HomeMy WebLinkAbout814 Pecan Ave (A) 12-909NOTES & SPECIFICATIONS: GENERAIL NOTES: 1. DO NOT SCALE THESE DRAWINGS, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO CHECK ALL DIMENSIONS AND VERIFY THE BUILDING CONSTRUCTION LAYOUT PRIOR TO COMMENCING CONSTRUCTION. 2. FOR ARCHITECTURAL REFERENCE, ELEVATIONS SHOWN HEREAFTER ARE BASED ON ELEVATION 0'-0" AT BUILDING FIRST FLOOR FINISH FLOOR SLAB. 3. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO FAMILIARIZE HIMSELF WITH ALL EXISTING CONDITIONS. ALL EXISTING CONDITIONS ARE NOT NECESSARILY SHOWN HEREON. 4, ALL TRADES SHALL BE RESPONSIBLE TO READ ALL DETAILS AND SPECIFICATIONS AND PLANS, IF ANY CONFLICT EXIST, THAT TRADE SHALL NOTIFY THE CONTRACTOR OF THE SAME PRIOR TO CONSTRUCTION. 5. CONTRACTOR SHALL DIRECT ANY DISCREPANCIES TO THE ARCHITECT PRIOR TO CONSTRUCTION AND CONTRACTOR SHALL BE RESPONSIBLE FOR WORK WHICH PROCEEDS WITHOUT DUE COURSE AND COORDINATION. 6, IT IS THE RESPONSIBILITY OF THE CONTRACTOR/ HOMEOWNER TO REVIEW THE CONSTRUCTION DRAWINGS TO VERIFY ALL ASPECTS OF THE DRAWINGS FOR ACCURACY. NO BACK CHARGES WILL BE ACCEPT FOR ANY REASON. MECHAMCAL NOTES 1. THE DRYER VENT SHALL NOT EXCEED 25'-0" IN LENGTH. THE MAXIMUM LENGTH SHALL BE REDUCED 2.5 FEET FOR EACH 45 -DEGREE BEND AND 5 FEET FOR EACH 90 -DEGREE BEND. FBC M1501.1 2. ALL AIR RETURNS MUST HAVE FIRE STATS. 3. A/C UNITS SHALL HAVE A MIN. OF 4" CLEARANCE ON ALL SIDES. PLUMBING NOTFS- 1. WATER HEATER T&P RELIEF VALVE TO BE FULL SIZE TO EXTERIOR. 2. WATER HEATER AT FLOOR LEVEL TO BE IN A PAN WITH DRAIN TO EXTERIOR (WITH THERMAL EXPANSION DEVICE). 3. SHOWER FIXTURES SHALL CONTAIN TEMPERATURE CONTROL VALVES. 4. ALL HOSE BIBS SHALL HAVE BACKFLOW DEVICES. ���TCAL NOTES 1. INSTALLATION OF WIRING IN ANY EXPOSED AREA WILL BE IN APPROVED CONDUIT OR USE MC CABLE. 2. ALL OUTLETS IN SLEEPING ROOMS SHALL BE ARC FAULT. SHEATHING NOTES 1. NAILS USED IN ALL SHEATHING APPLICATIONS SHALL BE 8D RING SHANK HAND OR GUN DRIVEN. (FOR GUN DRIVEN NAIL, THE SHANK SHAL BE .097 - .099 DIA. X 2 1/4" LONG W/ 15/64' DIA. HEAD, FULL ROUND). 2. SEE DETAIL F60 FOR NAIL SCHEDULE FOR WALLS. IF APPLICABLE. 3. SEE DETAIL 16/7.2 FOR NAIL SCHEDULE FOR ROOFS. IF APPLICABLE. 4. FULL DEPTH BLOCKING SHALL BE PLACED 0 ALL SHEATHING JOINTS NOT OCCURRING 0 PLATES. 5. ROOF SHEATHING ACTS AS A HORIZONTAL DIAPHRAGM. FIELD REPAIR NOTES 1. MISSED LINTEL STRAPS FOR MASONRY CONSTRUCTION MAY BE SUBSTITUTED WITH (1) SIMPSON HTSM18 STRAP W/ (4) 1/4" DIA. x 2 1/4' LONG TITENS TO BOND BEAM BLOCK AND (8) 10d x 1 1/2' GALV. NAILS TO TRUSS. (MAXIMUM UPLIFT VALUE 1175 LBS - CONSULT WITH ARCHITECT IF REQUIRED UPLIFT VALUE IS GREATER). 2. MISSED "J" BOLTS FOR WOOD LOAD BEARING WA S MAY BE SUBSTITUTED WITH 1/2' DIA. THREADED ANCHOR BOLTS SET INA 5/8n DIA. x 6' DEEP HOLE FILLED WITH"U.S. ANCHOR" ULTRA BOND OR "SIMPSON EPDXY-TIE SYSTEM FOLLOWING ALL MANUFACTURER'S RECOMMENDATIONS. (OR 1/2' DIA. x 5 1/4' LONG "REDHEAD" OR 'HILTI" STUD EXPANSION ANCHOR BOLTS FOLLOWING ALL MANUFACTURER'S INSTALLATION PROCEDURES. 3. MISSED DOWN RODS MAY BE SUBSTITUTED WITH #5 REBAR SET IN 3/4" DIA. x 6" DEEP HOLE FILLED WITH 'U.S. ANCHOR' ULTRA BOND OR "SIMPSON" EPDXY-TIE SYSTEM FOLLOWING ALL MANUFACTURER'S RECOMMENDATIONS. 4. CONTRACTOR MAY SUBSTITUTE HURRICANE STRAP FROM THE ARCHITECT SPECIFIED MANUFACTURER WITH STRAP OF GREATER HOLD DOWN VALUE OR GREATER UPLIFT VALUE (MEETING SHEARING VALUE OF ORIGINAL SPECIFIED STRAP) IN FIELD WITH OUT VERIFICATION, PROVIDED THAT ALL MANUFACTURER'S INSTALLATION INSTRUCTIONS ARE FOLLOWED. DRYWALL NOTES 1. GYPSUM BOARD FASTENER SCHEDULE. SPECS FOR 1/2" GYP. BOARD. 1. CEILING NAILS - 5d COOLERS ® 7" O.C., WALL NAILS - 5d COOLERS ® 8" O.C. GA -216 5.5, ASTM C 514 2. CEILING SCREWS - 1 1/8" LONG GALV. ® 12" O.C. WALL SCREWS - 1 1/8' LONG GALV. ® 12" O.C. GA -216 5.7, ASTM C 1002 2. ALL CEILING MOUNTED GYP. BOARD SHALL BE EITHER 1/2' CEILING GYP. BOARD OR 5/8' GYP. BOARD. GA 214-96 3. GYPSUM WALLBOARD ACT AS THE CEILING DIAPHRAGM. WOOD CONSTRUC'T'ION NOM: 1. ALL EXTERIOR AND INTERIOR BEARING WALLS TO BE NO. 3 GRADE KD SOUTHERN YELLOW PINE OR NO. 2 GRADE SPRUCE -PINE -FIR, UNLESS NOTED OTHERWISE, 2. STUDS SHALL BE SPACED AT 16' O.C. FOR ALL EXTERIOR BEARING WALLS. U.N.O. 3. ALL WOOD STRUCTURAL MEMBERS SHALL BE CONTROLLED STRESS GRADED LUMBER, HAVING A FIBER STRESS OF AT LEAST 1200 P.S.I. (Fb) 4. ALL LVL MEMBERS SHALL HAVE A MINIMUM ALLOWABLE BENDING STRESS OF 2,750 P.S.I. AND AN ALLOWABLE SHEAR STRESS OF 250 P.S.I. 5. INSTALL BLOCKING IN ALL WOOD STUDS OVER 8'-0" 0 MID -POINT AND SHEATHING JOINT. GENERAL STRUCTURAL NOM: 1. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF CONSTRUCTION INCLUDING VERIFICATION OF DIMENSIONS, ELEVATIONS, AND FIELD CONDITIONS, ANY DESCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO CONSTRUCTION. 2. CERTIFIED TRUSS SHOP DRAWINGS SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW I T SUBMITTAL AND APPROVAL PRIOR 0 5UB IIT L FOR PERMIT IF ANY CHANGES TO THE TRUSS DESIGN OR LAYOUT AFTER REVIEW BY ENGINEER, CONTRACTOR IS REQUIRED TO SUBMIT CHANGES TO ENGINEER FOR APPROVAL. 3. THESE DRAWINGS HAVE BEEN DESIGNED TO MEET THE REQUIREMENTS OF ASCE 7 AND THE FLORIDA BUILDING CODE FOR WIND REQUIREMENTS OF THE LOCATION OF THIS PROJECT. DESIGN SPECIFICATIONS ARE LISTED ON THIS COVER SHEET UNDER "CODE COMPLIANCE SUMMARY". 4. ALL DETAILS AND SECTIONS SHOWN ON THE DRAWINGS ARE INTENDED TO BE TYPICAL, AND SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. 5. ALL CONCRETE SHALL HAVE A MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF 2500 P.S.I. AT 28 DAYS FOR SLAB AND FOOTINGS. PROVIDE 3000 P.S.I. AT 28 DAYS FOR TIE BEAMS AND CONCRETE FILLED BLOCK CELLS. 6. GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3000 P.S.I. AT 28 DAYS IN ACCORDANCE WITH ASTM C1019 OR ASTM C476. 7. ALL MASONRY OPENINGS TO BE PRECAST, UNLESS NOTED OTHERWISE. 8. CONCRETE MASONRY UNITS SHALL BE IN ACCORDANCE WITH ASTM C30 OR C145 WITH MINIMUM NET AREA COMPRESSIVE STRENGTH OF 1900 P.S.I. 9. MORTAR SHELL BE TYPE M OR S IN ACCORDANCE WITH ASTM C270. 10. ALL REINFORCING STEEL SHALL BE NEW BILLET STEEL MINIMUM GRADE 40 AND IDENTIFIED IN ACCORDANCE WITH ASTM A615, A616, A617 OR A706, FREE FROM OIL, SCALE AND RUST, UNLESS NOTED OTHERWISE. 11. CONCRETE CAST AGAINST THE EARTH SHALL HAVE A MINIMUM CLEAR COVER OF 3" OVER REINFORCING STEEL. 12. REINFORCEMENT BAR SPLICES: X13 TIES AT 15' MIN., #5 BAR AT 25' MIN., #7 BAR AT 35' MIN. & W.W.F. AT 15' MIN. 13. STRUCTURAL STEEL SHALL CONFORM TO ASTM A36, EXCEPT TUBULAR STEEL COLUMNS, WHICH ARE TO BE CONSTRUCTED TO 46 KSI YIELD STRENGTH, ALL BOLTS SHALL BE A325 BOLTS, UNLESS OTHERWISE NOTED. WELDS SHALL BE PERFORMED WITH AN E70XX ELECTRODE. 14. ALL EXTERIOR AND INTERIOR BEARING WALLS TO BE NO. 3 GRADE KD SOUTHERN YELLOW PINE OR NO. 2 GRADE SPRUCE -PINE -FIR, UNLESS NOTED OTHERWISE. 15. ALL WOOD STRUCTURAL MEMBERS SHALL BE CONTROLLED STRESS GRADE LUMBER HAVING A FIBER STRESS OF AT LEAST 1200 P.S.I. (Fb). 