CITY OF SANFORD
BUILDING & FIRE PREVENTION
PERMIT APPLICATION
Application No:
Documented Construction Value: $ 5363.00
Job Address: 474 Hansom Parkway, Sanford, FL. 32771 Historic District: Yes No 0
Parcel ID: 12-20-30-300-0130-0000 Residential Q Commercial
Type of Work: New Addition Alteration Repair Demo Change of Use Move
Description of Work: Roof Replacement - IKO Cambridge Asphalt Shingles
Plan Review Contact Person: Justin Shelton
Phone: 321-441-2300
Name Michael Seaman
Fax: 321-441-2313 Email:
Property Owner Information
Title: Re -Roof Department Manager
Phone: 407-574-1770
Street: 474 Hansom Parkway Resident of property?
City, State Zip: Sanford, FL. 32771
Contractor Information
Name Collis Roofing, Inc. Phone:
Street: P.O. Box 520668 Fax:
City, State Zip: Longwood, FL. 32752
Name: n/a
Street:
City, St, Zip:
Bonding Company: n/a
Address:
321-441-2300
321-441-2313
yes
State License No.: CCC05802
Architect/Engineer Information
Phone:
Fax:
E-mail:
Mortgage Lender: n/a
Address:
WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR
PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. A NOTICE OF COMMENCEMENT MUST BE
RECORDED AND POSTED ON THE JOB SITE BEFORE THE FIRST INSPECTION. IF YOU INTEND TO OBTAIN
FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF
COMMENCEMENT.
Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has
commenced prior to the issuance of a permit and that all work will be performed to meet standards of all laws regulating construction
in this jurisdiction. I understand that a separate permit must be secured for electrical work, plumbing, signs, wells, pools,
furnaces, boilers, heaters, tanks, and air conditioners, etc.
FBC 105.3 Shall be inscribed with the date of application and the code in effect as of that date: 51' Edition (2014) Florida Building Code
Revised: June 30, 2015 Permit Application
NOTICE: In addition to the requirements of this permit, there may be additional restrictions applicable to this property that may befoundinthepublicrecordsofthiscounty, and there may be additional permits required from other governmental entities such as water
management districts, state agencies, or federal agencies.
Acceptance of permit is verification that I will notify the owner of the property of the requirements of Florida Lien Law, FS 713
The City of Sanford requires payment of a plan review fee at the time of permit submittal. A copy of the executed contract is required
in order to calculate a plan review charge and will be considered the estimated construction value of the job at the time of submittal.
The actual construction value will be figured based on the current ICC Valuation Table in effect at the time the permit is issued, in
accordance with local ordinance. Should calculated charges figured off the executed contract exceed the actual construction value,
credit will be applied to your permit fees when the permit is issued.
OWNER'S AFFIDAVIT: I certify that all of the foregoing information is accurate and that all work will
be done in om li ce with all applicable laws regulating construction and zoning.
ignatur er/A nt / ate Signatur
4ofContraAdAgent
Date Print
0%vne1/ gent' ,ame . Print Con ct eent's h e/ I
cr f(WE J. WILLIAMS,-'a..PU ------NotarPublic • ;=o : STEPHANIE J. WILLIAMS yStateofFloidaaoCommission # GG 008373 - Not
Public -State of Florida F,„;°
My Comm. = •o; Commission # GG 008373 ExpiresOct29, 2020 'FpFFI` My Comm. Expires Oct 29, 2020 Owner/
Agent is Person n to Me or TZ 11, nown to Me or Produced
1D Type of ID Produced ID Type of 1D BELOW
IS FOR OFFICE USE ONLY Permits
Required: Building Electrical Mechanical Plumbing Gas[] Roof Construction
Type: Occupancy Use: Flood Zone: Total
Sq Ft of Bldg: Min. Occupancy Load: # of Stories: New
Construction: Electric - # of Amps Plumbing - # of Fixtures Fire
Sprinkler Permit: Yes No # of Heads Fire Alarm Permit: Yes No APPROVALS:
ZONING: UTILITIES: WASTE WATER: ENGINEERING:
FIRE: BUILDING: COMMENTS:
Revised:
June 30, 2015 Permit
Application
THIS INSTRUMENT PREPARED BY:
Name: Stephanie Williams
Address: Collis Roofing. Inc.
P_r) Box 520668_ Longwood, FL. 32752
NOTICE OF COMMENCEMENT
State of Florida
County of Seminole
Permit Number:
1111111111111111111111111111111111111111
MARYANNE MORSE, SEMINOLE COUNTY
CLERK OF CIRCUIT COURT & COMPTROLLER
EK 8933 Py 1201 (Psis)
CLERK'S v 2016134620
RECORDED 12/29/2016 10! 42:29 AM
RECORDING FEES $10.011
RECORDED BY hdevore
Parcel ID Number: i :I 'ao - 3013CID-01 Y) `y00.0
The undersigned hereby gives notice that improvement will be made to certain real property, and In accordance with
Chapter 713, Florida Statutes, the following information is provided in this Notice of Commencement.
