HomeMy WebLinkAbout1145 W Airport BlvdSANFORD FIRE DEPARTMENT FIRE PREVENTIONDIVISION _ 300 N. Park Ave., Sanford, FI. 32771 / P. O. Box 1788, Sanford, Fl. 32772 (407 302-2516 / FAX (407) 302-2526 Fire Marshal Plans Review Sheet Date: October 9, 2006 Business Address: 1145 W. Airport Blvd. Occ. Ch. 40 Industrial- 38-Business Business Name: BRIO CENTER Architect: JRJJ & Associates Contractor: Design Enterprise . PH (407) 83071414 Fax. (407) 830-8448 PH (407) 875-0115 Fax. (407) 875-0308 PH (407) 830-1414 Fax. (407) 830-8448 Reviewed by: Timothy Robles, Fire Marshal /Plans Examiner Comment: Plans reviewed as Occ. Ch. 40 Industrial-38-Business Type IV fire sprinkler protected 4,900 sq ft type IV fire sprinkled building Occupancy's FD reserves right to require applicable code requirements if occupancy use changes. Sprinkler plans to be submitted for review, permitting, and inspections. Sealed letter from Engineer of Record stating design criteria for sprinkler system needs to be submitted with construction plans. F Fire Alarm Requirement: See below Fire Alarm notification: Each individual tenant space shall have two (2) horn strobes, for individual tenant notification (one in business office, and one in storage/industrial area). Application — New Building (4,900 s. q. ft.) 1 Q SANFORD FIRE DEPARTMENT FIRE PREVENTION DIVISION 300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772 (407 302-2516 / FAX (407) 302-2526 Fire Marshal 1.1 1.2 1.3 Mixed — N/A, Special Definitions — Ch. 40 Industrial-38-Business Classification of Occupancy — Ch. 40 Industrial-38-Business Classification of Hazard of Contents — Ordinary in office areas, and storage area classified as "High Hazard" per L.S.C. 101 1.4 Minimum Construction — Shall comply with Florida Building Code 2004 mercantile occupancy 1.5 2.2 Means of Egress Components R,' ar storage INEATEQ 2.3 Capacity of Egress — sales floor area based on one (])_person per 30 sq ft., storage area based on one (1) person per 300 sq. ft. 2.4 Number of Exits — two for each individual tenant ok 2.5 Arrangement of Egress O.K. — two for each individual tenant ok 2.6 Travel Distance — Rear EXT: [ALL BE DILINEATEDD.-WITH44'.;yellow�aint'on floor IeZ;ig ta'EXIT"doar *)... 2.7 Discharge from Exits — O.K., will field verify 2.8 Illumination of Means of Egress —additional EXIT SIGNS may be required (power shut down test required at night only) 2.9 Emergency Lighting — (1) foot candle (10 Ix & a minimum at any point of 0.1 foot-candle (1LX ) measured along the path of egress at floor level.Therfore additional emergency lights may be required, (power shut down test required at night only) Emergency Lights required In all rest rooms & Main Electrical Room M. 2.10 Marking of Means of Egress — O.K.; will field verify 2.11 Special Features —Reserved 3.1 Protection of Vertical Openings — Ch. 40 Industrial-38-Business 3.2 Protection from Hazards — (See exception 40-3.2.1 .LSC 101) 3.3 Interior Finish — Not required, building has an automatic fire sprinkler system 2 SANFORD FIRE DEPARTMENT FIRE PREVENTION DIVISION 300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772 (407 302-2516 / FAX (407) 302-2526 Fire Marshal 3.4 Detection, Alarm and Communications System: (as per N.F.PA.72- 3-8.3.1.2 (99) Ed. • 3.5 Extinguishing Requirements — as per NFPA 10, (2) 2A 10 BC rated fire extinguishers required per N.F.PA. 410 (see blueprints for locations). 