James A Whittum, P.E.
FL # 27689
A 8533 Acorn Ridge Court
Tampa, FL 33625
813-926-9719, Fax 813-920-1257.
June 27, 2003
Ken Gordon, Aero Door
2036 Apex Ct.
Apopka, FL 32703
Subject: HydroSwing Door
I have reviewed the design #8314-2D by Cottonwood Welding and
Manufacturing, Inc. for the HydroSwing door to be delivered to you:
(1) 60 ft x 18 ft, nominal size, Corporate Hangar # 1
The design of the above door complies with the Florida Building Code 2001, as
amended in 2002, Chapter 1=6 for an ASCE 7-98 Basic Wind Speed of 110 MPH (3
second gust), Type Il, Enclosed. Building.
Design wind pressures for wall components and cladding provided by others shall
low
Wind Pressure, psf, @ 110 MPH (3 second gust)
Main Wall Area 6 Feet From
Corners
Eff. Area, sf
positive
negative
10 30.4
33.4
50 26.7
28.7
500 21.2
24.3
Cc: Addressee (4) copies
CWMI-via fax (1) copy
File: door 8314-2D, 6-27-03
r
positive negative
30.4 42.5
26.7 34.9
21.2 24.3
Sincerely,
a 2 7 2093
James B. Whittum, P.E.
JBW Engineering, Inc.
Quote# 8314
Ken Gordon
Asm Door
Door size W x 18!
M
Welding point
Full horizontal weld
on stub column
Mounting
angle iron
k.I
Outside of
building
)Cs mark
location of
securing
plates
Mounting angle iron
I L I
Door Jamb
Upper pinpoint
Welding point
8' on 120 off for the full
height of the door
Welding points
1 /4" steel flat iron
(width and length can vary)
Check side drawing br plate
location
Vertical
building
jamb
07/02/2003 16:34 4073301502 DIAMOND GLASS CO PAGE 01
MtAMhDA
f"
:PRODUCT QQNIROL NOTICE OF ACCEPTANCE
YKK AP America Inc.
Gwaltney Dr,
Atlanta GA. 30336
MIAM1-DADE COUNTY, FLORIDA
METRO -TRADE FLAGLER BUILDING
BUILUING CODE COMPLIANCE OFFICE
METRO-DADE FLAGLER BUII.DING
140 WEST FLAGLER STREET, SUITE 1603
MIAMI, FLOR)DA 33130-1563
(305)375-2901 FAX (305) 375-2908
CON7I U'fOR LICENSING SECTION
(305) 375-2527 FAX (305) 375.2558
CONTRACTOR ENFORCEMENT DIVISION
(305) 375-2966 FAX (305) 375.2908
PRODUCT CONTROL DIVISION
Your application for Notice of Acceptance (NOA) of; (305) 375.2902 FAX (305) 372-6339
Series "YES 45 FS" Aluminum Flush Glazed Storefront System
under Chapter 8 of the Code of Miami -Dade County governing the use of Alternate Materials and Types of
Construction, and completely described herein, has been recommended for acceptance by the Miami -Dade
County Building Code Compliance Office (BCCO) under the conditions specified herein.
This NOA shall not be valid after the expiration date stated below. BCCO reserves the right to secure this
product or material at any time from a jobsite or manufacturer's plant for quality control testing. If this
product or material fails to perform in the approved manner, BCCO may revoke, modify, or suspend the
use of such product or material immediately. BCCO reserves the right to revoke this approval, if it is
determined by HCCO that this product or material fails to meet t.hc requirements of the South Florida
Building Code.
The expense of such testing will be incurred by the manufacturer. IV�% _
ACCEPTANCE NO.: 00-0705.02 (1
EXPIRES 17/2003 Raul Rodrigue4
Chief Product Control Division
THIS IS THE COVERS ET. $EE ADDITIONAL PAGES FOR. SPECIFIC AND GENERAL.
CONDITIONS
BUILDING 10121 A f jRQRUQ[ REVIEW COMDUTIEE
This application for Product Approval has been reviewed by the BCCO and approved by the Building
Code and Product Review Committee to be used in Miami -Dade County. Florida under the conditions set
forth above.
APPROVED: 08/09/2000
11=04S00011pd00011t"lat*slnvcko ctccepmrKe opw pag.dot
gort �_i"
Francisco J. Quintana, R.A.