DESCRIPTION OF PROPERTY.: (Legal description of the property and street address If available)
Curri'(iCie toilelrV ob" 00)W-fc GENERAL
DESCRIPTION OF IMPROVEMENT: Roof
Replacement OWNER
INFORMATION: Name: /
414 Address:
7l t' !'ts(J/M So l l U d , , d 7 Fee
Simple Title Holder (if other than owner) Name: n/a Address:
CONTRACTOR:
Name:
Collis Roofing, Inc. Address:
P.O. Box 520668, Longwood, FL. 32752 Persons
within the State of Florida Designated by Owner upon whom notice or other documents may be serve x r a as
provided by Section 713.13(1)(b), Florida Statutes.T Name:
n/a ''•'`•'• Address:
In
addition to himself, Owner Designates of I^ To
receive a copy of the Lienor's Notice as Provided in Ci cy r'
Section
713.13(1)(b), Florida Statutes. Expiration
Date of Notice of Commencement (The expiration date is 1 year from date of recording unless a different
date is specified) WARNING
TO OWNER ANY PAYMENTS MADE BY THE OWNER AFTER THE EXPIRATION OF THE NOTICE Offf COMMENCEMENT
ARE CONSIDERED IMPROPER PAYMENTS UNDER CHAPTER 713. PART I, SECTION 713.131; FLORIDA
STATUTES, AND CAN RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. i NOTICE
OF COMMENCEMENT MUST BE RECORDED AND POSTED ON THE JOB SITE BEFORE THE FIRS INSPECTION.
IF YOU INT ND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY!•' BEFORE
COMMENCI G V JRK • R RECORDING YOUR NOTICE OF COMMENCEMENT. 4 Under
penIa ties- penury I d clare that I have read the foregoing and that the facts stated in it are true' to
the best of I kndwle a nd belief. Mir
VkCA e ( 9-a YYR a K Ownees
Signature Owner's Printed Name Florida
Statute 713.13(1)(g):' The owner must sign the notice of commencement and no one also may be permitted to sign in Ns or her stead.' y
0
h•-
C,
c_ ) v
c: ua7
c
u
State
of T I (.Y'rri01 County of ? The
foregoing instrument was acknowledged before me this day of by by >'
I l r l G+?/ //J Who Is personally known to me Name
of person making statement 7) i ) OR
who has produced Identification El type of Identification pr duce - ! (/ JIIIIy,
STEPMANIEJ.
WILLIAMS / bt r NotartEp1lc •State of Florida sa •
0 Commission # GG 008373 ydla. signature a
A, I My Comm. Expires Oct 29. 2020
FLORM Ot1PARTMYltl7 PRroflassilanalBusiness8FRaouiam7tinn BCIS
Home i Log In ! User Registration I Hot Topics I Florida
l
Y ;Yk °:@ Product Approval IUSER:
Public User ct %.
ynr Florida
Building Code Online Submit
Surcharge Slats & Facts I Publications I FBC Staff I BCIS Site Map Links I Search Product
Approval Menu > Product or Application Search > Application List > Application Detail FL #
FL7006-R9 Application
Type Revision Code
Version 2014 Application
Status Approved Approved
by DBPR. Approvals by DBPR shall be reviewed and ratified by
the POC and/or the Commission if necessary. Comments
Archived
Product
Manufacturer IKO Industries, Ltd Address/
Phone/Email 40 Hansen Road South Brampton,
NON -US L6W 3H4 708)
496-2800 Ext200 rmetzOO1@tampabay.
rr.com Authorized
Signature Robert Metz rmetzOOI@tampabay.
rr.com Technical
Representative Bob Metz Address/
Phone/Email REMCO of Pinellas 456
Avila Circle NE Saint
Petersburg, FL 33703 727)
776-5261 rmetzOO1@tampabay.
rr.com Quality
Assurance Representative Don Shaw Address/
Phone/Email IKO Industries LTD 120
Hay Rd. Wilmington,
DE 19808 717)
579-6706 don.