5.1 Utilities — as per LSC 7-1 5.2 HVAC — as per LSC 7-2 5.3 Elevators, Escalators, Conveyors (4A-47) — N/A Sanford City Code — Chapter9: Required; Fire Sprinklers. Drop fire sprinkler heads below ceiling Monitoring: Required on all fire sprinkler valves (includes inside and out) Other: NFPA 1 3-5.1 Fire Lanes — Required (see sight plan) 3-6.1 Key Box- required already 3-7.1 Bldg. Address Number Posted and Legible — Post address in 6" six inch numbers contrasting in color (see blueprints). 3 Florida Energy Efficiency Code For Building Construction Florida Department of Community Affairs EnergyGauge FlaCom v 2.11 FORM 40OA-2004 Whole Building Performance Method for Commercial Buildings Jurisdiction: SANFORD, SEMINOLE COUNTY, FL (691500) Short Desc: BRINKS Project: BRINKS HOME SECURITY Owner: Address: 1145 WEST AIRPORT BLVD BRIO COMMERCE CENTER BUILDING #2 City: SANFORD State: FL PermitNo: 0-- Zip: 0 Storeys: 1 Type: Office *Conditioned Area: 4865 * denotes lighted Class: Renovation to existing building *Cond + UnCond Area: 4865 area. Does not include wall crosection areas Max Tonnage: 5.0 (if different, write in) Compliance Summary �JComponent Design Criteria Result Gross Energy Use 3,023.72 _ 4,575.13 PASSES LIGHTING CONTROLS EXTERNAL LIGHTING HVAC SYSTEM PLANT WATER HEATING SYSTEMS PIPING SYSTEMS Met all required compliance from Check List? PASSES None Entered PASSES None.Entered PASSES None Entered Yes/No/NA IMPORTANT NOTE: An input report Print -Out from EnergyGauge Com of this design building must be submitted along with this Compliance Report. 'Au 9/9/2006 EnergyGauge FlaCom v 2.11 FORM 40OA-2004 I;ViV1YL1A)1UE CER11 '1C.A11ON: I hereby certify that the plans,. ',and` Review of the plans and specifications covered by this specifications covered by this calculation are ' , calculation indicates compliance with the Florida Energy in compliance with the Florida Energy Code. Before construction is completed, this building will be Efficiency Code. -inspected for compliance in accordance with Section 553.908, F.S. PREPARED BY: GINS BOBES JR, P..E.,, BUILDING OFFICIAL: DATE: DATE: I hereby certify that this building is;yi compliance - I with the Florida Energy Efficiency Code. OWNER AGENT: DATE: I If required by Florida law, I hereby certify (*) that the system design is in REGISTRATION compliance with the Florida Energy Code. No. ARCHITECT: ELECTRICAL SYSTEM DESIGNER: LIGHTING SYSTEM DESIGNER: MECHANICAL SYSTEM DESIGNER: PLUMBING SYSTEM DESIGNER: (*) Signature is required where Florida Law requires design to be performed by registered design professionals. Typed names and registration numbers may be used where all relevant information is contained on signed/sealed plans. 9/9/2006 EnergyGauge FlaCom v 2.11 FORM 40OA-2004 2 Project: BRINKS Title: BRINKS HOME SECURITY Type: Office (WEA File: Orlando.TMY) Whole Building Compliance Design Reference Total 64.94 100.00 $3, 023.72 $4,575.13 ELECTRICITY(MBtu/kWh/$ 64.94 100.00 59,522.00 91,686.00 $3, 023.72 $4,575.13 AREA LIGHTS 16.04 17.87 14,701.00 16,387.00 $746.81 $817.71 MISC EQUIPMT 11.67 11.67 10,690.00 10,690.00 $543.05 $533.43 PUMPS & MISC 0.03 0.03 29.00 30.00 $1.47 $1.50 SPACE COOL 21.00 20.13 19,242.00 18,455.00 $977.49 $920.90 VENT FANS 16.20 50.30 14,860.00 - 46,124.00 $754.89 $2,301.59 Credits & Penalties (if any): Modified Points: = 64.95 PASSES External Lighting Compliance Description Category Allowance Area or Length ELPA CLP (W/Unit) or No. of Units (W) (W) (Sgft or ft) None 9/9/2006 EnergyGauge FlaCom v 