703 SON'Vi Hl FOR MARKING BACKUP MM5 - Part No 596.110240 rN tr WAM PE: R IFC 605.11:1, IFC, 605.11 i 4; NEC 690. 15 & NEC 690,14(C)(2111 PatNo: 596-00238 i >w� ,i� DISCONNECT �iN iu a i�li 6.3A 400V 600V 15A NEC 690.531 Pat No. 596-00241 g6.3A r44 r 600V 15A rwill NEC 690,531 Part No. 596-00253 NEC23€1.72(A)I PanNo. 55800309 'NEC 110,24(A) I Fart No, 55&00309 () EMT f Conduit Raceways *(Reflective Materia! Requir ) 3) & 1FC 605.11.1:2 Part No. 5%-00206 PER NEC 690 31(E)(3) & EEC 60511.1:2, 605.11.1.4 Part Na 596.00247 Inverter PER NEC 6900, 5(C) I Parrt No. 596.0023x1 Production 1 Net Meter PER NEC 690 5(C) I Part No, 595-00234 PER NEC 690 4(F) I Part No 596-00257 FEES NEC 690.541 Fart No. 596.0(1239 fa Production/ Net Meter (Bi-directional) *( efiective Material Required) PER NEC 69014(C)(21 IFC 60511.12 EFC 605.11,1. NEC 690.15 & NEC 690.531 Part Na 596.00245 PER NEC 70512(1)x4) & NEC 690.64 Part No. 596-00231 AC Disconnect/ Breaker! Paints of Connection PER EPC 605.11.1,1FC 605.11.1.4, NEC 690.15'& NEC 69014(CX2)1 Part No, 596-00237 PER NEC 690.521 Pat Na 596-(X1252 PER NEC 694.14(Cx2)1 Part No- 596 0(1239 The markings shall be of sufficient durability to withstand the environment involved. NEC 110.21 * The materials used for marking shall b reflective, weather resistant and suitable for the environment. If IFC 605.11.1.1 9 • WARNING F, WARNING r�r l P'0,11 � �I;'_ p ®aECaOk`�tC) `a�C�UFiCrC b PV ,`a`"`.a` iC.PIE CAUTION #Jk AW Alit F00 WARNING N1, DO NOT DISCONNECT UNDE=R LOAD t� PF{CST VC�'•ITAC IAC !SC0NNF :T wA%i[NA WARNING TURN OFF PHOTOVOLTAIC AC DISCONNECT PRIOR To WORKING INSIDE PANEL 10 • MAIN PV SYSTEM 1�� WARNING FAM AC DISCONNECT 'rr � T - If Hr1.11'1Rr� , CAUTIONP ELECTRIC SYSTE (�(} v � .. .f FA WARNING- • TURN OFF PHOTOVOLTAIC >O�AR DISCONNECT AG DISCONNECT PRIOR TO WORKING INSIDE. PANEL � •t t MAIN PV SYSTEM DISCONNECT 'x TO BE INSTALLED ON CIRCUIT BREAKER ENCLOSURE: THIS EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES, EXCLUDING MAIN OVERCURRENT DEVICE, SHALL NOT EXCEED AMPACITY OF BUSBAR. w 0 CL BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-23 SHEET NUMBER: 23 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency Circuit Noof Current q Y 60 Hz . Conductor Conductor Conductor Design OCPD OCPD Conduit Conduit Conduit Size Reference Circuit Description Type Material Size Current Type Rating Schedule Carrying Type and QTY Voltage - Line 1 to Neutral 120 V ID Conductors Voltaeg - Line 2 to Neutral 120 V 0-1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %4'' Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A co -2 3 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D. P.C.B. 20A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Existing Module Model Number: 315 G5DUO EQ -3 EQ -4 EQ -6 EQ -7 Meter Maxium Series Voltage Allowed: 1000 VDC CO -1 co -2 co -2 Temperature Coefficent - Voltage -0.28% per oC Temperature Coefficent - Current 0.04% per oC CI -3 CI -4 CI -4 EQ -9 Temperature Coefficent - Power -0.37% per oC EQ- 1,EQ-2 CI -2 Junction Integrated Specifications at STC Box Disconnect MPP Power - Pmp 315 W New Existing Solar Electrical MPP Current - Imp 9.55 A DC ACService Service MPP Voltage - Vmp 32.98 V Optimized String of 8 Modules Short -Circuit Current - Isc 10.04 A ----- ---.-- ------ ------ Open-Circuit Voltage - Voc 39.87 V I Temperature Adjusted Inverter Vmp - Min 32.06 V VOC - Max 40.42 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P320 EQ -5 Rated Input DC Power: 320 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE: SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following Component Model string limitations apply, based on the Inverter Selected. EQ2/CI12 EQ2 C12 ID Description Manufacturer Number Notes Inverter Input Bus Voltage at EQ -1 Solar PV Module QCell QPRO-265 See Module Information 350 V P300 Power P300 Power Specified Interconnection Voltage: Optimizer VOptimizer V EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ C11 EQ EQ -3 DC Junction Box N/A N/A NEMA 311 - Outdoor Rated Minimum Optimizers Per String: 8 EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Inverter Information Solar Solar Photovoltaic Photovoltaic EQ -5 Inverter SolarEdge SE3000U-US See Inverter Information ••• Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 3000H -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker- NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 3000 W EQ -8 Meter After Installation Maximum AC Power Output 3000 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A U W 0 Of M BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-24 SHEEP NUMBER: 24 OF 38 0 o -mac s 'IOP �(/f��••,`����1\I Y'�qy,` �\ �� NA L St � ► �. -0 w e • s � a PHOTOVOLTAIC POWER SOURCE WE WARNINGMAL Pf,)WFR SGURCE El wh LI -LE i�F 1t I t. , : SECOND SOURCE I S Psi SYSTEM PHOTOVOLTAIC POWER SOURCE _ A TIOW SOLAR CIRCUIT ° CAUTION • - --MA ad III V EM N WARNING r"A a DO NOT DISCONNECT � � • � TURN OFF PHOTOVOLTAIC �y�.0afw A � 0 UNDER LOAD - . • : � - rie AC DISCONNECT PRIOR T SIR, IWORKING INSIDE PANE! �r trcara Vit . „ • • ;t I1:_s PHOTOVOLTAIC AC DISCONNECT AM WARNING- WARNING___- _ °URN 3FF PF TOVOLTAI • . AC DISCONNECT PRIOR TO ' � i ,: ! + ` - , • + • : WORKING INSIDE E PA iEL i_i F ' s Y. , '.