shaw@iko.com Category
Roofing Subcategory
Asphalt Shingles Compliance
Method Certification Mark or Listing Certification
Agency FM Approvals - CER Validated
By Locke Bowden Validation
Checklist - Hardcopy Received Referenced
Standard and Year (of Standard) Standard Year ASTM
D3161 modified to 110 mph 2009 ASTM
D3462 2009 ASTM
D7158 Class H 2O08 ASTM
E108 2007 Equivalence
of Product Standards Certified
By http://
www.floridabui Idi ng.orglprlpr_app_dtl.aspx?param=wGEVXQwtDgse7mYBd2b3K6mXtoZLhN VX122N pl70J 1 E%3d 1/3
1/11/2017 Florida Building Code Online
Product Approval Method Method 1 Option A
Date Submitted 06/28/2015
Date Validated 06/30/2015
Date Pending FBC Approval
Date Approved 07/06/2015
Summary of Products
FL # Model, Number or Name Description
7006.1 Cambridge, Cambridge HD and CRC Laminated architectural fiberglass asphalt shingle
Biltmore AR manufactured at IKO's Kankakee, IL; Hawkesbury, Ont.;
Wilmington, DE; Sylacauga,AL and Toronto, Ont. plants
Limits of Use Certification Agency Certificate
Approved for use in HVHZ: Yes FL7006 R9 C CAC FM Letter - ASTM d3161 letter - 4-15-
2015 .pdfApprovedforuseoutsideHVHZ: Yes
Impact Resistant: N/A FL7006 R9 C CAC FM Letter - ASTM d3462 letter - 5 6
15.pdfDesignPressure: N/A
Other: FL7006 R9 C CAC FM Letter - ASTM E 108 letter - 5 3
15 .odf
Quality Assurance Contract Expiration Date
12/31/2020
Installation Instructions
FL7006 R9 II IKO-133-02-01 Letter - Installation
Instructions for FBC FL7006.pdf
Verified By: Duc T Nguyen 65034
Created by Independent Third Party: No
Evaluation Reports
Created by Independent Third Party:
7006.2 Hip and Ridge 12 Cap fiberglass This is a 12" x 12" fiberglass asphalt shingle used to cover
shingles the hip and/or ridge of an asphalt shingle roof system
manufactured in Toronto, Ont. and Brampton, Ontario
Limits of Use Certification Agency Certificate
Approved for use in HVHZ: Yes FL7006 R9 C CAC FM Letter - ASTM d3161 letter - 4-15-
2015 ,odfApprovedforuseoutsideHVHZ: Yes
Impact Resistant: N/A FL7006 R9 C CAC FM Letter - ASTM d3462 letter - 5 6
15.pdfDesignPressure: N/A
Other: FL7006 R9 C CAC FM Letter - ASTM E 108 letter - 5 3
15 •Ddf
Quality Assurance Contract Expiration Date
12/31/2020
Installation Instructions
FL7006 R9 II Hip and Ridge Cap Shingle Installation
Instructions. pdf
FL7006 R9 II IKO-133-02-01 Letter - Installation
Instructions for FBC FL7006,pdf
Verified By: Duc T Nguyen PE 65034
Created by Independent Third Party: No
Evaluation Reports
Created by Independent Third Party:
7006.3 Leading Edge Plus Asphalt Shingle One piece fiberglass asphalt shingle used as a starter strip at
Starter Strip the bottom of a roof system manufactured in Brampton and
Hawkesbury, Ontario plants
Limits of Use Certification Agency Certificate
Approved for use in HVHZ: Yes FL7006 R9 C CAC FM Letter - ASTM d3161 letter - 4-15-
2015 .PdfApprovedforuseoutsideHVHZ: Yes
Impact Resistant: N/A FL7006 R9 C CAC FM Letter - ASTM d3462 letter - 5 6
15.DdfDesignPressure: N/A
Other: FL7006 R9 C CAC FM Letter - ASTM E 108 letter - 5 3
15 .pdf
Quality Assurance Contract Expiration Date
12/31/2020
Installation Instructions
FL7006 R9 II IKO-133-02-01 Letter - Installation
Instructions for FBC FL7006.pdf
FL7006 R9 II Roofino- Products- Leading- Edge- Plus- ApDlication-
EN(1).Ddf Verified
By: Duc T Nguyen PE 65034 Created
by Independent Third Party: No Evaluation
Reports Created
by Independent Third Party: 7006.
