s SANFORD FIRE DEPARTMENT
FIRE PREVENTIONDIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, FI. 32772
(407 302-2516 / FAX (407) 302-2526
Fire Marshal
Plans Review Sheet
Date: October 9, 2006 Business Address: 1165 W. Airport Blvd.
Occ. Ch. 40 Industrial- 38-Business
Business Name: Prostalund PH (407) 830-1414
Fax. (407) 830-8448
Architect: JRJJ & Associates
PH (407) 875-0115
Fax. (407) 875-0308
Comment: Plans reviewed as Occ. Ch. 40 Industrial-38-Business Type IV fire sprinkler
protected
2,093sq ft type IV fire sprinkled building
Occupancy's FD reserves right to require applicable code requirements if occupancy use
changes. Sprinkler plans to be submitted for review, permitting, and inspections. Sealed
letter from Engineer of Record stating design criteria for sprinkler system needs to be submitted
with construction plans. F
Fire Alarm Requirement: See below
Fire Alarm notification: Each individual tenant space shall
have two (2) horn strobes, for individual tenant notification (one
in business office, and one in storage/industrial area).
- Application — New Building (2,093 s. q. ft.)
1
T
SANFORD FIRE DEPARTMENT ,
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI. 32771 / P. O. Box 1788, Sanford, FI. 32772
(407 302-2516 / FAX (407) 302-2526
Fire Marshal
1.1
1.2
1.3 Mixed — N/A,
2.3 Capacity of Egress — sales floor area based on one (])_person per 30 sq ft., storage area
based on one (1) person per 300 sq. ft.
2.4 Number of Exits — two for each individual tenant ok
2.5 Arrangement of Egress O.K. — two for each individual tenant ok 2.6 Travel Distance —
2.7 Discharge from Exits — O.K., will field verify
2.8 Illumination of Means of Egress —additional EXIT SIGNS may be required (power shut
down test required at night only)
2.9 Emergency Lighting — (1) foot candle (10 Ix & a minimum at any point of 0.1
foot-candle (1LX ) measured along the path of egress at floor level.Therfore
additional emergency lights may be required, (power shut down test required at night
only) Emergency Lights required In all rest rooms & Main Electrical Room (*).
2.10 Marking of Means of Egress — O.K.; will field verify
2.11 Special Features —Reserved
3.1 Protection of Vertical Openings — Ch. 40 Industrial-38-Business
3.2 Protection from Hazards — (See exception 40-3.2.1 .LSC 101)
3.3 Interior Finish — Not required, building has an automatic fire sprinkler system
3.4 Detection, Alarm and Communications System: (as per N.F.PA.72- 3-8.3.1.2 (99)
Ed.
2
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI. 32771 / P. O. Box 1788, Sanford, FI. 32772
(407 302-2516 / FAX (407) 302-2526
Fire Marshal
• 3.5 Extinguishing Requirements — as per NFPA 10, one (1) 2A 10 BC rated fire
extinguishers required per N.F.PA. #10 (see blueprints for locations).
5.1 Utilities — as per LSC 7-1
5.2 HVAC — as per LSC 7-2
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
Sanford City Code — Chapter9:
Required; Fire Sprinklers. Drop fire sprinkler heads below ceiling
Monitoring: Required on all fire sprinkler valves (includes inside and out)
Other: NFPA 1
3-5.1 Fire Lanes — Required (see sight plan)
3-6.1 Key Box— required already
3-7.1 Bldg. Address Number Posted and Legible — Post address in 6" Six inch
numbers contrasting in color (see blue prints).
3
Florida Energy Efficiency Code For Building Construction
Florida Department of Community Affairs
EnergyGauge F1aCom v 2.11 FORM 40OA-2004
Whole Building Performance Method for Commercial Buildings
Jurisdiction: SANFORD, SEMINOLE COUNTY, FL (691500)
Short Desc: PROSTALUND Project: PROSTALUND, INC.