Director
Miami -Dade County
Building Code Compliance Office
Internet mail address: postmaster@bulidlngeodeonline.com Homepage: http://www.buildingcodeonline.com
07/02/2003 16:34
4073301502
DIAMOND GLASS CO
PAGE 02
Ti
YKk'AP America Inc, ACCEPTANCE No.: 00-0705,0Z
APPROVED AUG 0 9 2000
EXPIRES August 07,1003
NOTICE OF ACCEE][ANCE: SPECIFIC CONDITIONS
Renewal of this Acceptance (approval) shall be considered after a renewil application has been filed and the
original submitted documents, including test -supporting data, engineering documents, are no older than eight
(8) years,
2. Any and all approved products shall be permanently labeled with the manufacturer's name, city, state, and the
following statement: "Miami -Dade County Product Control Approval', or as specifically stated in the
specific conditions of this Acceptance.
3. Renewals of Acceptance will not be considered if:
a, There has been a change in the South Florida Building Code affecting the evaluation of this product
and the product is not in compliance with the code changes,
b. The product is no longer the same product (identical) as the one originally approved,
e. It the Acceptance holder has not complied with all the requirements of this acceptance, including the
correct installation of the product.
d, The engincscr who originally prepared, signed and sealed the required documentation initially
submitted, is no longer practicing the engineering profession.
4. Any revision or change in the materials, use, and/or manufacture of the product or process shall automatically
be cause for termination of this Acceptance, unless prior written approval has been requested (through the
filing of a revision application with appropriate fee) and granted by this office.
5. Any of the following shall also be grounds for removal of this Acceptance:
a, Unsatisfactory performance of this product or process.
b. Misuse of this Acceptance as an endorsement of any product, for sales, advertising or any other
purposes,
6. The Notice of Acceptance number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. It any portion of the Notice of Acceptance is
displayed, then it shall be done in its entirety.
7. A copy of this Acceptance as well as approved drawings and other documents, where it applies, shall be
provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site
at all time, The engineer need not reseal the copies,
8. Failure to comply with any section of this Acceptance shall be cause for termination and removal of
Acceptance,
9, This Notice of Acceptance consists of pages 1, 2 and this last page 3.
END OF THIS ACCEPTANCE
` Man 1'ersz, P.E., Product n of Examiner
Prod*tjCenfrol Division
3of3
d
07/02/2003 16:34 4073301502 DIAMOND GLASS CO PAGE 03
YKK AP America Inc
ACCEPTANCE No.. 00-0705.Q2
APPROVED AUG 0 9 2000
EXPIRES August 07.2003
I. SCOPE
1.1 This renews the Notice of Acceptance No, 96-1029.05, which was issued on August 07 1997, It
approves an aluminum flush glazed storefront system, as described in Section 2 of this Notice of
Acceptance, designed to comply with the South Florida Building Code, 1994 Edition for Miami -
Dade County, for the locations when the pressure requirements, as determined by SFBC Chapter
23, do not exceed the Design Pressure Rating values indicated in the approved drawings.
2. PRODUCT DESCRIPTION
2.1 The Series "YES 43 FS" Aluminum Flush Glazed Storefront System and its components shall be
constructed in strict compliance with the following documents: Drawing No. SrBC110, Sheets 1
and 2 of 2, titled "YES 451~S," prepared by Tilteco Inc., dated on September 18, 1996, revised on
June 13, 1997, signed and sealed by Walter A Tillit Jr., P.E., bearing the Miami -Dade County
Product Control Approval stamp with the Notice of Acceptance number and approval date by the
Miami -Dade County Product Control Division. These documents shall hereinafter be referred to as
the approved drawings.
3. LUMTATIONS
3.1 This approval applies to single unit applications and multiple lites applications, as long as panel size
does not exceed the one tested and intermediate mullions are used between all panels, as shown in
the approved drawings.
4. INSTALLATION
4.1 The aluminum flush glazed storefront system, and its components shall be installed in strict
compliance with the approved drawings.
4.2 The installation of this product will reggir a hurricane protection system
S. LABELING
5.1 Each panel shall bear a permanent label with the manufacturer's name or logo, city, state and
following statement: "Miami -Dade County Product Control Approved".
6. BUILDING PERMIT REQUIREMENTS
6.1 Application for building permit shall be accompanied by copies of the following:
6.11 This Notice of Aceeptanm 01
6.1.2 Duplicate copies of the approved drawings, as identified in Section 2 of this Notice of
Acceptance, clearly marked to show the components selected for the proposed installation.
