HomeMy WebLinkAbout1611 Persimmon Ave (NO PERMIT #)CITY OF .; ANFOR® FIRE ®EPARTMENT 1303 SOUTH FRENCH AVENUE SANFORO, FL 32771 J. T. "Tom" Hickson Fire Chief Business: (305) 322-4952 Emergency: (305) 322-5332 May 23, 1985 Merthie' s Day Care Center 1611 Persimmon Ave. Sanford, FL 32771 RE: Plans submitted for review Gentlemen: 1. Exit lights to be placed over exit doors. 2. Emergency lighting to be provided. 3. Interior finish to be Class A or B. 4. Exit doors to swing out. 5. If occupancy is rated for more than 100 children the manual alarm system and smoke detectors must be direct connection to the fire department. 6. Portable fire extinguishers to be provided. If there are any questions please don't hesitate to call me. Sincerely yours, M. .Hoening/// Fire Prevention 0 er MCH/ch FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION SECTION 5 e BUILDING DESIGN BY COMPONENT PERFORMANCE APPROACH FORM 500-84 ADM0116MRQO BY TK oew arUM of cow1tuaITY AFFURa STATISTICS: RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS SEE S. 501.1 PROJECT NAME: Addition to Merthie's Day ZONE: 4 5 6 ADDRESS: Persimmon Ave. Care Center BUILDING CLASSIFICATIONS : Day Care CITY ZIPCODE: Sanford Florida 32771 BUILDING VALUE: S BUILDER: PERMITTINGOFFICE: CitV Of Sanford OWNER: Mr. & Mrs. Oscar Me r th i e JURISDICTION NO.: 6 91-5-00 BUILDING INFORMATION COMPONENT U-VALUE Total) NET AREA Square Feet) 3 Concrete Block Structure (CBS) Wood frame Other U= 9 1060 U= U= Other U=— d Under Attic Cavity se Buillt-up Roof OtherU= U- . 03 1040 O Total Unconditioned Floor Area Concrete Over Unconditioned Space Wood Over Unconditioned Space Slab on Grade U= U= U= 1040 y Clear Single Glaze Clear Double Glaze Tint Single Glaze Tint Double Glaze Skylights Other U= U= U= U= U= U = Ix Wood Metal Insulated Other U= U= . 50 84 U= U= W a o Total Lighting Wattage 306 Total Conditioned Floor = .29 Area ( sq. ft.) - 1040 Wattsisq. ft. u Lighting Budget Maximum = 2.o Watts/ sq. ft. SYSTEMS INFORMATION AIR CONDITIONER EFFICIENCY EER 8 . 5 ) or (SEER ) or (COP ) HEATING SYSTEM TYPE STRIPS HEAT PUMP GAS OIL SOLAR HEATING SYSTEM EFFICIENCY COP 1 ' 0 or EFFICIENCY = % (Steady-state) HOT WATER SYSTEM TYPE Exist ng ELECTRIC HEAT RECOVERY GAS OIL SOLAR Ua wall Allowable 0. 37 Uo wall Actual .22 Uo roof/coiling Allowable 0. 10 Uo roof/ceiling Actual .03 U. floor Allowable — U. floor Actual OTTV wall Allowable 30.3 — OTTV wall Actual 8.53 OTTV roof/ceiling Allowable __ —__ OTTV roof/ceiling Actual 1-8 In accordance with Section 553.907 F.S., I hereby certify that the plans and specifications covered Lbyleo in cumplia th the Florida Energy Code. r DATE: May 16 1985 Review of the plans and specifications covered by this calculation indicate com- pliance with the Florida Energy Code. Before construction is completed, this building will be inspected for compliance in accordance with Section 553.908 F.S.OWNERIAGENT BUILDING OFFICIAL: DATE: PERMfT NO. C ECKED by SECTION 5 WORKSHEET FOR ENERGY CALCULATIONS BUILDING DESIGN BY COMPONENT PERFORMANCE APPROACH FORM 500-84 Stow oN Film Ensrpy Code 1. GROSS WALL AREAS A) WALL TYPE: Concrete Block 1 U 6 0 _sq.ft. B) WALL TYPE: sq. ff. C) WALL TYPE: sq. ft. D) WALL TYPE: sq. h. TOTAL GROSS WALL AREA - sq. ft. 2. GLASS AREAS (Indudes areas of windows, sliding glass doors. glees entrance doors) m QC TvDw wn OC• aV npwwTATww I I 3. MORS (EXCLUDING GLASS DOORS) Door area inezterwr building envelope = $ 4 + = 84 sq. ff. Interior door area separating A/C from non A/C spaces ................. ....... ........... ........ ............ _ sq. ft. TOTAL OPAQUE DOOR AREA = 84 sq. ft. a. MET OPAQUE WALL AREAS WALL TYPE GROSS WALL sq. ft.) GLASS AREA sq. 11.) DOOR AREA sq. tt.) NET OPAQUE WALL AREA sq. ft.) A. Concrete Block 1060 36 84 940 B. C. D. 5. ROOF/CEILING AREA ROOF/CEILING TYPE AREA Trusses 1060 TOTAL GROSS ROOF/CEILING AREA 1060 SKYLIGHT (SHADING COEFFICENT • ) - 0 sq. It. TOTAL NET ROOF/CEILING AREA 1060 1060 sq. ft. 6. AIR FILM (ALL BUILDINGS) COMPONENT R-Value Outside Air Flkn krside Air FNm wall 17 68 Coiling 17 63 Flow