HomeMy WebLinkAbout1141 W Aiport BlvdFlorida Energy Efficiency Code For Building Construction
Florida Department of Community Affairs
EnergyGauge F1aCom v 2.11 FORM 40OA-2004
Whole Building Performance Method for Commercial Buildings
Jurisdiction: SANFORD, SEMINOLE COUNTY, FL (691500)
Short Desc: BRIOBLDG#2 Project: BRIO BUILDING #2 - TENANT
Owner:
Address: 1141 WEST AIRPORT BLVD
BRIO COMMERCE CENTER BUILDING #2
City: SANFORD
State: FL PermitNo: 0--
Zip: 0 Storeys: 1
Type: Office *Conditioned Area: 560 * denotes lighted
Class: Renovation to existing building *Cond + UnCond Area: 560 area. Does not include
wall crosection areas
Max Tonnage: 3.0 (if different, write in)
11 Compliance Summary 11
Component Design Criteria Result
Gross Energy Use 604.95 792.03 PASSES
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
PASSES
None Entered
PASSES
None Entered
PASSES
None Entered
Yes/No/NA
IMPORTANT NOTE: An input report Print -Out from EnergyGauge Com of
this design building must be submitted along with this Compliance Report.
3/8/2006
EnergyGauge FlaCom v 2.11 FORM 40OA-2004
COMPLIANCE CER'11F1CA'I'ION:
I hereby certify that the plans and Review of the plans and specifications covered by this
specifications covered by this calculation are calculation indicates compliance with the Florida Energy
in compliance with the Florida Ener y Code. Before construction is completed, this building will be
Efficiency Code. inspected for compliance in accordance with Section
553.908, F.S.
PREPARED BY: GUS BOBES JR P.E. BUILDING OFFICIAL:
DATE: Yr gk DATE:
I hereby certify that this building is in compliance
with the Florida Energy Efficiency Code.
OWNER AGENT:
DATE:
If required by Florida law, I hereby certify (') that the system design is in REGISTRATION
compliance with the Florida Energy Code.
No.
ARCHITECT:
ELECTRICAL SYSTEM DESIGNER:
LIGHTING SYSTEM DESIGNER:
MECHANICAL SYSTEM DESIGNER:
PLUMBING SYSTEM DESIGNER:
(') Signature is required where Florida Law requires design to be performed by registered design professionals.
Typed names and registration numbers may be used where all relevant information is contained on signed/sealed
plans.
3/8/2006 EnergyGauge F1aCom v 2.11 FORM 40OA-2004 2
Project: BRIOBLDG#2
Title: BRIO BUILDING #2 - TENANT
Type: Office
(WEA File: Orlando.TMY)
Whole Building Compliance
Total
Design
75.50
$604.95
Reference
100.00
$792.03
ELECTRICITY(MBtu/kWh/$
75.50
100.00
12,099.00
16,033.00
$604.95
$792.03
AREA LIGHTS
12.25
11.70
1,960.00
1,886.00
$98.00
$93.17
MISC EQUIPMT
7.68
7.68
1,231.00
1,231.00
$61.55
$60.81
PUMPS & MISC
0.18
0.18
17.00
31.00
$0.85
$1.53
SPACE COOL
25.96
21.39
4,160.00
3,424.00
$208.00
$169.15
VENT FANS
29.43
59.05
4,731.00
9,461.00
$236.55
$467.37
Credits & Penalties (if any): Modified Points:
= 75.51
PASSES
External Lighting Compliance
Description Category Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (W)
(Sgft or ft)
None
3/8/2006 EnergyGauge FlaCom v 2.11 FORM 40OA-2004 3
Project: BRIOBLDG#2
Title: BRIO BUILDING #2 - TENANT
Type: Office
(WEA File: Orlando.TMY)
Lighting Controls Compliance
Acronym Ashrae Description
ID
Area No. of Design Min Compli-
(sq.ft) Tasks CP CP ance
Pr0Zo1Sp1 16 Office - Open Plan
560 1 2 1 PASSES
PASSES
Project: BRIOBLDG#2
Title: BRIO BUILDING #2 - TENANT
Type: Office
(WEA File: Orlando.TMY)
System Report Compliance
PrOSyl System 1 Constant Volume Air Cooled No. of Units
Split System < 65000 Btu/hr 1
Component Category
Capacity Design Eff Design IPLV Comp-
Eff Criteria IPLV Criteria liance
Cooling System Air Cooled < 65000 Btu/h
Cooling Capacity
Air Handling Air Handler (Supply) -
System -Supply Constant Volume
13.00 10.00 13.00 PASSES
0.45 0.90 PASSES
PASSES
Plant Compliance
Description Installed Size Design
No Eff
Min Design Min Category_ Comp
Eff IPLV IPLV liance
None
3/8/2006 EnergyGauge FlaCom v 2.11 FORM 40OA-2004
Project: BRIOBLDG#2
Title: BRIO BUILDING #2 - TENANT
Type: Office
(WEA File: Orlando.TMY)
Water Neater Compliance
Description Type Category Design
Min Design Max Comp
Eff
Eff Loss Loss liance
Water Heater I Electric water heater > 12 [kW] 0.85
0.02 267.41 PASSES
PASSES
Piping System Compliance
Category Pipe Dia Is Operating Ins Cond Ins Req Ins Compliance
[inches] Runout? . Temp [Btu-in/hr Thick [in] Thick [in]
[F] SF.F]
None
3/8/2006 EnergyGauge FlaCom v 2.11 FORM 400A-2004
Project: BRIOBLDG#2
Title: BRIO BUILDING #2 - TENANT
Type: Office
(WEA File: Orlando.TMY)
Other Required Compliance
Category
Section
Requirement (write N/A in box if not applicable)
Check
Infiltration
406.1
Infiltration Criteria have been met
System
407.1
HVAC Load sizing has been performed
Ventilation
409.1
Ventilation criteria have been met
ADS
410.1
Duct sizing and Design have. been performed
T & B
410.1
Testing and Balancing will be performed
Motors
414.1
Motor efficiency criteria have been met
Lighting
415.1
Lighting criteria have been met
O & M
102.1
Operation/maintenance manual will be provided to owner
Roof/Ceil
404.1
R-19 for Roof Deck with supply plenums beneath it
Report
101
Input Report Print -Out from EnergyGauge FlaCom attached?