6.1.3 Any other documents required by the Building Official or the South Florida Building Code
(SFBC) in order to properly evaluate the installation of this syst
Man e1 Perez, P.E., Pro du ntrol Examiner
Prod ntrol Division
2 of 3
Z 3/4" 17" 1 17'
y 7 j 4• _2 3 4
17, 17"
2 3 4'
3 3/4'
17' 17"
S 7'
1 T
°. 3J4-
- �
q q
4
WAX.
t
p
(FLUS8
®�
I T
_
I
O-
-O
C� '
t
♦
O
-6
G. -
--0
o--
/
\l
-4
"-
n
o
n
STAWD
PUSN/PULLPUSH/PULL
PkfiHULL
1_3/4�
-
aE
30 3/8- O.LO.
i
30 3/e' D.LO.
3fl/}/B' D10.
2
2
. r
S �/ �- i 4- 14• g 3 •' S 3/4' 14' 145 3/4- 5 3 4' y 14' t 4' 8' I. 1 4- 1 a' S 3 4'
WX sUVI MNf.
3 3/i 3' I -3 E 3/4- 'n- O.O.w. 1 3/4' S 3 4' 6'-0' D.O.W. 0—) l 3J+'
(MAX) {►4lX}
3/E1' 3'-3 1/2- VADEE 3la" 3/e' 3'-3 t ' wl® 3/8' 3/8-
- s'-� t/2' wIOE 3/5'
RHR LHR
A). p3jamoVs SWGLE ➢0025 ®MICI%L MXVATION PAR OF DOORS
ScAm i/2' ' E'-4' SC,l x:
ALL -SIZES NOTED ARE MAXIMUW SIZES: SIZES SMALLER IN WIDTH U HEIGHT ARE PERMITTED.
CAULK JOINTS AND SHIM SPACE- MAX. 1/4" (FOP, TOP) MAX. 3/8" (FOR VERT.)
tEcuo
O1 0 3/16- FW.Lf TuApm CUSS
0ICH3R
— — —0 - L IfI.D: JAT6 Y'JLLEBN ANCHOR t
114 x ] 1/4' I FRTWO.4 mx ,/i x 3 3l4itt 17WCGYT
400R PARTS USI PEA! LEAF
Dom ttP£5
Tr
PAW
DES>rRlP1EON
P
I
11-�?O+SI
Ptr� P�J.TE----I-
5
��
P- -W-4 ._ --__-
-Q-
-.
-
PANIC
t
Et�307s,
80TTCU Plm_ ------
_
-a-
I
E7-(iSTa
TOP ficy.
2
33E
iL--BOITSr-LALur-�CL
' t
P-2103
H00K
P-:iz
% CT NDER
--.�-
2
P501
• CTUNDFR Ffgli fRNC-
t
P_333_
-
I
P-2362
EAT DB.ME
2
t
E9
S+G ACTTVE'
O
O
& INQF79 OF ORAYANGS
2 1NFT�TP.AIION
IS �EEEDE4
ERE WATER INFIETRATION
REOCFIREhI£kT IS NOi NE£DEPPROVED
Effirrin
+55 PSFPPRWEO
-� P�
FRAME PARTS U3T PER 's£1J'
DOOR TYPES
IY
P n0"
SLwGYRO
P
i
i
t-11.m BOT7.1Q4 ioffz---__a—
ES -a301 AQ1T017 PIM1cyT t
1 303 T AMCi
-Q-
t
El 319 F1' H & 'f E iFOR PAIR
HOTES:m SEUCIMN PART (SEL.W ANCHC NUU80 CAMV)
5,5
7.
Rt'1OM As Oo mW rrm TYi
DAIL fj€DR(;
MIE U3�aAw .
In
,to mm
BUkim []>Tf CflYHN11GE 0"if7.E
rx Aa At�oBu we
x5o axtrtr as.[
A1UMA. 307.7!
wr
I
ioe ooa w.
91N
m�
woEx OF aur+c a ooaa ItLY,7
ojwcaw an FABR4
rw� A,� 2a B I
f En
- A
m
v
W
GJ
m
N
R CTI
m
N
d
D
0
Z
t7
t D
1 cn
Lo
C)
0
i
I
.D
D
a)
m
m
N
zi t
1 3/4-
�"
-(DJACMK LEAP)
iAMIE LEA;)
DII tEYICE
P-21c"
i
fT DEHC£
P-y3�7
z
oa
P-2 ---I
i
ao
N/ PANIC PULL
a
WJ SSg. P9JLL
W PANIC PULL
/
\
Q
I�
o
♦
o
.O.W.
