HomeMy WebLinkAbout2660 Orlando Dr 17-1756; INTERIOR REMODELLEGEND f EXISTING TO REMAIN EXISTING TO BE REMOVED NO WORK IN THIS AREA DEMOLITION FLOOR PLAN KEY NOTES O PROVIDE A TEMPORARY DUST BARRIER AT RESTROOM ENTRANCE WHILE UNDER CONSTRUCTION O REMOVE EXISTING GRAB BARS REMOVE EXISTING LAVATORY AND MIRROR. O EXISTING URINAL TO REMAIN. O REMOVE EXISTING PAPER TOWEL DISPENSER. O REMOVE ALL EXISTING FLOOR AND WALL TILE FINISHES AND PREP FOR NEW FINISHES, O REMOVE EXISTING WING WALLS, PARTITIONS AND DOORS AS INDICATED AND REQUIRED FOR NEW LAYOUT. O REMOVE EXISTING WATER CLOSET AND CAP PLUMBING. O EXISTING WATER CLOSET TO REMAIN. 10 EXISTING LAVATORY TO REMAIN, 1 I REMOVE EXISTING ADA ROOM SIGNAGE FROM DOORS 12 REMOVE EXISTING HAND DRYER. NOTE: DURING CONSTRUCTION ONE RESTROOM WILL REMAIN OPENING WHILE OTHER RESTROOM IS BEING REMODELED. SITE PLAN Scale: NTS i AA TRUE NORTH PROJECT DIRECTORY CLIENT Rossco Construction Services Contact: John Ross 170 E. Boca Raton Rd. Suite #2 Boca Raton, FL 33432 DRAWING INDEX ARCHITECT LIS Architecture & Engineering Contact: H. Daniel Hotter R.A. 2572 W. St. Rd, 426 Ste. 2064 Phone: 321-244-0402 Oviedo, FL 32765 REVISIONS. COVER 2660 HWY 17 92 z aoIToo N tr N SANFORD,FL LU .j CO i U) r MC�) C�) C_ T-1.0 COVER SHEET & DEMOLITION PLAN ARCHITECTURAL z J m QMj �w�CO -11 C) W mm6TG ..... A-1.0 FLOOR PLAN AND ADA DETAILS GENERAL NOTES A. THE G.C. SHALL TAKE ALL NECESSARY PRECAUTIONS TO ENSURE THE SAFETY OF THE PUBLIC AND/OR WORKMEN ON THE JOB AND TO PREVENT ACCIDENTS OR INJURY TO ANY PERSON ON, ABOUT, OR ADJACENT TO THE PREMISES. THE G.C. SHALL COMPLY WITH ALL LAWS, ORDINANCES, CODES, RULES AND REGULATIONS RELATIVE TO SAFETY AND THE PREVENTION OF ACCIDENTS. B. THESE DEMOLITION PLANS ARE TO BE USED IN CONJUNCTION WITH THE d ENTIRE SET OF WORKING DRAWINGS. DO NOT REMOVE OR DEMOLISH ANYTHING WITHOUT VERIFYING AND COORDINATING WITH ALL GENERAL TRADES AS TO HOW THEY RELATE TO THE OVERALL PROJECT. O C. GENERAL CONTRACTOR SHALL PAY FOR ALL REQUIRED DEMOLITION PERMIT FEES AND OBTAIN ALL APPLICABLE DEMOLITION PERMITS. D. GENERAL CONTRACTOR SHALL REMOVE ALL DEBRIS & EQUIPMENT DAILYy��' DURING THE DEMOLITION WORK. E. GENERAL CONTRACTOR SHALL PATCH AND REPAIR ALL DAMAGED SURFACES AS OUTLINED IN THE DRAWINGS. F. