HomeMy WebLinkAbout1130 - 1140 Spinner Ln//30 -//yd SP/NNRR L Al James A Whittum, P.E. FL # 27689 A 8533 Acorn Ridge Court Tampa, FL 33625 813-926-9719, Fax 813-920-1257. June 27, 2003 Ken Gordon, Aero Door 2036 Apex Ct. Apopka, FL 32703 Subject: HydroSwing Door I have reviewed the design #8314-2D by Cottonwood Welding and Manufacturing, Inc. for the HydroSwing door to be delivered to you: (1) 60 ft x 18 ft, nominal size, Corporate Hangar # 1 The design of the above door complies with the Florida Building Code 2001, as amended in 2002, Chapter 1=6 for an ASCE 7-98 Basic Wind Speed of 110 MPH (3 second gust), Type Il, Enclosed. Building. Design wind pressures for wall components and cladding provided by others shall low Wind Pressure, psf, @ 110 MPH (3 second gust) Main Wall Area 6 Feet From Corners Eff. Area, sf positive negative 10 30.4 33.4 50 26.7 28.7 500 21.2 24.3 Cc: Addressee (4) copies CWMI-via fax (1) copy File: door 8314-2D, 6-27-03 r positive negative 30.4 42.5 26.7 34.9 21.2 24.3 Sincerely, a 2 7 2093 James B. Whittum, P.E. JBW Engineering, Inc. Quote# 8314 Ken Gordon Asm Door Door size W x 18! M Welding point Full horizontal weld on stub column Mounting angle iron k.I Outside of building )Cs mark location of securing plates Mounting angle iron I L I Door Jamb Upper pinpoint Welding point 8' on 120 off for the full height of the door Welding points 1 /4" steel flat iron (width and length can vary) Check side drawing br plate location Vertical building jamb 07/02/2003 16:34 4073301502 DIAMOND GLASS CO PAGE 01 MtAMhDA f" :PRODUCT QQNIROL NOTICE OF ACCEPTANCE YKK AP America Inc. Gwaltney Dr, Atlanta GA. 30336 MIAM1-DADE COUNTY, FLORIDA METRO -TRADE FLAGLER BUILDING BUILUING CODE COMPLIANCE OFFICE METRO-DADE FLAGLER BUII.DING 140 WEST FLAGLER STREET, SUITE 1603 MIAMI, FLOR)DA 33130-1563 (305)375-2901 FAX (305) 375-2908 CON7I U'fOR LICENSING SECTION (305) 375-2527 FAX (305) 375.2558 CONTRACTOR ENFORCEMENT DIVISION (305) 375-2966 FAX (305) 375.2908 PRODUCT CONTROL DIVISION Your application for Notice of Acceptance (NOA) of; (305) 375.2902 FAX (305) 372-6339 Series "YES 45 FS" Aluminum Flush Glazed Storefront System under Chapter 8 of the Code of Miami -Dade County governing the use of Alternate Materials and Types of Construction, and completely described herein, has been recommended for acceptance by the Miami -Dade County Building Code Compliance Office (BCCO) under the conditions specified herein. This NOA shall not be valid after the expiration date stated below. BCCO reserves the right to secure this product or material at any time from a jobsite or manufacturer's plant for quality control testing. If this product or material fails to perform in the approved manner, BCCO may revoke, modify, or suspend the use of such product or material immediately. BCCO reserves the right to revoke this approval, if it is determined by HCCO that this product or material fails to meet t.hc requirements of the South Florida Building Code. The expense of such testing will be incurred by the manufacturer. IV�% _ ACCEPTANCE NO.: 00-0705.02 (1 EXPIRES 17/2003 Raul Rodrigue4 Chief Product Control Division THIS IS THE COVERS ET. $EE ADDITIONAL PAGES FOR. SPECIFIC AND GENERAL. CONDITIONS BUILDING 10121 A f jRQRUQ[ REVIEW COMDUTIEE This application for Product Approval has been reviewed by the BCCO and approved by the Building Code and Product Review Committee to be used in Miami -Dade County. Florida under the conditions set forth above. APPROVED: 08/09/2000 11=04S00011pd00011t"lat*slnvcko ctccepmrKe opw pag.dot gort �_i" Francisco J. Quintana, R.A. Director Miami -Dade County Building Code