7 3 c" t 3Ja'
FI
3'-0' O.O.W.
[ I /�" ) 3/4'
I 6"-G' O O.Yi. [iuuci
I t 3/4'
( )
C>,ux )
ttt
Ri�yAT[atSG
- SINGLE 1100F
ELZyAIImL - PA[R OF DOOR5
SC=: I/2" - 1'-0"
sCUJ?: 1/2' - 1'-0- .
I
'EXIT
M
bIT OCWE
v
P-236Z�
W/ 51U. P1A.1
z
/ P-Z362
YYJ PAfAC P
2
P-ZZ 3�
W/ 51'p,t
t
0
c
o
o
q
c
THE
(ACTNE LEAF)
c
I
�
I
3 \
{
l
z
!
x
1
�
1
S-0" O.O.W.
t Ve i Ve
I 3'-0' O.o W.
II t 3/4" t 3/4"
6'-O" O.O.W. (MAX)
(MAX)
(VAX)
$LR
A.W. - SINGLE
ELEVATURT - PAIR flF QQGR
,DOORS
SCAM. I/2' - 1'-0'
SCALE: 1/2' -
ROPE: ANCHOR SPAC41G. DESIGN PRESSUAE,
CAU'LH JOINT 00 SNIM SPACE, OVERALL 9ZE, AND DAYLIGHT OPENING {PANEQ; SAME AS SKEET 1.
iir 1
< . 3J16" Fl;1Y TEWPER GU55 i
xFFliOrk'] 15 Qy1RnRt YSfN lk@
Sam W M 00E
fgTF v�a�a 2o4•
e _ _
mlicrc�+frs srvso" I
eIkDIMQ CODE cmrv� Off f
ac wwcE mr._00-O 7
VM
IILI CIOiUKV U41E
3(ri auvR .�
sras
�.., may surmall
o.� 6II
my C
lL9 malt tl/171N 7 � d
m
m
w
cs
n
N
m
uO
m
m
m
r—
m
v
r
In
�D
' m
m
m
CV
\
CV
m
m
i!-97M
OrDOIYI
DETAiI �
t/2 9CNt
3It Fw
CWAX1
® Rgp,ftAln3
5DPPW
ft-tDO� - i t/7tc at�
NCN4! �Nf'f'
uut �xo vc �artr
� �
--Tar
FK TNf0e1 tl-4421
wm uw
DET t
® l MI 23p
I DETAIL h o�xof
cru o h 1/2 s""
f� p sro
DETAIL Z
n�
11mwuw 1 va- atemurw
AT AU MUM F1STDAM
umms OT$RnSE WED a—Ds�s
/u s 1 .7/C i16O3(My %
t/.a,/rMTuc� �.
ssa s �/4' twow-MT
DEW& 4
I/i uui
2O0 DOOR 7 i
:ycsc i
21ODIs
SOD c
v
m
w
a
IL
i`
Ll7
�6
m
m
m
04
I CV
m
m
1 .,rr I
FLUSH BOLT 0 HEAD
DUAIL B
in su+t
I A.
FLUSH BOLT O THRESHHOW
OE ,11L 7
3/2 A.Vt
a i '
TYPICAL ELEVOON — PAIR OF DOORS
SCALE: 1 /2" 1' — O'
R m
w
d
n
N
m
In
CD
m
m
1`
m
v
m
i
M
m
m
j LV
N
0
t �
m
t
f
4 r/m,
a�
SPACE (W*
CE
z 4-0' (LOAX.} 4'--D' 4'-0- (UAk) 4'--0- (MAX.)
7_3/4' 1 3!a' 4 -0" (IUVL.}
® TYPICAL ELUATION
SCALE: 1/2" = 1'-D"
DESIGN PRESSURE _ +55 PSF, -65 PSF
96-1029.05
F Y (W�
\ L
M
is -APLYM Wa 1, �`Aa' ae1t.
i
m 1ss 1
vim am
m i
9 gvml r SM-DOW atr�
aria t
N
m
un
+--I
m
m
m
N
m
v
(M
tD
r-I
m
m
CV
I N
m
m
� s
n m
cR 1/a a' vrml
1 114 > f
DO
sm AkL >
a�v�--1--
sOYi ,/2 2
Fk&" 1. 1/4' SMOLEMf
.� AT AIL AWCHW f71S11ENETC$
o so2s UNLEZ OTHERwSE wTEO
EACH 1Ode
O
DETAIL
�c fn 3
2 11r roMMS(o* OR
! SIO rwmr , 1 fa• CUMMO,
sn
® 1/4•Ai wft Wood
Mo r+aasRr
,aw
[ r o -+� - 2 "r sa. A
SOWN
P.N.