16. ALL LVL MEMBERS SHALL HAVE A MINIMUM ALLOWABLE BENDING STRESS OF 2,750 P.S.I. AND AN ALLOWABLE SHEAR STRESS OF 250 P.S.I. 17. ALL SUPPORTING FOUNDATIONS AND PILINGS SHALL BE PREPARED AND INSTALLED AS PER SOIL DENSITY TESTS AND BEARING CAPACITY SHALL BE VERIFIED TO PROVIDE A MINIMUM ALLOWABLE SOIL BEARING CAPACITY OF 2,000 P.S.F. PRIOR TO POURING FOUNDATIONS OR DRIVING PILES. 18. FILL FOR FLOOR SLABS SHALL BE PLACED IN 12" LAYERS AND ROLLED AND COMPACTED TO MINIMUM FIELD DENSITY OF 95% AS DESCRIBED IN ASTM 1557D. ALL FILL SHALL BE CLEAN SAND, FREE .OF ORGANIC OR OTHER DELETERIOUS AMTERIALS. 19. ALL SECTIONS OF C.M.U. GREATER THAN 4'-0" IN LENGTH AND UNBROKEN BY OPENINGS ACT AS SHEAR WALL SEGMENTS AND INDIVIDUALLY PROVIDE BRACING FOR ADJACENT WALL FORCES AND MAY BE ASSUMED TO TRANSFER THRU BOND BEAMS TO INTERIOR SEGMENTS. 20. STAIRWAYS SHALL BE EQUIPPED WITH HANDRAILS LOCATED NOT LESS THAN 34" NOR MORE THEN 38" ABOVE THE LEADING EDGE OF A TREAD. 21. STAIRWAYS SHALL HAVE HANDRAILS ON ONE SIDE. 22. HANDRAILS SHALL HAVE EITHER A CIRCULAR CROSS SECTION WITH A DIAMETER OF 1 1/4' TO 2" OR A NONCIRCULAR CROSS SECTION WITH A PERIMETER DIMENSION OF AT LEAST 4 BUT NOT MORE THAN 6 1/4" AND A LARGEST CROSS SECTION DIMENSION NOT EXCEEDING 2 1/4" 23. HANDRAILS FOR STAIRWAYS SHALL BE CONTINUOUS FOR THE FULL LENGTH OF THE FLIGHT FROM A POINT DIRECTLY ABOVE THE TOP RI F T SER 0 HE FLIGHT TO A POINT DIRECTLY ABOVE LOWEST RISER OF THE FLIGHT. HANDRAIL ENDS SHALL BE RETURNED OR SHALL TERMINATE IN NEWEL POSTS OR SAFETY TERMINALS. 24. HANDRAILS SHALL BE PROVIDED ON AT LEAST ONE SIDE OF EACH CONTINUOUS RUN OF TREADS OR FLIGHT WITH FOUR OR MORE RISERS. 25. GUARDRAILS SHALL FORM A VERTICAL PROTECTIVE BARRIER NOT LESS THAN 36' HIGH. 26. OPEN GUARDRAILS SHALL HAVE INTERMEDIATE RAILS OR ORNAMENTAL PATTERN SUCH THAT A 4' DIAMETER SPHERE CANNOT PASS THROUGH ANY OPENING UP TO A HEIGHT OF 34". A BOTTOM RAIL OR CURB SHALL BE PROVIDED THAT WILL REJECT THE PASSAGE OF 2" DIAMETER SPHERE. 25. STAIRS SHALL HAVE A MINIMUM HEADROOM CLEARANCE OF 6'-8" MEASURED VERTICALLY FROM A LINE CONNECTING THE EDGE OF THE NOSINGS. SUCH HEADROOM SHALL BE CONTINUOUS ABOVE THE STAIRS TO THE POINT WHERE THE LINE INTERSECTS THE LANDING BELOW, ONE TREAD DEPTH BEYOND THE BOTTOM RISER. THIS MINIMUM SHALL BE MAINTAINED THE FULL WIDTH OF THE STAIRS AND LANDINGS. 26. THE DOOR BETWEEN THE GARAGE AND THE LIVING AREA SHALL BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1 3/8 INCHES IN THICKNESS, SOLID OR HONEYCOMB CORE STEEL DOORS NO LESS THAN 1 3/8 INCHES IN THICKNESS, OR 20 -MINUTE FIRE RATED DOORS. GARAGES BENEATH HABITABLE ROOMS SHALL BE SEPARATED FROM ALL HABITABLE ROOMS ABOVE BY NOT LESS THAN 5/8 INCH TYPE X GYPSUM BOARD. ROOF COVERING NOTES: ASPHALT SHINGLES FBC R905.2 ASPHALT SHINGLES INSTALLATION OF ASPHA T SHINGLES SHALL COMP THEY WITH THE PROVISIONS L L OF THIS SECTION AND THE MANUFACTURERS INSTALLATION INSTRUCTIONS. R905.2 ASPHALT SHINGLES, R905.2.1 SHEATHING REQUIREMENTS, R905.2.2 SLOPE R905.2.3 UNDERLAYMENT R905.2.4 ASPHALT SHINGLES R905.2.5 FASTENERS R905.2.5.1, R905.2.6 ATTACHMENT, R905.2.7 UNDERLAYMENT APPLICATION R905.2.7.2 UNDERLAYMENT AND HIGH WIND, R905.2.8 FLASHING R905.2.8.1 BASE AND COUNTER FLASHING, R905.2.8.2 VALLEYS R905.2.8.3 CRICKETS AND SADDLES, R905.2.8.4 SIDEWALL FLASHING R905.2.8.5 OTHER FLASHING, R905.2.8.6 DRIP EDGE CLAY AND CONCRETE TILE FBC R905.3 CLAY AND CONCRETE TILE THE INSTALLATION OF CLAY AND CONCRETE SHALL COMPLY WITH THE PROVISIONS OF THIS SECTION. CLAY ROOF TILE SHALL COMPLY WITH ASTM C1167. R905.3 CLAY AND CONCRETE TILE, R905.3.1 DECK REQUIREMENTS. R905.3.2 DECK SLOPE, R905.3.3 UNDERLAYMENT, R905.3.3.1 LOW SLOPE ROOFS, R905.3.3.2 HIGH SLOPE ROOFS. R905.3.3.3 UNDERLAYMENT AND HIGH WIND, R905.3.4 TILE R905.3.5 CONCRETE TILE, R905.3.6 FASTENERS, R905.3.7 APPLICATION METAL ROOF PANELS FBC R905.10 METAL ROOF PANELS THE INSTALLATION OF METAL ROOF PANELS SHALL COMPLY WITH THE PROVISIONS OF THIS SECTION. R905.10 METAL ROOF PANELS, R905.10.1 DECK REQUIREMENTS R905.10.2 SLOPE, R905.10.2.1, R905.10.3 MATERIAL STANDARDS R905.10.4 ATTACHENT ROOF FLASHING NOTES R905.2.8.4 SIDEWALL FLASHING . FLASHING AGAINST A VERTICAL SIDEWALL SHALL BE BY THE STEP -FLASHING METHOD. R905.2.8.5 OTHER FLASHING . FLASHING AGAINST A VERTICAL FRONT WALL, AS WELL AS SOIL STACK, VENT PIPE AND CHIMNEY FLASHING , SHALL BE APPLIED ACCORDING TO ASPHALT SHINGLE MANUFACTURER'S PRINTED INSTRUCTIONS. R905.2.8.6 DRIP EDGE. DRIP EDGE SHALL BE PROVIDED AT EAVES AND GABLES OF SHINGLE ROOFS, AND OVERLAPPED A MINIMUM OF 2 INCHES (51 MM). EAVE DRIP EDGES SHALL EXTEND 1A INCH �6.4 MM) BELOW SHEATHING AND EXTEND BACK ON THE ROOF A MINIMUM OF 2 INCHES 51 MM). DRIP EDGE SHALL BE MECHANICALLY FASTENED A MAXIMUM OF 12 INCHES (305 MM) ON CENTER. DRIP EDGE AT EAVES SHALL BE PERMITTED TO BE INSTALLED EITHER OVER OR UNDER THE UNDERLAYMENT. IF INSTALLED OVER THE UNDERLAYMENT, THERE SHALL BE A MINIMUM 2 INCH (51 MM) WIDTH OF ROOF CEMENT INSTALLED OVER THE DRIP EDGE FLANGE. VALLEY LUQNG NOTES R905.2.8.2 VALLEYS, VALLEY LININGS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS BEFORE APPLYING SHINGLES. VALLEY LININGS OF THE FOLLOWING TYPES SHALL BE PERMITTED: 1. FOR OPEN VALLEY (VALLEY LINING EXPOSED) LINED WITH METAL, THE VALLEY LINING SHALL BE AT LEAST 24 INCHES (610 MM) WIDE AND OF ANY OF THE CORROSION -RESISTANT METALS IN TABLE R903.1. 2. FOR OPEN VALLEYS, VALLEY LINING OF TWO PLIES OF MINERAL SURFACE ROLL. ROOFING, COMPLYING WITH ASTM D 249, SHALL BE PERMITTED. THE BOTTOM LAYER SHALL BE 18 INCHES (457 MM) AND THE TOP LAYER A MINIMUM OF 36 INCHES (914 MM) WIDE. 3. FOR CLOSED VALLEYS (VALLEY COVERED WITH SHINGLES), VALLEY LINING OF CNF PLY OF SMOOTH ROLL ROOFING COMPLYING WITH ASTM D 224 TYPE it OR TYPE III AND AT LEAST 36 INCHES (914 MM) WIDE OR VALLEY LINING AS DESCRIBED IN ITEMS 1 AND 2 ABOVE SHALL BE PERMITTED. SPECIALTY UNDERLAYMENT COMPLYING WITH ASTM D 1970 MAY BE USED IN LIEU OF THE LINING MATERIAL. RASHING NOTES R703.8 FLASHING APPROVED CORROSION -RESISTIVE FLASHING SHALL BE PROVIDED IN THE EXTERIOR WALL ENVELOPE IN SUCH A MANNER AS TO PREVENT ENTRY OF WATER INTO THE WALL CAVITY OR PENETRATION OF WATER TO THE BUILDING STRUCTURAL FRAMING COMPONENTS. THE FLASHING SHALL EXTEND TO THE SURFACE OF THE EXTERIOR WALL FINISH AND SHALL BE INSTALLED TO PREVENT WATER FROM REENTERING THE EXTERIOR WALL ENVELOPE. APPROVED CORROSION -RESISTANT FLASHINGS SHALL BE INSTALLED AT ALL OF THE FOLLOWING LOCATIONS: 1. AT TOP OF ALL EXTERIOR WINDOW AND DOOR OPENINGS IN SUCH A MANNER AS TO BE LEAKPROOF, EXCEPT THAT SELF -FLASHING WINDOWS HAVING A CONTINUOUS LAP OF NOT LESS THAN 1-1/8 INCHES (28 MM) OVER THE SHEATHING MATERIAL AROUND THE PERIMETER OF THE OPENING, INCLUDING CORNERS, DO NOT REQUIRE ADDITIONAL FLASHING ; JAMB FLASHING MAY ALSO BE OMITTED WHEN SPECIFICALLY APPROVED BY THE BUILDING OFFICIAL. 2. AT THE INTERSECTION OF CHIMNEYS OR OTHER MASONRY CONSTRUCTION WITH FRAME OR STUCCO WALLS, WITH PROJECTING LIPS ON BOTH SIDES UNDER STUCCO COPINGS. 3. UNDER AND AT THE ENDS OF MASONRY, WOOD OR METAL COPINGS AND SILLS. 