Owner:
Address: 1165 WEST AIRPORT BLVD
City: SANFORD
State: FL PermitNo: 0--
Zip: 0 Storeys: 1
Type: Office *Conditioned Area: 1163
Class: Renovation to existing building *Cond + UnCond Area: 1163
Max Tonnage: 3.5 (if different, write in)
Compliance Summary
* denotes lighted
area. Does not include
wall crosection areas
Component Design Criteria Result
Gross Energy Use 1,352.85 1,801.17 PASSES
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
PASSES
None Entered
PASSES
None Entered
PASSES
None Entered
Yes/No/NA
IMPORTANT NOTE: An input report Print -Out from EnergyGauge Co of
this design building must be submitted along with this Compliance Report.
9/14/2006 EnergyGauge FlaCom v 2.11 FORM 40OA-2004
I
MWAVIA WA I LIMIA
I hereby certify that the plans and
specifications covered by this calculation'arp,
in compliance with the Florida- Enemy
Efficiency Code.'.
PREPARED BY:- GUS BOBES JR P.E.
DATE:
I hereby certify that this building is in'compliiancr
with the Florida Energy Efficiency Code.
Review of the plans and specifications covered by this
calculation indicates compliance with the Florida .Energy
Code. Before construction is completed, this building will be
inspected for compliance in accordance with Section
553.908, F.S.
BUILDING OFFICIAL:
DATE:
OWNER AGENT;
DATE:
If required by Florida law, I hereby certify (*) that the system design is in REGISTRATION
compliance with the Florida Energy Code.
No.
ARCHITECT:
ELECTRICAL SYSTEM DESIGNER:
LIGHTING SYSTEM DESIGNER:
MECHANICAL SYSTEM DESIGNER:
PLUMBING SYSTEM DESIGNER:
(*) Signature is required where Florida Law requires design to be performed by registered design professionals.
Typed names and registration numbers may be used where all relevant information is contained on signed/sealed
plans.
9/14/2006 EnergyGauge FlaCom v 2.11 FORM 40OA-2004 2
Project: PROSTALUND
Title: PROSTALUND, INC.
Type: Office
(WEA File: Orlando.TMY)
Whole Building Compliance
Design
Reference
Total
74.20
100.00
$1,352.85
$1,801.17
ELECTRICITY(MBtu/kWh/$
74.20
100.00
27,057.00
36,461.00
$1,352.85
$1,801.17
AREA LIGHTS
10.05
10.77
3,675.00
3,916.00
$183.75
$193.45
MISC EQUIPMT
6.99
6.99
2,555.00
2,555.00
$127. 75
$126 22
PUMPS & MISC
0.08
0.08
28.00
31.00
$1.40
$1.53
SPACE COOL
26.77
21.62
9,763.00
7,886.00
$488.15
$389.57
VENT FANS
30.31
60.53
11,036.00
22,073.00
$551.80
$1, 090.41
Credits & Penalties (if any): Modified Points:
= 74.2
PASSES
External Lighting Compliance
Description
Category Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (W)
(Sgft or ft)
None
9/ 14/2006
EnergyGauge FlaCom v 2.11 FORM 40OA-2004 3
Project: PROSTALUND
Title: PROSTALUND, INC.
Type: Office
(WEA File: Orlando.TMY)
Lighting Controls Compliance.
Acronym Ashrae
Description Area No. of Design Min Compli-
ID
(sq.ft) Tasks CP CP ance
PrOZo 1 Sp 1 17 Office - Enclosed 1,163 1 4 1 PASSES
II PASSES II
Project: PROSTALUND
Title: PROSTALUND, INC.