�. �,.., {..ER„7 • IWI •. • • PHOTOVOLTAICWARNING A k"Ni I N G.. CAUTION: DC DISCONNECT SOLAR -kttONNECTED 101 e z_ * X41 G siJAi. POWER �OJ3?I MAIN SYSTEMWARN IN SYSTEM 1 � � F URCE IS CDISCONNECT `xc� WARNING _+t LECTRICAL HOCK HAZARD � � ��E � _..__... _ . _.. ._.. _..__.. .p.. a; ,.'.,,'�. ,� , `�.T�'iti �';,.4°s*,r,- ".., • 11 � I� ; } �7i-.zE.* �t,2`-, ; .: � PO NOT Ti` t C? i TT`RMUNAd S LOAD'S60L', MAY UL LNW4Gi �► - CAUTION: IN Tlt O:IL a 110:5; 1 !ON � � � • SOX ELECTRIC Y NNECTEC DC VOLTAGF IS ALWAYS PR BST WARNING: WHEN SOLAR MOMLES PHOTOVOLTAIC ARE EXF TO SUNLIGHT TURN OFF PHOTOVOLTAIC e m e .� }• a . "`�J � � app?" � a >4 .� �«�. ' 11 �,�s �� �€s ,�,v `��ds�, :11 SOLARDISCONNECT A DISCONNECT PRIORT C SCNI •11 f � WORKING INSIDE PANED klLJ r�e„b,sw as w <k+,sex •,U'. pMAIN PV SYSTEM SHEET TITLE: er Q g I®i Fel ' SI TOCK d dk, ` FL) - e� INS" -� - __.aT T tICt MOWmmmw -251 11 ��:l����:l�����������������:111:::11!111:11:1:1 1 11:1111 111 11 111 SHEET NUMBER: 25 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency 60 Hz Circuit g No. of Current Conductor Conductor Conductor Design OCPD OCPD Conduit Conduit Conduit Size Reference Circuit Description Type Material Size Current Type Rating Schedule Carrying Type and QTY Voltage - Line 1 to Neutral 120 V ID Conductors Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %4" Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A Co -2 3 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 16 A D.P.C. B. 20A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Existing Module Model Number: 315 G5DUO EQ -3 EQ -4 EQ -6 EQ -7 Meter Maxium Series Voltage Allowed: 1000 VDC CO -1 GO -2 CO -2 Temperature Coefficent - Voltage -0.28% per oC Temperature Coefficent - Current 0.04% per °C CI -3 CI -4 CI -4 EQ -9 Temperature Coefficent - Power -0.37% per oC EQ -1, EQ -2 CI -2 Junction Integrated Specifications at STC Box Disconnect MPP Power - Pmp 315 W New Existing Solar Electrical MPP Current - Imp 9.55 A DC AC Service Service MPP Voltage - Vmp 32.98 V Optimized String of 14 Modules Short -Circuit Current - Isc 10.04 A --------.--- ------ Open-Circuit Voltage - Voc 39.87 V I I Temperature Adjusted Inverter Vmp - Min 32.06 V VOC - Max 40.42 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P320 EQ -5 Rated Input DC Power: 320 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE. SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ2 12 EQ2 C12 Component Model string limitations apply, based on the Inverter Selected. ID Description Manufacturer Number Notes Inverter Input Bus Voltage at EQ -1 Solar PV Module QCell QPRO-265 See Module Information 350 V P300 Power P300 Power Specified Interconnection Voltage: Optimizer VOptimizer V EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ Cil EQ EQ -3 DC Junction Box N/A N/A NEMA 311 - Outdoor Rated Minimum Optimizers Per String: 8 EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Inverter Information Solar Solar Photovoltaic Photovoltaic EQ -5 Inverter SolarEdge SE38000-US See Inverter Information ••• Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 380OH-US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker - NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 3800 W EQ -8 Meter After Installation Maximum AC Power Output 3800 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current at Specified Interconnection Voltage: 16 A BY: BDD DATE: 8/29/2018 REVISION: SHEEP TITLE: E-26 SHEET NUMBER: 26 OF 38 SHEET NUMBER: 27 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule of Current Interconnection Frequency 60 Hz Circuit Conductor Conductor Conductor Design OCPD OCPD Conduit No. Conduit Conduit Size Reference Circuit Description Carrying Voltage -Line 1 to Neutral 120 V ID Type Material Size Current Type Rating Schedule Conductors Type and QTY Voltaeg - Line 2 to Neutral 120 V 0-1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %4" Voltage - Line 3 to Neutral (If CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A co -2 3 CarFlex 3/4" Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CI -4 Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D.P.C. B. 20A Voltage - Line 2 to Line 3 - V Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information EQ -8 Manufacturer Name: QCell Module Model Number: 