4 Marathon 25 AR, CRC Superglass 1 3 tab fiberglass asphalt shingle manufactured at IKO's http://
www.floridabui I di ng.orglprlpr_app_dtl.aspx?param=wGEVXQwtDgse7m YBd2b3K6m XtoZ LhN VXI22N pl7OJ 1 E%3d 26
1/11/2017
w
M25AR
Limits of Use
Approved for use in HVHZ: Yes
Approved for use outside HVHZ: Yes
Impact Resistant: N/A
Design Pressure: N/A
Other:
Florida Building Code Online
Brampton, Ontario, Hawkesbury Ont., Toronto, Ont.;
Sylacauga, AL and Kanakakee, IL plants
Certification Agency Certificate
FL7006 R9 C CAC FM Letter - ASTM d3161 letter - 4-15-
2015 .Ddf
FL7006 R9 C CAC FM Letter - ASTM d3462 letter - 5 6
15.Ddf
FL7006 R9 C CAC FM Letter - ASTM E 108 letter - 5 3
15 .Ddf
Quality Assurance Contract Expiration Date
12/20/2020
Installation Instructions
FL7006 R9 II IKO-133-02-01 Letter - Installation
Instructions for FBC FL7006.Ddf
Verified By: Duc T Nguyen 65034
Created by Independent Third Party: No
Evaluation Reports
Created by Independent Third Party:
Back Next
Contact Us :: 2601 Blair Stone Road, Tallahassee FL 32399 Phone: 850-487-1824
The State of Florida is an AA/EEO employer. Copyright 2007-2013 State of Florida.:: Privacy Statement :: Accessibility Statement :: Refund Statement
Under Florida law, email addresses are public records. If you do not want your e-mail address released in response to a public -records request, do not send electronic
mail to this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 850.487.1395. -Pursuant to Section
455.275(1), Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address if they have
one. The emails provided may be used for official communication with the licensee. However email addresses are public record. If you do not wish to supply a
personal address, please provide the Department with an email address which can be made available to the public. To determine if you are a licensee under Chapter
455, F.S., please click here .
Product Approval Accepts:
W EN aC heck
Credit Card
Safe
http://www.floridabui Idi ng.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDgse7mYBd2b3K6mXtoZLhN VX122N pl70J 1 E%3d 313
CONSTRUCTION MATERIALS
TECHNOLOGIES
March 30, 2015
IKO Industries, Ltd
120 Hay Rd.
Wilmington, DE 19809
Re: FBC FL7006
Sir(s),
PRI Construction Materials Technologies has completed a technical review and attached sealed shingle
instructions in compliance the 2014 Florida Building Code.
This review was completed based on the receipt of following evidence from IKO Industries, Ltd:
1) IKO Shingle Application Instructions — 3-Tab Shingles
EN-3Tab_Appins_8AGXEFS-2012-11_reformatted 2013-02-rev07/13-Florida)
2) IKO Laminated Shingles Application Instructions
EN-Laminated_Appins_8TTEFS-2012-04_reformatted 2013-02-rev07/13-Florida)
3) IKO Hip and Ridge 12 Application Instructions
EN-HipandRidge12_3HRTri-2013-08_reformatted 2013-08)
4) IKO Leading Edge Plus Shingle Application Instructions
EN-3LEP-Tri-2012-06_reformatted 2013-03)
5) ASTM D3161 Test Report (FM Approvals Project No. 3040947)
The attached instructions should be used in conjunction with the published manufacturer's application
instructions and applicable code. In the event the instructions conflict, these instructions shall govern.
Statement of Independence: PRI Construction Materials Technologies and/or Duc T. Nguyen, FL P.E. do not
have nor plan to acquire a financial interest in any company manufacturing or distributing products for which
the test reports are issued.
Signed: C Signed: L^
Brad Grzybo ski Duc T.Aduven
Managing rector Florida Re ere Professional Engineer
P.E. Number: 65034
Date: April 30, 2015 Date: April 30, 2015
Attachments: A) IKO Shingle Application Instructions - 3-Tab
B) IKO Laminated Shingles Application Instructions
C)' IKO Hip and Ridge 12 Application Instructions
D) IKO Leading Edge Plus Application Instructions
II.N1iBB11iYXIM
PRI Construction Materials Technologies, LLC. 6412 Badger Drive Tampa, FL 33610 Tel: 813-621-5777 Fax: 813-621-5840 e-mail: matedalstesting@pdcmt.com WebSite: httpJlwww.pdcmt.com
IKO
Installation Instructions for
Asphalt Shingles
Page 2 of 5
IKO Shingle Application Instructions — 3-Tab Shingles
ASTM D3161, Class F — IKO Marathon 25 AR and CRC Superglass M25AR)
NOTE: THESE INSTRUCTIONS SHALL BE USED IN CONJUCTION WITH IKO'S PUBLISHED
APPLICATION INSTRUCTIONS AND THE APPLICABLE CODE. IN THE EVENT THE INSTRUCTION
CONFLICT, THESE INSTRUCTIONS WILL GOVERN.
ROOF DECK: Solidly sheathed and fastened deck conforming to 2014 FBC.
UNDERLAYMENT: Applied in accordance with building code requirements. For areas where the roof slope is
less than 4" per foot down to 2" per foot, use 2 layers of underlayment conforming to building code
requirements, the first sheet overlapping the eave protection by 19", followed by full 36" widths overlapping
each preceding course by 19" or other Approved underlayments in accordance with the qualified application
instructions. For areas where the roof slope is 4" per foot or greater, cover the deck with one ply of
underlayment laid parallel to the eaves, with 2" horizontal laps and 4" end laps. Apply metal drip edges on top
of any underlay along rake edges and directly to the deck along eaves in accordance with building code
requirements.