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING SITE AND BUILDING CONDITIONS PRIOR TO CONSTRUCTION. G. ABANDONED PIPES SHALL BE CAPPED IN A MANNER TO PERVENT ANY DEAD ENDS IN PIPE RUNS. p O p m H. DEMOLITION MEANS AND METHODS ARE CONTRACTORS RESPONSIBILITY G. RESTROOMS TO BE AVAILABLE AND FUNCTIONING AT ALL TIMES FOR EMPLOYEES DURING RENOVATION DEMOLITION FLOOR PLAN Scale: 1/2" = V-0" TRUE NORTH KEY PLAN NOT IN SCOPE: KITCHEN 1580 SF DINING 1051 SF INTERIOR RENOVATION: RESTROOMS 188 Square Feet TRUE NORTH 0 w U ZD 0 O a. w Of SCALE 1/16" = 1'-0" m O VICINITY MAP POPEYES o 2660 HWY 17 92 z aoIToo N tr N SANFORD,FL LU .j CO i U) r MC�) C�) C_ z J m QMj �w�CO -11 C) W mm6TG ..... �•.,I,,.anw, •s.�sW 0 LL1. > M M �a�� U ::Dz w C— � o L) 0 r� m U z Gr q A In Al CO 0 0 J UN U m v .n ° - ZD w hminom Wq§Pa;ngnlQ 1— r W C/) z I z 0 Z 0 0 f9W Q i w ..,. Q Q 0 ( LL.Yi t}fll lD m J - pi—,aut f �,u Gesl M �anfrylkW (:•rJar kl Iry4�hnalQ w N N LU M z O J N CD z o � v N W U F > N V) M w - CD Q N N 7 In L (Uq NV)(I-w TRUE NORTH 0 w U ZD 0 O a. w Of SCALE 1/16" = 1'-0" m O VICINITY MAP POPEYES o Cn 2660 HWY 17 92 z SANFORD,FL LU .j i U) r C_ 0 -11 C) C14 ..... �•.,I,,.anw, •s.�sW 0 LL1. M U �� U C— � ,,I L) 0 r� m U z Gr q A In Al CO 0 J w U m - hminom Wq§Pa;ngnlQ .` z I 0 LU i f9W Q i Y4. ..,. 1. viN,nn,,N ( LL.Yi t}fll lD w - pi—,aut f �,u Gesl ' it �anfrylkW (:•rJar kl Iry4�hnalQ Cn U .j i U) C_ 0 -11 C) C14 (n C0 0 cr_ M U �� o C— � J rL L) 0 r� m U C O "' CO (� 0 J w O U m .. .k�«.f�! WntW:{ilrna,j 5uilatl 5a „row nb� \ Urtandu SknlwU'�' _ Q V ItrtbJll fhp,l� - I Z Q Mdlnrr,uc. �' - VD fIn lwp�rllnanl , z /•' f kan.n se,nmda. � LLJ I % ._ TRUE NORTH O (��'�i fMnlnl ynnwr0 Cny GNvcn ncugemy '. �1 P Uj _ 0 CD LU a� PROJECT SUMMARY O �- O LEGAL ,JURISDICTION: CITY OF SANFORD, FL w O = O N 4, O w a BUILDING CODE: FLORIDA BUILDING CODE 5TH EDITION 4CU r- J <c n w 2014 FLORIDA FIRE PREVENTION CODE 0 o = o LU (NEPA 1 &NEPA 101, 2012 FLORIDA EDITION) <C 1 b C) ELECTRICAL: NFPA 70, NATIONAL ELECTRICAL CODE, 2012 EDITION qq�1 Q C) PLUMBING: 2014 FLORIDA BUILDING CODE, PLUMBING RVI� MINER MECHANICAL: 2014 FLORIDA BUILDING CODE, MECHANICAL P `' ^ �J�f- O GAS: 2014 FLORIDA FUEL GAS CODE - U DACE � ENERGY 2014 FLORIDA BUILDING CODE ENERGY CONSERVATION - 5TH EDITION - cn Lu ACCESSIBILITY: 2014 FLORIDA BUILDING CODE ACCESSIBILITY - 5TH EDITION SAI�IFORD 90WII.�D1y!IS�iV w BUILDING FOOTPRINT AREA: EXISTING - UNALTERED A PERMIT ISSUED SHALL BE CONSTRUED TO BE A RENOVATION AREA: 184 SF LICENSE TO PROCEED WITH THE (.