Type: Office
(WEA File: Orlando.TMV)
System Report Compliance
PrOSyl System 1 Constant Volume Air Cooled No. of Units
Split System < 65000 Btu/hr 2
Component Category Capacity Design Eff Design IPLV Comp-
Eff Criteria IPLV Criteria liance
Cooling System Air Cooled < 65000 Btu/h 13.00 10.00 13.00 PASSES
Cooling Capacity
Air Handling Air Handler (Supply) - 0.45 0.90 PASSES
System -Supply Constant Volume
PASSES
Plant Compliance
Description Installed Size Design Min Design Min Category Comp
No Eff Eff IPLV IPLV liance
None
9/14/2006 EnergyGauge FlaCom v 2.11 FORM 40OA-2004 4
Project: PROSTALUND
Title: PROSTALUND, INC.
Type: Office
(WEA File: Orlando.TMY)
Water Heater Compliance
Description Type Category Design Min
Design Max Comp
Eff Eff
Loss Loss liance
Water Heater 1 Electric water heater > 12 [kW] 0.85
0.02 267.41 PASSES
PASSES
Piping System Compliance
Category Pipe Dia Is Operating Ins Cond Ins Req Ins Compliance
[inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in]
[F] SF.FJ
None
9/14/2006 EnergyGauge FlaCom v 2.11 FORM 400A-2004
Project: PROSTALUND
Title: PROSTALUND, INC.
Type: Office
(WEA File: Orlando.TMY)
Other Required Compliance
Category
Section
Requirement (write N/A in box if not applicable)
Check
Infiltration
406.1
Infiltration Criteria have been met
System
407.1
HVAC Load sizing has been performed
Ventilation
409.1
Ventilation criteria have been met
ADS
410.1
Duct sizing and Design have been performed
ED
T & B
410.1
Testing and Balancing will be performed
Motors
414.1
Motor efficiency criteria have been met
Lighting
415.1
Lighting criteria have been met
O & M
102.1
Operation/maintenance manual will be provided to owner
Roof/Ceil
404.1
R-19 for Roof Deck with supply plenums beneath it
Report
101
Input Report Print -Out from EnergyGauge FlaCom attached?
El
9/14/2006 EnergyGauge F1aCom v 2.11 FORM 40OA-2004 6
EnergyGauge F1aCom v 2.11
INPUT DATA REPORT
Project Information
Project Name: PROSTALUND Orientation: North
Project Title: PROSTALUND, INC. Building Type: Office
Address: 1165 WEST AIRPORT BLVD Building Classification: Renovation to existing building
State: FL
Zip: 0
Owner:
No.of Storeys: l
GrossArea: '1163
Zones
No Acronym Description
Type
Area
Multiplier
Total Area
1 PrOZol Zone 1
CONDITIONED
[Sl1
1162.5
[sl7
1
1162.5
Spaces
No Acronym Description
Type Depth Width
Height Multi
Total Area
Total Volume
lft] [ft]
lft] plier
lsf]
1cfl
9/14/2006
EnergyGauge FlaCom v 2.11
1
In Zone: PrOZol
1 Pr0ZolSvI
Zo0Sp1 Office - Enclosed
37.50
31.00
11.50
1 1162.5
13368.8
Lighting
No
Type Category
No. of
Watts per
Power
Control Type
No.of
Luminaires
Luminaire
[W]
Ctrl pts
In Zone: PrOZol
In Space: Pr0Zo1Sp1
1
Recessed Fluorescent - General Lighting
1
600
600
Manual On/Off
2 El
No vent
2
Recessed Fluorescent - General Lighting
1
600
600
Manual On/Off
2
No vent
Walls
No Description
Type Width H (Effec) Multi
Area DirectionConductance Heat
Dens. R-Value
IN
[ft] plier
[sf]
[Btu/hr. sf. F] Capacity
[lb/cfl [h.sLFBtu]
[Btu/sLF]
In Zone: PrOZol
I PrOZOI WaI
Metal 31.00
12.00 1
372.0
East
0.0957 0.7570
16.80 10.45
siding/R11 Batt/0.5"
Gyp
2 Pr0ZOIWa3
0.5 Ply/35/8" Mtl 48.00
12.00 1
576.0
West
0.0798 0.5388
7.98 12.54
std@24"oc/R 11 /0.5'
Gyp
Windows
No
Description Type Shaded U SHG Vis.Tr
W
H (Effec) Multi
Total Area
[Btu/hr sf F]
[ft]
[ft] plier
[sf]
In Zone: PrOZol
In Wall: PrOZo1Wal
1
PrOZolWalWi1 SINGLE CLEAR No
1.0018 0.81 0.88
22.00
8.00 2
352.0
9/14/2006 . EnergyGauge FlaCom v 2.11
Doors
No Description
Type
Shaded? Width H (Effec) Multi
Area
Cond. Dens. Heat Cap.