NAILING: Use galvanized (zinc coated) roofing nails, 11 or 12 gauge, with at least 3/8" diameter heads, long
enough to penetrate through plywood or 3/4" into boards. Use 4 nails per shingle placed 6-1/8" above the butt
edge, approx. 1" and 13" from each end and 1/2" above each cutout. Drive nails straight so that nail head is
flush with, but not cutting into shingle surface.
NAILING ON STEEP SLOPES: For steep slopes of 21" per foot (60°) or more, use 6 nails per shingle placed
as shown below. Ensure that no nail is within 2" of a joint/cutout of the underlying shingle. Seal down each
shingle at time of application with three 1 " diameter (approx. size and thickness of a quarter) spots of asphalt
plastic cement placed under the shingle 2" above the bottom edge and equally spaced along the shingle.
Apply plastic cement in moderation since excessive amounts may cause blistering. CAUTION: Shingles
should seal to the underlying course when the factory applied asphalt sealant is sufficiently warmed by the
heat of direct sunlight.
EXPOSURE: Installed shingles shall have a maximum average exposure of 5-5/8".
STEEP SLOPES
SEALING STRIP — i • • f i •
12" I r-1/8"
6-118"
11 t_
NAILS NAILS
DO NOT NAIL INTO OR ABOVE THE SEALING STRIP
PRI Construction Materials Technologies, LLC. 6412 Badger Drive Tampa, FL 33610 Tel: 813-621-5777 Fax: 813-621-5840 e-mail: matedalstesting@pdcmt.cwm WebSite: hftpl/www.pdcmt.com
I KO
Installation Instructions for
Asphalt Shingles
Page 3 of 5
IKO Laminated Shingles Application Instructions
ASTM D3161, Class F — Cambridge, Cambridge HD, and CRC Biltmore AR)
NOTE: THESE INSTRUCTIONS SHALL BE USED IN CONJUCTION WITH IKO'S PUBLISHED
APPLICATION INSTRUCTIONS AND THE APPLICABLE CODE. IN THE EVENT THE INSTRUCTION
CONFLICT, THESE INSTRUCTIONS WILL GOVERN.
ROOF DECK: Solidly sheathed and fastened deck conforming to 2014 FBC.
UNDERLAYMENT: Applied in accordance with building code requirements. For areas where the roof slope is
less than 4" per foot down to 2" per foot, use 2 layers of underlayment conforming to building code
requirements, the first sheet overlapping the eave protection by 19", followed by full 36" widths overlapping
each preceding course by 19" or other Approved underlayments in accordance with the qualified application
instructions. For areas where the roof slope is 4" per foot or greater, cover the deck with one ply of
underlayment laid parallel to the eaves, with 2" horizontal laps and 4" end laps. Apply metal drip edges on top
of any underlay along rake edges and directly to the deck along eaves in accordance with building code
requirements.
NAILING: Use galvanized (zinc coated) roofing nails, 11 or 12 gauge, with at least 3/8" diameter heads, long
enough to penetrate through plywood or 3/4" into boards. Use 4 nails per shingle placed in the nail line 7-3/8"
below the top edge, approx. 1" and 13" in from each end. Drive nails straight so that nail head is flush with,
but not cutting into shingle surface.
NAILING ON STEEP SLOPES: For steep slopes of 21" per foot (60°) or more, use 6 nails per shingle placed
as shown below. Ensure that no nail is within 2" of a joint/cutout of the underlying shingle. Seal down each
shingle at time of application with three 1" diameter (approx. size and thickness of a quarter) spots of asphalt
plastic cement placed under the shingle 2" above the bottom edge and equally spaced along the shingle.
Apply plastic cement in moderation since excessive amounts may cause blistering. CAUTION: Shingles
should seal to the underlying course when the factory applied asphalt sealant is sufficiently warmed by the
heat of direct sunlight.
EXPOSURE: Installed shingles shall have a maximum average exposure of 5-7/8".
NAIL LINE
6 3/8"t
NAILING - STEEP SLOPES APPLICATION
Use six nails as shown.
mot„ .1" — 1„
F1 1] r]
CFMFNT
PROPER APPLICATION REQUIRES THAT THE NAILS PENETRATE BOTH THE OVERLAY AND UNDERLAY PORTIONS OFTHE SHINGLE
PRI Construction Materials Technologies, LLC. 6412 Badger Drive Tampa, FL 33610 Tel: 813-621-5777 Fax: 813-621-5840 e-mail: matedalstesting@pricmt.com WebSite: httplhvww.pdcmt.com
IKO
Installation Instructions for
Asphalt Shingles
Page 4 of 5
IKO Hip and Ridge 12 Application Instructions
ASTM D3161, Class F — IKO Hip and Ridge 12)
NOTE: THESE INSTRUCTIONS SHALL BE USED IN CONJUCTION WITH IKO'S PUBLISHED
APPLICATION INSTRUCTIONS AND THE APPLICABLE CODE. IN THE EVENT THE INSTRUCTION
CONFLICT, THESE INSTRUCTIONS WILL GOVERN.
