PLAN REVIEW RESPONSE
Date: April 12, 2007
Contact Person: Mike Puryear
Contact Phone Number: 407-830-1414
Contact E-mail Address:
Reference Number: 07-1482
Project Description: Tenant improvement
Job Address: 1263 W. Airport Blvd.
Contact Fax Number: 407-830-8448
The following is a list of the areas of the submitted plans that contained violations of the codes
adopted by the City of Sanford and enforced by the Building Division. The violations noted must
be addressed before the plans can be approved. Changes to plans shall be submitted on the
same size format as the original submittal. Changes to construction documents that require an
Architect or Engineer's seal must be submitted with the appropriate seal.
ARCHITECTURAL
A-1 The plans indicate that the space is intended to be for storage. Provide the division for the
intended use. FBC 311.
PLUMBING
P-1 This space is intended to be a storage space. A service sink is required. FPC Table 403.1
Any error or omission in this plan review shall not be construed to grant approval of any violation
of any of the adopted codes or municipal ordinances of this jurisdiction.
Please direct any questions you may have to Wayne Thorne at (407) 330-5686 or fax to (407)
328-3859. You may also contact me by E-mail at thornew@ci.sanford.fl.us.
- 1 -
PROJECT SUMMARY
Short Desc: BRIO1263
Owner:
Addressl: 1263 WEST AIRPORT BLVD
Address2: BRIO COMMERCE CENTER
Description: BRIO SPEC OFFICE - 1263 11
City:
State:
Zip:
Type: Office Class:
Jurisdiction: SANFORD, SEMINOLE COUNTY, FL (691500)
Cond Area: 278 SF Cond & UnCond Area:
No of Storeys: 1 Area entered from Plans
Permit No: 0-- Max Tonnage
If different, write in:
3/7/2007 EnergyGauge FLAMM 2004 v3.00
SANFORD
FL
0
Renovation to existing
278 SF
0 SF
1.5
Compliance Summary 11
Component Design Criteria Result
Gross Energy Use 353.2 398.8 PASSES
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
PASSES
None Entered
PASSES
None Entered
None Entered
None Entered
Yes/No/NA
IMPORTANT NOTE: An input report of this design building must be submitted
along with this Compliance Report.
3/7/2007
EnergyGauge FLA/COM 2004 v3.00
2
CERTIFICATIONS
hereby certify that the plans and specifications covered by this calculation are in compliance with the
Florida Energy Code r r
Prepared By: Building Official:
Date: 3 7 3'T Date:
I certify that this building is in compliance with the Florida Energy Efficiency Code
Owner Agent: Date:
If Required by Florida law, I hereby certify (") that the system design is in compliance with the Florida
Energy Efficiency Code
Architect: Reg No:
Electrical Designer: Reg No:
Lighting Designer: Reg No:
Mechanical Designer: Reg No:
Plumbing Designer: Reg No:
(") Signature is required where Florida Law requires design to be performed by registered design
professionals. Typed names and registration numbers may be used where all relevant information is
contained on signed/sealed plans.