Compliance Office Internet mail address: postmaster@bulidlngeodeonline.com Homepage: http://www.buildingcodeonline.com 07/02/2003 16:34 4073301502 DIAMOND GLASS CO PAGE 02 Ti YKk'AP America Inc, ACCEPTANCE No.: 00-0705,0Z APPROVED AUG 0 9 2000 EXPIRES August 07,1003 NOTICE OF ACCEE][ANCE: SPECIFIC CONDITIONS Renewal of this Acceptance (approval) shall be considered after a renewil application has been filed and the original submitted documents, including test -supporting data, engineering documents, are no older than eight (8) years, 2. Any and all approved products shall be permanently labeled with the manufacturer's name, city, state, and the following statement: "Miami -Dade County Product Control Approval', or as specifically stated in the specific conditions of this Acceptance. 3. Renewals of Acceptance will not be considered if: a, There has been a change in the South Florida Building Code affecting the evaluation of this product and the product is not in compliance with the code changes, b. The product is no longer the same product (identical) as the one originally approved, e. It the Acceptance holder has not complied with all the requirements of this acceptance, including the correct installation of the product. d, The engincscr who originally prepared, signed and sealed the required documentation initially submitted, is no longer practicing the engineering profession. 4. Any revision or change in the materials, use, and/or manufacture of the product or process shall automatically be cause for termination of this Acceptance, unless prior written approval has been requested (through the filing of a revision application with appropriate fee) and granted by this office. 5. Any of the following shall also be grounds for removal of this Acceptance: a, Unsatisfactory performance of this product or process. b. Misuse of this Acceptance as an endorsement of any product, for sales, advertising or any other purposes, 6. The Notice of Acceptance number preceded by the words Miami -Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. It any portion of the Notice of Acceptance is displayed, then it shall be done in its entirety. 7. A copy of this Acceptance as well as approved drawings and other documents, where it applies, shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at all time, The engineer need not reseal the copies, 8. Failure to comply with any section of this Acceptance shall be cause for termination and removal of Acceptance, 9, This Notice of Acceptance consists of pages 1, 2 and this last page 3. END OF THIS ACCEPTANCE ` Man 1'ersz, P.E., Product n of Examiner Prod*tjCenfrol Division 3of3 d 07/02/2003 16:34 4073301502 DIAMOND GLASS CO PAGE 03 YKK AP America Inc ACCEPTANCE No.. 00-0705.Q2 APPROVED AUG 0 9 2000 EXPIRES August 07.2003 I. SCOPE 1.1 This renews the Notice of Acceptance No, 96-1029.05, which was issued on August 07 1997, It approves an aluminum flush glazed storefront system, as described in Section 2 of this Notice of Acceptance, designed to comply with the South Florida Building Code, 1994 Edition for Miami - Dade County, for the locations when the pressure requirements, as determined by SFBC Chapter 23, do not exceed the Design Pressure Rating values indicated in the approved drawings. 2. PRODUCT DESCRIPTION 2.1 The Series "YES 43 FS" Aluminum Flush Glazed Storefront System and its components shall be constructed in strict compliance with the following documents: Drawing No. SrBC110, Sheets 1 and 2 of 2, titled "YES 451~S," prepared by Tilteco Inc., dated on September 18, 1996, revised on June 13, 1997, signed and sealed by Walter A Tillit Jr., P.E., bearing the Miami -Dade County Product Control Approval stamp with the Notice of Acceptance number and approval date by the Miami -Dade County Product Control Division. These documents shall hereinafter be referred to as the approved drawings. 