�JORK AND NOT AS J AUTHORITY TO VIOLATE, CANCEL, ALTER OR SET cn SEATING: NOT IN SCOPE UNALTERED ASIDE ANY OF THE PROVISIONS OF THE TECHNICAL UU CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT � TME (BUILDING OFFICIAL FROM THEREAFTER TYPE CONSTRUCTION: V B UNPROTECTED REQUIRING A CORRECTION OF ERRORS IN PLANS. X ` TION OR VIOLATIONS OF THIS CODE w J n O J Uj 0 Q � r~ LU w Cn 0... i j O U i 1� OF- X11 F- \>1 •F ••'4�4 m : 'A b�781 G� • l � ` `�' raj • •; � A EN FL, RE 0 81 OCCUPANCY: A2 - ASSEMBLY (BELOW 150 OCCUPAN�r�STHUC — .... PROJECT DESCRIPTION: THIS PROJECT CONSISTS OF AN INTERIOR RENOVATION OF THE RESTROOM AREA FOR AN EXISTING POPEYES RESTAURANT TO MEET ADA REQUIREMENTS. THE DINING, KITCHEN AND DRIVE THROUGH AREAS WILL REMAIN IN OPERATION DURING THE REMODELING PROCESS. DURING CONSTRUCTION ONE RESTROOM WILL REMAIN OPEN WHILE THE OTHER RESTROOM IS BEING REMODELED. PROJECT GENERAL NOTES A. IT IS INTENDED THAT A COMPLETE OCCUPIABLE BUILDING PROJECT IS PROVIDED. B DO NOT SCALE THESE DRAWINGS. VERIFY ALL DIMENSIONS AND CONDITIONS IN THE FIELD. ANY DISCREPANCIES IN THESE DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND KFC CM PRIOR TO STARTING WORK. C. GC SHALL PROVIDE EACH SUBCONTRACTOR WITH A COMPLETE AGENCY -PERMITTED DRAWING SET AT TIME OF CONSTRUCTION OFFICE PROJECT NO. 2017-038 ISSUE DATE 06-05-17 DRAWN CHECKED VI ILLI IVV. T-1 V w U a: LL 8'-3Y" 2 R CD I LO INTERCERAMIC: GOLD MEUNIER 13" x 13" RE57"R®CSM FINISHES ELEVATION Scale: 3/0 = 1'"0" GENERAL SIGNAGE NOTES: THE FOLLOWING ELEMENTS AND SPACES OF ACCESSIBLE BUILDINGS SHALL BE IDENTIFIED BY THE INTERNATIONAL SYMBOL ACCESSIBILITY. ACCESSIBLE PASSENGER LOADING ZONES (SEE DETAIL 1 THIS SHEEN ACCESSIBLE ENTRANCES WHEN NOT ALL ENTRANCES ARE ACCESSIBLE. INACCESSIBLE ENTRANCES SHALL HAVE SIGNAGE COMPLYING WITH DETAIL 5 THIS SHEET INDICATING THE DIRECTION TO THE NEAREST ACCESSIBLE ENTRANCE. ACCESSIBLE TOILET AND BATHING FACILITIES WHEN NOT ALL ARE ACCESSIBLE (SEE DETAIL 6 THIS SHEET) SAFETY DEVICES DESIGNED AND INTENDED FOR PUBLIC USE (E.G., FIRE ALARM PULL STATIONS, MANUAL MECHANISMS AC:0VATION EMERGENCY SIGNALING DEVICES, FIRE EXTINGUISHERS, ETC.) SHALL BE IDENTIFIED WITH SIGNAGE COMPLYING WITH ALL NUMBERED NOTES (THIS SHEET) SIGNS IDENTIFYING TOILETS SHALL USE THE WORDS "MEN" AND "WOMEN" OR "MEN'S TOILET" AND "WOMEN'S TOILET" ONLY. MALE AND FEMALE CARICATURES (I.E., PICTOGRAMS) SHALL ALSO BE PROVIDED. IF PICTOGRAMS ARE PROVIDED, THEN THEY SHALL BE