Sprinkler Supervision System
For
Mainline Supply
2291 West Airport Boulevard
Sanford, Florida
By
High Security
Florida Contractor #EF-M0071
V.A.C. R.
Li Lit. kuI 61AT 610A4
gwirC 1�
kww suePLq Rl t�ER
OUTS;,Ae E9v-tp��t R" r,
NOS ' � C� 20.A-r t,)
11C4 W is a�� RezraI u41 S�R�71ce 'T o FAc r� uJ"��r�-1 t.o�k
c7rµEAs -dui locate l (hem
— A I CQ.61 E -ro b-t- i,l SrEb 'Fb2 "W cr, _
Smoke— cAP-Aer.+o,Q -To fie- mo-"*T� GLboMc 'F'P4 c P-
Peace of Mlnd Systems for
4c—j,►4ttii - 93. A--wac f�nti�.v�t
www.GE-interlogix.com
Grow Your
Now you can get a UL 864 listed commercial fire solution with the
Business
programming ease and flexability of NetworX. The NX-B-CF is a
with the
Platform
12V integrated burglary/tire product for commercial applications.
You Know
It's the simple way to expand into commercial fire without the cost
and frustration of learning a new platform.
Powerful
The NetworX NX-8-CF provides 48 tones of protection for fire
Performance
and intrusion. It also supports an array of accessories and modules,
including cellular backup and door access control. ICs ideal for
applications where integrated systems provide the most
comprehensive, cost-effective solution.
Programmed
Since the NX-8-CF is based on the proven NetworX platform,
For
Convenience
you already know how to program and install the panel quickly
and easily. It comes with eight hardwire zone inputs and four
programmable outputs that can be set up to activate external
devices during an alarm event. The dedicated programmable
notification appliance circuit outputs a temporal code and is
individually silenceable. To meet the UL 864 requirement for
commercial fire, the NX--8--CF has a NX-870E module for dual
phone line supervision.
GE Interlogix security and life safety products are designed to
work together and provide the most comprehensive solution for
security professionals.
NetworX NX-9-CF
Integrated Commercial Intrusion/Fire System
Standard Features
o Supports up to 20 two -wire smoke detectors. Four -wire
smoke detectors can be used with hardwired initiating
devices up to 48zones
o Supports one NA for horns and strobes
e Supports hardwire or wireless intrusion detection devices
for maximum flexibility and quick installation
® The NX-1700E module provides access control for up to
fifteen door.
o The NX-591E" offers secure alarm transmission in case
of line cut or other telephone service interruption.
Intrusion only
® The NX-,216E allows expansion with any mix of fire and
intrusion up to 48 zones
o NX-ME power supply allows additional power to be
added in 1-Amp increments
iP :Vot UL S64 li Led for the NX—R-cf,
Specifrca6ons
Operating Power
Auxiliary Power
w/SUVA transformer
w/NX-:= power supply
Loop Reor,nce
Standard Loop
2-wire smokes
Loop Response
Operating Temperature
NX-14"F LCD keyboard
Current draw
w/o sounder
Dimensions
Enclosure Dimensions
Shipping Weight
UL Listings
16.5V AC 50VA transformer Residential and Commercial UL Burglary ratings
UL 609 Commercial
UL 1M3 Residential Burglary
72V AC 1 Amp UL 1610 Grade B & C Central Station Burglar Alarm
12V AC 2 Amps UL 1637 Home Health Care Signaling
NX--9—CF Fire Panel had UL 864 rating for commercial fire
300 Ohms Max. fte L
30 Ohms Max. Type RS
Type CS
Selectable 50ms or 500ms
320 to 120OF
Farm
110mA max.
75 rrA
6.4 Wx5.3Hx 1.0"D
15.5Wx 18.5Hx4.5"D
20lbs.