315 G5DUO EQ -3 EQ -4 EQ -6 Existing Meter Maxium Series Voltage Allowed: 1000 VDC EQ -7 Temperature Coefficent - Voltage -0.28% per oC CO -1 CO -2 CO -2 Temperature Coefficent - Current 0.04% per °C CI -3 CI -4 CI4 EQ -9 Temperature Coefficent - Power -0.37% per -C EQ- 1,EQ-2 CI -2 Junction Integrated Specifications at STC Box Disconnect MPP Power - Pmp 315 W New Existing MPP Current - Imp 9.55 A DC AC Solar ServiceElectrica) Service MPP Voltage - Vmp 32.98 V Optimized String of 9 Modules Short -Circuit Current - Isc 10.04 A -- — ______ Open -Circuit Voltage - Voc 39.87 V Temperature Adjusted Inverter Vmp - Min 32.06 V VOC - Max 40.42 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P320 EQ -5 Rated Input DC Power: 320 W Maxlum Input Voltage 48 V Maximum Short Circuit Current: 10 A The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an Maximum Output Current: 15 A "Optimized String of Modules". NOTE: SolarEdge Power Optimizers ONLY to be used with Equipment Schedule SolarEdge Inverter, as specified in this drawing. The following EQ 2 12 EQ Component Model string limitations apply, based on the Inverter Selected. C12 Ip Description Manufacturer Number Notes Inverter Input Bus Voltage at P300 Power EQ -1 Solar PV Module QCell QPRO-265 See Module Information 350 V P300 Power Specified Interconnection Voltage: Optimizer Optimizer EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information Maximum Power Per String: 5250 W EQ C11 EQ I.1 EQ -3 DC Junction Box N/A N/A NEMA 3R - Outdoor Rated Minimum Optimizers Per String: $ EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Inverter Information Solar Solar Photovoltaic Photovoltaic EQ -5 Inverter SolarEdge SE3000U-US See Inverter Information ••• Manufacturer Name: Solar Edge Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP See Page EQ4 for Detailed Specs Module Model Number: SE 3000H -US EQ -7 Existing Electrical Service N/A N/A 150A Main Breaker - NEMA 3R Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Nominal Power Output 3000 W EQ -8 Meter After Installation Maximum AC Power Output 3000 W EQ -9 Insulation Piercing Splice NSI IPSC4002 See Page EQ5 for Detailed Specifications Connector Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A `�e6atttt►►►ePeo ♦♦o♦������ 0 N D ooio'. s� +•+.++�+° soo`f' �/ONAL i � ��� ��� �♦ BY: BDD DATE: 8/29/2018 REVISION: SHEEP TITLE: E-28 SHEET NUMBER: 28 OF 38 �i WARN1IN G &A WARNING " PHOTOVOLTAIC POWER SOURCE WARNING WARNING Ak Pa FR souRrFSECOND SOURCE IS PV SYSTEM • ' � • DO ;,may y- a.�civi3�Ii`lLri%..4'79. p� ,�• 3^, � :�.iP � �N�i% SIC IE#� qRCE M - r,SIDES MAY fiF tnN, F RGIZEDCAUTION. SOLAR IR IT - `, CAUT.10 Its ti4C'Pvr3I ih}P t _ • . • . • OV SYS TtM z; rtauW r BREAKER SAQKf-k0 i / • %rU UVARNiN PKII,ARNING rl DCS NOT DISCONNECT � � • � � TARN OFF PHOTOVOLTAIC -- I .-#_ 4L Sf CICK HAZARD UNDER LOAD - AC DISCONNECT PRIOR TO LSO N0 I AJC • WORKING INSIDE PANEL. ��� WARNING ��� PHOTOVOLTAIC AC DISCONNECT 5RNI • I€*7 TNC OPEN P Si',1 ym PHOTOVOLTAIC AC DISCONNECT � .. • • } i 1 a .14 J S.' r s 4 NMI! t t. ;!01.., to ... ,; %1 WARNING URN CUFF PHOTOVOLTAIC • • • 1 / • s AC DISCONNECT PRIOR TO �, . r .,_��.€:y ., c,� r�:�� • WORKING INSIDE {PANEL PHOTOVOLTAIC WARNING FAI WARNING FA �L 7MCSHOCil,HA r G DC DISCONNECT SOLA ELECTRIC SYSTEM CONNECTED 10 - - � - C S 11 TtiEM7C£1SJ€3ttit£m iHt. AND 9'1AY F:F FI4FPG17FP � � • MAIN PV SYSTEM WARNING � DATE: 1 18 PV SYSTEM DC DISCONNECT VSiARNING r��.� P�sc�aa�� ��i �a SECOND SOURCE I PV SYSTEM � AC DISCONNECT NNECT � EC,T�I�AL SHOCK HAZARD Ism .rtil II:� I c rc�uKEFI IdAt �REVISION: ELE CTR CAL Nor SHOO HAZARD Y �� 9ERMiNALS.ON BOTH 1ANE AND 'Al( �' CRC CIT CUR rhd € 9.ir%ALS �IDE�S MAY UL ENLROVED _.. 8 + / - : CAUTION: ;N 4f- 0 'EN V0,S1J,a3N SOLAR ELECTRIC SYSTEM CONNECTED DC VOLTAGE 1S At WAYS PRESENT WHEN SOLAR MODULES � � « � PH T V O LTA C� "A WARNING. ARE EXP-OSqDT SUNLIGHT TURNOFF PHOTOVOLTAIC Ai; DISCONNECT NEDT ", AC DISCONNECT PRIOR TO I` ,.v- .�� ., �� SOLAR DISCONNEG'T r{ e �}t! {pp j • WORKING INSIDE PANEL. g� SHEET TITLE:QW, WARNING NO MAIN PV SYSTEM L y LC F I i L St IOCK I111A l PH(.)I t9CaL-rAIC AC DISCONNECTDISCONNECT TtDUCH Fa ��'P�: OAD SIDES,M Y13L'-Ni IN THE OPEt,€ F`CX CJS Y •*#E-29 SHEET NUMBER: 29 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency q Y 60 Hz Circuit Reference ID Circuit Description Conductor Type Conductor Material Conductor Size Design Current OCPD Type OCPD Rating Conduit Schedule Noof Current . Carrying Conductors Conduit Type Conduit Size and QTY Voltage - Line 1 to Neutral 120 V Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.84 A N/A N/A CO -1 2 PVC %4" CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A co -2 3 CarFlex 3/4" Voltage - Line 3 to Neutral (If Applicable) V CI -3 Inverter