4. CONTINUOUSLY ABOVE ALL PROJECTING WOOD TRIM. 5. WHERE EXTERIOR PORCHES, DECKS OR STAIRS ATTACH TO A WALL OR FLOOR ASSEMBLY OF WOOD -FRAME CONSTRUCTION. 6. AT WALL AND ROOF INTERSECTIONS. 7. AT BUILT-IN GUTTERS. R703.12 DRAINED ASSEMBLY WALL OVER MASS ASSEMBLY WALL. WHERE WOOD FRAME OR OTHER TYPES OF DRAINED WALL ASSEMBLIES ARE CONSTRUCTED ABOVE MASS WALL ASSEMBLIES, FLASHING OR OTHER APPROVED DRAINAGE SYSTEMS SHALL BE INSTALLED AS REQUIRED BY R703.8 CONSTRUCTION DRAWINGS 118 0 MODEL 814 Pecan Avenue Sanford, Florida Seminole County CONTRACTOR DESIGNER ARCHrrECr Sovanic, Inc. 5401 S. Kirkman Rd. Orlando, Florida 32819 407.926.4157 jacKs & Sticks, Inc. 894 Clearview Avenue Lakeland, Florida 33801 407.448.8999 GIAMG NOTE R308.4 THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS FOR THE PURPOSES OF GLAZING: GLAZING IN SWINGING DOORS EXCEPT JALOUSIES. 1. GLAZING IN FIXED AND SLIDING PANELS OF SLIDING DOOR ASSEMBLIES 2. AND PANELS IN SLIDING AND BIFOLD CLOSET DOOR ASSEMBLIES. GLAZING IN DOORS AND WALLS OF ENCLOSURES FOR HOT TUBS, 5. WHIRLPOOLS SAUNAS, STEAM ROOMS BATHTUBS & SHOWERS. GLAZING IN ANY PART OF THE BUILDING WALL ENCLOSING THESE COMPARTMENTS WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS THAN 60 INCHES MEASURED VERTICALLY ABOVE ANY STANDING OR WALKING SURFACE. 6, GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT TO A DOOR WHERE THE NEAREST VERTICAL EDGE IS WITHIN A 24 -INCH (610 mm) ARC OF THE DOOR IN A CLOSED POSITION AND WHOSE BOTTOM EDGE IS LESS THAN 60 INCHES (1524 mm) ABOVE THE FLOOR OR WALKING SURFACE. 7. GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL, OTHER THAN THOSE LOCATIONS DESCRIBED IN ITEMS 2 AND 3 ABOVE, THAT MEETS ALL OF THE FOLLOWING CONDITIONS: 7.1. EXPOSED AREA OF AN INDIVIDUAL PANE GREATER THAN 9 SQ. FT. (0.84 M ). 7.2. BOTTOM EDGE LESS THAN 18 INCHES (457 MM) ABOVE THE FLOOR. 7.3. TOP EDGE GREATER THAN 36 INCHES (914 MM) ABOVE THE FLOOR. 7.4. ONE OR MORE WALKING SURFACES WITHIN 36 INCHES (914 MM) HORIZONTALLY OF THE GLAZING. THE GLAZING. 9. GLAZING IN WALLS AND FENCES ENCLOSING INDOOR AND OUTDOOR SWIMMING POOLS AND SPAS WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS THAN 60 INCHES (1525 mm) HORIZONTALLY OF THE WATER'S EDGE. THIS SHALL APPLY TO SINGLE GLAZING AND ALL PANES IN MULTIPLE GLAZING. 10. GLAZING ADJACENT TO STAIRWAYS, LANDINGS AND RAMPS WITHIN 36 INCHES (914 mm) HORIZONTALLY OF A WALKING SURFACE WHEN THE EXPOSED SURFACE OF THE GLASS IS LESS THAN 60 INCHES (1524 mm) ABOVE THE PLANE OF THE ADJACENT WALKING SURFACE. 11. GLAZING ADJACENT TO STAIRWAYS WITHIN 60 INCHES (1524 mm) HORIZONTALLY OF THE BOTTOM TREAD OF A STAIRWAY IN ANY DIRECTION WHEN THE EXPOSED SURFACE OF THE GLASS IS LESS THAN 60 INCHES (1524mm) ABOVE THE NOSE OF THE TREAD. GARAGE SEPARATION 1. THE GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND IT'S ATTIC AREA BY NOT LESS THAN 1/2" GYPSUM BOARD APPLIED TO THE GARAGE SIDE. GARAGES BENEATH HABITABLE ROOMS SHALL BE SEPARATED FROM ALL HABITABLE ROOMS ABOVE BY NOT LESS THAN 5/8' TYPE X GYPSUM BOARD OR EQUIVALENT. WHERE THE SEPARATION IS A FLOOR -CEILING ASSEMBLY, THE STRUCTURE SUPPORTING THE SEPARATION SHALL ALSO BE PROTECTED BY NOT LESS THAN 1/2" GYPSUM BOARD OR EQUIVALENT. WIND PRESSURE WINDOW DESIGN WIND PRESSURE, ALL SIZES = POSITIVE PRESSURE OF 22 p.s.f., NEGATIVE PRESSURE OF 30 p.s.f. SLIDING GLASS DOORS, ALL SIZES = POSITIVE PRESSURE OF 21 p.s.f., NEGATIVE PRESSURE OF 28 p.s.f. ENTRY DOORS, ALL CONFIGURATIONS = POSITIVE PRESSURE OF 20 p.s.f., NEGATIVE PRESSURE OF 25 p.s.f. GARAGE DOORS, ALL SIZES = POSITIVE PRESSURE OF 20 p.s.f., NEGATIVE PRESSURE OF 24.5 p.s.f. rl:3:3:1w"AFIN MCC 1111 A BUMPUS AND ASSOCIATES, INC. ARCHITECTURE -PLANNING -INTERIOR DESIGN THRESHOLD INSPECTIONS 603 FRONT STREET CELEBRATION, FLORIDA 34747 VOICE (407) 566-0200 A.B. ANCHOR BOLT MIN. MINIMUM ABV ABOVE MIRR MIRROR A/C AIR CONDITIONER M.J. MECHANICAL JOINT ACI AMERICAN CONCRETE INSTITUTE MONO. MONOLITHIC A.F.F. ABOVE FINISHED FLOOR M.P.H. MILES PER HOUR AFI ARC FAULT INTERRUPT MWFRS MAIN WIND FORCE RESISTING SYSTEMS AH AIR HANDLER OLE N/C NOT APPLICABLE ALUM ALUMINUM NDS NATIONAL DESIGN SPECIFICATION AMP AMPERE FOR WOOD CONSTRUCTION APA THE ENGINEERED WOOD ASSOCIATION NIC NOT INCLUDED ASCE AMERICAN SOCIETY OF CML ENGINEERS NO. NUMBER A.T.R. ALL THREADED ROD N.T.S. NOT TO SCALE B BOTTOM BLK. BLOCK OBS. OBSCURE BOT. BOTTOM O.C. ON CENTER BRIG BEARING O.H.D. OVERHEAD DOOR OSB ORIENTED STRAND BOARD C&C COMPONENTS AND CLADDING p PRESSURE CANT CANTILEVER PAR PARALLEL CIR CIRCLE P.C. PRECAST LINTEL CLG CEILING PED PEDESTAL C.M.U. CONCRETE MASONRY UNIT PERP PERPENDICULAR C.O. CLEAN OUT PKT. POCKET COL. COLUMN PLT. PLATE COMP. COMPACTED PLUMB. PLUMBING COND CONDENSER PLWD PLYWOOD CONT. CONTINUOUS PREFAB PREFABRICATED CPT CARPET P.S.F. POUNDS PER SQUARE FOOT d PENNY P.S.I. PO' INDS PER SQUARE INCH D DRYER P.T. PRESSURE TREATED DBL. DOUBLE PVC POLYVINYL CHLORIDE DECOR DECORATIVE Qn, QUANTITY DET. DETAIL DH DOUBLE HUNG R ROD DIA. DIAMETER REC RECEPTACLE DISC. DISCONNECT REF. REFERENCE D.L. DEAD LOAD REFG. REFRIGERATOR DR DOOR REINF. REINFORCED DRY DRYER RES. RESIDENCE REQ'D. REQUIRED EA. EACH RM ROOM E.B. EYE BROW RND ROUND ELECT ELECTRICAL R.O. ROUGH OPENING ELEV ELEVATION EMBED. EMBEDMENT S SHELF E.W. EACH WAY S.B.P. SOIL BEARING PRESSURE EXT. EXTERIOR SD SMOKE DEFECTOR SECT. SECTION FBC FLORIDA BUILDING CODE SF SQUARE FOOT FIN FINISH S.G.D. SLIDING GLASS DOOR FIX FIXTURE SH SINGLE HUNG F.G. FIXED GLASS SPECS SPECIFICATIONS FLR FLOOR S.P.F. SPRUCE -PINE -FIR FOUND. FOUNDATION SQ. FT. SQUARE FOOT FTG. FOOTING SW SWITCH GA GYPSUM ASSOCIATION S.W.C. SHEAR WALL CONNECTOR GAL. GALLON S.W.S. SHEAR WALL SEGMENT GALV. GALVANIZED S.Y.P. SOUTHERN YELLOW PINE G.B. GLASS BLOCK T TOP GDR GIRDER T&G TONGUE AND GROOVE GFI GROUND FAULT INTERRUPT TEMP TEMPERED GLS GLASS THK. THICK GYP. GYPSUM T -NAIL TOENAIL HB HOSE BIB T.V. TELEVISION HDR HEADER TYP. TYPICAL HGT HEIGHT U URINAL HOR HORIZONTAL UL UNDERWRITERS LABORATORIES, INC. HT HEIGHT U.N.O. UNLESS NOTED OTHERWISE HVAC HEATING, VENTILATING U.S.G. UNITED STATES GYPSUM COMPANY AND AIR CONDITIONING V VOLTS INCAND. INCANDESCENT VENT. VENTILATED INSUL. INSULATION VIN VINYL KD KILN DRIED LUMBER VISA. VISQUEEN L LAVATORY VOL VOLUME LBS. POUNDS W WASHER L.L. LIVE LOAD W/ WITH LT LAUNDRY TUB W.C. WATER CLOSET LVL LAMINATED VENEER LUMBER WD. WOOD M. MASTER WDW WINDOW MANUF. MANUFACTURER WH WATER HEATER MAX. MAXIMUM W.I.C. WALK-IN CLOSET MC MEDICINE CABINET WP WATER PROOF W.W.F. WELDED WIRE FRAME SANFORD BUILDING DEPT' THESE PLANS ARE REVIF_Wf-D AND CONDITIONALLY ACCEPTED FOR C'FRMIT. A F'FRM! 70 Pic ROCEED RCD EED WISHALLTH CONSTRUED TO BE A `LGE 'r VIOLATE. THE WORI< A'f' TUT F•`}GTTASIDE k" OF THE CANCEL_ �,,.'TF-R. OFt N`Or2SHALL PRO"•'i CiNS U r�F_ T' �SiCAL tj_ t S. 155UA vCF� OF A I'fRMi REV'- N i -tic. BU ILDING A CORREC- L-)EP)- FR�`r"� 't I t.G nt t E r 2f �UIkIN ON Tf � „l Ua: Ci:NSTRUGTION TION nh rF'f'vi Hl < c'LE5 OR 07 HLF DRAWNG INDEX COVER PAGE ELEVATIONS/SECTION - FLOOR PLAN FOUNDATION/PLUMBING HEADER PLAN LINTEL SCHEDULE TRUSS PLAN ELECTRICAL PLAN D ETAI LS DETAILS SANFORD BUILDING DEPT. THESE PLANS ARE REVIEWED AND CONDITIONALLY ,T ISSUED SHALL F_ ACCEPTED FOR IIERE RMA l_: CENSEIIT A PERI` TO PROCEED WIBTH ,0NSTRUE'k 10 Acs AUTHORITY TO VIOLOF ATE, HE THC j\-0 Nti� r T A.;IDE AN' C f11V L . <, v E I I ,l` n CC GF �, NOR SHALL _.,JF GUILDING n I C.ORRn -C- L�E.._5> .,�-i1 -''. '.