3. LUMTATIONS 3.1 This approval applies to single unit applications and multiple lites applications, as long as panel size does not exceed the one tested and intermediate mullions are used between all panels, as shown in the approved drawings. 4. INSTALLATION 4.1 The aluminum flush glazed storefront system, and its components shall be installed in strict compliance with the approved drawings. 4.2 The installation of this product will reggir a hurricane protection system S. LABELING 5.1 Each panel shall bear a permanent label with the manufacturer's name or logo, city, state and following statement: "Miami -Dade County Product Control Approved". 6. BUILDING PERMIT REQUIREMENTS 6.1 Application for building permit shall be accompanied by copies of the following: 6.11 This Notice of Aceeptanm 01 6.1.2 Duplicate copies of the approved drawings, as identified in Section 2 of this Notice of Acceptance, clearly marked to show the components selected for the proposed installation. 6.1.3 Any other documents required by the Building Official or the South Florida Building Code (SFBC) in order to properly evaluate the installation of this syst Man e1 Perez, P.E., Pro du ntrol Examiner Prod ntrol Division 2 of 3 Z 3/4" 17" 1 17' y 7 j 4• _2 3 4 17, 17" 2 3 4' 3 3/4' 17' 17" S 7' 1 T °. 3J4- - � q q 4 WAX. t p (FLUS8 ®� I T _ I O- -O C� ' t ♦ O -6 G. - --0 o-- / \l -4 "- n o n STAWD PUSN/PULLPUSH/PULL PkfiHULL 1_3/4� - aE 30 3/8- O.LO. i 30 3/e' D.LO. 3fl/}/B' D10. 2 2 . r S �/ �- i 4- 14• g 3 •' S 3/4' 14' 145 3/4- 5 3 4' y 14' t 4' 8' I. 1 4- 1 a' S 3 4' WX sUVI MNf. 3 3/i 3' I -3 E 3/4- 'n- O.O.w. 1 3/4' S 3 4' 6'-0' D.O.W. 0—) l 3J+' (MAX) {►4lX} 3/E1' 3'-3 1/2- VADEE 3la" 3/e' 3'-3 t ' wl® 3/8' 3/8- - s'-� t/2' wIOE 3/5' RHR LHR A). p3jamoVs SWGLE ➢0025 ®MICI%L MXVATION PAR OF DOORS ScAm i/2' ' E'-4' SC,l x: ALL -SIZES NOTED ARE MAXIMUW SIZES: SIZES SMALLER IN WIDTH U HEIGHT ARE PERMITTED. CAULK JOINTS AND SHIM SPACE- MAX. 1/4" (FOP, TOP) MAX. 3/8" (FOR VERT.) tEcuo O1 0 3/16- FW.Lf TuApm CUSS 0ICH3R — — —0 - L IfI.D: JAT6 Y'JLLEBN ANCHOR t 114 x ] 1/4' I FRTWO.4 mx ,/i x 3 3l4itt 17WCGYT 400R PARTS USI PEA! LEAF Dom ttP£5 Tr PAW DES>rRlP1EON P I 11-�?O+SI Ptr� P�J.TE----I- 5 �� P- -W-4 ._ --__- -Q- -. - PANIC t Et�307s, 80TTCU Plm_ ------ _ -a- I E7-(iSTa TOP ficy. 2 33E iL--BOITSr-LALur-�CL ' t P-2103 H00K P-:iz % CT NDER --.�- 2 P501 • CTUNDFR Ffgli fRNC- t P_333_ - I P-2362 EAT DB.ME 2 t E9 S+G ACTTVE' O O & INQF79 OF ORAYANGS 2 1NFT�TP.AIION IS �EEEDE4 ERE WATER INFIETRATION REOCFIREhI£kT IS NOi NE£DEPPROVED Effirrin +55 PSFPPRWEO -� P� FRAME PARTS U3T PER 's£1J' DOOR TYPES IY P n0" SLwGYRO P i i t-11.m BOT7.1Q4 ioffz---__a— ES -a301 AQ1T017 PIM1cyT t 1 303 T AMCi -Q- t El 319 F1' H & 'f E iFOR PAIR HOTES:m SEUCIMN PART (SEL.W ANCHC NUU80 CAMV) 5,5 7. Rt'1OM As Oo mW rrm TYi DAIL fj€DR(; MIE U3�aAw . In ,to mm BUkim []>Tf CflYHN11GE 0"if7.E rx Aa At�oBu we x5o axtrtr as.