ACCOMPANIED BY THE EQUIVALENT VERBAL DESCRIPTION PLACED DIRECTLY BELOW THE PICTOGRAM. THE PICTOGRAM BORDER DIMENSION (THE UNOBSTRUCTED FIELD WITHIN WHICH IT IS LOCATED) SHALL BE 6" MIN. FLOOR DRAINS ARE NOT ALLOWED IN THE REQUIRED TURNING RADIUS (WHICH ARE ESSENTIALLY MOST OF THE FLOOR IN A RESTROOM). FLOORS SHOULD BE LEVEL, CHANGES IN LEVEL ARE NOT PERMITTED. ��a ~ 5 TYP. INTERIOR SIGN HEIGHT y. ao m swat 2 6 PROVIDE` 30" X 48" g CLR. FL, 5 SPACE o I , MENS TOILET- 3 WOMEN'S TOILET o u I 4 az c' W x`uu I h; a a „ t co CIA CN o My , e� " 48 GRAB BAR NUMBERED 1. NOTES:_ B" MIN. BORDER DIMENSION- MALE/FEMALE FIGURES. I I WALL TO CENTERLINE. INSULATE ALL DRAIN AND HW LINES BELOW LAV. SEE DETAIL •-y USE OF MALE/FEMALE CHARACTERS IS REQUIRED 1 m r, ¢ � A H A O INSTALL 48" SIDE GRAB BARS I �, x "' 3, LETTERS AND NUMBERS SHALL BE RAISED ass" FROM THE BACKGROUND ON WHICH THEY ARE BELOW R I . mN I \ o c3 MOUNTED AND SHALL BE %" MIN. TO 2" MAX. IN HEIGHT. LETTERS SHALL BE CAPITAL LETTERS LETTERS AND NUMERALS SHALL HAVE SHARPLY DEFINED EDGES AND MAY BE EITHER SANS 42 GRAB BAR �q 0ONLY. g M c(70 1T f ADA DIMS \ c� SERIF OR SIMPLE SERIF. r. \ \ a o, I ¢ \ IN, LL °T' 42 GRAB N a U INSTALL PAPER TOWEL DISPENSER , N 5' LETTERS SHALL HAVE A WIDTH TO -HEIGHT RATIO BETWEEN 3:5 AND 1:1. SHALL BETWEEN 1:5 AND 1:10. BAR FLUSH CONTROL SHALL 1'-5" 5'-0" w 0 MIN. LAVATORY SHOWN MAY NO. ` �1 I \`�„ BE LOCATED ON THE Q MIN. 11 CLEAR FLOOR SPACE OPEN SIDE OF THE WATER IN PROJECT -SHOWN FOR uC HOT WATER AND DRAIN THEY ARE LOCATED IN AN EGGSHELL (SEMI -MATTE), MATTE (FLAT), OR OTHER NON -GLARE FINISH CLOSET PIPES TO BE INSULATED PROTOTYPICAL ADA RESTROOM ELEVATIONS GENERAL NOTES: Scale'/" - 1'"0" 1. PROVIDE PROPER 2x BLOCKING AT WALL RECESSED MOUNTED ACCESSORIES. BOWL AND PIPES MUST BE 2. GRAB BARS, FASTENERS AND MOUNTING DEVICES SHALL BE INSTALLED PER MOUNTED EITHER BY HAVING LIGHT CHARACTERS ON A DARK BACKGROUND OR DARK ADA REQUIREMENTS. CONTAINED WITHIN THIS AREA BENJAMIN MOORE HOT WATER SUPPLY & DRAIN ° 2159-30 APPLE CRISP - 3. REFER TO FLOOR PLAN NOTES FOR BLOCKING AND SUBSTRATE NOTES. LINE SHALL BE INSULATED IF CL ABOVE BOTH WALL TILE SKIRT NOT PROVIDED (TYP) a ' . AND MOSAIC TILES 4. LOCATE FLUSH HANDLE ON WIDE SIDE OF WATER CLOSET. R - Scale: 3/8" = 1'-0" 5. ALL DIMENSIONS THIS DRAWING ARE TO FINISH SURFACE. in Scale: PITS INTERCERAMIC: 6. PROVIDE 5/8" CEMENTITIOUS BOARD SUBSTRATE FULL HEIGHT BEHIND ALL 1"x 