+a::. i ,:_�.. :,ar15TRUCTION 11,E OP's OTl la a: �°tt� y Ic SQ. FT. CALCULATIONS LIVING AREA GARAGE---- FRONT ARAGE FRONT PORCH TOTAL AREA UNDER ROOF ROOF VENTRATION CALLS. TOTAL REQUIRED TOTAL EAVE VENTILATION TOTAL OFF RIDGE VENTS CP n 1 �.I 4.1 A n T.� C 1 1j. C 1 U. 1 -7 1 7.2 1180 -206 - 54 1530 5 SQ FT MIN - 6 SQ FT - 3 SQ FT CODE COMMIANCES Y APPLICABLE CODES: FLORIDA BUILDING CODE 2007 RESIDENTIAL NEC 2008 DESIGN LIVE AND DEAD LOADS: FLOOR: 40 PSF LIVE, 10 PSF DEAD STAIRS: N/A ROOF: PER TRUSS MANUFACTURER OR 20 PSF LIVE, 10 PSF DEAD (SHINGLE) 20 PSF LIVE, 20 PSF DEAD (TILE) BASIC WIND SPEED: 120 M.P.H. APPLICABLE INTERNAL PRESSURE COEFFICIENT: 0.18 WIND EXPOSURE: --B (ENCLOSED) WIND IMPORTANCE FACTOR: 1.0 TYPE OF CONSTRUCTION: -V, B BUILDING DATA: SINGLE FAMILY RESIDENTIAL DWELLING: ONE (1) STORY HEIGHT OF STRUCTURE: -12'-4" MEDIAN ROOF HT TO GRADE OFFICE DNM JAC APUD DB DATE: 1/22/2012 SCALE. AS SHOWN JOB NLINIBEIs 1180/814 SHEET C P j CL ;mJr a cZS � (D c at O o 0 $_4 P4 rwr- E- Z DNM JAC APUD DB DATE: 1/22/2012 SCALE. AS SHOWN JOB NLINIBEIs 1180/814 SHEET C P j CL ;mJr a (D at cd b a. P 0 $_4 P4 d DNM JAC APUD DB DATE: 1/22/2012 SCALE. AS SHOWN JOB NLINIBEIs 1180/814 SHEET C P j CL ;mJr ROOF PITCH 12 5 OFF RIDGE VENT OL 81-111 TRUSS BEARING FINISH GRADE ROOF PITCH 5 COMPOSITION SHINGLES } i GOMPHIN 051TION SrxLES L I Li k L] L1 U- Lt�-Ll U L Ll 1IL L �[J t: D L �-J L Ir-AIurwLd I-II IVIC1 r-INIUM Y FINISH FLOOR - TEXTURED MASONRY FINISH LEFT SIDE ELPV SCALE = l/4"=1'-0' OL s'-1" TRUSS BEARING FINISH GRADE ROOF PITCH 5 } 12 OFF RIDGE VST COMPOSITION SHINGLES TEXTURED MASONRY FINISH ' RFAR ELEVATION SCALE - 1/4'=1'-U" 4" WIDE SMOOTH MASONRY SAND TEXTURED MASONRY FINISH FRONT ELEVATION SCALE - LAC -I ROOF PITCH _ _ Ll � 1__ -Ll. -1 l u uu U -I �I ILI -Li- I LLLU U �LJLL]U l 1Ll 1U�� I. L LJ U . Ll U --Ll �__L�ilId- LI Li L U -�1 COMPOSITION SHINGLES 8' -III TRUSS BEARING FINISH GRADE III I i� ROOF PITCH 12 5 it1tJ1Z 1 �,711JL LLL V SCALE - 114'=1'-0" 1 -SECTION DRM JAC AND DB DATE: 1/22/2012 SCALE: AS SHOWN " MA4EIM 1180/814 SWEET 0 m 0 a m � � b O D O Oo F, a r - W'Itf a d m� Ez w O V 1 A �W O a U w Nomillook DRM JAC AND DB DATE: 1/22/2012 SCALE: AS SHOWN " MA4EIM 1180/814 SWEET 0 m 0 a m � � b O D O Oo F, a r - W'Itf a d m� Ez w O V 1 A �W O a U w DRM JAC AND DB DATE: 1/22/2012 SCALE: AS SHOWN " MA4EIM 1180/814 SWEET 0 m 0 a m � � b D O F, a a d DRM JAC AND DB DATE: 1/22/2012 SCALE: AS SHOWN " MA4EIM 1180/814 SWEET 0 � mss I 2'-011 8._0.. 2'-0" 12'-0" 3'-4" 4'-8" I 14'-0" 34'-0" i 0 FLOOR PLAN SCALE _ ]/4"=P-0" 5Q. FT. GAL CUL AT I ON5 LIVING 118 LANAI 0 ENTRY 54 # OTHER 0 s#z GARAGE 296 � TOTAL AREA 20685 L NPER ROOF 1530 > 3'-0" x 6'-8" PANELED BIFOLD 40685 4'-0" x 6'-8" PANELED BIFOLD w—a 5'-01 x 6'4" PANELED 51FOLD 2868 2'-8" x 6'-8" b PANEL HOLLOW 21068 V-10" x 6'4" 6 PANEL HOLLOW -' Hz w h x wd O U 'n _ M. Bath m FT 8'-0" Flat 9 m "� ■ 3'- 2'-4" 3'-0" Il' -8" 12'-8" ■ N 21068 A 5 5H ■ 45d WALL W.I.C. M. Bedrm 8'-0" Flat - 11'.4" x 13'-0" 8' Flat / r 0 �_ / I CIA N Rm IN LL_Great x Vaulted Vaulaul Cig.ted Clg. 2.5:12 B.C. Slope 2'-9" 2 � TILE BEAT a 20' AFF.28 6a V2 " C 54" It 11'-6" if, 8' Flat ATTI ACCESS "' `4 JOB LOCATE„ CLR —7, SBNvB ■ bi_QII 21.611 1D BAR CAP a 42' AFF. = Bedrm Nf' w Dw ,0688 8' Flet � I 5n BMC , --I—------I Kitchen 8'-10"x 10'-4" Vaulted Clg. TU8 4 SHOLLER 2.5:12 B.C. Slope O N AIR RANGE t!J HANDLER — w/ HOOD I ' 0 O O I -R 1 8 � RETURN N ■ — .... -- 40688 I ■ Q 8' Flat r N T ee - Foyer -- 1 -Car Garage Z0 MR 8 ' Fla[ MT. _ _ 1-R < s _ r 14'-0'.;2t0'-1" x 8' la - - cv — 20608 ,e 0 50M ' 0 N N F-\ -------- —� 3'-0" 2'-0" 6'-10' Ilk X Entry / \ I / \ DRIER VENT - Bedrm #3 / \ I / \ 0 12'-8" x 10'-1" I / em7o olD \ I d 8' Flat NB 00 MPH RATED ■ - ---- -- ■ ■ ■ IN ■ . _ ■ � mss I 2'-011 8._0.. 2'-0" 12'-0" 3'-4" 4'-8" I 14'-0" 34'-0" i 0 FLOOR PLAN SCALE _ ]/4"=P-0" 5Q. FT. GAL CUL AT I ON5 LIVING 118 LANAI 0 ENTRY 54 # OTHER 0 s#z GARAGE 296 � TOTAL AREA 20685 L NPER ROOF 1530 > PATIO 100 * TOTAL AREA 1630 * FLOOR LEGEND ■ - 5 0 ROD IN FILLED CELL =M - 2x4 FRAME WALL 2xb FRAME WALL - $" C.M.U. WALL - DENOTES 8'-I" PLT. WEIGHT I. ALL INTERIOR WALLS ARE 2" x 4" CONSTRUCTION 16" O.G. EXCEPT NOTED WET WALLS. 2. SEE COVER SWEET FOR WINDOW AND DOOR PRESSURE NOTE. wu*moW SCHEDULE SINGLE HUNG BLOCK WINDOWS CODE ROUGW OPENING SW- 33 211/4" x 38 " SW -25 313/4" x 63" -VERIFY ALL RO, W/ BUILDER -TEMPERED GLASS REQUIREMENTS AS PER FLORIDA BUILDING CODE 2004 EDITION -EGRESS REQUIREMENTS AS PER FLORIDA 5UILDING CODE 20044 EDITION DOOR SCHEDULE CODE SIZE 3068E Y-0" x b'-0" b -PANEL INSULATED 3068E FR 3'-0" x 6'-0" FRENCH DOOR 8010 OHD 8'-0" x 1'-0" OVERHEAD DOOR 20685 2'-0" x 6'-S" PANELED BIFOLD 30685 3'-0" x 6'-8" PANELED BIFOLD 40685 4'-0" x 6'-8" PANELED BIFOLD 50685 5'-01 x 6'4" PANELED 51FOLD 2868 2'-8" x 6'-8" b PANEL HOLLOW 21068 V-10" x 6'4" 6 PANEL HOLLOW r- DllM JAC AND DB DATE:- 1/22/2012 ATE1/22/2012 SCALE. AS SHOWN .JOB NUMBER 1180/814 SFEET- • �04 Hz w h x wd O U DllM JAC AND DB DATE:- 1/22/2012 ATE1/22/2012 SCALE. AS SHOWN .JOB NUMBER 1180/814 SFEET- • _1 H5f I r FOUNDATION PLAN SCALE = 1/4"=P-0° CONCRETE SPECS SLAB- 2500 PS.I. IN 28 DAYS FOOTERS- 2500 P S.I. IN 28 DAYS LINTELS- 3000 P,S.I. IN 28 DAYS FILLED CELLS- 3000 Phi IN 28 DAYS 5'-0" 4'-011 3'-10" 4'-0"5'-0" 3'-10" 3'-6" 31-10" '-0' 1 411 1) (a 0-4 00 Ww W 0F 1,.-4 4 RECESS FORJl—I z i OUT SWING DOOR o '—' 00 ow -< v, A�0ll 2'-11" 2'-511 `A 4--- I RECESS SNOUIER I ■ ■ - ■ SEE DETAIL 19!1.2 SLAB NOTE `n 4" CONCRETE SLAG W/ ---1 - g v FIEsERMESH (OR b"x(o" 0 ----- 10/10 W.WF_) OvER 6 MILL v15Q AND CLEAN, COMPACTED, ■ TEWITE TREATED FILL. 11 31_011 ■ • n, awli � N To4 - --- 4" DOWN AIR SIOZR 1 F4YrPLER 1 141-0"Fem / owl* —AC CHASE 1 I W SLAB NOTE I ■ 4" CONCRETE SLAB W/ ■ 4" DOWN FIBERMESN (OR 6"x6" - I ao 1040 WIUF) OVER 6 MILL vISQ AND CLEAN, , TERMITE TREcaMpAcTEDATED FILL. I I LL I ___ 3x4" RECESS FOR 61 I GARAGE DOOR'Nor I I �' I J —I_ - z i 3'-4" 4'-511 41-011 51.011 12'-0" 14'-011 Ilk Ilk 34'-0" FOUNDATION PLAN SCALE = 1/4"=P-0° CONCRETE SPECS SLAB- 2500 PS.I. IN 28 DAYS FOOTERS- 2500 P S.I. IN 28 DAYS LINTELS- 3000 P,S.I. IN 28 DAYS FILLED CELLS- 3000 Phi IN 28 DAYS DNW JAC AND DB DATE- 1/22/2012 SCALB- AS SHOWN ,roe NUMBM 1180/814 sir- • 0-4 00 Ww W 0F 1,.-4 � z o '—' 00 ow -< v, v, v, DNW JAC AND DB DATE- 1/22/2012 SCALB- AS SHOWN ,roe NUMBM 1180/814 sir- • 00 Ww 1,.