NetworX Technical Support: 800-727-2339
Ordering information
NX-8-CF-Kit Includes NX-8-CF with NX-870E, (2) NX-148E-CF keypads and transformer
NX-8-CF Control panel plus NX-870E in red commercial fire/burg enclosure
NX-148E-CF Alphanumeric LCD red keypads
NX-870E Dual phone line fire supervision module
Transformer 16.5V, 50VA
GE Interlogix
www-GF-lnterlogix.com 12345 SW leveton Drive
2266 Second Street North
Tualatin, OR 97062
North St. Paul, MN 55109
Phone:503-692-4052
Phone:651-777-2690
USA & Canada: 800-547-2556
USA & Canada: WO.777-5484
Technical Service:800-648-7424
Technical Service.' 800-777-2524
Faxback.•800-483-2495
OM GE Mfflogm
%--100000-0103 -
M
• Firee•LIVALarems
June 30, 1997
F-200
BG-8 Series
Manual Fire Alarm Pull Stations
Section: Conventional Initiating Devices
GENERAL
The BG-8 Manual Fire Alarm Pull Station provides a single-
action, normally -open contact alarm initiating point for use
with UL listed Fire Alarm Control Panels.
S711
FEATURES
• Complies with Americans with Disabilities Act.
• Sturdy metal construction.
• Simple operation.
• Operation does not require replacement of parts.
• Drawing of flames on cover helps communicate purpose
of this device to people who do not read English words.
• Designed to prevent false alarms when bumped, shaken,
or jarred.
• Listed to UL 38.
APPLICATIONS
Designed for indoor use in atmospheres which are not po-
tentially explosive. Use as a means of allowing anyone on
the premises to turn in a non -coded alarm quickly, without
chance of error. Typical uses include:
1. Schools.
2. Hospitals.
3. Retail stores.
4. Industrial plants.
5. Warehouses.
Compatible with any appropriate control panel to:
1. Initiate local alarm signals.
2. Trip a municipal fire alarm box.
3. Start fire pumps.
4. Any other function that can be initiated or controlled
by the closing of a switch contact.
OPERATION
The stations feature non -break -glass operation. They are
operated by a pull.on the pull cover. This causes a key
latch to act against a retaining mechanism until adequate
force is applied to open the station. As the station opens,
a switch is released to initiate an alarm. The retainer in
Model BG-8 is a permanent, high -tensile, flatspring, which
eliminates the need for a glass retainer. When so oper-
ated, the cover hangs down (and cannot be reset without
use of a reset key) indicating that the station was used to
initiate an alarm. OPERATED STATIONS CAN BE SEEN
UP TO 100 FEET AWAY.
The attractive design of the stations highlights their engi-
neered simplicity and unusual dependability; bumping,
shaking, or jarring will not activate the switch or circuit. In -
California
UDC o. State Fire
Marshal
7150-0075:148
CS115
ADA M9EA
D
BG-8 (shown full size)
This document is not Intended to be used for installation purposes. We try to keep our prod-
uctISOinformation up-to-date and accurate. We cannot cover all specific applications or antici-
pate all requirements. All specifications are subject to change without notice. For more Engineering and Manufacturing
information, contact Fire-Lite. Phone: (203) 484.7161 FAX: (203) 484.7118 Quality System Certified to
8Flf£•(JTErAl.8tTT1S 12 Clintonville Road, Northiord, Connecticut 06472
Intemational Standard ISO-9001 Made In the U.S.A.
DF-50628 — Page 1 of 2
structions for operation of the station are clearly marked on
the front of the pull cover.
The BG-8 Station is die -formed from 1/8" thick satin finish
aluminum, with the operating instructions in raised letters.
BG-8 contacts rated at: 1 amp., 30 VAC, and 30 VDC.
Master key fits all stations used in an installation of the
same series.
INSTALLATION
The station mounts with two screws (supplied) to a stan-
dard single -gang electrical switch box. It can also be
mounted to a surface mount box. 6" wire leads are pro-
vided for making easy connections.