1" MOSAIC TILE NEW TILED WALLS. Lu COJ 'o 6" STRIP Lu R CD I LO INTERCERAMIC: GOLD MEUNIER 13" x 13" RE57"R®CSM FINISHES ELEVATION Scale: 3/0 = 1'"0" GENERAL SIGNAGE NOTES: THE FOLLOWING ELEMENTS AND SPACES OF ACCESSIBLE BUILDINGS SHALL BE IDENTIFIED BY THE INTERNATIONAL SYMBOL ACCESSIBILITY. ACCESSIBLE PASSENGER LOADING ZONES (SEE DETAIL 1 THIS SHEEN ACCESSIBLE ENTRANCES WHEN NOT ALL ENTRANCES ARE ACCESSIBLE. INACCESSIBLE ENTRANCES SHALL HAVE SIGNAGE COMPLYING WITH DETAIL 5 THIS SHEET INDICATING THE DIRECTION TO THE NEAREST ACCESSIBLE ENTRANCE. ACCESSIBLE TOILET AND BATHING FACILITIES WHEN NOT ALL ARE ACCESSIBLE (SEE DETAIL 6 THIS SHEET) SAFETY DEVICES DESIGNED AND INTENDED FOR PUBLIC USE (E.G., FIRE ALARM PULL STATIONS, MANUAL MECHANISMS AC:0VATION EMERGENCY SIGNALING DEVICES, FIRE EXTINGUISHERS, ETC.) SHALL BE IDENTIFIED WITH SIGNAGE COMPLYING WITH ALL NUMBERED NOTES (THIS SHEET) SIGNS IDENTIFYING TOILETS SHALL USE THE WORDS "MEN" AND "WOMEN" OR "MEN'S TOILET" AND "WOMEN'S TOILET" ONLY. MALE AND FEMALE CARICATURES (I.E., PICTOGRAMS) SHALL ALSO BE PROVIDED. IF PICTOGRAMS ARE PROVIDED, THEN THEY SHALL BE ACCOMPANIED BY THE EQUIVALENT VERBAL DESCRIPTION PLACED DIRECTLY BELOW THE PICTOGRAM. THE PICTOGRAM BORDER DIMENSION (THE UNOBSTRUCTED FIELD WITHIN WHICH IT IS LOCATED) SHALL BE 6" MIN. FLOOR DRAINS ARE NOT ALLOWED IN THE REQUIRED TURNING RADIUS (WHICH ARE ESSENTIALLY MOST OF THE FLOOR IN A RESTROOM). FLOORS SHOULD BE LEVEL, CHANGES IN LEVEL ARE NOT PERMITTED. ��a ~ 5 TYP. INTERIOR SIGN HEIGHT y. ao m swat 2 6 PROVIDE` 30" X 48" g CLR. FL, 5 SPACE o I , MENS TOILET- 3 WOMEN'S TOILET o u I 4 az c' W x`uu I h; a a E t co CIA CN I My , e� r h z NUMBERED 1. NOTES:_ B" MIN. BORDER DIMENSION- MALE/FEMALE FIGURES. 0 ¢ WALL TO CENTERLINE. INSULATE ALL DRAIN AND HW LINES BELOW LAV. �� 2. USE OF MALE/FEMALE CHARACTERS IS REQUIRED 1 m 1\.� { \`' � A H A O INSTALL 48" SIDE GRAB BARS I � t0 co 3, LETTERS AND NUMBERS SHALL BE RAISED ass" FROM THE BACKGROUND ON WHICH THEY ARE REINSTALL HAND DRYER AT PROPER MOUNTING HEIGHT. I . mN I \ o c3 MOUNTED AND SHALL BE %" MIN. TO 2" MAX. IN HEIGHT. LETTERS SHALL BE CAPITAL LETTERS LETTERS AND NUMERALS SHALL HAVE SHARPLY DEFINED EDGES AND MAY BE EITHER SANS ` , z �q 0ONLY. Q M c(70 1T f I \ c� SERIF OR SIMPLE SERIF. r. \ \ a o, I ¢ \ IN, LL °T' ALPHABETIC / NUMERIC SIGNAGE SHALL BE ACCOMPANIED BY GRADE 2 BRAILLE. N a U INSTALL PAPER TOWEL DISPENSER , N 