[ A1UMA. 307.7! wr I ioe ooa w. 91N m� woEx OF aur+c a ooaa ItLY,7 ojwcaw an FABR4 rw� A,� 2a B I f En - A m v W GJ m N R CTI m N d D 0 Z t7 t D 1 cn Lo C) 0 i I .D D a) m m N zi t 1 3/4- �" -(DJACMK LEAP) iAMIE LEA;) DII tEYICE P-21c" i fT DEHC£ P-y3�7 z oa P-2 ---I i ao N/ PANIC PULL a WJ SSg. P9JLL W PANIC PULL / \ Q I� o ♦ o .O.W. 7 3 c" t 3Ja' FI 3'-0' O.O.W. [ I /�" ) 3/4' I 6"-G' O O.Yi. [iuuci I t 3/4' ( ) C>,ux ) ttt Ri�yAT[atSG - SINGLE 1100F ELZyAIImL - PA[R OF DOOR5 SC=: I/2" - 1'-0" sCUJ?: 1/2' - 1'-0- . I 'EXIT M bIT OCWE v P-236Z� W/ 51U. P1A.1 z / P-Z362 YYJ PAfAC P 2 P-ZZ 3� W/ 51'p,t t 0 c o o q c THE (ACTNE LEAF) c I � I 3 \ { l z ! x 1 � 1 S-0" O.O.W. t Ve i Ve I 3'-0' O.o W. II t 3/4" t 3/4" 6'-O" O.O.W. (MAX) (MAX) (VAX) $LR A.W. - SINGLE ELEVATURT - PAIR flF QQGR ,DOORS SCAM. I/2' - 1'-0' SCALE: 1/2' - ROPE: ANCHOR SPAC41G. DESIGN PRESSUAE, CAU'LH JOINT 00 SNIM SPACE, OVERALL 9ZE, AND DAYLIGHT OPENING {PANEQ; SAME AS SKEET 1. iir 1 < . 3J16" Fl;1Y TEWPER GU55 i xFFliOrk'] 15 Qy1RnRt YSfN lk@ Sam W M 00E fgTF v�a�a 2o4• e _ _ mlicrc�+frs srvso" I eIkDIMQ CODE cmrv� Off f ac wwcE mr._00-O 7 VM IILI CIOiUKV U41E 3(ri auvR .� sras �.., may surmall o.� 6II my C lL9 malt tl/171N 7 � d m m w cs n N m uO m m m r— m v r In �D ' m m m CV \ CV m m i!-97M OrDOIYI DETAiI � t/2 9CNt 3It Fw CWAX1 ® Rgp,ftAln3 5DPPW ft-tDO� - i t/7tc at� NCN4! �Nf'f' uut �xo vc �artr � � --Tar FK TNf0e1 tl-4421 wm uw DET t ® l MI 23p I DETAIL h o�xof cru o h 1/2 s"" f� p sro DETAIL Z n� 11mwuw 1 va- atemurw AT AU MUM F1STDAM umms OT$RnSE WED a—Ds�s /u s 1 .7/C i16O3(My % t/.a,/rMTuc� �. ssa s �/4' twow-MT DEW& 4 I/i uui 2O0 DOOR 7 i :ycsc i 21ODIs SOD c v m w a IL i` Ll7 �6 m m m 04 I CV m m 1 .,rr I FLUSH BOLT 0 HEAD DUAIL B in su+t I A. FLUSH BOLT O THRESHHOW OE ,11L 7 3/2 A.Vt a i ' TYPICAL ELEVOON — PAIR OF DOORS SCALE: 1 /2" 1' — O' R m w d n N m In CD m m 1` m v m i M m m j LV N 0 t � m t f 4 r/m, a� SPACE (W* CE z 4-0' (LOAX.} 4'--D' 4'-0- (UAk) 4'--0- (MAX.) 7_3/4' 1 3!a' 4 -0" (IUVL.} ® TYPICAL ELUATION SCALE: 1/2" = 1'-D" DESIGN PRESSURE _ +55 PSF, -65 PSF 96-1029.05 F Y (W� \ L M is -APLYM Wa 1, �`Aa' ae1t. i m 1ss 1 vim am m i 9 gvml r SM-DOW atr� aria t N m un +--I m m m N m v (M tD r-I m m CV I N m m � s n m cR 1/a a' vrml 1 114 > f DO sm AkL > a�v�--1-- sOYi ,/2 2 Fk&" 1. 1/4' SMOLEMf .� AT AIL AWCHW f71S11ENETC$ o so2s UNLEZ OTHERwSE wTEO EACH 1Ode O DETAIL �c fn 3 2 11r roMMS(o* OR ! SIO rwmr , 1 fa• CUMMO, sn ® 1/4•Ai wft Wood Mo r+aasRr ,aw [ r o -+� - 2 "r sa. A SOWN P.N. DE M sm" 1/2 SA DE7A1 ! SB 1pEE +/ � vr 'mow wwx {IKJ OCTAIL st4c ,p ++rwvv a oscrn�s IRiT! TIE $MR —1 :-5rgA!�_ ftmnv a uf• 62-0,70 oz. 1Fsws !r sIONOVD r seam" w hwvmm("-t*) 7RCI,0 A ■ LI>i E R G Y EF'FINCY CODE FOR BUILDING CONS Florida Department of, Commur ity Affairs EnergyGauge FlaCom v1.22 FORM 40OA-2001 Whole Building Performance lMethod for Commercial Buildings Jurisdiction: SANFORD. SEMINOLE COUNTY, rL (691500) Short Desc: Owner: Corp Arpt Hangers Southeast Ramp Hanger Development, Inc. Protect. Phase l A T-Hangers, Corporate and Address: Colun, Orlando Sanford Airport City: Sanford State: Florida PermitNo: 0 Zip: 0 Storeys: .1 TYPe: Office (Business) GrossArea: 8965 Class: New Finished building Net Area: 896 Max ronnage: 3 (if different, ,<`rite in) J!"Component Compliance Summary Design Criteria Result Cross Energy Use _--- 0751.07 Other Envelope Requirements - A 100.00 PASSES - PASSES LIGHTING CONITRO:S EXTERNAL LIGHTING PASSES IiVAC SYSTEM PASSES PLANT PASSES WATER HEATING SYSTETvIS PASSES PIPING SYSTEMS PASSES Met all required cOmpliance from Check List? Not Checked Yes/No/NA --INIPOR TANT NOTE. An input report.Print out from Energy Gauge p'laCon, o j. this design building must be sub"witted along tuitlr this CoMpliance _Report I hereby certify that the plans and Review of the plans and specifications covered by this specifications CO'Vered by this calculation calculation indicates compliance with the Florida Energy are in compliance with the Florida Energy Code. Before construction is completed, this building will be Efficiency Code. inspected for compliance in