-4 � z o '—' 00 ow -< v, v, v, DNW JAC AND DB DATE- 1/22/2012 SCALB- AS SHOWN ,roe NUMBM 1180/814 sir- • 1 -Gar (],.araga 4'.0" 20'...] L-4 (G) V2 R6 i _'. HOT m 3 Nn ET 4.2 --------- ------ SCAU = 1/4W-0" mma [WIWI 91 K9,1169 pol �,_ -5FE SHEET 42 FOR PRECAST HEADER SCHEDULE. -HEADER DEPTHS CALLED OUT ON THE HEADER PLAN ARE THE MINIMUM DEPTH REQUIREMENTS. HEADERS CAN EXCEED THE MINIMUM DEPTH REQUIREMENTS. I ------------- 771 r -4(C) L-4 -((;) c:) Vw T 2 =L I E30T gpo'- 14 51E T 42 p", F& Ekoflt " 41 E- (C U) E­ cf) 7D pq P4 5H FT 43 CD s 61-811 1p!� Fy LiraiA I'lln F2 x 4 11 -4(C) I ATTIC A CE5 L4 (G) 1 -Gar (],.araga 4'.0" 20'...] L-4 (G) V2 R6 i _'. HOT m 3 Nn ET 4.2 --------- ------ SCAU = 1/4W-0" mma [WIWI 91 K9,1169 pol �,_ -5FE SHEET 42 FOR PRECAST HEADER SCHEDULE. -HEADER DEPTHS CALLED OUT ON THE HEADER PLAN ARE THE MINIMUM DEPTH REQUIREMENTS. HEADERS CAN EXCEED THE MINIMUM DEPTH REQUIREMENTS. c:) C5 p", E- U) E­ cf) 7D pq P4 cz) pq C-0 1.4 CD Rt SAFE UPLIFT LOADS FOR 8" PRECAST & PRESTRESSED U—LINTELS SAFE GRAVITY LOADS FOR 8" PRECAST & PRESTRES' ED U—LINTELS SAFE LOAD — POUNDS PER LINEAR HOOT SAFE LOAD — POUNDS PER LINEAR FOOT allALqY PkWA6T 0(*�my_ A B C D E F G A B C D E F G (8x8) (8x12) (8x16) (8x20) (8x24) (8x28) (8x32) (8x8) (8x12) (8x16) (8x20) (8x24) (8x2P.) (8x32) MARKTYPE 8F8 -1T 8F12 -1T 8F16 -IT 81'20-tT 81'24-1T 81'28-1`i' BF32-1T MARK CLEAR TYPE 8I18 W 8F8 -OB 81+'12-oB 87'16-0B 8F20 -0B 6P'24 -01i811'28-011 8F37 -0B NU, LENGTH -_ - 8F8 -2T 8F12 -2T 8F16 -2T 8F20 -2T 8F24 -2T 8F28 -2T 8F32 -2T N0. SPAN LENGTH �---�� 81'8-1B 8112-11.1 8116-113 11120 -to 81'24-1B 81'28-113 8F32 -1B WINDOWS, PORCH, & GARAGE DOORS 19"72 31773 4460 5"74"7 "7034 832:1 9608 L-1 1 9 99 2 9--10 99 (349,) PRECAST ��r �.� 3069 4605 61.13 7754"7 89"74 10394 11809 PRECAST LINTEL 8,7X8„ FILLED) L-1 2'-1Q'7 (34") PRECAST 1972 3173. 4460 5"747 7034 8321 9608 —6 �� 3069 4605 (3113 7547 8974 10394 11809„ PRECAST LINTEL 8"X16” COMPOSITE) » t569 2524 3547 4569 5591 6613 7636 7 77 9 99 99 < `r 9 r 9502 10951 L-2 31-613 42 PRECAST L-2 2 —2 3 —6 42 PRECAST 2231 1089 ir19 516�i 8807 8051 1569 2524 3547 4569 5591 6613 7636 ( ) 3069 4605 6113 7547 8974 10394- 11809 ToLal ATT(1WaLTe SL1hel'1L>11)OSGCI Load - Pel4I1GS Eel' Linear FOe� z 0 „ 97 1363 2192 3079 3966 4853 5740 6627 „ ,7 79 2561 2751 3820 4890 5961 7034 8107 L-3 4 -0 (48) PRECAST rt �� �� r L-3 21— 8 4'— 0 (48) PRECAST 1966 " r r Mark No. Clear Span Lintel Size Filled (1) #5 Filled (2) #5 Filled (1) #5 Filled (1) #5 T Filled (2) #5 w 1363 2191 3079 3966 4853 .740 6627 2693 460 6113 7547 8974 10394 11809 ), ), x 8x8 8x8 T & B (2)#5B T & B )-613 99 t207 94 0 2724 3508 4292 5077 5861 99 9 99 " , 9 't ` 2931 '11753 4576 5400 6224 C i1 07 1 11,169 2.110 L-4 4 -6 (54) PRECAST r r r L-4 31— 2 4 —6 (54) PRECAST 1599 r r< 1207 1940 2724 3508 4292 5077 5861 2189 437 6113 7547 (7 8672 10291 11809 1-6)3 7 „ 1016. 1632 2290 2949 3607 4165 4924 9 99 9 97 �, 1349 1438 1999 2560 3123 3686 4249 L-1 1 2 —toll 7845 8122 12374 12591 1286"7 L-5 5'- 4 (64") PRECAST r � r << L-5 4 )-oll —4 (64”) PRECAST 121 � << ,� 1016 1632 2290 2949 3607 4265 4,124 1663 3090 5365 7547 (ss) 7342 (19) 8733(10) 10127(10 L-2 2)-2" 3'-6" 5413 5604 8488 8680 8871 9 „ 909 1492 2093 2694 3295 3897 4498 9 99 9 99 99 ,� 1.105 1173 1631 2090 2549 3009 3470 , 77 , 77 � L-6 5 —10 (70") PRECAST 929 1492 r r L-6 4 —6 5'-10" (70) PRECAST 1062 2 .r� r r 718 -- 3 L-3 2 —8 4 —0 438; 4538 6868 7023 7178 2093 r�694 3198 3897 4498 141 2612 4,360 7168 (45 6O3E� (1st 7181(10 8328 (20 c rc c rr r r rr c c � � 7 `97 7 99 L-' 6-677 (78") PRECAST 835 (12) 1340 1880 2419 2959 3498 4038 L_7 5'_27' 67-677 (78") PRECAST 908 1138 1177 3480 3031 3707 �i383 X061 L-4 3 —2 4 -6 3686 3817 5772 5902 6033 d, 835 1340 1880 2419 2959 3498 4038 1238 2177 3480 5381 8360 10394 (37) 8825 (11, 7 17 9 „ � ` ' E-+ L 3039 r r rc ,r , r , L-5 4 -Q 5 —4 2906 3010 4546 4649 4"753 C � � 99 99 727 (23) 1021 1634(12) 2102 (It) 2571(to) �30�39(to) 3508 (9) 9 99 , 7, 7) , � � 3 1011 1729 2632 2205 2698 �i191 3680 L-8 71— 6 (90) PRECAST L--8 6 —2 7 —6 (90) PRECAST X43 � 727 1166 1634 2102 2571 3039 3508 loll 1729 2661 3898 5681 8467 44 6472 n 7 ,,, , „ � H � ( ( L-6 4'_ 6 5 —1 Q 2577 2669 4028 4-120 4212 r- c c �� �� I- c �' , c c c c! ( -� ,7 77 X91 680 1133 (19) 1471(1,) 1811 (15) 21 52(16) (16) 2494 (15) 1-03, 7 ,7 , �,� 699 1160 1b1,) 2564 1486 28 1.8 "1302 L-1 Q 9'_4 { 112 ) PRECAST 591 851 1326 1705 2084 2463 2842 L--10 8 9 —4 (112") PRECAST 554 752 1245 1843 2564 11486 4705 (37 6390 (47 L-7 5'-277 67 -6" 2167 2245 3382 3460 3538 Q c C c c c r r c 2777 r r � 9 97 97 530 552 914 (to) 1185 (15) 1458 (1J) 17 32 (15) 2007 (15) 79 9 99 535 890 1241 209.3 2 7 r7 2163 2. 36 , 9 � 79 9 , 77 L-11 10 =6 (126) PRECAST r r r L-11 91- 2 to' -6" (126") PRECAST 4'75 r r r � f r r r L-8 6 —2 7 —6 1865 1932 2908 2975 3042 � rT � 530 686 1183 1526 1865 2204 2544 643 1052 15�3�3 20�1�3 2781 3613(38 4754(45, c �P4 9 97 » y 474 485 798 (15) 1034 (15) 1272(t5) 1510 (10 1749 (15) , „ 9 99 I yr , 582 945 1366 1846 2423 3127 4006 L-9 7 7 — p" 8 9 -499 1636 1696 2548 2607 2666 -.1 Q0 a L-12 11'-4" (136) PRECAST 494 599 1028 1422 1738 2053 2369 L-12 10 —0 11 —4 (136"') PRECAST 362 582 945 1366 1846 2423 3127 4006 / ` a , „ 470 (0) 441 723 (14) 936 (14) 1151(15) 1366 (15) 1582 (15) 99 9 99 79 -� �_.r _r — 540 - - 873 1254 1684 2193 2805 3552 L-10 8' - 0„ 914' 1425 1476 2215 2267 2319 L-13 12 -0 (144) PRECAST L-13 10'-8 12 —0 (144) PRECAST 337 470 543 928 1349 1649 1948 224"7 X40 87:3 1254 1684 2193 2805 3552 9 9, 9 99 _-----___-_ ......._____.____ _.__..___---.- ____ L-11 9 -2 1 Q -6 1236 128:1 1918 1936. 2009 � �"• "`` `'8 18`18 2316 288`3 L-14 13'-477 (16Q97 PRECAST 418 (15> 373 606 (14) 783 (14) 981(14) 1141(14) 1321(1) L-14 12'-0f1 13'-4'7 PRECAST 296471 755 1075 14� < < 999428 455 770 1 t45 1444 1718 1993 (160") 17 t 755 1075 1428 1.838 231.6 2883 L-12 10 - Q 11'411128 1170 1749 1790 1832 9 77 384 15) 346. 559 14) 723 (14) 887 (14) 1052 ,.4) 12 424 � '70f 1002 1326 1.697 212"r 2630 9 79 1-61, L-15 14 —0 (168") PRECAST ( ( ( 18(14) L-15 121-897 147_079 (168") PRECAST 2'79 -- L-13 11 —2 12tool 1042 1554 159.1. 1628 410 420 709 1.050 1434 (8) 1694 (e) 1954 (7) 1142 706 1002 1326 1697 2127 2630 L-16 14'-8"176" PRESTRESSED 239 323 519 (t 3) 671 (13) 823 (13) L-16 13 976 (14) 1129(11) ,-4 " 14'-8" (1769') 'PRESTRESSED NR - NTT NR NR NR NR NR L-14 12'-0" 137-497 931 933 1438 1473 1507 ( ) 246 390 855 988 1324 ri) 1625 (it) 1874 11) N. 458 �`'18`3 _ 1370 19022517 2� r r 71 r 2245 2 , „ 9 < < r r L-15 12 —8 14 _01) 78`3 784 1356 1389 1421 L-17 157-477 (184") PRESTRESSED 211 301 485 (13) 618 (13> 7sr (13> 909 (1:1) 1052 (13) L-17 14'-0f7 15'-497 184" PRESTRESSED NR NE NR _ NE NR NR NR >J 230 364 609 89"7 1224 8) 1562 14) 1801 (14) ( ) � �R. 412 � - r , ; - r < < F 2 c r r � r , _ 99 7 _ „ ( ( 710 120 1733 208 1310 2v13 L-16 13 4 14 8 760 765 1395 1448 1512 Q r F F F c + r r r- � r wr ._..