Input Circuit THWN - 2 Cu #12 AWG 15 A N/A N/A Voltage - Line 1 to Line 2 240 V CIA Inverter Output Circuit THWN - 2 Cu #10 AWG 12.5 A D. P.C.B. 20A Voltage - Line 2 to Line 3 - V ECO -3 E04 E" 7 C10-11 M2 03-2 EQ -1, EQ -2 14 Cl*C114 10 EQ -1, EQ -2 ak2 Junction Integrated Box Disconnect New DC AC Service Optimized String of 9 Modules ------ -t 1 1 Inverter m. The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an "Optimized String of Modules". Equipment Schedule EQ2 12 EQ2 C12 Component Description Manufacturer Model ID Number EQ -1 Solar PV Module QCell QPRO-265 P300 Power P300 Power Optimizer VOptimizer EQ -2 DC Optimizer SolarEdge SE P300 EQ C11 EQ I_,l EQ -3 DC Junction Box N/A N/A EQ4 Integrated Disconect SolarEdge N/A Solar Solar EQ -5 Inverter SolarEdge SE3000U-US Photovoltaic Photovoltaic Module Module EQ -6 New Circuit Breaker Enclosure GE TQL100REP EQ -7 Existing Electrical Service N/A N/A Existing Meter Enclosure N/A N/A EQ -8 EQ -9 Insulation Piercing Splice NSI IPSC4002 Connector Existing Meter � ExistingSolar Electrical Service Notes See Module Information See DC Optimizer Information NEMA 311 - Outdoor Rated Disconnect Integrated with Inverter See Inverter Information See Page EQ4 for Detailed Specs 150A Main Breaker - NEMA 3R Meter to be Replaced with Bi -Directional Net Meter After Installation See Page EQ5 for Detailed Specifications Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information's Manufacturer Name: QCell Module Model Number: 315 G5DUO Maxlum Series Voltage Allowed: 1000 VDC Temperature Coefficent - Voltage -0.28% per oC Temperature Coefficent - Current 0.04% per oC Temperature Coefficent - Power -0.37% per oC Specifications at STC MPP Power - Pmp 315 W MPP Current - Imp 9.55 A MPP Voltage - Vmp 32.98 V Short -Circuit Current - Isc 10.04 A Open -Circuit Voltage - Voc 39.87 V Temperature Adjusted Vmp - Min 32.06 V VOC - Max 40.42 V DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P320 Rated Input DC Power: 320 W Maxium Input Voltage 48 V Maximum Short Circuit Current: 10 A Maximum Output Current: 15 TA NOTE: SolarEdge Power Optimizers ONLY to be used with SolarEdge Inverter, as specified in this drawing. The following string limitations apply, based on the Inverter Selected. Inverter Input Bus Voltage at Specified Interconnection Voltage: 350 V Maximum Power Per String: 5250 W Minimum Optimizers Per String: 8 Inverter Information _ Manufacturer Name: Solar Edge Module Model Number: SE 3000H -US Nominal Power Output 3000 W Maximum AC Power Output 3000 W Maximum Continous Output Current at Specified Interconnection Voltage: 12.5 A `�e►►e a ► s s � rrrr6�s % � O N d S BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-30 SHEET NUMBER: 30 OF 38 cava. F{lFed�E2 ��+aa�� • C � • PHOTOVOLTAIC POWER SOURCE WARNING. • 1PAN�Id WARNINGWARNING S1=Ct3NC3 SOURCE IS PV SYSTEM LLLG'I'P,I(' AL SHOCK HAZARD own ft—!7FW;NAi,s ON SOT! 1 _i`'4Er ND ^=,`lc,iT14f-` SY TE!)i A, PEt ����, C,��i � # °<'�I.L k ; J°v E L C,A[ Si4 FutA y t r__ F lE?C ti? ", a S�"vFR: t2cC 9g ', tIPCtt!Es+d E 1 3. • CAUTION- SOLAR CIRCUIT CAl.I1`It�N T • - < • PV srS-aEM cdRcU=c 6REArcER as mac: �cFtv • � • ` � ' • � i FAI WARNING: I 1I''UUARNING %�� DO NOT DISCONNECT � � • � TURIN OEE PHOTOVOLTAIC 5 - - �--L,-ii�,JCAL SHOCK HAZARD UNDER LOAD AC DISCONNECT PRIOR TO DO NO I ,OtlGH ALS, . • n •PHOTOVOLTAIC AC DISCONNECT T7-R?VJ,1AL3 OfBOTH I IN AND A WORKING INSIDE PANEL FAF'j WARNING v -OAC ^i,0E-, ElAY BE Et4-RGIZE I PNOTOVOLTAIC AC DISCONNECT FG' Ths '"apkN PDS i e p y ` Wi A-RNIN0-� /�i� WARNINGFATURN OFF PHOTOVOLTAIC FAJ _ LEGTI, `�,C HAZLRL, • • • • • AC DISCONNECT PRIOR TO a,HEC CC'ND-K 3ORS0P IHG 3 1► • # , : • E . WORKING INSIDE PANEL • A, %If,,V ISE ICER IZEJ • PHOTOVOLTAICFA WARNING FAI i11ilARNIN d fiAl CAUTI£ N: FI-ECI'P,�- -H�X HAZARD DC DISCONNECTO SOLAR ELECTRIC SYSTEM CONNECTED 10 - r . - :11 FHr DL' ONOUr TORS O IPI • r MAIN PV SYSTEM F WARNIN PV • r WARNING DUAL P£a---R,SJJRrf 1A 1 SYSTEM DG DISCONNECT ONlVEGT LECTRICAL SHOCK HAZARD SECONDSOURCE I v Y TEM A DISCONNECT ECT DO 0rTOUCHTEFMINA�-' WARNING PAR E P�fil�=�c���� F.r: ��� �L� NeOTHLlrt AANQ REVISION: 0P t3ATlri0' VOLTACE !! i �-OA a SIDES MAY F IFP {ZED ELECTRICAL SHOCK HAZARD IN !i `OPENpos;-ri�w•� I)pNor TCuctiTERMINAL,; '. • TERM NAtS ON BOTH LINE AND �t �f? lac d�;T _ J�?_a._;,, . < •. !! LOAD SIDES MAY BE ENERCULU � 1 i • i M -I _ • • • CAUTION: IN Ift OPEN 11051 ON SOLAR ELECTRIC SYSTEM CONNECTED DC VOLTAGE IS ALWAYS PRESENT "A WARNING WHEN SOLk4i�fifViOC�tLES PHOTOVOLTAIC ARF h E POSIFI)'TO SUNLIGHT TURN OFF PHOTOVOLTAIC �< AIS DISCONNECT AC DISCONNECT PRIOR TO SOLAR DISCONNECT ', •+ WORKING INSIDE PANEL gfm- 7 m . < AC y , /i ilk WARNING t !