❑
3/8/2006 EnergyGauge FlaCom v 2.11 FORM 40OA-2004 6
EnergyGauge F1aCom v 2.11
INPUT DATA REPORT
Proiect Information
Project Name:
BRIOBLDG#2
Orientation:
North
Project Title:
BRIO BUILDING #2 - TENANT
BuildingType: Yp
Office
Address:
1137 WEST AIRPORT BLVD
Building Classification:
Renovation to existing building
BRIO COMMERCE CENTER BUILDING #2
State:
FL
No.of Storeys:
I
Zip:
0
GrossArea:
560
Owner:
Zones
No Acronym Description Type Area Multiplier Total Area
1 PrOZoI Zone 1 CONDITIONED [sfl [sfJ
560.0 1 560.0 ❑
Spaces
No Acronym Description Type Depth Width Height Multi Total Area Total Volume
[ft] IN [ft] plier lsfl I lef]
3/8/2006 EnergyGauge FlaCom v 2.11
1
In Zone: PrOZol
1 PrOZolsol
ZoOSpl Office - Open Plan
28.00
20.00
9.00
1
560.0
5040.0 El
Lighting
No
Type Category
No. of
Watts per
Power
Control Type
No.of
Luminaires
Luminaire
[W]
Ctrl pts
In Zone: PrOZol
In Space: PrOZo1Sp1
1
Recessed Fluorescent - General Lighting
No
1
640
640
Manual On/Off
2
ventEJ
Walls
No Description
Type Width H (Effec) Multi
Area DirectionConductance
Heat
Dens. R-Value
[ft]
[ft] plier
[sf]
[Btu/hr. sf. F]
Capacity
[lb/cf] [h.sf.FBtu]
[Btu/sf.F]
In Zone: PrOZol
1 PrOZo1Wal
0.5 Ply/35/8" Mtl 20.00
10.00 1
200.0
North
0.0798
0.5388
7.98 12.54
std@24"oc/R 11 /0.5"
Gyp
2 PrOZo 1 Wa2
Metal 20.00
12.00 1
240.0
South
0.0957
0.7570
16.80 10.45
siding/R11 Batt/0.5"
Gyp
Windows
No
Description Type Shaded
U SHG Vis.Tr
W
H (Effec)
Multi
Total Area
[Btu/hr sf F]
[ft]
[ft]
plier
[sf]
In Zone: PrOZol
In Wall: Pr0Zo1Wa2
1
PrOZo1Wa2Wil SINGLE CLEAR No
1.0018 0.81 0.88
17.00
4.00
2
136.0
El
3/8/2006 EnergyGauge F1aCom v 2.11 2
Doors
No Description
Type
Shaded? Width H (Effec) Multi
Area Cond. Dens. Heat Cap. R-Value
IN [ft]
plier
[sfJ [Btu/hr. sf. F] [lb/cf] [Btu/sf. F] [h-sf.F/Btu]
In Zone:
In Wall:
Roofs
No Description
Type
Width H (Effec) Multi
Area
Tilt Cond. Heat Cap
Dens. R-Value
IN IN plier
[sf]
[deg] [Btu/hr. Sf. F] [Btu/sf. F]
[lb/cf] [h.sf.FBtu]
In Zone: PrOZol
1 PrOZo1Rf1
Mtl Bldg Roof/R-19
Batt
20.00 28.00 1
560.0
0.00 0.0492 1.34
9.49 20.34
❑
Skylights
No Description
Type
U SHGC Vis.Trans
W H (Effec) Multiplier
Area Total Area
[Btu/hr sf F1
[ft] [ft]
[Sf] [Sf]
In Zone:
In Roof:
Floors
No Description
Type
Width H(Effec) Multi
Area
Cond. Heat Cap. Dens.