3/7/2007 EnergyGauge FLA/COM 2004 v3.00 3
Project: BRIO1263
Title: BRIO SPEC OFFICE - 1263
Type: Office
(WEA File: Orlando.TMY)
Whole Building Compliance
Design Reference
Total 88.28
100.00
$353
$399
ELECTRIC ITY(MBtu/k 88.28
100.00
Wh1$) 7049
$353
8024
$399
AREA LIGHTS 11.36
11.72
919
937
$46
$4 7
MISC EQUIPMT 7.69
7.69
612
612
$31
$30
PUMPS & MISC 0.37
0.37
23
32
$1
$2
SPACE COOL 39.19
21.25
3130
1712
$157
$85
VENT FANS 29.67
58.97
2365
4731
$118
$235
Credits & Penalties (if any): Modified Points: _ 88.28
PASSES
External bighting Compliance
Description Category
Allowance Area or Length ELPA CLP
(W/Unit) or No. of Units (W) (W)
(Sgft or ft)
None
3/7/2007 EnergyGauge FLA/COM 2004 v3.00 4
Project: BRIO1263
Title: BRIO SPEC OFFICE - 1263
Type: Office
(WEA File: Orlando.TMY)
Lighting Controls Compliance
Acronym Ashrae Description
ID
Area No. of Design Min Compli-
(sq.ft) Tasks CP CP ance
Pr0Zo1Sp1 16 Office - Open Plan
278 1 2 1 PASSES
PASSES
Project: BRIO1263
Title: BRIO SPEC OFFICE - 1263
Type: Office
(WEA File: Orlando.TMY)
System Report Compliance
PrOSyl System 1 Constant Volume Air Cooled No. of Units
Split System < 65000 Btu/hr 1
Component Category
Capacity Design Eff Design IPLV Comp-
Eff Criteria IPLV Criteria liance
Cooling System Air Cooled < 65000 Btu/h
Cooling Capacity
Air Handling Air Handler (Supply) -
System -Supply Constant Volume
13.00 13.00 13.00 PASSES
0.45 0.90 PASSES
PASSES
Plant Compliance
Description Installed Size Design
No Eff
Min Design Min Category Comp
Eff IPLV IPLV liance
None
3/7/2007 1 EnergyGauge FLA/COM 2004 v3.00
Water Heater Compliance
Description Type Category Design Min Design Max Comp
Eff Eff Loss Loss fiance
II 1 None II
Piping System Compliance
Category Pipe Dia Is Operating Ins Cond Ins Req Ins Compliance
(inches] Runout? Temp. [Btu-in/hr Thick lint Thick fin]
IF] .SF.FI
None
Project: BRIO1263
Title: BRIO SPEC OFFICE - 1263
Type: Office
(WEA File: Orlando.TMY)
Other Required Compliance
Category Section Requirement (write N/A in box if not applicable) Check
._
Infiltration __ -4061 . _ ..: _ , ..-.Infiltration-Criteria have been, met ._. - ..._ .
System 407.1 HVAC Load sizing has been performed
Ventilation 409.1 Ventilation criteria have been met
ADS 410.1 Duct sizing and Design have been performed
T & B 410.1 Testing and Balancing will be performed
Motors 414.1 Motor efficiency criteria have been met
Lighting 415.1 Lighting criteria have been met
O & M 102.1 Operation/maintenance manual will be provided to owner
Roof/Ceil 404.1 R-19 for Roof Deck with supply plenums beneath it
Report 101 Input Report Print -Out from EnergyGauge FlaCom attached?
3/7/2007 EnergyGauge FLA/COM 2004 v3.00 6
EnergyGauge FLAXOM 2004 v3.00
INPUT DATA REPORT
Project Name:
Project Title:
Address:
State:
Zip:
Owner:
Pro iect Information
BRIO1263 Orientation:
BRIO SPEC OFFICE - 1263 Building Type:
1263 WEST AIRPORT BLVD Building Classification:
BRIO COMMERCE CENTER
FL, No.of Storeys:
0 GrossArea:
North
Office
Renovation to existing building
I
278 SF
Zones
No Acronym Description Type Area
fstl
Multiplier
Total Area
sf]
jsfJ
1 Prozo I Zone 1 CONDITIONED 278 3
1
3 Ej
Spaces
No Acronym Description Type Depth Width Height Multi Total Area
IN IN IN plier 1sf1
Total Volume
icfi
3/7/2007 EnergyGauge FLA/COM 2004 v3.00
In Zone: PrOZol
1 PrOZo1Svi Zo0Spl
No Type
Office -:Open Plan 27.83 10.00 9.00 1 278.3 2504.3 ❑
Lighting
Category No. of Watts per Power Control Type No.of
Luminaires Luminaire [W] Ctrl pts
In Zone: PrOZol
In Space: Pr0Zo1Sp1
1 Recessed
No
Fluorescent - General
Lighting
1
300 300 Manual On/Off
2 ❑
vent
Walls
No Description
Type
Width H (Effec) Multi
Area
DirectionConductance
Heat
Dens.