2.11 FORM 40OA-2004 3 Project: BRINKS Title: BRINKS HOME SECURITY Type: Office (WEA File: Orlando.TMY) Lighting Controls Compliance Acronym Ashrae Description Area No. of Design Min Compli- ID (sq.ft) Tasks CP CP ance PrOZo1Sp1 17 Office - Enclosed 4,865 1 9 2 PASSES PASSES Project: BRINKS Title: BRINKS HOME SECURITY Type: Office (WEA File: Orlando.TMY) System Report Compliance PrOSyl System 1 Constant Volume Air Cooled No. of Units Split System < 65000 Btu/hr 3 Component Category Capacity Design Eff Design IPLV Comp- Eff Criteria IPLV Criteria liance Cooling System Air Cooled < 65000 Btu/h 13.00 10.00 13.00 PASSES Cooling Capacity Air Handling Air Handler (Supply) - 0.29 0.90 PASSES System -Supply Constant Volume PASSES Plant Compliance Description Installed Size Design Min Design Min Category Comp No Eff Eff IPLV IPLV liance None 9/9/2006 EnergyGauge FlaCom v 2.11 FORM 40OA-2004 Project: BRINKS Title: BRINKS HOME SECURITY Type: Office (WEA File: Orlando.TMY) Water Heater Compliance Description Type Category Design Min Design Max Comp Eff Eff Loss Loss liance Water Heater 1 Electric water heater > 12 [kW] 0.85 0.02 267.41 PASSES PASSES Piping System Compliance Category Pipe Dia Is Operating Ins Cond Ins Req Ins Compliance [inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in] [F) SF.F] None 9/9/2006 EnergyGauge FlaCom v 2.11 FORM 400A-2004 Project: BRINKS Title: BRINKS HOME SECURITY Type: Office (WEA File: Orlando.TMY) Other Required Compliance Category Section Requirement (write N/A in box if not applicable) Check Infiltration 406.1 Infiltration Criteria have been met System 407.1 HVAC Load sizing has been performed Ventilation 409.1 Ventilation criteria have been met ADS 410.1 Duct sizing and Design have been performed T & B 410.1 Testing and Balancing will be performed Motors 414.1 Motor efficiency criteria have been met Lighting 415.1 Lighting criteria have been met O & M 102.1 Operation/maintenance manual will be provided to owner Roof/Ceil 404.1 R-19 for Roof Deck with supply plenums beneath it Report 101 Input Report Print -Out from EnergyGauge F1aCom attached? 9/9/2006 EnergyGauge FlaCom v 2.11 FORM 40OA-2004 6 f f � EnergyGauge F1aCom v 2.11 INPUT DATA REPORT Proiect Information Project Name: BRINKS Orientation: North Project Title: BRINKS HOME SECURITY Building Type: Office Address: 1145 WEST AIRPORT BLVD Building Classification: Renovation to existing building BRIO COMMERCE CENTER BUILDING #2 State: FL No.of Storeys: 1 Zip: 0 GrossArea: 4865 Owner: Zones No Acronym Description Type Area Multiplier Total Area [sfl [sfJ 1 PrOZoI Zone 1 CONDITIONED 4864.5 1 4864.5 Spaces No Acronym Description Type Depth Width Height Multi Total Area Total Volume [ftl IN [ftl plier (sil tef] 9/9/2006 EnergyGauge F1aCom v 2.11 1 In Zone: PrOZol 1 PrOZo1Sp1 Zo0Sp1 No Type Office - Enclosed 69.00 70.50 9.00 1 4864.5 43780.5 El Lighting Category No. of Watts per Power Control Type No.of Luminaires Luminaire [W] Ctrl pts In Zone: PrOZol In Space: PrOZo1Spl 1 Recessed Fluorescent - No vent General Lighting 1 960 960 Manual On/Off 2 2 Recessed Fluorescent - No vent General Lighting 1 960 960 Manual On/Off 2 3 Recessed Fluorescent - No vent General Lighting 1 960 960 Manual On/Off 2 El 4 Recessed Fluorescent - General Lighting 1 960 960 Manual On/Off 2 No vent 5 Recessed Fluorescent - No vent General Lighting 1 960 960 Manual On/Off 1 n No Description In Zone: PrOZol 1 PrOZo1Wal 2 PrOZo 1 Wa2 Walls Type Width H (Effec) Multi