R-Value
IN IN
plier
[sf]
[Btu/hr. sf. F] [lb/cf] [Btu/sf.
F]
[h.sf.F/Btu]
In Zone: PrOZol
In Wall: PrOZo1Wa3
1 PrOZolWa3Drl Wood door, 2 in.
No 3.00 7.00
1
21.0
0.4192 37.00
2.41
2.39
❑
Roofs
No Description
Type
Width H (Effec) Multi
Area
Tilt
Cond. Heat Cap
Dens.
R-Value .
[ft] [ft] plier
[sf]
[deg]
[Btu/hr. Sf. F] [Btu/sf. F]
[lb/cf]
[h.sf.F/Btu]
In Zone: PrOZol
1 PrOZo1Rfl
Mtl Bldg Roof/R-19
31.00 37.50 1
1162.5
0.00
0.0492 1.34
9.49
20.34
❑
Batt
Skylights
No Description
Type
U SHGC Vis.Trans
W
H (Effec) Multiplier
Area
Total Area
[Btu/hr sf F]
IN
A
[sf]
[Sf]
In Zone:
In Roof:
Floors
No Description
Type
Width H (Effec) Multi
Area
Cond. Heat Cap. Dens.
R-Value
IN [ft] plier
[sf]
[Btu/hr.
sL F] [Btu/sL F] [Ib/cf]
[h.sLFBtu]
In Zone: PrOZol
1 PrOZolFll
Concrete floor,
31.00 37.50 1
1162.5 0.5987 9.33 140.00
1.67
❑
carpet and rubber
pad
9/14/2006 EnergyGauge F1aCom v 2.11
Systems
PrOSyI System 1 Constant Volume Air Cooled Split
System < 65000 Btu/hr
Component Category Capacity Efficiency IPLV
1 Cooling System (Air Cooled < 65000 Btu/h Cooling 42000.00 1100 13.00
Capacity)
2 Air Handling System -Supply (Air Handler (Supply) - 1400.00 0.45
Constant Volume)
Plant
Equipment Category Size Inst.No Eff.
Water Heaters
No. Of Units 2
IPLV
W-Heater Description Capacit Cap.Unit UP Rt. Efficienc
Loss
1 Electric water heater 50 [Gal] ] 16382 [kW] 0.8500 [Ef] 0.0200 [Btulh]
Ext-Lighting
Description Category No. of Watts per Area/Len/No. of units Control Type Wattage
Luminaires Luminaire [sf/ft/No] [w]
No . Type
- Piping
Operating Insulation
Temperature Conductivity
[F] [ Btu-in/h.sf.F]
Nomonal pipe Insulation Is Runout?