ARCHITECT/ENGINEERING
SPECIFICATIONS
Manual Fire Alarm Stations shall be non -code, non -break -
glass type equipment with a key operated reset, and so
designed that after actual Emergency Operation, they can-
not be restored to normal except by use of a key. An op-
erated station shall be designed such that upon activation,
it will be visually detectable at a minimum distance of one
hundred feet, front or side. Manual Stations shall be con-
structed of die -formed aluminum, with operating directions
provided on the front cover in raised letters. The word FIRE
shall appear on the front of the stations in raised letters,
five -eights inch high or larger. Stations shall be suitable
for surface mounting on matching backbox, or semi -flush
mounting on a standard single -gang box or switch plate,
and shall be installed within the limits defined by the Ameri-
cans with Disabilities Act (ADA) dependent on manual sta-
tion accessibility or per local requirements. Manual Sta-
tions shall be Underwriters Laboratories listed.
O
From prev
station
fire alarm
control panel.
previous
BG-8 / BG-8SP (Rear View)
PRODUCT LINE INFORMATION
Model Description
BG-8 Manual Fire Alarm Pull Station. Single-action.
Normally -open contact.
BG-8SP SPANISH Manual Fire Alarm Pull Station, with
FUEGO (FIRE) and JALE (PULL) in large capital
letters. Single-action. Normally -open contact.
BG-2R Surface mounting backbox for BG-8 Series sta-
tions. One end tapped for 1/2" conduit. Color:
MATCHING RED.
To next
station or
nd-of-line
device.
FUEGO
�FIRE
ALARM
WellTe"Xarms
4"
(10.1
BG-8SP
5/8" (1.59)
BG Series Backbox
1-3/8"
(3.49)
/4"
25)
Page 2 of 2 — DF-50628
� ESL
P R O D U C T I N FORMATION B U L L E T I N
• Intelligent, self -diagnostics
• On -site maintenance alert
• Fieid replaceable optical chamber
• Low -profile design
• Plug-in terminal block
• Advanced false alarm immunity
449/448 SERIES
Self -Diagnostic, Four -
Wire, Photoelectric
Smoke Detectors
Model numbers:
449AT, 449C, 449CT, 449CRT, 449CST, 449CSTE,
"9CSRT, 449CSRH, 449CTE
UDC
APPWWWW
Callfomla State Fire Marshal Approved
MEA (New York City) Approved
ULC model numbers:
"8AT, 448C, 448CT, 448CST, 448CSRH, "8CTE
The ESL 449/448 Series self -diagnostic, four -wire
smoke detectors continually monitor their own
sensitivity and operational status, and provide a
visual trouble indication if they drift out of sensitivity
range or fail internal diagnostics. This unique,
patented technology meets NFPA 72 field sensitivity
testing requirements without the need for external
meters.
Additional diagnostic information is activated by
applying a magnet near the detector's integral reed
switch. This initiates a self -diagnostic routine and
provides visual indication of sensitivity level, or if
service is required.
This series is easily cleaned by simply replacing
ESL's proprietary field -replaceable optical chamber. All
models are designed to reduce false alarms from
dust, insects, RFI, and external light.
An integral combination rate -of -rise and fixed
1350F (570C), 50-foot rated, heat sensor is available
with all "T" model detectors (see selection guide),
allowing latching of the alarm for either smoke or
heat. The 449CSRH includes an isolated alarm
output for heat and activates an internal non -latching
sounder (local alarm) for smoke, making it ideal for
motel/hotel and dormitory rooms where smoking is
permitted.
continued
ESL 449 Series Smoke Detectors
Architectural and Engineering Specifications
The ESL 449 Series low -profile, self -diagnostic, four -wire
smoke detectors work on the light scattering principle. A
pulsed infrared light -emitting diode serves as the light source,
and a high-speed photodiode as the sensing element. When
the amount of light reflected onto the photodiode reaches the
sensitivity setting, the smoke sampling rate increases. Three
(3) successive smoke sensings above the sensitivity setting
are required to sound an alarm. This design has superior
protection against false alarms caused by dust, insects, RF
and ambient -light.