DE M
sm" 1/2 SA
DE7A1 ! SB
1pEE +/
� vr
'mow wwx {IKJ
OCTAIL
st4c ,p
++rwvv a oscrn�s IRiT! TIE
$MR —1
:-5rgA!�_
ftmnv a uf• 62-0,70 oz.
1Fsws
!r
sIONOVD r seam"
w hwvmm("-t*)
7RCI,0 A
■
LI>i E R G Y EF'FINCY CODE FOR BUILDING CONS
Florida Department of, Commur ity Affairs
EnergyGauge FlaCom v1.22 FORM 40OA-2001
Whole Building Performance lMethod for Commercial Buildings
Jurisdiction:
SANFORD. SEMINOLE COUNTY, rL (691500)
Short Desc:
Owner:
Corp Arpt Hangers
Southeast Ramp Hanger
Development, Inc. Protect. Phase l A T-Hangers, Corporate and
Address:
Colun,
Orlando Sanford Airport
City:
Sanford
State:
Florida
PermitNo: 0
Zip:
0
Storeys: .1
TYPe:
Office (Business)
GrossArea: 8965
Class:
New Finished building
Net Area: 896
Max ronnage: 3 (if different, ,<`rite in)
J!"Component
Compliance Summary
Design Criteria Result
Cross Energy
Use
_---
0751.07
Other Envelope Requirements - A
100.00 PASSES
-
PASSES
LIGHTING CONITRO:S
EXTERNAL LIGHTING
PASSES
IiVAC SYSTEM
PASSES
PLANT
PASSES
WATER HEATING SYSTETvIS
PASSES
PIPING SYSTEMS
PASSES
Met all required cOmpliance from Check List?
Not Checked
Yes/No/NA
--INIPOR TANT NOTE. An input report.Print out from Energy Gauge p'laCon, o j.
this design building must be sub"witted along tuitlr this CoMpliance _Report
I hereby certify that the plans and Review of the plans and specifications covered by this
specifications CO'Vered by this calculation calculation indicates compliance with the Florida Energy
are in compliance with the Florida Energy Code. Before construction is completed, this building will be
Efficiency Code. inspected for compliance in accordance with Section
553, 908, F.S.
PREPARED BY: James A Sum �d BUILDING € FFICIAL:
DATE: DATE:
i hereby, ceiVy th ,his building is in compliance
with the Florda Energy Effici cy Code.
OWNER
AGEl�'T''
03.
If. required_ by Florida law, I hereby certify (*} that the system design is in
compliance with the Florida Energy Code. REGISTRATION
No.
ARCHITECT:
ELECTRICAL SYSTEM DESIGNER
LIGHTING SYSTEM DESIGNER:
MECHANICAL SYSTEM DESIGNER:
PLUMBING SYSTEM DESIGNER:
f
(*) Signature is required where Florida Law requires design to be performed by registered design professionals.
Typed names and registration numbers may be used where all relevant information is contained on signed/sealed
Plans.
Project: Corp Arpt Dangers
Title: Phase 1A T-Dangers, Corporate and Comm
Ty e: Office f Rissiness)
)Location: SANFORD, SEM HOLE COUNTY, FL (5915i1�)
f
Whole Building Compliance
eaSP.r9
E LECTRNCBTY
51.07
100.O0
11.56
E
t
t
.. C E :.,w " �.,:: ,:
i
13.70
26.12
a v li
4.01
15.36
t
t
-
�Credits & Penalties (ir;' any): N[odafied Points: = 51.08 ----
--
..