5' LETTERS SHALL HAVE A WIDTH TO -HEIGHT RATIO BETWEEN 3:5 AND 1:1. SHALL BETWEEN 1:5 AND 1:10. , s w 0 STROKE -WIDTH -TO -HEIGHT RA110 BE LAVATORY SHOWN MAY NO. ` �1 I \`�„ � Q 6' MATCH FIXTURE TO BE USED IN, / CLEAR FLOOR SPACE ALL SIGNS SHALL HAVE LETTERS, NUMERALS, CHARACTERS AND THE BACKGROUND ON WHICH IN PROJECT -SHOWN FOR uC 30' X 48' MIN, H THEY ARE LOCATED IN AN EGGSHELL (SEMI -MATTE), MATTE (FLAT), OR OTHER NON -GLARE FINISH DIMENSION ILLUSTRATION-SHONFONLY ONLY. CHARACTERS AND SYMBOLS SHALL CONTRAST HATH THE BACKGROUND ON WHICH THEY ARE BOWL AND PIPES MUST BE MOUNTED EITHER BY HAVING LIGHT CHARACTERS ON A DARK BACKGROUND OR DARK 0 CONTAINED WITHIN THIS AREA CHARACTERS ON A LIGHT BACKGROUND. HOT WATER SUPPLY & DRAIN 7• EXIT SIGNS AT EXIT DOORS SHALL INCLUDE RAISED BRAILLE IN ACCORDANCE WITH 2010 ADA LINE SHALL BE INSULATED IF CL STANDARDS FOR ACCESSIBILITY DESIGN SECTION 703 AND 704 AND FOLLOW LOCAL AND STATE SKIRT NOT PROVIDED (TYP) CODES. MOUNT PER INTERIOR SIGN HEIGHT NOTES ABOVE. A DETAIL AT LAVATORY L0 a ADA ROOM SIGNAGE Scale: 3/8" = 1'-0" Scale: PITS 1111�eu Gdaw L,.ml,JbO,rYxLd41.wu3..r!G3m>'xi4LGaiai�Ii3.sYai,x✓.w„�t.�.:'U'�.Sabb6i«a..s:.:dbi.0 Lyi JLY.i d^iRY,An.Y .o ,v.«. ,« t' ro'.A+»w.d�F'..�.ku^��`wUw„d...Jukt+aA.,a.k&.o-n,.v`eu'2 b,u..viAELS,IPu. �«rk6 d.u.a GG�tv^'uS AV. .k4Y,rz x ,.,;t, ...w «,w,,, aaxa�uu x�. w.a.:u.sk �a ,.a.yam...r.�.w.av's�.wa�aw,e.wvrr.,, wu..��....�.w o.e>wmmvwrw«, .onamx.+>.�„_ .�..,a..o...�..... .. ,.. m.. ......_,__ _._..._-_.__-__. _ _ RESTROOM FLOOR PLAN Scale: 1/2" = 1'"0" .. ....... .. . O............... * .. ........... _ I If Oi w U O n w w w 0 F- 0 z Lu w I - w U z w z z O w 0 RESTROOM PLANT KEY NOTES: I h; � E t co CIA CN I e� INSTALL SINK TO PROVIDE A 34" A.F.F. LIP HEIGHT TOP OF LAV AND V-3" MIN. FROM m a) N co INSTALL NEW ADA ROOM SIGNAGE ON WALL NEXT TO DOOR LATCH SIDE. 0 ¢ WALL TO CENTERLINE. INSULATE ALL DRAIN AND HW LINES BELOW LAV. LC - O REINSTALL MIRROR VERTICALLY W/ B.O. AT 40" A.F.F. CV)M LL O INSTALL 48" SIDE GRAB BARS 0 � t0 co -I p REINSTALL HAND DRYER AT PROPER MOUNTING HEIGHT. 0 3 INSTALL 42" REAR GRAB BARS. (d3 c3 (D is REINSTALL FLUSH VALVE TO PLACE HANDLE ON OPEN SIDE OF WC. w Q M c(70 o c ,b3 o c� 0 j f LL re N a U INSTALL PAPER TOWEL DISPENSER 0 a C/) 5 , s w 0 w : O Q INSTALL NEW TILE FLOOR AND TILE WALL FINISHES ON ALL WALLS a J co H Q ADJUST DOOR CLOSERS TO 5 LBS MAX. PRESSURE TO OPERATE AND MIN 5 Q SECONDS TO CLOSE. ADD LEVER HANDLE WITH LOCKING. 