Cut hip and ridge shingles into thirds, using the perforation marks as a cutting guide. These shingles are
designed for a 5 1/8" (130 mm) exposure. (For a neater appearance, the top of each side of each piece has
been factory trimmed on a 1" (25 mm) taper (see drawing). Bend each piece over the hip or ridge, and nail 5
5/8" (143 mm) above the butt edge 1" (25 mm) in from each edge, exposing each piece 5 1/8" (130 mm).
Apply hip pieces starting at the lower end of the hip, working up toward the ridge. On hip roofs, apply ridge
pieces starting at each end, meeting in the middle. On gable roofs, apply ridge pieces starting at the end
opposite to the prevailing wind direction and continue to the other end. Note: To obtain a three-dimensional
effect, (which is recommended, but not required), apply hip and ridge shingles double thickness by stacking 2
pieces on top of one another, the lower piece extending about 3/4" (19 mm) further than the top piece (see
diagram). The final shingle should be set in cement, and the exposed nail heads of the final shingle should be
covered with cement. Prior to application in cold weather, storing the shingles in a heated area will allow for
easier bending.
NOTE: SHINGLES MUST BE APPLIED PROPERLY. THEYARE DESIGNED FOR USE AS HIP AND RIDGE
SHINGLES ONLY, AND SHOULD NOT BE USED FOR ANY OTHER APPLICATIONS. WE ASSUME NO
RESPONSIBILITY FOR LEAKS OR DEFECTS RESULTING FROM POOR APPLICATION OR FAILURE TO
PROPERLY PREPARE THE SURFACE TO BE ROOFED OVER, OR FAILURE TO PROVIDE PROPER
VENTILATION IN ACCORDANCE WITH MINIMUM PROPERTY STANDARDS REQUIREMENTS. REVIEW
ALL APPLICABLE BUILDING CODES, MINIMUM PROPERTY STANDARDS, AND REQUIREMENTS PRIOR
TO APPLYING THESE SHINGLES USING THESE APPLICATION INSTRUCTIONS.
cn mm,
TAPER CUT
PRI Construction Materials Technologies, LLC. 6412 Badger Drive Tampa, FL 33610 Tel: 813-621-5777 Fax: 813-621-5840 e-mail: matedalstesfing@pdcmt.com WebSite: http:/hvww.pricmt.com
IKO
Installation Instructions for
Asphalt Shingles
Page 5 of 5
IKO Leading Edge Plus Application Instructions
ASTM D3161, Class F — IKO Leading Edge Plus)
NOTE: THESE INSTRUCTIONS SHALL BE USED IN CONJUCTION WITH IKO'S PUBLISHED
APPLICATION INSTRUCTIONS AND THE APPLICABLE CODE. IN THE EVENT THE INSTRUCTION
CONFLICT, THESE INSTRUCTIONS WILL GOVERN.
1. Apply any underlayment, eave protection, valley (lashings, or drip edges to roof deck as required.
2. Each 39 3/8" x 131/4" (1000 mm x 336 mm) IKO Leading Edge Plus strip is perforated lengthwise for
separation into two (2) shingles. Take one IKO Leading Edge Plus strip and fold flat at perforation to
separate.
3. Take one of the separated shingles 39 3/8" x 6 5/8" (1000 mm x 168 mm) and remove approximately
20"(500 mm). Install this shingle on the lower left corner of the roof deck, granule side up, with the
factory installed sealant adjacent to the eaves. The shingle should overhang the rake edge and eaves
by a nominal 1/4" (6 mm) minimum. Fasten the shingle to the roof deck with nails located 3" to 4" (75
mm to 100 mm) from the eave edge and 1" (25 mm) in from each end.
4. Take the leftover 20" (500 mm) piece shingle. Rotate the piece and align it vertically up the rake edge
with the factory installed sealant adjacent to the outer edge of the roof. The shingle should overhang
the rake edge by a nominal 1/4" (6 mm) minimum. Fasten the shingle to the roof deck with fasteners
located 3" to 4" (75 mm to 100 mm) from the rake edge and 1" (25 mm) in from each end.
5. Repeat Steps 3 — 4 for the right lower corner of the roof deck.
NAILING: Use galvanized (zinc coated) roofing nails, 11 or 12 gauge, with at least
3/8" (9 mm) diameter heads, long enough to penetrate through plywood or 3/4" (20
mm) into boards. Use 4 nails per shingle placed 3" to 4" (75 mm to 100 mm) from
the eave edge and approximately 1" and 13" (25 mm and 330 mm) in from each end.