Area DirectionConductance Heat Dens. R-Value IN [ft] plier [sf] [Btu/hr. sf. F] Capacity [lb/cf] [h.sf.FBtu] [Btu/sf.F] Metal siding/R 11 Batt/0.5" 70.50 12.00 1 846.0 East 0.0957 0.7570 16.80 10.45 Gyp Metal siding/R11 Batt/0.5" 70.50 12.00 1 846.0 South 0.0957 0.7570 16.80 10.45 Gyp 9/9/2006 EnergyGauge F1aCom v 2.11 2 ( 1. Windows No Description Type Shaded U SHG Vis.Tr W H (Effec) Multi Total Area [Btu/hr sf F] IN [ft] pher [sf] In Zone: PrOZo1 In Wall: PrOZo1Wa1 1 PrOZo1Wa1Wi1 SINGLE CLEAR No 1.0018 0.81 0.88 61-00 8.00 1 In Wall: PrOZo1Wa2 488.0 ❑ 1 PrOZolWa2Wil SINGLE CLEAR No-1,0018 0.81 0.88 3.00 4.00 1 12.0 ❑ Doors No Description Type Shaded? Width H (Effec) Multi Area Cond. Dens. Heat Cap. R-Value [ft] [ft] plier [sf] [Btu/hr. sf. F] [lb/cf] [Btu/sf. F ] [h.sf.FBtu] In Zone: PrOZol In Wall: PrOZo1Wa2 1 PrOZo1Wa2Drl Aluminum door, No 3.00 7.00 2 21.0 0.1919 43.67 0.53 L25 in. 5.21 ❑ polystyrene Roofs No Description Type Width H (Effec) Multi Area Tilt Cond. Heat Cap Dens. R-Value [ft] IN plier [sf] [deg] [Btu/hr. SL F] [Btu/sL F] [lb/cf] [h.sLF/Btu] In Zone: PrOZol 1 PrOZo1Rfl Mt1 Bldg Roo f/R-19 Batt 70.50 69.00 1 4864.5 0.00 0.0492 1.34 9.49 2034 ❑ Skylights No Description Type U SHGC Vis.Trans W H (Effec) Multiplier Area Total Area [Btu/hr sf F] IN IN [SfJ {sf] 9/9/2006 EnergyGauge FlaCom v 2.11 3 In Zone: In Roof: No Description Type In Zone: PrOZol 1 Pr0Zo1F11 Concrete floor, carpet and rubber pad PrOSyl System 1 Floors Width H (Effec) Multi Area Cond. Heat Cap. Dens. R-Value IN IN plier [sf] [Btu/hr. sf. F] [Btu/sf. F] [lb/cf] [h.sf.F/Btu] 70.50 69.00 1 4864.5 0.5987 9.33 140.00 1.67 1 Cooling System (Air Cooled < 65000 Btu/h Cooling Capacity) 2 Air Handling System -Supply (Air Handler (Supply) - Constant Volume) Systems Constant Volume Air Cooled Split System < 65000 Btu/hr Capacity Efficiency IPLV 60000.00 13.00 `13.00 1950.00 0.29 No. Of Units 3 9/9/2006 EnergyGauge F1aCom v 2.11 4 ❑■ El MM Ext-Lighting Description Category No. of Watts per Area/Len/No. of units Luminaires Luminaire [sf/ft/No] Control Type Wattage [W] Piping No Type Operating Insulation Nomonal pipe Insulation Is Runout? Temperature Conductivity Diameter Thickness [F] [ Btu-in/h.sLF] [in] [in] Fenestration Used Name Glass Type No. of Glass SHGC VLT Conductance Panes [Btu/h.sf.F] ApLbWndl SINGLE CLEAR 1 1.0018 0.8150 0.8810 El _ Materials Used Mat No Acronym Description Only R-Value RValue Thickness Conductivity Density SpecificHeat Used [h.sf.F/Btu] IN [Btu/h.ft.F] [lb/cf] [Btu/lb.F] 264 214 Mat1264 Mat1214 ALUMINUM, 1/16IN POLYSTYRENE, EXP., No 0.0002 0.0050 26.0000 480.00 0.1000 1-1/41N, No 5.2100 0.1042 0.0200 1.80 0.2900 ❑ 187 Mat1187 GYP OR PLAS BOARD,1/21N No 0.4533 0.0417 0.0920 50.00 0.2000❑ 9/9/2006 EnergyGauge FlaCom v 2.11 5 151 Matll51 CONC HW, DRD, 140LB, No 0.4403 0.3333 4IN 0.7570 140.00 0.2000 ❑ 178 Mat1178 CARPET W/RUBBER PAD Yes 1.2300 12 23 Mad12 Mat123 3 in. Insulation No 10.0000 0.2500 0.0250 2.00 0.2000 ❑ ❑ 4 Ivlat14 6 in. Insulation Steel siding No 20.0000 0.5000 0.0250 5.70 0.2000 Mat194 BUILT-UP ROOFING, No No 0.0002 0.0050 26.0000 480.00 0.1000 El94 3/81N 0.3366 . 0.0313 0.0930 70.00 0.3500 ❑ Constructs Used No Name Simple Construct Massless Construct Conductance [Btu/h.sf.F] Heat Capacity [Btu/sf.F] Density [Ib/c I RValue [h.sf.F/Btu] 1002 Aluminum door, 1.25 in. polystyrene No No 0.19 0.53 43.67 5.2104 ❑ Layer Material Material No. Thickness Framing (ft] Factor 1 264 ALUMINUM, 1/16IN 2 214 POLYSTYRENE, EXP., 1-1/4IN, 264 ALUMINUM, 1/16IN 0.0050 0.1042 0.0050 0.00 0.00 0.00 ❑ El ❑ No Name Simple Construct Massless Construct Conductance [Btu/h.sf.F] Heat Capacity [Btu/sf.F ] Density (Ib/cfJ RValue [hsf.FBtu] 1004 Concrete floor, carpet and rubber pad No No . 