R-Value
IN
[ft] plier
[sf]
Btu/hr. sf. F
[ l
Ca
Capacity y
[Ib/cfJ
[h.sf.F/Btu]
[Btu/sf.F]
In Zone: PrOZol
1 PrOZoIWa1
0.5 Ply/35/8" Mtl
77.00
10.00 1
770.0
North 0.0798
0.539
7.98
12.5 ❑
std@24"oc/R 11 /0.5"
Gyp
2 PrOZo I Wa2
Metal
siding/R1 I Batt/0.5"
8.00
12.00 1
96.0
South 0.0957
0.757
16.80
10.5 ❑
Gyp
Windows
No Description Type . Shaded U SHGC Vis.Tra
[Btu/hr sf F]
In Zone: PrOZol
In Wall: Pr0Zo1Wa2
1 Pr0Zol Wa2Wil User Defined' No 1.0000 1.15 0.90
i
3/7/2007 EnergyGauge FLA/COM 2004 v3.00
W H (Effec) Multi Total Area
IN IN plier [sf]
6.00 7.00
2 84.0 ❑
2
Doors
No Description Type Shaded? Width H (Effec) Multi Area Cond. Dens. Heat Cap. R-Value
IN IN plier [sf] [Btu/hr. sf. F] [Ib/cf] [Btu/sf. F] [h.sLF/Btu]
In Zone:
In Wall:
70
No Description
In Zone: PrOZol
1 PrOZoIRf]
Type
Mtl Bldg Roof/R-19
Batt
Width
IN
10.00
Roofs
H (Effec) Multi
IN plier
27.83 1
Area
[sf]
278.3
Tilt Cond. Heat Cap
[deg] [Btu/hr. SL F] [Btu/sf. F]
0.00 0.0492 1.34
Dens. R-Value
[Ib/cf[ [h.sf.F/Btu]
9.49 20.3
❑
Skylights
No Description Type
U SHGC Vis.Trans
W H (Effec) Multiplier
Area Total Area
[Btu/hr sf F]
[ft] [ft]
[SfJ [Sf]
In Zone:
In Roof:
Floors
No Description
Type
Width
H (Effec) Multi
Area
Cond. Heat Cap. Dens.
R-Value
IN
IN plier
[sf]
[Btu/hr. sL F] [Btu/sf. F] [Ib/cf]
[h.sf.F/Btu]
In Zone: PrOZol
1 PrOZOI Fl l
Concrete floor,
10.00
27.83 1
278.3
0.5987 9.33 140.00
1.67
❑
carpet and rubber
pad
3/7/2007
EnergyGauge FLA/COM 2004 v3.00
3
Systems
PrOSyI System 1 Constant Volume Air Cooled Split
System < 65000 Btu/hr
Component Category Capacity Efficiency IPLV
1 Cooling System (Air Cooled < 65000 13tu/h Cooling 18000.00 13.00 13.00
Capacity) ;
2 Air Handling System -Supply (Air Handler (Supply) - 600.00 0.45
Constant Volume)
No. Of Units 1
Plant
Equipment
Category Size Inst.No Eff.
IPLV
Water Heaters
W-Heater Description
Ca pacit3Cap. Unit I/P Rt. Efficiency
Loss
Ext-Lighting
Description
Category No. of Watts per Area/Len/No. of units Control Type
Luminaires Luminaire [sf/ft/Nol
Wattage
[w]
Piping
No Type
Operating Insulation Nomonal pipe
Temperature Conductivity Diameter
IF] l Btu-in/h.sf.FI lint
Insulation
Thickness
lint
Is Runout?