— _ - � L-18 17'-497 (208") PRESTRESSED t8r 2�� 404 (12) X20 (12) 6�i7 (12) 754 (m) 872 (12) L-18 16,_017 17'-4" (208") PRESTRESSED N R. NR NIz NR NR 1vlz NIz NIz 7— 79 �9_ �' Q 192 303 500 732 993 (8) 1268 (14) 1470 (14) 300 548 950 1326 t609 1849 2047 L-17 14 Q 15'— 4 687 681 1326 1376 H37 L-19 19)-4)) 232" PRESTRESSED 162 222 :347 (11) 446 (I1) 546 (12) 646 (12) 748 (l2) ,7 9 99 77 ,, NR NR NE NE NR NR NR 7, 7 ,7 r r ( ) L-19 18 —0 19 —4 (232) PRESTRESSED N.R. r ` ` L-18 16 —0 17 —4 511 523 1153 1191 1250 M A 166 261 424 616 831 (8) 1017 (14) 122,E (14) 235 420 750 1037 1282 15 19 1716 L—� 21'-477 {256") PRESTRESSED 142 198 306 (11.) 393 (11) 480 (11) 567 (11) 654 (11) 09_099 21,_4,7 256" PRESTRESSED NR NR NR NR NR NR NR L-19 189_0„ 197_477 406 408 1019 1057 1104 142 230 369 531 713 (7) 903 (w) 1046 (1s) L -2O 2 ( ) N.R. 180 340 598 845 1114 1359 1468 9 77 7 7, L-20 18 - 8 2 Q - Q 376 377 980. 1017. 1063 9 ,7 77 r 137 192 295 1o) 378 11) 461 (to) 545 (11) 629 11) 9 99 9 99 99 r, NE NE NE NR NR NR NR L-21 22 —0 (264) PRESTRESSED c c c c L-21 20 —8 22'-0" (264) PRESTRESSED N.R. 137 221 354 508 681 (7) 861 (13) 997 (13) 165 315 550 784 1047 1285 1399 L-21 207_097 219_477 302 303 880 913 954 10) 9 91 99 124 t75 26"7 Io) 341 (10) 416 (10) 491 (1n) 566 9 99 9 99 � - NR NE NR NR NE NR NR L-22 24 —0 (288) PRESTRESSED r ( ( L—�22 22 —8 24 —0 (28899) PRESTRESSED N,R. L-22 22,_8f7 249_079 237 239 740 775 801 124 200 1316 450 600 (7) 756 (12) 8 r5 (13) 129 250 150 651 881 1092 1222 (#) THE NUMBERS IN PARENTHESIS ARL PERCENT REDUCTIONS FOR GR40 FIELD ADDED REBAR. (#) THE NUMBERS IN PARENTHESIS ARE PERCENT REDUCTIONS 1,'OR GR40 YIELD ADDED REBAR. NOTE: Bold numbers represent precast lintels prestressed using (2) 7/16" Diameter Prestressing Strands. ENGINEERING SPECIFICATIONSj (- i rFY111CA1, PRODUCT DESCRIPTION r -Ir YP �E ��,tNATION Iligh strength precast concrete lintels designed to be unfilled or filled to form a composite reinforced beam using concrete masonry units. �, : -• .�.. -.:•,`.; >� ®., MATERIALS = FILLED WITH GROUT U = UNFILLED • e • • • • • • • s • QUANTITY OF #5 REBAR AT mf'c 6" precast lintels = 3500 psi Concrete masonry units (CMU) per ASTM C90 with nriluuiuiu net area 130rPTOM UI'' LINTEL CAVITY • f'c 6" prestressed, 6" and 12" precast lintels = 6000 psi compressive strcnght = 1900 psi - - r - • f'e 4" precast lintels = 8000 psi Rebar per ASTM A615 trade 60 8U8 8F8—013/1T 8F8 013/2I 81+8-1B/1T 8I 8 IB/2T 777 • Grout per ASTM 0116 f'g - 3000 psi w/ maximum Prestressing strand per ASTM A116 Grade 270 law relaxation � 116—IB/ � � � IT � 3/5 inch aggregate and H to 11 inch slump. • 7/32 inch wire per ASTM A510 • Mortar per ASTM 0270 'Type M or S ' 'a GENERAL NOTES • e • e `� ® e NOMINAL WIDTH QUANTITY OF #5 Ct U 1. Provide full mortar head and bed joints. U. Cast -in-place concrete may be provided in composite lintel in lieu of 8F20-0B/1T H20-0B/2T 8F20-1B/1T 81,'20—ID/2 NOMINAL HEIGHT REBAR AT TOP 1 2. Shure filled hutels as required. concrete masonry units. U 4 U �4 3. Installation of lintel must comply with architectural 9. Safe load ratings based on rational design analysis per ACI 318 and ACI 530 e � e • • • 0- e � • ^ W � and/or structural drawings. 101'roduct Approvals; Miami Dade Comity, Florida Nos. 03-0605.05#5 REBAR AT `IOP�4 5 4. U -Lintels are manufactured witll 5-1/2 inch long notches at and 03-0605.04. Florida Certificate of product Approval number FL156.���3 _013/11 �� 8F28 _OB�2T 8F28 _1B�1T 8F28 _IB�2T MIN. (1) REW D hI ends to uccoulodate vertical cell rehiforchlg and grouting. 11:Phc exterior surface of lintels installed in exterior co812ncrete maauury walls a' 7:1t-1/2" CLEAR X 5. Reference the CAST -CREPE Load Reflection Graph shall have a coating of stucco applied in accurdanue with MIN 0920 �T® Brochure for lintel deflection information. or other approved coating. • • • • e • • e E- 4 . 6. Bottom field added rebar to be located at the bottom 12J.intels loaded simultaneously with vertical (gravity or uplift) and horizontal of lintel cavity. (lateral) loads should be checked for the combined loading with the < < r, �, ° I G.M.U. 7.7/32 inch diameter wee stirrups are welded to the bottom following equalium 8F12—OB/Vl 8F12-08/21 8F12-1B/1T H12 -2/2T F 00 ° a steel for mechanical auohorage. Applied vertical load Applied horizontal load Safe vertical load f Safe horizontal load S 1.0 ° GROUT SAFE LOAD 'TABLE NO'T'ES Lo 1. All values based on minimum 4 inch nominal bearing. 6. For composite lintel heights not shown, use safe load from oFANrk JAC llf3 Exception: Safe loads for unfilled lintels must be reduced next lower height. #6 RIiJ13AR AT BOTTOM by 20 i if bearing length is less than 6-1/I inches. 9. For lintel lengths not shown, use safe load from® ® OF LINTEL CAVITY DATE. P. N.R. = Not Rated. next longest length.` ` BOTTOM REINFORCING 3. Safe loads are superimposed allowable load. WAR safe loads in units of pounds per linear fuot.1/22/2012 7—b/6"ACTUAL PROVIDED IN LINTEL 4. Safe loads based on Grade 40 or Grade 60 field rebar. 11All safe loads based on simply supported 8p -m. (VARIES) ��: r. Additional lateral lead capacity eau be obtained by the 12;1'hc number in the parenthesis indicates the percent reduction 8 NOMINAL WIDTH ) designer by providing additional reinforced masonry above for grade 40 field added rebar.5 SHOWN the precast lintel. Sue Eculforced CMU on Page 4. Example: V-6" lintel Type 6F32-11 safe gravity load = 64 R- 72 (15) ��� JOB NUMBER 0. One #7 rebar may be substituted for two #5 rebars in 6" lintels only, w/ 10% reduction -:> 6472 (.05) = 5501 plf • " • • • • • • • • e m e e e • e • • • • • • • 1180/814 7. The designer may evalutc concentrated loads from the safe load tables b calculating the iiiaxnnunr resisting moment and shear at d -away �� r , �� u r �c i v �c s c — �c r r �r r , `SHEET' y g g y 8F 16—OB 1T 6M—OB/21' 8F16 -1B 1T 8FI G -1B 2T 8F24 -013/1T 8F24—OB 2T 8F24 -1B 11 8I� 24— IIB 2T 8F32-0B/IT 81,32 OB 2T 8F32—IB/IT 8F 32— IB 21 from the face of support. y,5 0 m CJI II II II I II I I II II II I II II II �� CJ2 CJ3 II II I I I I II I I 11 I I II •. �I. — — CJ4 II LI II II II CD o� I II II III P4 I II II ILk J6 II II II II II �� II II ---------------------- ro d P4 ' I H9 c9 1,4W X\ All o � — — — — ATTIC A cEs ... /JOS LOC T D a AI AI Al Al i I Al H5 I, H3 .zz= — H2 — .—. -. — —._ _.= i HI CJ5 .. -:_: I .. .. I II .. II .. II .. II .. II .. II .. .. I II .. _ _ II CJ5 CJ3 II II II II II ( II II I ( II II II = : CJ3 CJI a CJI ` ut, db:_ Nc SCALE - 1/4"=P -O" COWCTOR SCHEDULE W REF. 51MP5CN WOOD TRU55 PRODUCT REF. NO. HETA20 TO CONCRETE UPLIFT 1805 L55. (TYPICAL UN.O.) EASTI=NER5 PER (10)10d x 11/2" NAILS SINGLE CONNECTOR CONNECTOR SCBEDULE 'B' REF. 51MF50N GIRDER TRU55 PRODUCT REF. NO, (2) HETA20 TO CONCRETE O UPLIFT 2035 LBS. l FA5TENER5 PER (12) I0dx1.5" NAILS SINGLE CONNECTOR NOTES: I. THIS 15 A TRUSS OR RAFTER STRAP PLACEMENT PLAN. ITS INTENDED TO AID IN THE INSTALLATION OF TRU55 OR RAFTER STRAPS ONLY. THE ARCHITECT'S OR ENGINEER'S 5EAL DOES NOT RELIEVE THE TRUSS CO. 4 TRUSS DESIGNER OF THEIR RE5PON51BILITIE5 TO ENSURE THE INTEGRITY OF THE TRUSS STRUCTURE. VERIFY THE TRUSS CO. SEALED TRUSS PLACEMENT PLAN AND SEALED PROFILES. 