6. Apply full-length IKO Leading Edge Plus shingles to the remaining eave edges of the roof deck. Install
the shingles granule side up with the factory applied sealant adjacent to the eaves. The shingles
should overhang the rake edge and eaves by a nominal 1/4" (6 mm) minimum. Fasten the shingles to
the roof deck with nails located 3" to 4" (75 mm to 100 mm) from the eave edge, 4 nails per shingle.
7. Apply roof shingles as per the instructions printed on each product's package. Make certain the first
course of field shingle lies flush with the edges of the fastened IKO Leading Edge Plus. In this way,
the sealant on the IKO Leading Edge Plus shingles will adhere to the first -course field shingles and
help keep them from lifting in high winds.
PRI Construction Materials Technologies, LLC. 6412 Badger Drive Tampa, FL 33610 Tel: 813-621.5777 Fax: 813-621.5840 e-mail: matedalstesting@pricmt.com WebSite: hltpltwww.pricmt.com
LIMITED POWER OF ATTORNEY
Altamonte Springs, Casselberry, Lake Mary, Longwood, Sanford,
Seminole County, Winter Springs
Date: 1 /11 /2017
I hereby name and appoint: Ray Henderson
an agent of: Collis Roofing, Inc.
Name of Company)
to be my lawful attorney -in -fact to act for me to apply for, receipt for, sign for and do all things
necessary to this appointment for (check only one option):
t] The specific permit and application for work located at:
474 Hansom Parkway, Sanford, FL. 32771
Street Address)
Expiration Date for This Limited Power of Attorney:
License Holder Name: J. Douglas Lanier
State License Number: CCC058022
Signature of License Holder: a 0a, )
STATE OF FLORIDA
COUNTY OF Seminole
The foregoing instrument was acknowledged before me this 11 day of January ,
200 17 , by J. Douglas Lanier who is LN personally known
to me or who has produced as
identification and who did (did not) t n o
Sign Aure
rdrj eTa 1ANIE J. WILLIAMS
ary ublic - State of FloridacCommission # GG 008373
My Comm. Expires Oct 29, 2020
Rev. 08.12)
Stephanie J. Williams
Print or type name
Notary Public - State of _
Commission No.
My Commission Expires:
Florida
0
City of Sanford
Roof Permit Application Checklist
All permit application packages must be complete prior to acceptance. You must check each box to the
left or indicate n/a on this submittal. A complete application package shall include the following:
El Building Permit Application completed, signed and notarized. Application must include correct address
and complete parcel I.D. number.
Copy of applicable contractor's license issued by the State of Florida (if the contractor is the
applicant).
A site specific notarized power of attorney shall be required from the licensed contractor if
he/she appoints an employee of his/her company to sign the permit application as the contractor.
Certificate of insurance indicating worker's compensation insurance coverage and naming the City of
Sanford as certificate holder, or a copy of a worker's compensation exemption issued by the State .of
Florida (must be submitted with each application if contractor is the applicant).
D1a Completed and signed Owner Builder Statement / Affidavit (if the owner is the applicant).
These guidelines were compiled to assist the applicant in preparing a roofpermit application and may not be
complete. The applicant is required to meet all City of Sanford, state, and federal code requirements.
COLLIS ROOFING, INC.
P.O. Box 520668
Longwood, FL 32752-0663
Ph. (321) 441-2300
Fax (321) 441-2313
Lic. N CCCOSS022
Date: October 24, 2016 Phonc: 407-574-1770
Attention: Michael Seaman Email:
Job Address: 1474 Hansom Pk%% — Sanford 32771
Collis Roofing, Inc. proposes to supply the labor and materials necessary to apply your roofing as follows:
A) Remove old shingles and underlayment to bare deck and dispose of properly.
B) Inspect existing decking for water damage and re -nail according to code.
C) ALL NECESSARY NN'OOD-WORK IS BILLED ON A TENIE AND MATERIAL BASIS, AND IS NOT
INCLUDED IN THIS PROPOSAL. SEPARATE INVOICE WILL BE SENT TO THE CUSTOMER ONCE,
THE JOB IS CONIPLE'TE. (x initinl)
I. Supply and install code approved RIIINO U20 synthetic underlayment to deck using simplex nails.(2 layers)
2. Supply and install code approved self -adhered underlayment along all valleys per manufacturer specifications.
3. Supply and install code approved 2 W' galvanized painted drip at all eaves, directly to the deck. '
4. Supply and install code approved 2 %" galvanized painted cave drip at all rake/gable ends. (Dri. Coplor: UMr4- 5.
Secure the cave metal with mastic and then apply starter shingles at all eaves with the seal strip at the edge of the roof. 6.