A confirmed alarm causes the normally flashing power
indicator LED to light continuously and the alarm relay to
operate. A trouble indication is automatically displayed by
flashing the LED every second. This meets NFPA 72 field
sensitivity testing requirements. An internal 85 dB horn
(available in 'S" models) emits a temporal 3 when the
detector alarms and a steady tone when power polarity is
reversed.
Product Data
Sensitivity ................................................. 3.1-1.0%/ft. (max.)
3.1 •r 0.50%/ft. (min)
Operating temp. range ............... 32°F to 120°F (0°C to 50°C)
Operating humidity range .................................... 0 to 95% RH
Minimum voltage - C, CT, CRT, CST; CSRT, CSRH,
CSTE......................................................................... 8.5V
AT.............................................................................. 5.1 V
Maximum voltage - C, CT, CRT, CST, CSRT, CSRH,
CSTE........................................................................... 33V
AT................................................................................ 27V
Maximum ripple (peak to peak)........................................10%
Typical average standby current....................................27t�
CSTE........................................................................
Typical alarm current - C, CT and AT............................15mA
- CRT.......................................................................... 31 mA
Selection Guide
The proprietary optical sensing chamber is field replaceable,
allowing quick and easy cleaning and maintenance.
Models with auxiliary relays are approved for releasing
service.
This low profile product is equipped with a hinged cover, a
concealed tamper -resistant latch, and insect screens.
Wiring terminates in plug-in, clamp -type screw terminals.
Detectors mount to a standard single -gang electrical box, a
four -inch octagonal, four -inch square electrical box, or
WIREMOLD 5739 fixture box.
Smoke Detector Spacing
On smooth ceilings (as defined in NFPA 72), spacing of 30 feet
(9.1 meters) may be used as a guide. Other spacing may be used
dependutg on ceiling height, high air movement and other
conditions or response requirements.
CST ..............
....................:....................................... 40mA
- CSRT, CSRH, CSTE................................................ 51 mA
Typical avg. polarity reverse current
- CST, CSRT, CSTE, and CSRH................................10mA
Sounder specifications ......................................... 85 dB at 10'
Heat detector specifications
fixed temperature ..................................... 135°F (57.2°C)
rate of rise .... 15°F/min. & >105°F (8.30C/min. & >40.6°C)
Auxiliary relay contacts 2A @ 28 VDC or 120 VAC (resistive)
Alarm contacts ........................ 500 mA @ 36 VDC (resistive)
Field wiring size .................................................. 14 - 24 AWG
Packaging .......................10 detectors are packed in a carton
Color .................................................... white cover/white base
. with UV inhibitor to prevent yellowing
Listing .............................. UL 268, ULC FM, CSFM and MEA
r
Isolated fixed 1350F (57°C) and rate of rise heat detector, independently trips the LED and
H
Isolated Fixed Temp.
alarm and Rate of Rise
output. Snake detector activates internal sounder (local alarm) and auxiliary relay, but
Heat Detector
does not latch. Approved as both single station snake alarm and system heat detector.
Ideal for hotel, motel and dormitory rooms where smoking is allowed.
R
Auxiliary Relay
Used to activate other devices such as elevator recall, door holders, sm bes, etc. Listed for
releasing service.
S
Built-in Sounder
85dB built-in sounder alarms when smoke is detected or when power wiring polarity is
reversed.
T
Intergrated Fixed
Intergrated Fixed 135°F (57°C) temperature and rate of rise heat detector.
Temp. and Rate of
Either heat detector or smoke detector can trip and latch LED and alarm protection.
Rise Heat Detector
relay
E
Built-in end of line
Relay is normally energized and will trip with loss of power. Can also provide notification
power supervision relay