R-Value
IN IN plier
[sf]
[Btu/hr. sf. F] [Btu/sf. F] [lb/cf]
[h.sf.F/Btu]
In Zone: PrOZol
1 PrOZo 1 F11
Concrete floor,
20.00 28.00 1
560.0 0.5987 9.33 140.00
1.67
❑
carpet and rubber
pad
3/8/2006 EnergyGauge F1aCom v 2.11
3
PrOSyl
System 1
►vent Category
1 Cooling System (Air Cooled < 65000 Btu/h Cooling
Capacity)
2 Air Handling System -Supply (Air Handler (Supply) -
Constant Volume)
Systems
Constant Volume Air Cooled Split
System < 65000 Btu/hr
Capacity Efficiency IPLV
36000.00 13.00 13.00
1200.00 0.45
No. Of Units 1
3/8/2006 } EnergyGauge F1aCom v 2.11 4
I
Fenestration Used
Name
Glass Type No. of
Glass SHGC
VLT
Panes
Conductance
[Btu/h.sf.Fl
ApLbWndl
SINGLE CLEAR 1
1.0018 0.8150
0.8810
❑
Materials Used
Mat No
Acronym
Description
Only R-Value RValue Thickness
Conductivity
Density
SpecificHeat
Used [h.sf.FBtu]
[ft]
[Btu/h.ft.Fl
[lb/cf]
[Btu/Ib.F]
187
Mat1187
GYP OR PLAS
No 0.4533
0.0417
0.0920
50.00
0.2000
❑
BOARD,1 /2IN
151
Matll51
CONC HW, DRD, 140LB,
No 0.4403
0.3333
0.7570
140.00
0.2000
❑
41N
178
Matl178
CARPET W/RUBBER PAD
Yes 1.2300
❑
211
Matl211
POLYSTYRENE,EXP.,1/2I
No 2.0850
0.0417
0.0200
1.80
0.2900
❑
N,
12
Matl12
3 in. Insulation
No 10.0000
0.2500
0.0250
2.00
0.2000
❑
23
Matl23
6 in. Insulation
No 20.0000
0.5000
0.0250
5.70
0.2000
❑
4
Mat14
Steel siding
No 0.0002
0.0050
26.0000
480.00
0.1000
❑
IL 94
Mat194
BUILT-UP ROOFING,
No 0.3366
0.0313
0.0930
70.00
0.3500
❑
3/8IN
Constructs Used
3/8/2006 EnergyGauge FlaCom v 2.11 5
No
Name
Simple
Massless Conductance
Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F]
[lb/cf]
[h.sf.FBtu]
1004
Concrete floor, carpet and rubber
pad No
No 0.60
9.33
140.00
1.6703
❑
Layer
Material
Material
Thickness
Framing
No.
IN
Factor
1
151
CONC HW, DRD, 140LB, 41N
0.3333
0.00
❑
2
178
CARPET W/RUBBER PAD
0.00
❑
No
Name
Simple
Massless Conductance
Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sLF]
[Btu/sf.F]
[lb/cf]
[h.sLFBtu]
1015
0.5 Ply/35/8" Mtl std@24"oc/R11/0.5"
Gyp No
No 0.08
0.54
7.98
12.5383
❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
211
POLYSTYRENE,EXP.,1/2IN,
0.0417
0.00
❑
2
12
3 in. Insulation
0.2500
0.00
❑
3
187
GYP OR PLAS BOARD,1/2IN
0.0417
0.00
❑
No
Name
Simple
Massless Conductance
Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sf.F]
[Btu/sf.F]
[Ib/cf]
[h.sLF/Btu]
1020
Metal siding/RI I Batt/0. 5 "Gyp No
No 0.10
0.76
16.80
10.4535
❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
4
Steel siding
0.0050
0.00
❑
2
12
3 in. Insulation
0.2500
0.00
❑
3
187
GYP OR PLAS BOARD,1/2IN
0.0417
0.00
❑
3/8/2006 EnergyGauge F1aCom v 2.11 6
t
No Name
1047 Mtl Bldg Roof/R-19 Batt
Layer Material Material
No.
Simple Massless
Construct Construct
No No
1 94 BUILT-UP ROOFING, 3/81N
2 23 6 in. Insulation
Conductance
[Btu/h.sLF]
Heat Capacity
[Btu/sf.F]
Density
[lb/cf]
RValue
[h.sf.FBtu]
0.05
1.34
9.49
20.3366 ❑
Thickness
Framing
IN
Factor
0.0313
0.00 ❑
0.5000
0.00 ❑
3/8/2006 EnergyGauge FlaCom v 2.11
W