Supply and install all lead tlashings for plumbing penetrations. 7.
Supply and install 30 linear feet of aluminum ridge vents. 8.
Supply and install standard galvanized preformed valley metal. 9.
Supply and install IKO Cambridge di n nsional shin les p r n ianufacturecs specifications and all applicable building codes (
Please specify shingle color: ly,-'fQ - 10.
Clean up all debris and walk perimeter with a roll magnet. 11.
All materials to be installed to manufacture recommendations. 12.
Collis Roofing, Inc. will provide all applicable permits. 13.
All workmanship to be warranted for five (5) years from date of completion of building (Sample Attached). The
above work shall be performed in a substantial workmanlike manner for the sum of: S $.363 Supply
and install (1) 2'x2' self -Bashing glass skylight*"" With
payment to be made as follows: Deductible and first check due at signing, balance upon completion. PRICING
EXPIRES THIRTY (30) DAN'S FROM THE DATE GIVEN ABOVE. Respectfully
Submitted: Joey McVay, Collis Roofing The
above prices and scope of %work are satisfactory and Collis Roofing, Inc. is hereby authorized to do the work as set forth above and
in accordance with the terms and conditions attached hereto; payments will be made as outlined. Collis
Roofing, Inc. Date:
Approved By: ACCORDING
TO FLORIDA'S CONSTRUCTION LIEN LAW (SECTIONS 713.001-713.37. FLORIDA STATUTES), THOSE
WHO WORK ON YOUR PROPERTY OR PROVIDE MATERIALS AND ARE NOT PAID IN FULL IIAVE A RIGHT
TO ENFORCE THEIR CLAIM FOR PAYMENT AGAINST YOUR PROPERTY. IF YOUR CONTRACTOR Oil
A SUBCONTRACTOR FAILS TO PAN' SUBCONTRACTORS, SUB -SUBCONTRACTORS, OR MATERIAL SUPPLIERS,
THE PEOPLE WHO ARE ONYED MONEY MAY LOOK T'O YOUR PROPERTY FOR PAYMENT, EVEN IF
YOU HAVE ALREADY PAID YOUR CONTRACTOR IN FULL. IF YOU FAIL TO PAN' YOUR CONTRACTOR, YOUR
CONTRACTOR MAY ALSO HAVE A LIEN ON YOUR PROPERTY. THIS MEANS IF A LIEN IS FILED YOUR
PROPERTY COULD BE SOLD AGAINST YOUR WILL TO PAY FOR LABOR, MATERIALS, OR OTIIER SERVICES
THAT YOUR CONTRACTOR OR A SUBCONTRACTOR MAY HAVE FAILED TO PAN'. TO PROTECT YOURSELF,
YOU SHOULD STIPULATE. IN THIS CONTRACT THAT BEFORE ANY PAYMENT IS MADE., YOUR CONTRACTOR
IS REQUIRED TO PROVIDE YOU WITH A WRITTEN RELEASE OF LIEN FROM ANY PERSON OR
CONIPANY THAT HAS PROVIDED TO YOU A "NOTICE TO OWNER." FLORIDA'S CONSTRUCTION LIEN LAZY
IS COMPLEX AND IT IS RECOMMENDED THAT YOU CONSULT AN ATTORNEY. Page
I of3 Initial O
CONSTRUCTION ENGINEERING LD
1809 West Virginia Drive ! Kissimmee, FL 34744
Office 407-944-9561•, 407=90.8-6257 ,p Fax 407.-944-9563
Wiley@constructionengineering.com
www.constructionengineefing.corri
i
Memo To: City of Sanford Building Department-
From: Wiley Jones, PE
j RE: 474 Hansom Parkway
Sanford, Florida
Permit No: 17-157 / 969204
Mr. Wiley Jones, P.E., Senior Engineer with Construction- Engineering LLC, performed.a site
visit to the residence located -at 474 Hansom Parkway, Sanford, Florida on'December 5,
2018. The purpose of the site visit was to access the roof to determine if it meets the
requirements of the 2017 Florida Building code, Existing Building, 6th edition.
Mr. Jones had shingles removed at random locations on the roof and the roofing components
were inspected: All roof components inspected by Mr. Jones met'or exceeded the
requirement of the 2017.Florid6 Building Code.
It is the opinion of Mr. Jones that the shingle roof installed at 474 Hansom Parkway, Sanford,
Florida was properly installed and meets the re,'quirements of the 2017.Florida Building code:
Please, do not hesitate'to call .Mr. Jones at 4.07=908-6257 if you wish'to discuss this job.
Wiley Jones, P.E.
FL License No. 64019" .- i
i December 9; 2018 _ j