accordance with Section 553, 908, F.S. PREPARED BY: James A Sum �d BUILDING € FFICIAL: DATE: DATE: i hereby, ceiVy th ,his building is in compliance with the Florda Energy Effici cy Code. OWNER AGEl�'T'' 03. If. required_ by Florida law, I hereby certify (*} that the system design is in compliance with the Florida Energy Code. REGISTRATION No. ARCHITECT: ELECTRICAL SYSTEM DESIGNER LIGHTING SYSTEM DESIGNER: MECHANICAL SYSTEM DESIGNER: PLUMBING SYSTEM DESIGNER: f (*) Signature is required where Florida Law requires design to be performed by registered design professionals. Typed names and registration numbers may be used where all relevant information is contained on signed/sealed Plans. Project: Corp Arpt Dangers Title: Phase 1A T-Dangers, Corporate and Comm Ty e: Office f Rissiness) )Location: SANFORD, SEM HOLE COUNTY, FL (5915i1�) f Whole Building Compliance eaSP.r9 E LECTRNCBTY 51.07 100.O0 11.56 E t t .. C E :.,w " �.,:: ,: i 13.70 26.12 a v li 4.01 15.36 t t - �Credits & Penalties (ir;' any): N[odafied Points: = 51.08 ---- -- .. Project: Corp Arpt Bangers — ----1 Title: Phase 1A T-Hangers, Corporate and Comm Type: Office (Business) Location.: SANFOR D. SEMINOLE COUNTY,FL (69150()) External Lighting Compliance (Description Category Allowance Area or Length ELPA CLP (W Unit) or No. of Units (W) {� (Sgft or ft) Ext Light I Entrance (iv/ Canopy) High 10.00 144.0 1.440 500 traffic -retail, hotel, airport_ theatre etc Ext Light 2 Public drivewayslu-alk- vat's 0.15 2.400.0 360 1_050 Design: 1550 (W) PASSES�� Allowance: 1800 (W) Project: Corp Arpt Hangers Title- Phase I T-Hangers, Corporate and Comm Type: Office (Business) ll Location: SANFOR D, SEMINOLE COUNTY, FL (691500) Lighting Controls Compliance Acronym Ashrae lDeserintion Area No. of Design Min Compli- IO (sq.ft) Tasks CP CP ance Lobby 21 Lobby (General) - Reception and 238 1 2 2 PASSES Waiting Toilets 13 Toilet and Washroom 61 1 3 3 PASSES Break Room 9 Food Senlce -Kitchen itchen 187 1 4 4 PASSES Offices 28 Offices (Partitions>4.5 ft below .729 1 2 2 PASSES ceiling) Enclosed offices, all open ;plan offices without partitions Hangers 47 Storage & Warehouse - Material 7.442 1 2 2 PASSES handling 'ASSES Project: Corp Arpt Hangers T' Title: Phase 1A T-Hangers, Corporate and Comin Type: Office. (Busiacss) Location: SANFORD, SEMINOLE COUNTY, FL (691500) System Report Compliance A/C-1 System 1 Constant Volume Air Cooled No. of Units Split System < 65000 Btu/hr 1 Component Category Capacity Design Eff Design IPLV Comp- Eff Criteria IPLV Criteria liance Cooling System Air Cooled < 65000 Btu'h Cooling Capacity. 10.00 10.00 10.00 PASSES Air Handling Air Handler (Supple) - System -Supply Constant Volume 021 0.80 PASSES } PASSES Plant Compliance Description installed Size Design Min No Eff Eff Design Min Category Comp iP'LV YPLV fiance None Project: Corn Arpt Rangers Titie: Phase 1 A T-Hangers, Corporate and Comm Type: Office (Business) Piping System Compliance Category Pipe Dia Is Operating Ins Cond Ins Req Ins Complian [inchesl Runout? Temp [Btu-in/hr Thick [in] Thick [in] M SF.Fj Domestic and Service Hot Water Systcnns 0.75 False 11.5.00 0.23 1.00 0.93 PASSES Cooling Systems (Chilled Water, Brine and Refrigerant) 0.5(? False 135.0C► 0.�3 Ci 7; � - 1.50 Not Check, s Lot Checked Project: Corp Arpt Hangers Title: Phase IA T-Hangers, Corporate and Comma Type: Office (Business) Other Required Compliance Category Section Requirement (write N/A in bog if not applicable) Cheek Infiltration 4OE.1 Infiltration Criteria have been met �System 407. 3 HtiAC Load sizing has beer.. performed Li El � Ventilation 409.1 Ventilation criteria have been met M ADS 410.1 Duct sizing and Design have been performed !