2. THIS DIAGRAM IS INTENDED FOR USE BY PERSONS KNOWLEDGEABLE IN AND FAMILIAR WITH GENERALLY ACCEPTED METHODS AND STANDARDS OF TRUSS ERECTION AND HAND FRAMING. TRU55 ERECTION AND HAND FRAMING SHOULD NOT BE ATTEMPTED BY ANY PERSON WITHOUT THESE QUALIFICATIONS. 3. TRUSS ERECTION AND BRACING RE5PON5181LIT1ES MUST LIE WITH THE BUILDER. IT I5 THE RE5PON515ILITY OF THE BUILDER TO VERIFY ALL DRAWINGS. 4. ANY AND ALL REPAIRS/ALTERATIONS TO ANY TRU55 MUST f5E APPROVED AND ACCEPTED BY A REPRESENTATIVE OF THE TRU55 CO. 5. ALL TRU55 TO TRU55 HANGERS SHALL BE SPECIFIED 4 SUPPLIED BY THE TRU55 CO. UNLESS OTHERWISE NOTED ON THIS TRU55 LAYOUT BY THE SIGNING ARCHITECT, 6. ALL TRUSS CONNECTORS ARE TYPICAL UNLESS A CONNECTOR NUMBER 15 CALLED OUT. SEE CONNECTOR SCHEDULE 'A' ON TH15 SHEET FOR ALL TYPICAL CONNECTORS. 1. FOR CONNECTOR LOCATIONS WHERE A NUMBER IS CALLED OUT, SEE CONNECTOR SCHEDULE W ON TH15 SHEET FOR THE CONNECTOR I l� CD o� �- ` ut, db:_ Nc SCALE - 1/4"=P -O" COWCTOR SCHEDULE W REF. 51MP5CN WOOD TRU55 PRODUCT REF. NO. HETA20 TO CONCRETE UPLIFT 1805 L55. (TYPICAL UN.O.) EASTI=NER5 PER (10)10d x 11/2" NAILS SINGLE CONNECTOR CONNECTOR SCBEDULE 'B' REF. 51MF50N GIRDER TRU55 PRODUCT REF. NO, (2) HETA20 TO CONCRETE O UPLIFT 2035 LBS. l FA5TENER5 PER (12) I0dx1.5" NAILS SINGLE CONNECTOR NOTES: I. THIS 15 A TRUSS OR RAFTER STRAP PLACEMENT PLAN. ITS INTENDED TO AID IN THE INSTALLATION OF TRU55 OR RAFTER STRAPS ONLY. THE ARCHITECT'S OR ENGINEER'S 5EAL DOES NOT RELIEVE THE TRUSS CO. 4 TRUSS DESIGNER OF THEIR RE5PON51BILITIE5 TO ENSURE THE INTEGRITY OF THE TRUSS STRUCTURE. VERIFY THE TRUSS CO. SEALED TRUSS PLACEMENT PLAN AND SEALED PROFILES. 2. THIS DIAGRAM IS INTENDED FOR USE BY PERSONS KNOWLEDGEABLE IN AND FAMILIAR WITH GENERALLY ACCEPTED METHODS AND STANDARDS OF TRUSS ERECTION AND HAND FRAMING. TRU55 ERECTION AND HAND FRAMING SHOULD NOT BE ATTEMPTED BY ANY PERSON WITHOUT THESE QUALIFICATIONS. 3. TRUSS ERECTION AND BRACING RE5PON5181LIT1ES MUST LIE WITH THE BUILDER. IT I5 THE RE5PON515ILITY OF THE BUILDER TO VERIFY ALL DRAWINGS. 4. ANY AND ALL REPAIRS/ALTERATIONS TO ANY TRU55 MUST f5E APPROVED AND ACCEPTED BY A REPRESENTATIVE OF THE TRU55 CO. 5. ALL TRU55 TO TRU55 HANGERS SHALL BE SPECIFIED 4 SUPPLIED BY THE TRU55 CO. UNLESS OTHERWISE NOTED ON THIS TRU55 LAYOUT BY THE SIGNING ARCHITECT, 6. ALL TRUSS CONNECTORS ARE TYPICAL UNLESS A CONNECTOR NUMBER 15 CALLED OUT. SEE CONNECTOR SCHEDULE 'A' ON TH15 SHEET FOR ALL TYPICAL CONNECTORS. 1. FOR CONNECTOR LOCATIONS WHERE A NUMBER IS CALLED OUT, SEE CONNECTOR SCHEDULE W ON TH15 SHEET FOR THE CONNECTOR I l� CD o� P4 E'er d P4 QW c9 1,4W o � sem-, p, 0 .. - RICAL PIAN F , ELECTRICAL LEGEND qp - DUPLEX REC. D--Q--Q--Q- 2 - INCANDIr5CINT WALL LIGHTS If - QUADPLEX REC. 210V Q - 220 VOLT JUNCTION BOX new P - 220 VOLT REC. 11°y Q - IIID VOLT JUNCTION BOX wmgp - WATER PROOF REC. M - EXHAUST FAN ai qp - GROUND FAULT REC. S - SMOKE DETECTOR O yew - 11/2 SWITCHED REC. W1 BATTERY BACK-UP ® - FLOOR OUTLET - CARBON MCNOXIDE $ DETECTOR FL ST 553.885 - SWITCH Q - A/C THERMOSTAT �3 - 3 WAY SWITCH In RECESSED CAN LIGHT $D - DIMMER SWITCH -¢-- - INcAND. CEILING FIx ® -MINI CAN LIGHT FQ - INCAND. WALL FIX �- HALOGEN, UNDER CABINET LIGHTING - TRACK LIGHTING d - PHONE �t - FLUORE&C-ENT FIX -4 - CAT5 - EXTERIOR FLOOD LOT Ey � -� -CABLE CONNECTION - CEILING FAN PREWIRE ® VAPOR PROOF ❑ RECESSED CAN LIGHT - EMERGENCY LIGHTNG W/ mmmBATTERY � BACKUP ELECTRICAL NOTES NOTES: L SMOKE DETECTORS SHALL BE IN ALL 6LEEPIW3 AREAS, SHALL BE INTERCONNECTED, SHALL BE WITHIN 1'-0' TO V-0' OF PEAK, AND SHALL BE 3'-0' MIN FROM ANY SUPPLY OR RET FN AIR STREAM, AND EQUIPPED WITH A BATTERY BACK-UP. 2. ELECTRICAL MATERIALS AND INSTALLATIONS SHALL COMPLY W/ APPLICABLE PROVISIONS OF THE NATIONAL ELEC. CODE 2008, LOCAL CODES, AND THE LOCAL POWER CO. 3. INSTALLATION OF WIRING IN ANY EXPOSED AREA WILL BE N APPROVED CONDUIT OR USE MC CABLE. 4.2008 NEC 210.12 ALL 120 -VOLT, SINGLE-PHASE, 15 AND 20 AMPERE BRANCH GIRCUIT5 SUPPI-YMCa OUTLETS INSTALLED IN DWELLING UNIT: FAMILY ROOMS, DININCf ROOMS, LIVWi ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROGMS, RECiEATIGN ROOM5,. CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS SHALL BE PROTECTED BY A LISTED ARC -FAULT CIRCUIT MTERRIPTER COMBINATION -TYPE, IN5TALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. 5.2008 NEC 406JI IN ALL AREAS 5PECIFIED IN 21092, ALL 125 -VOLT, 15 ANP 20 AMPERE FIFCEPTACLES SHALL BE LIM TAMPER-RE5ISTANT RECEPTACLES, 6.2008 NEC 913J CAR 3GN MONOXIDE ALARMS SHALL BE INSTALLED WITHIN 10 FEET OF EACH I3EDROCK ALARM5 WILL BE POWERED BY THE MILDING WIRING AND HAVE BATTERY 15ACKUF'8. ELECTRICAL SERVICE _w AMP SERVICE (VERIFY SIZE OF SERVICE) 04/0 401INUr9 SER CABLE IN 2142' C"UIL 220v A/C DISC. METER LIGHTS t OUTLETS �2Pi -4 '14 COFFER uV 5 AMP BIEPKER TYPICAL ELECTRICAl_ 92 COFFER WV 5 Al iP BREAKER ER Ey � W a REQV) (40 CIi;rUIT5) � 12 COPPER WV 20 AMP DRE KER V MAIN DISCONNECT pq W COPPER TO WATER HEATER 6 p R UND�Clcally U % COPPER TO RANGE w SERPOW 04 BSD COPPER TO N'8"x8'-0" GALVANIZED GROUND ROD. BOND TO FTG STEEL WHEN REQ'D. ELECTRICAL RISER. SHEET. i �2Pi -4 Ey � W H � pq 6 p U w SHEET. i -4 SHEET. a F g' C.M.U. 4' LONG. SLAB W1 F15EWESH OVER 6 MIL VAPOR BARRIER a a' x 16' GONG. FOOTING W1(2) #5� BARS CONT. 11113' MIN. COVER CLEAN, COMPACTED, TERMITE TREATED FILL STFMUJALL POOfiINe CURS DEiAL r_2 SCALE: 3i4",I'_0" ROOF MATERIAL (SEE OVERHANG DETAIL) - PRE-ENGINEERED TRUSSES 0 24" O.C, (U,N,C,) W/ HURRICANE ANCHOR ON EACH TRUSS (SEE TRUSS PLAN FOR 5PEC5.) PROVIDE BUILDING PAPER OR GALV. STEEL PLATE BETWEEN INSULATION AS SPECIFIED TRU55 4 G.M.U. BLOCK SEE ELEV, FASCIA 4 SOFFIT - _ --� --/S" GYPSUM BOARD OR (SEE OVERHANG 1/2" U.S,G, 5AG RESISTANT DETAIL) SEE OVERHANGCEILING BOARD OR EQUAL DETAIL V'e (ASTM C 1395 / C 1395M) FILLED LINTEL BLOCK W/ (1) #5� ROD CONT. W/ MIN, 25" SPLICE (2" FROM TOP) (1) #5� ROD v OPENINGS 5'-0" OR GREATER l U.N.OJ PRECAST LINTEL AT ALL OPENINGS U.N.O. ON PLAN _41 1/2" GYP BOARD OVER 3/4' P.T. FURRING AL -FOIL INSULATION (R4.2 MIN.) ALUM. WINDOW OR FIXED GLASS (SEE FLOOR PLAN) PRECAST SILL MARBLE SILL #5� ROD IN FILLED CELL AS WALL FINISH MATERIALPER FLOOR PLAN TIED TO (SEE ELEVATIONS) —� - CONT. ROD IN FOOTER 31 LINTEL ROD ABOVE S" C.M.U. BLOCK = . _ BASE TRIM AS SPEC. EQUAL _ 4' CONC. SLAB W/ FIBER MESH - q = OVER MIL VAPOR BARRIER _ 0'-o" FIN. FL. FIN. GRADE 111111h, _ ';A _ \\/\\/\\/'�\j\\/ /\\ \\ \\ XIS/ \\ CLEAN, COMPACTED, TERMITE TREATED FILL 0"x16" 5TEMWALL FOOTING W/ (2) 05� RODS CONT. (3" MIN. DOVER) ONE = STORY all C --mu BLOC< WALL CN FEMALL I=CON I G 1 SCALE: 3/411=1'-0" T ROOF MATERIAL (SEE OVERHANG DETAIL) PRE-ENGINEERED TRUSS OR CONVENTIONAL FRAMED ROOF W/ HURRICANE ANCHOR —\ INSULATION AS SPECIFIED (A/C SPACE ONLY) No - GYPSUM B0ARD OR 1/2" U.S.G.. SAG RESISTANT CEL INCA BOARD OR, EQUAL (ASTM C 1395 / C 1395M) (AIC SPACE ONLY) PRECAST LINTEL (SEE HEADEER PLAN) TYPICAL CICU 13LCC< SECT I CN la CPN INC SCALE: 3/4"=1'-0" #5O BAR CONTINUOUS