+ MAIN PV SYSTEMSHEET TITLE: AJERte.OD V n!7I N L�L� IKI AL iIOC HAZARD PHTOVOLrAiCAcDFSCC�NNDtT DIS{� NECT ! . •, !l tuRTdRl IJ�T� _ _ TERMItAFS t POTV LINE 1110 p r `t , . E -JI r! SHEET NUMBER: 31 OF 38 The markings shall be of sufficient ","r - /� ON NORTH SIDE OF BUILDING durability to withstand the � r , Tram nu -ram ypr *Nt _-,- 0 2[E� NEC 234 t€�0 55900 � _ � o)_ environment involved. NEC 110.21 .rt�trrrr rr,���.,r1,rt�,b ae��rtyr� THIS PANEL FED FROM INV 1 MAX AVAILABLE FAULT CURRENT, 46,552 AMPS 1d -ITE Elea,_- erre c,J 1p', ,r, *b� 'pilld� f �y l L r -d� � i t � =; i ela Syr 7 DATE 2/15112 T m �.�.f h b The materials �.���'�l.A ��r mC�r��n� shall r r iIh n NE� '� _r Q r9s;e Vii, l � ���"� ,�i-�A�71iar ,[ire �t;�L 9 I:_�f)�.��i,� � .. _s, RA � ...,..... {J� (f,mv in unit.t-Wp>rt',,J[0�r� th r r� r froo"id rN 0 *NEC110 AI Part No55 reflective, weather resistant ,and suitable _ �rr ,".sc Eia '-i ansa ir-,f,i mA,nal lakAir;n for the environment." IFC 605.1 1.1.1 cava. F{lFed�E2 ��+aa�� • C � • PHOTOVOLTAIC POWER SOURCE WARNING. • 1PAN�Id WARNINGWARNING S1=Ct3NC3 SOURCE IS PV SYSTEM LLLG'I'P,I(' AL SHOCK HAZARD own ft—!7FW;NAi,s ON SOT! 1 _i`'4Er ND ^=,`lc,iT14f-` SY TE!)i A, PEt ����, C,��i � # °<'�I.L k ; J°v E L C,A[ Si4 FutA y t r__ F lE?C ti? ", a S�"vFR: t2cC 9g ', tIPCtt!Es+d E 1 3. • CAUTION- SOLAR CIRCUIT CAl.I1`It�N T • - < • PV srS-aEM cdRcU=c 6REArcER as mac: �cFtv • � • ` � ' • � i FAI WARNING: I 1I''UUARNING %�� DO NOT DISCONNECT � � • � TURIN OEE PHOTOVOLTAIC 5 - - �--L,-ii�,JCAL SHOCK HAZARD UNDER LOAD AC DISCONNECT PRIOR TO DO NO I ,OtlGH ALS, . • n •PHOTOVOLTAIC AC DISCONNECT T7-R?VJ,1AL3 OfBOTH I IN AND A WORKING INSIDE PANEL FAF'j WARNING v -OAC ^i,0E-, ElAY BE Et4-RGIZE I PNOTOVOLTAIC AC DISCONNECT FG' Ths '"apkN PDS i e p y ` Wi A-RNIN0-� /�i� WARNINGFATURN OFF PHOTOVOLTAIC FAJ _ LEGTI, `�,C HAZLRL, • • • • • AC DISCONNECT PRIOR TO a,HEC CC'ND-K 3ORS0P IHG 3 1► • # , : • E . WORKING INSIDE PANEL • A, %If,,V ISE ICER IZEJ • PHOTOVOLTAICFA WARNING FAI i11ilARNIN d fiAl CAUTI£ N: FI-ECI'P,�- -H�X HAZARD DC DISCONNECTO SOLAR ELECTRIC SYSTEM CONNECTED 10 - r . - :11 FHr DL' ONOUr TORS O IPI • r MAIN PV SYSTEM F WARNIN PV • r WARNING DUAL P£a---R,SJJRrf 1A 1 SYSTEM DG DISCONNECT ONlVEGT LECTRICAL SHOCK HAZARD SECONDSOURCE I v Y TEM A DISCONNECT ECT DO 0rTOUCHTEFMINA�-' WARNING PAR E P�fil�=�c���� F.r: ��� �L� NeOTHLlrt AANQ REVISION: 0P t3ATlri0' VOLTACE !! i �-OA a SIDES MAY F IFP {ZED ELECTRICAL SHOCK HAZARD IN !i `OPENpos;-ri�w•� I)pNor TCuctiTERMINAL,; '. • TERM NAtS ON BOTH LINE AND �t �f? lac d�;T _ J�?_a._;,, . < •. !! LOAD SIDES MAY BE ENERCULU � 1 i • i M -I _ • • • CAUTION: IN Ift OPEN 11051 ON SOLAR ELECTRIC SYSTEM CONNECTED DC VOLTAGE IS ALWAYS PRESENT "A WARNING WHEN SOLk4i�fifViOC�tLES PHOTOVOLTAIC ARF h E POSIFI)'TO SUNLIGHT TURN OFF PHOTOVOLTAIC �< AIS DISCONNECT AC DISCONNECT PRIOR TO SOLAR DISCONNECT ', •+ WORKING INSIDE PANEL gfm- 7 m . < AC y , /i ilk WARNING t !+ MAIN PV SYSTEMSHEET TITLE: AJERte.OD V n!7I N L�L� IKI AL iIOC HAZARD PHTOVOLrAiCAcDFSCC�NNDtT DIS{� NECT ! . •, !l tuRTdRl IJ�T� _ _ TERMItAFS t POTV LINE 1110 p r `t , . E -JI r! SHEET NUMBER: 31 OF 38 Site Condition Assumptions Conductor Schedule Conduit Schedule Interconnection Frequency q Y 60 Hz Circuit Reference Ip Circuit Description Conductor Type Conductor Material Conductor Size Design Current OCPD Type OCPD Rating Conduit Schedule . Noof Current Carrying Conductors Conduit Type Conduit Size and QTY Voltage -Line 1 to Neutral 120 V Voltaeg - Line 2 to Neutral 120 V CI -1 PV Source Circuit PV Wire Cu #12 AWG 9.28 A N/A N/A C0-1 2 PVC %4" Voltage - Line 3 to Neutral (If Applicable) V CI -2 PV Output Circuit PV Wire Cu #12 AWG 15 A N/A N/A CO -2 7 x 3 PVC 3 x 1-1/2" CI -3 Inverter Input Circuit THWN - 2 Cu #8 AWG 45 A N/A N/A CO -3 3 PVC 3" Voltage - Line 1 to Line 2 240 V CI -4 CI -5 Inverter Output Circuit Service Feed Conductors THWN - 2 THWN - 2 Cu Cu #8 AWG 2 x #2/0 AWG 40 280 A A T. P.C.B. T.P.C.B. 50A 400A Voltage - Line 2 to Line 3 _ V EQ1,EQ2 C Boner EQ3 Optimized String of 17 Modules Optimized String of 17 Modules Optimized String of 17 Modules Combiner Box EQ3 � I Optimized String of 17 Modules I Optimized String of 17 Modules Optimized String of 17 Modules I Combiner Box EQ3 I j Optimized String of 17 Modules I I I I Optimized String of 17 Modules I I Optimized String of 17 Modules Combiner I Boz EQ3 CI -3 CO -3 EQ -1 0 Optimized String of 17 Modules I I I Cl -5 CO-1EQ-8 Optimized String of 17 Modules r—_ DC Wireway Optimized String of 17 Modules — ---- J Existing Meter Combiner Box EQ 11 Q Optimized String of 17 Modules EQ -9 Optimized String of 17 Modules Optimized String of 17 Modules ----_1 i i i Inverter i Inverter i Inverter i Inverter i Inverter i Inverter i Inverter CO- g — Existin Electrical Combiner EQ3 i l i i i i i i i C I -4 Service Box Optimized