� T & I3 410.1 Testing and Balancing n-vill be performed Electrical 413.1 Metering criteria have been met Motors 414.1 Motor eff`iciencv criteria have been met Lighting 415.1 Lighting ch g criteria have been met O & .M 102.1. Operation/maintenance-manual will be prmided to owner Root/Ceil 404.1 R-19 for Roof Deck with supplypirleanns beneath it _ Report 301 l� Input Repoli Print-CAat from.. Energy Casa�,v p �l- EnergyGauge F1aCoan attache9d: � �+ t ENERGY' EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department Of Community Affairs EnergyGauge FlaCom vl..22 INPUT DATA REPORT troJect Information Project Name: Corp Arpt Hangers Orientation: West Project Title: Phase IA T-1-fangers, , Corporate and Coml,11, Building Type: Office (Business) Address: Orlando Sanford Airport Building Classification: New Finished building State: Florida No.of Storeys: 'I zip: 0 GrossArea: 8965 Owner: Southeast Ramp Hanger Developme No Acronym Description I UnIces Zone I Type Load Profile Area Multiplier Total Area 1sfJ Isf] CONDITIONED Uses Building Load 8964.7 I. 8964.7 Profile 6/15/03 EnergyGauge Fla,Corn FLCCSB v1.22 1 Spaces No Acronym Description Type Depth Width Height MUIT Total Area Total Volume IN Ift] Ift] Mier [so In Zone: Offices I I Lobbv zoospl. Lobby (General) - Reception 17.00 14.00 MOO 1 238.0 2380.0 and Waiting 2 Toilets Zo0Sp2 Toilet and Washroom 11.00 5.50 10.00 3 181.5 1815.0 3 Break Room Zo0Sp3 Food Service - Kitchen, 17.00 11.00 10,00 2 374.0 3740.0 4 Offices Z()()sp4 Offices (Partitioris>4.5 ft 41.68 17.50 10.00 1 729.4 7294.0 below ceiling) Enclosed offices, all open plan offices without partitions 5 Hangers Zo0Sp5 Storage & Warehouse - 124.03 60,00 16.00 1 7441.8 119068.8 Material Handling Lighting No Type Power Control Type No.of IWI Ctrl pts In Zone: Offices In Space: Lobby 'I Recessed Fluorescent - No vent 210.00 Manual On On/Off I El 2 Compact Fluorescent 17.00 Manual On/Off I E] In Space: Toilets I Compact Fluorescent 34.00 Exception for One fixture or I El In Space: Break Room ballast i Recessed Fluorescent - No vent 210.00 Manual ai/Off 2 In Space: Offices I Compact Fluorescent 630.00 Manual On/Off 2 In Space: Hangers 6/15/03 EnergyGauge FlaCom FLCCSB v1.22 2 i. Metal Halide 3200.00 Exception for Area used as a 2 ❑ Whole Walls No Description Type Width H (Effec) Multi Area DirectionConductance Beat Dens. R-Value [ft) [ft] plier, 1811 [Btu/hr. sf. F1 Capacity [lb/cf] jb.sLF/Btuj [Btu/sf. Fj In Zone: Offices I Pr0ZoIWaI Metal 17.50 1.0,00 1. 175.0 North 0.0957 0.7570 16.80 10.4-5 s iding/R 1.1. 13att/0. 5" Gyp 2 Pr0ZOI Wag Metal 73.50 10.00 1 735.0 West 0.0957 0,7570 16.80 1.0.45 p siding/R1 lBattJO.S" Gyp 3 Pr0ZoIWa3 Metal 73.50 14.00 1. 1029.0 North 0.0957 0,7570 16.80 1.0,45 siding/R11 Batt/0. ill Gyp Windows No Description Type Shaded UCen SC Vis.Tr W H (Effec) Multi Total Arca [Btu/hr sf F] [ft) [ftj plier [gg) In 'Lane, Offices In Wall West 1 Pr0Zo 1. Wa2 Wi I SINGLE CLEAR No 1.0018 0,95 0.88 4.00 4.00 4 64.0 El Doors No Description Type Shaded! Width. H (El ffec) Multi Area Cond. Dens. Heat Cap. R-Value IN [ft] plier [sf) [Btu/hr. A F1 [ib/cf] [Btu/sE F] [h.sLF/Btu1 In Zone: Offices ---- In Wall: West 1. Pr0Zol Wa2Dr1. Solid core flush No 3.00 6.66 2 20.0 0.5834 0.00 0.00 1.71 [] In Wall: Interior Partition 6/15/03 EnergyGauge FlaCom FLCCSB v.1-22 3 I PrOZol Wa3Drl Panel with 7/1.6" No 3.00 6.66 1 20.0 1.1057 0.00 0.00 0.90 panels Roofs No Description Type Width If (Effec) Multi Area Tilt Cond. Heat Cap (lens. R-Value s [ft1 [ft1 plier [sf] [deg] [Btu/hr. Sf. F1 [Btu/sf. F1 [lb/cfj [h.sf.F/Btuj In zonc: Offices l PrOZolltfl Mtl Bldg RoofIR-19 17.50 73,43 1 1285.0 0.00 0.0492 1.34 9.49 20.34 0 Batt � Nights . 