0 W CL L0 a Lu Mtrj Lu COJ 'o . N N C' Lu M O LL O G? z ¢ o N LLI U CV N U r <� 0Lu CD CD U j '(n C `-L Lo L N C) 0- LL w U O n w w w 0 F- 0 z Lu w I - w U z w z z O w 0 RESTROOM PLANT KEY NOTES: I h; � E I e� INSTALL SINK TO PROVIDE A 34" A.F.F. LIP HEIGHT TOP OF LAV AND V-3" MIN. FROM � �"/ INSTALL NEW ADA ROOM SIGNAGE ON WALL NEXT TO DOOR LATCH SIDE. 0 ¢ WALL TO CENTERLINE. INSULATE ALL DRAIN AND HW LINES BELOW LAV. LC - O REINSTALL MIRROR VERTICALLY W/ B.O. AT 40" A.F.F. O INSTALL 48" SIDE GRAB BARS 0 � -I p REINSTALL HAND DRYER AT PROPER MOUNTING HEIGHT. 0 3 INSTALL 42" REAR GRAB BARS. (d3 c3 0 (::D REINSTALL FLUSH VALVE TO PLACE HANDLE ON OPEN SIDE OF WC. w Q INSTALL SOAP DISPENSER. c(70 o c� 0 0 f LL w INSTALL PAPER TOWEL DISPENSER 0 a C/) 5 , s w 0 w O Q INSTALL NEW TILE FLOOR AND TILE WALL FINISHES ON ALL WALLS a J co H Q ADJUST DOOR CLOSERS TO 5 LBS MAX. PRESSURE TO OPERATE AND MIN 5 Q SECONDS TO CLOSE. ADD LEVER HANDLE WITH LOCKING. 0 CL Lu GRAB BAR SHALL BE '1-'1/2" MAX., OUTSIDE DIA.- TYPICAL O CLR.Lo 2- 1/4"x3' EXPANSION ANCHORS ATp CLEAR ? Lo CLEAR Z O a MASONRY OR CONC. WALL 2- # l Ox2" ^ I U p 0 FLOOR FLOOR >- SCREWS AT WOOD OR STEEL STUD f SPACE a 0 SPACE R a WALL-TYP: / r� M OU / Co I- fy w _I w V wA/ > (U w \' $"MIN. KNEE R. w 2"x6" BLOCKING AT WOOD STUD WALLS. , MIN. KNEE (OMIT BLOCKING AT MASONRY OR SPACE DEPTHMIN. DEPTH CONC. WALL) - TYPICAL C 48" MIN.48" MIN. u X GRAB RAR 3" = V-0° I ACCESSIBLE LAVATORY 3/,L" = 1'-w C/) ACCESSIBLE (LAVATORY 3/4" = P-0" I J (TOILET) (LAVATORY) (URINAL) 3'-6" S.S. GRAB BAR T.S. COVER DISPENSER U) CONTROLS MOUNTED ON 14" PAPER TOWEL DISPENSER MIN. PROJECTION PULL STATION m WIDE SIDE OF TOILET AREA MIRROR MOUNTED @ 40" A.F.F. MAX TO FROM WALL /--SEMI-RECESSED 4-0" S.S. GRAB BAR BOTTOM OF REFLECTING _CEPTACLE r0 IO- o� _ a SURFACE Q � FA F_:O Lu z7< INSULATE HOT 4 FAFER & DRAIN14 II PIPES v M ; Y A,xQ X `r U, I h; CD E I e� @!'.«wi3i.aE«4°.4"YI#..w."u+ww>„a"�U3'ia,F.�+ 7+• :,..:i..A. t,.f ...A ,1.17t0.ivCdk'L .u„ uL..G.1`:Y3.i2:2Yr�l�l C O 0 N (d3 c3 O m c(70 o c� 0 f LL w U) 0 a w 0 w O U J 0 a J co la �� 4 � (D 6� ca Q. I; k E k 0 N � rn w q Q) LLw 0 o d C:D 0 a n< N CO �SCLCHJC UHIC I h; E @!'.«wi3i.aE«4°.4"YI#..w."u+ww>„a"�U3'ia,F.�+ 7+• :,..:i..A. t,.f ...A ,1.17t0.ivCdk'L .u„ uL..G.1`:Y3.i2:2Yr�l�l PROJECT NO. -~ 2017-038 I t ISSUE DATE 1? 06-05-17 DRAWN -- CHECKED A-1.0