String of 17 Modules I I I I I I I I I Optimized String of 17 Modules I I DC AC DC AC DC AC DC AC DC AC DC AC DC AC I I I I I I I I I % Optimized String of 17 Modules -77 I ( Integrated I Integrated I Integrated I Integrated I Integrated I Integrated I Integrated I EQ— —------� i Disconnect i Disconnect i Disconnect i Disconnect i Disconnect i Disconnect i Disconnect Combiner E Q 3 New Box Solar Optimized String of 17 Modules I Service i Panel Optimized String of 18 Modules AC Wireway I Optimized String of 18 Modules J EQ -10 EQ -6 Voltage - Line 3 to Line 1 - V Environmental Assumptions Minimum Annual Temperature 20 C Maximum Annual Temperature 35 C PV Module Information Manufacturer Name: QCell Module Model Number: 315 G5DU0 Maxium Series Voltage Allowed: 1000 VDC Temperature Coefficent - Voltage -0.28% per °C Temperature Coefficent - Current 0.04% per °C Temperature Coefficent -Power -0.37% per °C Specifications at STC MPP Power - P m p 315 W MPP Current - Imp 9.55 A MPP Voltage - Vmp 32.98 V Short -Circuit Current - Isc 10.04 A Open -Circuit Voltage - Voc 39.87 V Temperature Adjusted V m Min p- 32.06 V VOC - Max 40.42 VI DC Optimizer Information Manufacturer Name: Solar Edge Module Model Number: SE P320 Rated Input DC Power: 320 W Maxium Input Voltage 48 V The Drawing Below Details the Assembly of PV Modules, and Power Optimizers to form what is otherwise referred to as an "Optimized String of Modules". Equipment Schedule Maximum Short Circuit Current: 10 A Maximum Output Current: 15 A Component Description Manufacturer Model Number Notes NOTE. SolarEdge Power Optimizers ONLY to be used with SolarEdge Inverter, as specified in this drawing. The following string limitations apply, based on the Inverter Selected. EQ2///12 EQ2 C12 P300 Power P300 Power Optimizer Optimizer EQ C11 EQ I-1 \ ; Solar Solar Photovoltaic Photovoltaic Module Module EQ -1 Solar PV Module QCell QPRO-265 See Module Information EQ -2 DC Optimizer SolarEdge SE P300 See DC Optimizer Information EQ -3 DC Junction Box N/A N/A NEMA 3R - Outdoor Rated Inverter Input Bus Voltage at Specified Interconnection Voltage: 350 V EQ -4 Integrated Disconect SolarEdge N/A Disconnect Integrated with Inverter Maximum Power Per String: 5250 W EQ -5 Inverter SolarEdge SE14.4k-US See Inverter Information Minimum Optimizers Per String: $ EQ -6 New Solar AC Combiner GE See Page EQ5 for Detailed Specs Inverter Information EQ -7 Existing Electrical Service N/A N/A 400A Main Breaker - 3PH 208 - NEMA 3R EQ -8 Existing Meter Enclosure N/A N/A Meter to be Replaced with Bi -Directional Net Meter After Installation Manufacturer Name: Solar Edge Module Model Number: SE 14.4KUS EQ -9 EQ -10 Insulation Piercing Splice Connector NSI IPSC4002 See Page EQ6 for Detailed Specifications Nominal Power Output 14,400 W New Wireway N/A N/A NEMA 3R - 10" x 10" Maximum AC Power Output 14,400 W Maximum Continous Output Current at Specified Interconnection Voltage: 40 A w 0 BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-32 SHEET NUMBER: 32 OF 38 Existmi n Service Detail Connection to Existing Electrical System via insulation piercing splice connectors. L n BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-33 SHEET NUMBER: 33 OF 38 x a m n n n O >o 0 E � �q �U LLJ Q w a- co �W L n BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-33 SHEET NUMBER: 33 OF 38 Product #- TriA, 1 212RC U UUCUL Listft Phase I" Space. IfT Space Feed Dow GSA Compliance GO Sc hedu le New Solar Service m Eauiament Saecifications Single Phase - U: 120240V a::c Standard 22 125A, Main Breakjer 0 utd oGr Ty pe 35P, En cios- u re UL I P h as e,. -12 24 Top N 'Yes RD G7,&31-6411307 List P.,rx,-e S512 �Otil E OF L ONAI v4`%� Aa4 LLJ D CD Q-1 n BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E- 34 SHEET NUMBER: 34 OF 38 gm C) CQ CQ � �o 0 0� �Q o� Cl- L.Li o. ch� Cl - �W LLJ D CD Q-1 n BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E- 34 SHEET NUMBER: 34 OF 38 TUKI I_PEAK,Bii�G5 , QMW TENNUMt LOW IMILISig Cow Of ELECIRMY 144#ier yield per surfwe area, lower 1305S costs, hiew pmer claisses, and an offidency rate of up to 19.9 %, 11"Wam A"EMM TECIOMLM Optimally!", woat-werte-weathef with excellent law-hgfti and tempewure bebaviour. ENDURIN G K04 PEAFORMANC! Long-term yield sec-unty with Ant LID TA-chnolqU, Anti PID T4 Techfmlote, 4m -Spot Protect and Traceable Qual'q Tra,QTIO, EXTRZEMEZE WEEMARM11"hij High.490; alumin�urn aticy frame, c�erljfied for high snow (5400, Pa) and windbads 14130012,a).. A REQ: 1A & LE i fil Inclusive, 12 -year preruct warranty and 215 -ye zg finear parfoam,ancG warTanW. SWE OF TW ARTMCCIDULE 1 1 U0 combines catng edg2 cell separation QANTUIM D and inn ativ P- w i Ting Frith Q.A NT M Tac h no fogy, T14E IDEALSOLUTION FOR; FW'.ftt%f grar,'m raddail ir pi 11,1111, 1111111111111111 �7jcci-*T "I r" camurn hd I In auxt ill Solar Panel Specifications *WvMm-=V- Q 4I. -ti-fiT ART ME cKM ax-r-00mg P) I Ea, r5'Gz8C--A -!!:sol E" freltv-1 B (-,] W-1, V. I )I 1k S -era o a ta vielat u r, rear is lunner InNomimia I- M-W '01 F'senn"a t I G&I rTm -x INN mm ic 32 mm (m dudmE !