9 No Description TYPe UCen Shading Vis.Tran W fi (Effec) Multiplier Area Total Area [Btu/hr sf F1 Coeff [Dj [ft.] [s [S I In Zone: In Roof: i Floors No Description Type Width H(Effec) Multi Area Cond. Heat Cap. hens. It -Value [ft] [ft] plier [st7 [Btu/hr. sf. F] [Btu/sf. F1 jib/cf] [h.sf.F/Btu1 In Zone: Offices l PrOZolrll Underground wall 1.7.50 73.43 1 1255.0 3.1233 9.33 140.00 0.32 171 6/15/03 EnergyOauge F1aCom FILCCSB vl.22_ 4 A/C-1. System I� Y Constant Volume .Air Cooled Split Pdo. Of Units i System < 65000 Btu/hr I Component Cat ory Capacity Efficiency IPLV 1 Cooling System. (Air Cooled < 65000 .Btu/h. Cooling 36000.00 10.00 10.00 Capacity) 2 Air Handling System -Supply (Air Handler (Supply) - 1200.00 0.21 El Constant Volume) Plant Equipment Category Size Inst.No Eff. IPLV Water Heaters W-Ileater,Description Capacit Cap.Unit I/P Rt. Efficienc Loss 1 Storage Water Heater - Electric 40 Gal 9 [kW] 0.8900 [EF] [%/hr] [� Ext-Lighting • Description Categories. Area/Len/No. of units Wattage [sf/ft/No) [w] I Ext Light 1 Entrance (w/ Canopy) High 144.00 500.00 (� traffic -retail, hotel, airport, theatre etc 2 Ext Light 2 Public drivewayshvalkways 2400.00 1050.00 [� Piping .No Type Operating Insulation Nomonal pipe Insulation Is Itunout? Temperature Conductivity Diameter Thickness IF] f Btu-in/h.sf.F] fin] [in] I 1 Domestic and Service Hot Water Systems 115.00 0.23 0.75 1.00 No Cj I 6/1.5/03 EnergyGauge FlaCom FLCCSB v1.22 5 2 Cooling Systems (Chilled Water, Brine and 1,35.00 0.23 0.50 Fenestration Used 0.75 No ❑ 0 Name Glass Type No. of Grass SC VLT Frame Frame Panes Conductance Conductance Absorptance [13tu/h.sf Fj [Btu/h.sf.F] ApLbWndl. SINGLE CLEAR 1 1.0018 0.9500 0.8810 0.4340 0.7000 ❑ Materials Used Mat No Acronym Description Only R-Value RValue Thickness Conductivity Density SpecificHea Used [h.sf.F/Btu] IN [l3tu/h.ful [lb/ctj t 18 Mat118 2 in. Wood No 264 Mat1264 ALUMINUM; 1/16IN No 214 Mat1214 POLYSTYRENE, EXP., No 1-1/41N. 187 Mat11.87 GYP OR PLA.S No BOARD,1/2IN 206 Ma11206 CELLULOSE,FILL,5.5IN R- No 20 15.1 Mad 1.51 CONC HW, DRD, 1401,13, No 4IN 1.78 Mat] 1.78 CARPET W/RUBBER PAD Yes ?65 Mat1265 Soil, 1 It No 48 Matl48 6 in- Heavyweight concrete No 123 MatI123 CONC BLOCK No MW,8IN,HOLLOW 159 Mall1.59 CONC No HW-UND.RD-140LB-41N 57 Matl57 3/4 in. Plaster or gypsum No 6/15/03 2.3857 , 0.1670 0.0700 37.00 0.3900 0.0002 0.0050 26.0000 480.00 0.1000 ❑ 5.2100 0.1042 0,0200 1.80 0.2900 ❑ 0.4533 0.0417 0.0920 50.00 0,2.000 ❑ 20,8318 0.4583 0.0220 3.00 0.3300 ❑ 0.4403 0.3333 0.7570 140.00 0.2000 ❑ 1.2300 2.0000 1.0000 0,5000 100.00 0.2000 ❑ 0.5000 0.5000 1,0000 140.00 0.2000 ❑ 1.7227 0.6667 0.3870 53.00 0.2000 ED 0.3202 0.3333 1.041.0 140.00 0.2000 ❑ 0,1488 0,0625 0.4200 100.00 0.2000 ❑ 1EnergyGauge FlaCom FLCCSB v1.22 6 72 Mat172 AIR LAYER; 3/41N OR Yes 0.9000 LESS, VERT, WALLS 267 Ma11267 0.75" stucco No 0.1563 266 Mat1266 2x4(u16" oc + RI1 Batt. No 8.3343 215 Mat1215 POLYSTYRENE, EXR, No 8.3350 2IN, 105 Mat1105 CONC BLK: HW, 8IN, No 1.1002 HOLLOW 256 Mat1256 WOOD, SOFT, 1-1/2IN No 1.9939 268 Matl268 0.625" stucco No 0.1302 42 Matl42 8 in. Lightweight concrete No 2.0212 block 269 Mat1269 .75" ISO BTWN24" oc No 2.2321 86 Matl86 BRICK:, COMMON, 4IN No 0.8012 211 Mat121,1 POLYSTYRENE,EXPJ/21 No 2.0850 N 12 Matf 12 3 in. Insulation No 10.0000 218 Mat1.218 POLY-URETHANE,E1eP.,1/2 No 3.2077 IN, 23 Mat123 6 in. Insulation No 20.0000 4 Matl4 Steel siding No 0.0002 27.1 Mat1271 2x4L24" oc + RI i Batt No 10.4179 272 Mat1272 Panel with 7/16" panels Yes 0.9044 273 Mat1273 Hollow