'1 /"'°° / - EnergyGauge FLA/COM 2004 v3.00
Fenestration Used
Name
Glass Type No. of
Glass
VLT
Panes
Conductance
Conductance
[Btu/h.sf.Fl
ApLbWndl
User Defined 1
1.0000
1.1494
0.9000
❑
Materials Used
Mat No
Acronym
Description
Only R-Value
RValue Thickness
Conductivity
Density
SpecificHeat
Used
[h.sf.F/Btul
IN
[Btu/h.ft.Fl
[lb/c f[
[Btu/Ib.F]
187
Mat1187
GYP OR PLAS
No
0.4533
0.0417
0.0920
50.00
0.2000
❑
BOARD,1 /21N
151
Mad151
CONC HW, DRD, 140LB,
No
0.4403
0.3333
0.7570
140.00
0.2000
❑
41N
178
Mat1178
CARPET W/RUBBER PAD
Yes
1.2300
211
Mat1211
POLYSTYRENE,EXP.,1/21
No
2.0850
0.0417
0.0200
1.80
0.2900
❑
❑
N,
12
Mad12
3 in. Insulation
No
10.0000
0.2500
0.0250
2.00
0.2000
❑
23
Mat123
6 in. Insulation
No
20.0000
0.5000
0.0250
5.70
0.2000
❑
4
94
Mat14
Steel siding
No
0.0002
0.0050
26.0000
480.00
0.1000
❑
Mat194
BUILT-UP ROOFING,
No
0.3366
0.0313
0.0930
70.00
0.3500
El
3/8IN
Constructs Used
No Name Simple Massless Conductance Heat Capacity Density RValue
Construct Construct [Btu/h.sf.F] [Btu/sf.F[ [lb/cf] [h.sf.F/Btu]
1004 Concrete floor, carpet and rubber pad No No 0.60 9.33 140.00 1.7 ❑
3/7/2007 EnergyGauge FLA/COM 2004 v3.00 5
Layer
Material
Material
Thickness
Framing
No.
IN
Factor
1
151
CONC HW, DRD, 140LB, 4IN
0.3333
0.000
❑
2
178
CARPET W/RUBBER PAD
0.000
❑
No Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct [Btu/h.sf.Fl
[Btu/sf.Fl
[Ib/cf]
[h.sf.F/Btu[
1015 0.5 Ply/35/8"
Mtl std@24"oc/R11/0.5" Gyp No
No 0.08
0.54
7.98
12.5
❑
Layer
Material
Material
Thickness
Framing
No.IN
Factor
1
211
POLYSTYRENE,EXP.,1/2IN,
0.0417
0.000
❑
2
12
3 in. Insulation
0.2500
0.000
❑
3
187
GYP OR PLAS BOARD,1/2IN
0.0417
0.000
❑
No Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct lBtu/h.sLFl
[Btu/sf.Fl
[lb/cf]
[h.sf.F/Btul
1020 Metal siding/RI I Batt/0.5 "Gyp No
No 0.10
0.76
16.80
10.5
❑
Layer
Material
Material
Thickness
Framing
No.
IN
Factor
1
4
Steel siding
0.0050
0.000
❑
2
12
3 in. Insulation..
0.2500
0.000
❑
3
187
GYP OR PLAS BOARD,1/2IN
0.0417
0.000
❑
No Name
Simple
Massless Conductance Heat Capacity
Density
RValue
Construct
Construct lBtu/h.sf.Fl
[Btu/sf.Fl
[lb/cf]
[h.sf.F/Btul
1047 Mtl Bldg Roof/R-19
Batt
No
No 0.05
1.34
9.49
20.3
❑
Layer
Material
Material
Thickness
Framing
No.
IN
Factor
1
94
BUILT-UP ROOFING, 3/81N
0.0313
0.000
❑
2
23
6 in. Insulation
0.5000
0.000
❑
3/7/2007 EnergyGauge FLA/COM 2004 v3.00 6
3/7/2007 EnergyGauge FLA/COM 2004 v3.00