0.60 9.33 140.00 1.6703 ❑ Layer Material Material Thickness Framing No. [ft] Factor 1 151 CONC HW, DRD, 140LB, 4IN 0.3333 0.00 2 178 CARPET W/RUBBER PAD 0.00 ❑ 9/9/2006 EnergyGauge FlaCom v 2.11 6 No Name Simple Massless Conductance Heat Capacity Density RValue Construct Construct [Btu/h.sf.F] [Btu/sf.F] [lb/cfJ [hsf.FBtu] 1020 Metal siding/RI I Batt/0.5 'Gyp No No 0.10 0.76 16.80 10.4535 ❑ Layer Material Material Thickness Framing No. IN Factor 1 4 Steel siding 0.0050 0.00 ❑ 2 12 3 in. Insulation 0.2500 0:00 3 187 GYP OR PLAS BOARD,1/21N 0.0417 0.00 ❑ No Name Simple Massless Conductance Heat Capacity Density RValue Construct Construct [Btu/h.sf.F] [Btu/sf.F] [Ib/cf] [h.sf.FBtu] 1047 Mtl Bldg Roof/R-19 Batt No No 0.05 - 1.34 9.49 20.3366 El Layer Material Material Thickness Framing No. [ft] Factor 1 94 BUILT-UP ROOFING, 3/8IN 0.0313 0.00 ❑ 2 23 6 in. Insulation 0.5000 0.00 ❑ 9/9/2006 EnergyGauge FlaCom v 2.11 7 APPLICATION The SD37 i; a UL555S Leakage Class 1 Smoke Damper con- structed with triple V-groove or one-piece airfoil blades, used in ducts that penetrate smoke rated barriers. The damper may be installed vertically or horizontally within 24" (610) of a smoke bar- rier. The SD t7 is designed for use in systems with airflow in either direction witt velocities to 2,000 fpm and pressures to 4" w.g. STANDARD CONSTRUCTION FRAME 5" x 16 gage (127 x 1.6) galvanized, single piece, hat -shaped channel, tructurally superior to 13 (2.3) gage steel channel frame. BLADES 6" (152) wide galvanized steel. Triple v-groove or airfoil shaped approxima ely 6" (152) on center. BEARINGS Stainless teel sleeve type, pressed into frame. JAMB SEAL Stainless steel, flexible metal compression type. BLADE SEALS Silicone ed a type, mechanically fastened to the blade edge, for smoke sea to 450°F (232°C). LINKAGE Concealed in frame. UL555S Elevated Temperature Rating 2507 (121 'C) or 350•F (177°C) depending on actuator. DAMPER SIZES MINIMUM SIZE 8"w x 6"h ( .03 x 152). Model SD37 meets the requirements for smoke dampers established by: • National Fire Protection Association NFPA Standards 90A, 92A, 92B and 101 • BOCA National Building Codes • ICBO Uniform Building Codes • SBCCI Standard Building Codes • ICC International Building Codes • CSFM California State Fire Marshal Smoke Damper Listing (#3230-245:110) UL CLASSIFIED UL555S Listing R5531 Lo SEE COMPLETEMARKING UU ON PRODUCT goo r C Width MAXIMUM SIZE t3 Single Sect on - �1 S{1AHeight 36"w x 7 ."h (914 x 1829) ti ®ten Multiple Se tion C51C1�j 144"w x 6"h (3658 x 2438), 72"w x 144"h (1829 x"3658) or 288"w x 4 8"h (7315 x 1219). OPTIONS • DSDN Smoke Detectors for no or low air flow applications. • DSDF Smolle Detectors for low or normal air flow applications. • SP100 Swi ch Package to allow remote indication of damper blade positic n. • Sleeves of arious lengths and gages. NOTES 1. Dampers furnished approximately 1/4" (6) smaller than given open- ing dimensio s. 2. Dimensions hown in ( } indicate millimeters. Spec SD37-902 12" (305) Min. Sideplate 8112" (2 6) Actuator \� or , Mounting ` 12" (305) ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. Internal Actuator Mounting •uo•vi Mounting 0 Ruskin February 2005