core flush (1.375") Yes 1.2777 274 Matl274 Solid core flush (1.375") Yes 1.7141 275 Mdat1275 Panel with 7/16" panels Yes 1.0019 (1.375") 276 M:at1276 Hollow core Rush (1.75") Yes 1.3239 277 Mat1277 Panel with 1-1/8" panels Yes 1..7141 (1.75") 278 Matl278 Solid core flush (1.75") Yes 1.6500 279 Mat1279 Solid core flush (2.25") Yes 2.8537 280 Mat1280 Fiberglass/Mineral wool core Yes 0.8167 281 M:at1281, Paper Honeycomb core Yes 0.9357 282 Matl282 Solid Urethane foam core Yes 1.6500 283 Ma11283 Solid mineral fiberboard core Yes 1.781.6 284 Mat1284 Polystyrene core (18 ga steel) Yes 2.0071 1 F9 0.0625 0.4000 1.6.00 0.2000 ❑ 0.2917 0.0350 9.70 0.2000 ❑ 0.1667 0.0200 1.80 0.2900 ❑ 0.6667 0,6060 69.00 0.2000 ❑ 0.1250 0.0660 32.00 0.3300 ❑ 0.0521 0.4000 16.00 0,2000 ❑ 0.6670 0.3300 38.00 0.2000 E] 0.0625 0.0280 4.19 0.3000 0 0.3333 0.4160 .120.00 0.2000 El 0.0417 0.0200 1.80 0.2900 ❑ 0.2500 0.0250 2.00 0.2000 0 0.0417 0.0130 1.50 0.3800 1:1 0.5000 0.0250 5.70 0.2000 ❑] 0.0050 26.0000 480.00 0.1000 ❑ 0.2917 0.0280 7.11. 0.2000 ❑ U Ell 6/15/03 EnergvGauge FlaCom FLCCSB v1.22 7 �o:� iviat;�a rotiurethane core (18 ga 'sres 2.5983 steel) 2 286 Mat1.286 Polyurethane core (24 ga Yes 2.5983 steel) 1 287 Mat1287 Polyurethane core (24 ga Yes 4.1.500 steel) 2 288 Mat1288 Solid Urethane foam core Yes 4.1500 81. Matl81 ASPHALT-l"XING, Yes 0.1500 ROLL 244 Mat1244 PLYWOOD, 1/21N No 0.6318 185 Mat] 185 CLAY TILE, PAVER, 3/81:N No 0.0301. 82 MatI82 ASPHALT -SHINGLE .AND Yes 0.4400 SIDING 1.1 Mail11. 2 in. Insulation No 6.6800 47 Matl47 2 in. Heavyweight concrete No 0.1,670 95 Matl95 CONC BLOCK No 0.7107 H W-41N-HG.LLOW 248 Mat1248 ROOF GRAVEL OR No 0.0500 SLAG 1/21N 94 Mat194 BIJILT-UP ROOFING, No 0.3366 3/81N ! ii FR I 0.0417 0.0660 34.00 0.2900 [� 0.0313 1.0410 120.00 0.2000 �.7 0.1670 0.0250 2..00 0,2000 0.1.670 1.0000 140.00 0.2000 [� 0.3333 0.4690 101.00 0.2000 L] 0.0417 0.8340 55.00 0.4000 E] 0.0313 0.0930 70.00 0.3500 m No Name Simple Massless Conductance heat Capacity ]Density RValue Construct Construct [Btu/h.sf.1F] [Btu/sf.F] [lb/cf] [h.sEF/Btu] 1.007 Underground wall in basement, 4 in. h.tiw, No No 3.12 9.33 140.00 0.3202 cone . Layer Material Material Thickness Framing Ito, [ftj Factor 1 159 CONIC HW-U-NDRD-.140LB-4IN 0.3333 0.00 6/13/03 El nergyGauge FlaCom FLCCSB `•1.22 8 No Name Simple Massless Conductance Meat Capacity Density . RValue _ Construct Construct [Btu/h.sf.Fj []Btu/sLF] [ib/cf] (h.sf.F/Btuj 1020 Metal siding/R1lBatt/0.5"Gyp No No 0.10 0.76 1.6.80 .10.4535 [] Layer Material Material No, 1 4 Steel siding 2 12 3 in. Insulation 3 187 GYP OR PLAS BOARD, Thickness Framing; IN Factor 0.0050 0.00 0,2500 0.00 0.0417 0.00 ❑ No Dame Simple Massless -Conductance Heat Capacity Density 1SValue Construct Construct lBtu/h.st:Fj lBtu/si:14-1 [ib/cfj lh.sf.F/Btuj 1021 Panel with 7/16" panels No Yes 1. l 1 0.9044 .Layer Material Material Thickness Framing No. IN Factor 1 272 Panel Nvith 7/16" panels 0.00 No Name Simple Massless Conductance .Heat Capacity Density 12Value — C211struct Construct lBtt►/h.sf.Fj [Btu/st:F'j [lb/cfj lh.sf.FllBtu) 1023 Solid core flush No Yes 0.58 1.7141 C/ l 5/03 La yer Material Material "Thickness Framing No. lftj Factor 1 274 Solid core flush (1.375°j 0.00 EnergyGauge F1aCom FLCCSB V1.22 w 91 No Name Simple Density RValue Massless Conductance Heat Capacity Construct Construct [Btu/h.sf.F] [Btu/s1:F] [lb/cf] [h.sf.F/Btuj I047 . Mtl Bldg Roof/R-I9 Bait No No 0.05 L34 9.49 20,3366 A � I Layer Material Material ~� Thicimess Framing No. [ft] Factor 1 94 BUILT-UP ROOFING, 3/8W 0.0313 0.00 ' I 2 23 6 in. Insulation 0.5000 0,00 6/15/03 EnergyGauge FlaCom JF.LCCSB ,,,1.22 1.0 i I