LINTEL COURSE W/ ' (1) 050 BAR FILLED SOLID. —25' MIN, LAP ON #5 Y BARS IN CORNER tlla •..9� 4 �1tl �db � m � ® S'N ,'Mi .. `fit v.tiY� 40. FILLED VERTICAL 05 BAR CONTINUOUS - CELL W/ (1) i5O BAR TOPICAL CORNER INF. LINTEL ISCU S , DE I SCALE: 3/4"=1'-0" A/C CHASE 6" P.V.C. PIPE THRU STEM WALL ;L r-lxl -mAr,= SEE TYP. WALL SECTION FOR FOOTING 51ZE A/C CPA3E THRU FOOT�NG SCALE: 3/4"=1'-0" SEE ELEV. PRE-ENGINEERED TRUSSES 24" O.C. COMPOSITION SHINGLES ON 15# FELT ON 15/32" 055 OR 15/32" CDX PLYWOOD ALUM. DRIP --___ ALUM. FASCIA MATCH EXISTING VENT. ALUM. 1, 501=1=1T , OVEHANDTAI SCALE: 3/4"=1'-0" Lu Q LOS ROOF EDGE (GADLE) ROOF EDGE NOTE: pp LINES ARE FOR ZONE DESIGNATION ONLY ROOF NAILING PATTERN (COMMON NAIIaS� ZONE 1: USE ad RING SHANK NAILS 1@ 6" O.G. EDGES - 12" O.G. FIELD ZONE 2: USE ad RING SHANK NAILS a 6" O.G. EDGES all O.G. FIELD ZONE 3: USE ad RING SHANK NAILS 6 6" O.G. EDGES - 6" O.G. FIELD GABLE TRU55: USE ad NAILS m 4" O.C. MECHANICAL DRIVEN USE MIN -0990 RING SHANK x 21/4" LONG w/ 15/64"0 HEAP (FULL ROUND) ZONE 1: 6" O.C. EDGES- a" O.C. FIELD ZONE 2: 4" O.G. EDGES- 6" O.G. FIELD ZONE 3: 4" O.G. EDGES- 4" O.C. FIELD GABLE TRU55: USE ad NAILS 1@ 4" O.C. ROOF DIAPHRAGM NOTES 1, ROOF SHEATHING ACTS AS A HORIZONTAL DIAPHRAGM 2. GYPSUM WALLBOARD ACTS A5 THE CEILING DIAPHRAGM NAIL 5(_,,HE1DU E FOR RCCF5 _ SCALE: 3/4"=1'-0" WALL F3EYON 4" CONC. SLAB W/ FIBER MESH OVER (o MIL VAPOR BARRIER DRIVEWAY SLAB NOTE: RECESS FOR 3' GARAGE DOOR al'XLVII THICKENED // �// //\//��` CLEAN, COMPACTED, EDGE W/ (1) CONT. \�\\�/ TERMITE TREATED FILL GARAGE DOCK FCCMN DETAIL SCALE: 3/4"=1'-01• 4� kk Kvvr �vu� � rca ---------•-----._—__---- a 'cwt 9I (D (D P4E- cj- I I a - / Z O RIDGE 0< O P4 0 r-+ w L------------ — ®fes o 1 _ � 4 � � 51 I ----- �� I ® 1 �n -1--- O 3 4n LOS ROOF EDGE (GADLE) ROOF EDGE NOTE: pp LINES ARE FOR ZONE DESIGNATION ONLY ROOF NAILING PATTERN (COMMON NAIIaS� ZONE 1: USE ad RING SHANK NAILS 1@ 6" O.G. EDGES - 12" O.G. FIELD ZONE 2: USE ad RING SHANK NAILS a 6" O.G. EDGES all O.G. FIELD ZONE 3: USE ad RING SHANK NAILS 6 6" O.G. EDGES - 6" O.G. FIELD GABLE TRU55: USE ad NAILS m 4" O.C. MECHANICAL DRIVEN USE MIN -0990 RING SHANK x 21/4" LONG w/ 15/64"0 HEAP (FULL ROUND) ZONE 1: 6" O.C. EDGES- a" O.C. FIELD ZONE 2: 4" O.G. EDGES- 6" O.G. FIELD ZONE 3: 4" O.G. EDGES- 4" O.C. FIELD GABLE TRU55: USE ad NAILS 1@ 4" O.C. ROOF DIAPHRAGM NOTES 1, ROOF SHEATHING ACTS AS A HORIZONTAL DIAPHRAGM 2. GYPSUM WALLBOARD ACTS A5 THE CEILING DIAPHRAGM NAIL 5(_,,HE1DU E FOR RCCF5 _ SCALE: 3/4"=1'-0" WALL F3EYON 4" CONC. SLAB W/ FIBER MESH OVER (o MIL VAPOR BARRIER DRIVEWAY SLAB NOTE: RECESS FOR 3' GARAGE DOOR al'XLVII THICKENED // �// //\//��` CLEAN, COMPACTED, EDGE W/ (1) CONT. \�\\�/ TERMITE TREATED FILL GARAGE DOCK FCCMN DETAIL SCALE: 3/4"=1'-01• 4� kk DRW JAC APva DB DATE - 1/22/2012 SCALE: AS SHOWN JOB NUMBER: 1180/814 SHEET- • � rca a a 'cwt P4E- cj- Z P4 r-+ w ®fes o � DRW JAC APva DB DATE - 1/22/2012 SCALE: AS SHOWN JOB NUMBER: 1180/814 SHEET- • MASONRY WALL ALUMINUM WINDOW FRAME- TAPCON PER WINDOW hJANUFACTURER SPECS, lx P.T. BUCK STRIP T -NAILED W/.109 DIA. MIN. To MASONRY Q S" O.G. MIN. AND PLACE WITHIN 6" FROM CORNERS WITH i" MIN. EMBEDMENT INTO BLOCK OR 2x P.T. BUCK STRIP INSTALL 3/16" DIA. SELF TAPPINC3 CONC. ANCHORS a" MAX. FROM ENDS AND 24" O'C. MAX. WITH 1" MIN. EMBEDMENT INTO BLOCK (2x BUCK TO EXTEND BEYOND WINDOW FRAME ON INTERIOR) WINDOW ATTACHMENT DETAIL r13 SCALE 3/4'1,1'-0" / "5 VERT. WALL REIN, GROUT CELLS 5OLID 2x8 P.T- 02 SYP JAMF3 — TRACK/5FRACKET FASTEN PER MANUF. 5PEC5. G- ARAC3E DOOR ATTACHMENT DETA SCALE: N.T.S. MASONRY WALL 1/211 x 511 "Ll' f5OL I WASHER SQ. ASHER 4 NUT AT FILLED CELL (4 PER SIDE) ,- P,T. DOOR STOP BRICK MOLD PRE -HUNG POOR FRAME SHIM A5 NECESSARY TAPCON5 PER POOR MANUFACTURER E. Ix P.T. BUCK STRIP T -NAILED W/ .109 DIA. MIN. TO MASONRY o 8'I O.C. MIN. AND PLACE WITHIN (o" FROM CORNERS WITH I" MIN, EMBEDMENT INTO BLOCK OR 2x P.T. BUCK STRIP INSTALL 3/16" DIA. SELF TAPPING CONC. ANCHORS a" MAX. FROM ENDS AND 24" O.C. MAX. WITH 1" MIN. EMBEDMENT INTO BLOCK Ox BUCK TO EXTEND BEYOND DOOR FRAME ON INTERIOR) :)CCR ATTACHMENT DETAILit SCALE: 3/4"=1'-0" 1.2 - ° (1) HTSM16 W/ (4) 1/4" x 21/4" TITN5 TO BOND BEAM 4 (a) 10d x 11/2' GALV. NAILS TO TRUSS. (11715 LB5 MAX UPLIFT) FILLED LINTEL BLOCK W/ (1) S5 ROD CONT. W/ MIN. 25" SPLICE (2" FROM TOP) CCRRECTION FOR I55ID LINTEL STRAP DETAIL SCALE. 3/4"=1'-0" 4" CONC. SLAB W/ FIBER MESH OVER 6 MIL VAPOR BARRIER 7luI. CLEAN, COMP., TERMITE TREATED FILL (1) S5 ROD CONT. OFFSET THICKENED EDGE � SCALE: 3/4"=I'-0" —4" CONCRETE SLAB 1 1 1 FOOTING W/ (2) #5 BAR5 I I� 1 1� II II �� #5 REBAR TYP. 1� i =R nMq - = - -- - -ell a1 —'W W m- - — -gym- - — - m- i ® _ Lf5FNT BAR W/ 25• LAP E.W. TYP OF 2 GORNFR 5AR DET41L (F0R FOOTING REO'MTS) SCALE. 3/411=1'-0" CERAMIC TILE FLOOR DRAIN SLOPE FLOOR 4' SHOWER RECESS -7 W/ (1) 05 REBAR CONT.'^. RECE33 AT 3HOWER SCALE: 3/4"=1'-0" TYP. INTERIOR WALL 4" CONC. 5LA5 W/ FIBERMESH OVER (o MIL VAPOR BARRIER 19 2 1 L2,,) cc CD C7 p SLAB SLOPES AWAY 4" CONC. SLAB W/ Cf) � w FROM HOUSE FIBERMESH OVER 6 FIN, GRADE MIL VAPOR BARRIERP4 E- F' a . F P4 pr, ��y ISI VAAyVAVAAVAA�A� CD G� co1.4 w CLEAN, COMP., TERMITE (1) #5 REBAR CONT. TREATED FILL THIC;<ENED E[DGjE DETAIL 1� SCALE: 3i4"=1'-0" �_2 a � a a Q a EXIST. ROOF SYSTEM AND ROOF STRAPPING Q F o P4 �a 1 SEE ELEVATIONS 1.2 DRILL 6" INTO EXIST. LINTEL, - EPDXY 4 DRIVE #5 4 BEND _ I _ FILLED LINTEL BLOCK W/ VERT., 25" LAP REO'D. _ _ (1) #5� ROD CONT. W/ MIN. 25" SPLICE (2" FROM TOP) SPLIT FACE OF BLOCK 9 PROP. FILLED CELL LOC- ATION. (TYP.) ALTERNATE LOCATION OF FOOTING DETAIL W/ FILLED CHAIR BLOCK DRILL 6" INTO EXIST. FTC., EPDXY 4 DRIVE 05 4 BEND VERT., 25" LAP REO'D. C ORRECTICN FOR M153EID [DOWELS IDETA SCALE: 3/4"=1'-0" 8" C.M.U. BLOCK 4" CONC. SLAB W/ FIBER MESH OVER MIL VAPOR BARRIER 0'-0' FIN. FL. ° e NOTE. STEM WALL SHOWING. SAME W/ MONOLITHIC FOOTER JAC APVD: DB Y r DATE f TYP. INTERIOR WALL 4" CONC. 5LA5 W/ FIBERMESH OVER (o MIL VAPOR BARRIER 19 2 1 L2,,) cc CD C7 p SLAB SLOPES AWAY 4" CONC. SLAB W/ Cf) � w FROM HOUSE FIBERMESH OVER 6 FIN, GRADE MIL VAPOR BARRIERP4 E- F' a . F P4 pr, ��y ISI VAAyVAVAAVAA�A� CD G� co1.4 w CLEAN, COMP., TERMITE (1) #5 REBAR CONT. TREATED FILL THIC;<ENED E[DGjE DETAIL 1� SCALE: 3i4"=1'-0" �_2 a � a a Q a EXIST. ROOF SYSTEM AND ROOF STRAPPING Q F o P4 �a 1 SEE ELEVATIONS 1.2 DRILL 6" INTO EXIST. LINTEL, - EPDXY 4 DRIVE #5 4 BEND _ I _ FILLED LINTEL BLOCK W/ VERT., 25" LAP REO'D. _ _ (1) #5� ROD CONT. W/ MIN. 25" SPLICE (2" FROM TOP) SPLIT FACE OF BLOCK 9 PROP. FILLED CELL LOC- ATION. (TYP.) ALTERNATE LOCATION OF FOOTING DETAIL W/ FILLED CHAIR BLOCK DRILL 6" INTO EXIST. FTC., EPDXY 4 DRIVE 05 4 BEND VERT., 25" LAP REO'D. C ORRECTICN FOR M153EID [DOWELS IDETA SCALE: 3/4"=1'-0" 8" C.M.U. BLOCK 4" CONC. SLAB W/ FIBER MESH OVER MIL VAPOR BARRIER 0'-0' FIN. FL. ° e NOTE. STEM WALL SHOWING. SAME W/ MONOLITHIC FOOTER JAC APVD: DB Y r DATE 1/22/2012 ��: AS SHOWN JOB NUMBER: 1180/814 a SHEET'*