Diameter Thickness
[►n] [inl
9/14/2006 EnergyGauge FlaCom v 2.11
4
0
M
Fenestration Used
Name
Glass Type No. of
Glass SHGC
VLT
Panes
Conductance
[Btu/h.sf.F]
ApLbWndl
SINGLE CLEAR 1
1.0018 0.8150
0.8810
❑
Materials Used
Mat No
Acronym
Description
Only R-Value RValue Thickness
Conductivity
Density
SpecificHeat
Used [h.sf.F/Btu]
IN
[Btu/h.ft.F ]
[Ib/cf]
[Btu/Ib.F]
18
Mat118
2 in. Wood
No 2.3857
0.1670
0.0700
37.00
0.3900 -
❑
187
Mat1187
GYP OR PLAS
No 0.4533
0.0417
0.0920
50.00
0.2000
❑
BOARD,1 /21N
151
Mad151
CONC HW, DRD, 140LB,
No 0.4403
0.3333
0.7570
140.00
0.2000
❑
41N
178
Mat1178
CARPET W/RUBBER PAD
Yes 1.2300
❑
211
Mat12ll
POLYSTYRENE,EXP.,1/2I
No 2.0850
0.0417
0.0200
1.80
0.2900
❑
N,
12
Mat112
3 in. Insulation
No 10.0000
0.2500
0.0250
2.00
0.2000
❑
23
Matl23
6 in. Insulation
No 20.0000
0.5000
0.0250
5.70
0.2000
❑
4
Mat14
Steel siding .
No 0.0002
0.0050
26.0000
480.00
0.1000
❑
94
Mat194
BUILT-UP. ROOFING,
No 0.3366
0.0313
0.0930
70.00
0.3500
❑
3/81N
Constructs Used
9/14/2006 EnergyGauge FlaCom v 2.11
No Name Simple Massless Conductance Heat Capacity Density RValue
Construct Construct [Btu/h.sLF] [Btu/sf.F] [lb/cf] [h.sLF/Btu]
1001 Wood door, 2 in. No No 0.42 2.41 37.00 2.3857 ❑
Layer Material Material Thickness Framing
No.
[ft] Factor
1 18 2 in. Wood 0.1670 0.00 ❑
No
Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sLF]
[Btu/sf.F]
[lb/cf]
[h.sLFBtu]
1004
Concrete floor, carpet and rubber pad No
No 0.60
9.33
140.00
1.6703
❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
151
CONC HW, DRD, 140LB, 4IN
0.3333
0.00
❑
2
178
CARPET W/RUBBER PAD
0.00
❑
No
Name
Simple
Massless Conductance
Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sLF]
[Btu/sf.F]
[lb/cf]
[h.sLFBtu]
1015
0.5 Ply/35/8"
Mtl std@24"oc/R11/0.5" Gyp No
No 0.08
6.54
7.98
12.5383
❑
Layer
Material
Material
Thickness
Framing
No.
[ft]
Factor
1
211
POLYSTYRENE,EXP.,1/2IN,
0.0417
0.00
❑
2
12
3 in. Insulation
0.2500
0.00
❑
3
187
GYP OR PLAS BOARD,1/21N
0.0417
0.00
❑
9/14/2006 EnergyGauge F1aCom v 2.11
6
No
1020
Name
Metal siding/RI I Batt/0. 5 "Gyp
Simple
Construct
No
Massless
Construct
No
Conductance
[Btu/h.sf.F]
0.10
Layer Material Material
Thickness
No.
IN1
4 Steel siding
0.0050
2 12 3 in. Insulation
0.2500
3 187 GYP OR PLAS BOARD,1/21N
0.0417
No
Name
Simple
Massless
Conductance
Construct
Construct
[Btu/h.sf.F]
1047
Mtl Bldg Roof/R-19 Batt
No
No
0.05
9/14/2006
Layer Material Material Thickness
No.
[ft]
1 94 BUILT-UP ROOFING, 3/81N 0.0313
2 23 6 in. Insulation 0.5000
EnergyGauge FlaCom v 2.11
Heat Capacity
Density
RValue
[Btu/sf.F]
[lb/cf]
[h.sf.FBtu]
0.76
16.80
10.4535
❑
Framing
Factor
0.00
❑
0.00
❑
0.00
❑
Heat Capacity
Density
RValue
[Btu/sf.F]
[lb/cf]
[h.sf.FBtu]
1.34
9.49
20.3366
❑
Framing
Factor
0.00 ❑
0.00 ❑
7