`ire) wt-4ta 18.7 ag Rae, Gavel.7,mm thermnN pre-snewstd gimawa Wit reRectwn t&-�RO'Ca Ilk C"a #W Campewte hirr, F-joe 13twx anadimd alurwium C0.01 G x 20 rwrrocryst2W m OWNTIM "ter twi crit:, junafiza tox I Ot Mr. mm" x % M MM x 13-2 1 'T1 1r, a Nube--tiun cctjr,-� IPEI� with bypamm diades. Caue ,- m, �-) I IGU, m- i 4,mTn-- Sciar ttablr(4-11.100m Casn"Abot Mdri-Canfac!, IOU-, IP65 Affl" QW; YAW11MIN AVO KE AT STAMAWD T WN11TIONS, STEI 41PIN 01 TrAERANCE +5W 0 - OW) power'm MR 7 pw tv 3 JIEI -3 � 1.7. a 5 a cftf" tT C W I C U IT* 4e fig JAJ 10-04 IGM19 E DW cirri ft wV1111 (y) YIN x.13 40, 40 M" eft a� vpp*, 44" 141 9 L 5 gJ60 9.06 Voltale at VA" r1W 1 5198 33..-2 3. G.5r Effl- Clel-q, T1 C%' I 1' I r9.7 19.0 V4 j V/Z W10 W, 9N F 9fiam'Am AT Mm"M 9FEMW CM IT -0 N 5 WA": RNK Ir WP V PWF nN I 12J) 3. 4 237.2 24, 9 E 54vt LfruAt Carrev, Ai Opp Cirruff vrilapo yff IV 3 3 1 1;4 37119 Ment a MPP 6W IA J 7AZ 1.0 V Wile at MPP va" IF) 31.97 31-39 31.70 JUT&M i" Z!� %'� 4unrin A M 111. W gm -P, "mirraun'u-'rumm, it-, "T a., C • S"L AOM AW 0, M 1.4' Q +?(FACK VAIm, 0=0 VALS5 au (1call fEWWWWE WAIRANTY PERPURNAKE IT WWWRAMAKI Its k P"', 9-8 1k ig randl,� " jxw; r aj'n-e' T ------ I MM yaw. T havM tw mw 0 74% IE E' gqw=m F& y, Wr k " 93 2 % at UWMW W"r sp In Wyams. Al W" 85% ro mm" Ix" lqkm 22%yzvs� bvt Wwrl" umn. at M O&SOM 33C 1 Un U. 931 31.9e 2 19,ft 244-C 32.111 VDIC -Gimft TAW*C'-nM6=54W.7L MC 63 7" *d V, A 9WCW loci Cbm A Tt" Gel cit U EWW3&11, VOTE- 1,--allar-un tnsJrcffwmFlu 3t be b*wmd. Um t15 s73191jten/ and u mama0cycamm-1 Lw W=tel EzI savtrx z--rwnt ftt bytAw 1ntw7ndam or jfqr--Awj fmbrAabor, a MA Mau t th ts Senn urAh'`1-rt' 06mfi air rt- I TD- a-43 J C(aggA 4-fi 99"7 1 r1 *-419 jUi 3A-44 66 -49 -73CC-C I f M 61L.WMnAWj- t3tfl&--m i lik E i W%% Frig,imeered in Germany A 'ki BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-35 SHEET NUMBER: 35 OF 38 cmpvbm it 5 TC amdrt-*m Q5 1C I WO Wrf TTEMAPRATIAE COEROXF1 Ta M pe, me re -r. Geff&eft of 01 a ry-Al T e m/p rm-, -e rzo. ff Irc Iie ot & V [%I KI Tem perjtum,CcteffV' of Pw, 'V r -AA -1 -a-3f W.M1 o'"mang i Te-spe-rarr"t NXT T 4 G PROPERTIES FOR SYSTEM DEWN Wamum sruemyo"I V= tvi 1000 S" C[3&5 VMMUM Rz-vp-rsA- f9 oil 7n Rre R.Ping Puslfftll Lan Ift] 54-0014 eMt W-1 Meftle TeMperMire 40 A. UP tO ALM (Irp-m-, I a a d M 3 C C Wa M &'F W, I t h I E G 6Q21 5) on Canuffungtomy VDIC -Gimft TAW*C'-nM6=54W.7L MC 63 7" *d V, A 9WCW loci Cbm A Tt" Gel cit U EWW3&11, VOTE- 1,--allar-un tnsJrcffwmFlu 3t be b*wmd. Um t15 s73191jten/ and u mama0cycamm-1 Lw W=tel EzI savtrx z--rwnt ftt bytAw 1ntw7ndam or jfqr--Awj fmbrAabor, a MA Mau t th ts Senn urAh'`1-rt' 06mfi air rt- I TD- a-43 J C(aggA 4-fi 99"7 1 r1 *-419 jUi 3A-44 66 -49 -73CC-C I f M 61L.WMnAWj- t3tfl&--m i lik E i W%% Frig,imeered in Germany A 'ki BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-35 SHEET NUMBER: 35 OF 38 DC Optimizer Specifications Power M :iY Optimizer (for 1*1811-Pr~'Er Power Optimizer P320 P370 P400 P405 P505 f ......... . .. .......... .. ......... . . . ...... . ............ . . Yes b n PV power optimization at the module -level t 25% more energy Mitigates all typees eof mmoidule r tch 10'rres, from mnl.Jatuntol�eanrL .partial sdng - Flexible- 5k 5tem des4grt for maxinmm Space uhfization Fast install ` n vAth a sinele Dolt ISA gei-teration ffwaintenance vifth Elie -[anal I- for r - Compliant with arc fault pTotection and rapt stwtd to NECrequirements (1 installed a5 part of the ScaiarEdge- garter Wdule-le-velv)ltage stwtdown for installeef arvd fighter safely Maximum Allo ed Sr te-n 'a°ottaSe ,.... Pathe inverters „ limen *ions JW ax L x H InpL:t Con nectar .:gLtp :t Wire Ty Connector 0IJtP <t Wire Length Protection dating (teltive flume .... .. .. ... ........... .. . 04 Hatad STC af t* w- t5 q 1 Vdc ........................,.,....,.,.....,,...,,,.,.,,.......,........,,..,..........,....... ... .. .. ,... ., .. ., ... >.. ,, All ► �c Phare ,.r Three Phe iry erters € ............. .. ..... .. .. .....,. . 129r15�x36,� 128x152x50f � 12Sx:152x59a :�15�x���x5.�a x1.1 €, ....., rnm in ......122 5x397xIA2 5x5 7x196 5r597x232 , MCAS Double lrt ul2ted 095130 I 1-23..9 Mft .. .. .. ... .. .. .. ... .. ..., .. .. .. .,. .. .. .. ,.. .. .. ., ........>....,............................, ,. ,. ., ... .. ,, ..> -# -1�5 -• - +ilk ............ .. ......... ..... .. . .. ...,. C % +F IP69 NP#I i6P - 0IDG mow 000wft +fes PV SYSTEM DESIGN USING SINGLE PHASE SINGLE PHASE THREE PHASE 20TV, THREE PHASE SOLARED E I EftTEI� H AVE . inirniiString Leng n P32� I�3TI�r R�4Iti 'P&Wer optirni:ey-s£..., .. I.P 5 11505 Max; Munn String Lergtf Ma,idmurn Power per String 25 SE76OD-US - SE'.14&&- 5M 115 � 1 P2mIlel Strings a Different Lengtf Yes; E� F�r'rtifka� t?LYj .. fca�rr�irl�:a� ref �.r �'.�%:air yiart}i.�tu�,rt91�', 25 F M %ittIF1ttr11�e 1F e.• I` Y iy_ a.a tee, ��. '•.,� G�;1©�;.� �+,�/-,,y�: �'rtr7NAL S-1-4 s''�`i10l1f11`��+ BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: 6-36 SHEET NUMBER: 36 OF 38 Inverter Specifications with HD -Wave Technolog% for North America SE3000Hi1 X11 r M -US S • M i 0 Optimized installation with HD -Wave technology �.._�.�.�......µ�....._...,��e�W OUTPUT Ficyed voltage longer strings �.t1'� I me grate d arc,. It proteectiol and rapid shunt m forNEC 2,014 ani 201 7, per agile X0.21 rv/690.%2 WO € 3 I. 7 i 5 S�PiiD '..,....,.,.,,. IILVJ }' U"-1741 SA #d oir CPUC Rule 21 gridc)s,i"nnpliance ., ....... .............. 38W Zit V � ..,,..,, � flow 4F 240V w, Extremely snm/111 M2X_ AC POW&F 0 Utp Ll 3WO High r� l l ty witIvout arvy 6ectrotyl.'r, r ,.pato NOW 11400 ,01 AC Oatl�sut pottage Min. -Nom: -Max. , Built-in mule- i�3�e 6061 t in � vac Outdoor ani indoor i ` l tl n Optional, ew-pe gam& data, ANSI : 2.20 Class 0.5 JO.5% accuracy) ) AC Mitput vlattage min -(damn.-". Single Phase Inverter solawith H ' -Wave r Americ • q 6111 1111 r SSE � ' SE7 F1 1�5 SE1�JJ1°1 x.15 �E1 SE tl s (SE3'ItIEI-S SE 115 � �.._�.�.�......µ�....._...,��e�W OUTPUT w �.t1'� R;j*&6, AC giver Output WO € 3 I. 7 i 5 S�PiiD '..,....,.,.,,. IILVJ }' Val ., ....... .............. 38W Zit V � ..,,..,, � flow 4F 240V M2X_ AC POW&F 0 Utp Ll 3WO 7600 NOW 11400 VA AC Oatl�sut pottage Min. -Nom: -Max. , .... . .. . . . ... � � vac AC Mitput vlattage min -(damn.-". J' vac f41-�- ...... ..... ................ . ... AC ? 3I N ..< ixSn`.R#�E�1 a,rtarw"''au bIJtpLtC..Lrren .....£.. ,.<, 16 24 , A M21410rsL°em P3r'st n _ia OL pLt C.i 'rertt FDI7 ,,e ...................<,..,,.,..,,.,.......,,.....,,..,......,.,..,...,.,.........,..............,...,...... ............... 11t11etj Monitcwin& lslar ng Prvtectlon, Yes ..,.. Cour='E y CREEP- -L?€a' li Thrc "i tolds m, _r _ e Maxt"fiLerFt DC Power @Q401ry 46,50 5900 7750 ...... . <, 1 ..... hd Mahn m Powe �il��� , < - 51i9�Q - iiS+D d"' 8 M2XiFriLM In i t Ct�rrca�t � _ y' _ - NfaximuminLt rrerta ' 1 ....... rv,ax_ Ir15Lt5 rt Circuiturrent .....�... .... ., ,,..,. ...................... 4_`b <,<,....,<................................... ....,.. ......3Q5..,.,, .,,alk.,., 14�c „ ,....... I$e�rerse.; ,,lar` �t�a^�eciic>ri �'es .................................................. tr rdE c Isolation Den<,...<,. I�, t3rtacn...............,...,..,...........,..,.<..,.,... A4,2XiMU tirt�aertefEi enc ..,,,.,,,... lli&, ..,,.,....,..,,,........,...............,....<..,...,...<, ei rt 1 ''t -•i_ ., .............................<,.,,,,.,....,... .......................°.,....,.....,,. ,'..... .<. 1MTI N LAT RES Syppp r ed � rL e tion 1ntrrb#ces RL-vc-n a r. e Data ANSI C12.20 ft £ ter s,ct i ce ,+apt+ al i[ula { I E 1,1 l kutoma,tic Rapid Shutdsayin £upas: AC Grid Discxmroeet 4 STANDARD CXWPUANCE S2fets1.!11741 U1741 Sk UL1699-8,. CSS# C22-2, Canadian AFC arc; trs T LL M-07 Grid'i onnection 5 rdarCs VE Rule 21, Kulee 14 1� i, Fnvmons FCC,P2rt 15 Class B INSTALLATION SPECIFICATIONS wt L- i.Zii�c�1S.€'€ 4.£tf�CiL T �I'*+e f i�idwi4g t'$.i�f S tC Input Conduit Rze I # of Svings A Dimersions vrithh S25&,y SWitCh (F1KXDl ,..tea ... ...... .. ... .. ............... .... .. .. dc�tse +�perartln•'�m Ra „ 314' minirnum/1 t 4WG 344' rminirma i14-4 AWG 3,x4- minimum / 1-3 strings I 3W minimum /1-2 strings A 1a0-6 ,� -6 AWG ,.. ,.<...................... ......... 2i..3x1�.�ax�v3,�54�61sz3T� 17,7 x 111._6 x &1,� 450 x 374 x 174 x 105 in j mm 22110 7 11.11 2Ei :11,. �c 25 �c5+D< d8A ...... Nartral'tre1; hlaUt clvtctaal 13 tai +1401-5 tour j. +I F # d0 E i .. . ..................................... ....................... ......:........ !,,.........,..........,...,......,... , ..,, iEMA 3Rrerter with Sit�h.�, < to* mow. /WWbMdiW.4 BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-37 SHEET NUMBER: 37 OF 38 N 0 Insulation Piercing Connector Specifications_ 001 1 T4 T r, IT=1 Wire Size: 440-3AING (f0a.in) Tap Size: 2-10 A�*VG "' S M P ) - 150 (AL Am p s) Amperage Rating: 190 1"Cu"!, Dimensirins: L--2.2 0 - Vli— 1. 8 0 - H=3.10 SpFacial Features: No need to strip wire - No tape or cover needed - Exclusive turbo spacer keeps tap side open while main conduclor is being tighteened: Splice, Tap Power Connectors Black Thermal Plastic Fiber Reinforced Thermal Fl3StiC C I a m p 90 C 600 V 90 C UL 00B Listed C) ry BY: BDD DATE: 8/29/2018 REVISION: SHEET TITLE: E-38 SHEET NUMBER: 38 OF 38