Project: Corp Arpt Bangers — ----1
Title: Phase 1A T-Hangers, Corporate and Comm
Type: Office (Business)
Location.: SANFOR D. SEMINOLE COUNTY,FL (69150())
External Lighting Compliance
(Description Category Allowance Area or Length ELPA CLP
(W Unit) or No. of Units (W) {�
(Sgft or ft)
Ext Light I Entrance (iv/ Canopy) High 10.00 144.0 1.440 500
traffic -retail, hotel, airport_
theatre etc
Ext Light 2 Public drivewayslu-alk- vat's 0.15 2.400.0 360 1_050
Design: 1550 (W)
PASSES��
Allowance: 1800 (W)
Project: Corp Arpt Hangers
Title- Phase I T-Hangers, Corporate and Comm
Type: Office (Business)
ll
Location: SANFOR D, SEMINOLE COUNTY, FL (691500)
Lighting Controls Compliance
Acronym Ashrae lDeserintion Area No. of Design Min Compli-
IO (sq.ft) Tasks CP CP ance
Lobby 21 Lobby (General) - Reception and 238 1 2 2 PASSES
Waiting
Toilets 13 Toilet and Washroom 61 1 3 3 PASSES
Break Room 9 Food Senlce -Kitchen itchen
187 1 4 4 PASSES
Offices 28 Offices (Partitions>4.5 ft below .729 1 2 2 PASSES
ceiling) Enclosed offices, all open
;plan offices without partitions
Hangers 47 Storage & Warehouse - Material 7.442 1 2 2 PASSES
handling
'ASSES
Project: Corp Arpt Hangers
T'
Title: Phase 1A T-Hangers, Corporate and Comin
Type: Office. (Busiacss)
Location: SANFORD, SEMINOLE COUNTY, FL (691500)
System Report Compliance
A/C-1 System 1
Constant Volume Air Cooled No. of Units
Split System < 65000 Btu/hr 1
Component Category Capacity
Design Eff Design IPLV Comp-
Eff Criteria IPLV Criteria liance
Cooling System Air Cooled < 65000 Btu'h
Cooling Capacity.
10.00 10.00 10.00 PASSES
Air Handling Air Handler (Supple) -
System -Supply Constant Volume
021 0.80 PASSES
}
PASSES
Plant Compliance
Description installed Size Design Min
No Eff Eff
Design Min Category Comp
iP'LV YPLV fiance
None
Project: Corn Arpt Rangers
Titie: Phase 1 A T-Hangers, Corporate and Comm
Type: Office (Business)
Piping System Compliance
Category
Pipe Dia Is Operating Ins Cond Ins Req Ins
Complian
[inchesl Runout? Temp [Btu-in/hr Thick [in] Thick [in]
M SF.Fj
Domestic and Service Hot Water
Systcnns
0.75 False 11.5.00 0.23 1.00 0.93
PASSES
Cooling Systems (Chilled Water, Brine
and Refrigerant)
0.5(? False 135.0C► 0.�3 Ci 7; � -
1.50 Not Check,
s
Lot Checked
Project: Corp Arpt Hangers
Title: Phase IA T-Hangers, Corporate
and Comma
Type: Office (Business)
Other Required Compliance
Category Section
Requirement (write N/A in bog if not applicable)
Cheek
Infiltration 4OE.1
Infiltration Criteria have been met
�System 407. 3
HtiAC Load sizing has beer.. performed
Li
El
�
Ventilation 409.1
Ventilation criteria have been met
M
ADS 410.1
Duct sizing and Design have been performed
!�
T & I3 410.1
Testing and Balancing n-vill be performed
Electrical 413.1
Metering criteria have been met
Motors 414.1
Motor eff`iciencv criteria have been met
Lighting 415.1
Lighting
ch g criteria have been met
O & .M 102.1.
Operation/maintenance-manual will be prmided to owner
Root/Ceil 404.1
R-19 for Roof Deck with supplypirleanns beneath it
_
Report 301
l�
Input Repoli Print-CAat from.. Energy Casa�,v p �l- EnergyGauge F1aCoan attache9d:
� �+
t
ENERGY' EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department Of Community Affairs
EnergyGauge FlaCom vl..22
INPUT DATA REPORT
troJect Information
Project Name: Corp Arpt Hangers Orientation: West
Project Title: Phase IA T-1-fangers, , Corporate and Coml,11, Building Type: Office (Business)
Address: Orlando Sanford Airport
Building Classification: New Finished building
State: Florida No.of Storeys: 'I
zip: 0 GrossArea: 8965
Owner: Southeast Ramp Hanger Developme
No Acronym Description
I UnIces Zone I
Type Load Profile Area Multiplier Total Area
1sfJ Isf]
CONDITIONED Uses Building Load 8964.7 I. 8964.7
Profile
6/15/03 EnergyGauge Fla,Corn FLCCSB v1.22 1
Spaces
No Acronym Description
Type
Depth Width
Height MUIT
Total Area
Total Volume
IN
Ift]
Ift] Mier
[so
In Zone: Offices
I I Lobbv zoospl.
Lobby (General) - Reception
17.00
14.00
MOO 1
238.0
2380.0
and Waiting
2 Toilets Zo0Sp2
Toilet and Washroom
11.00
5.50
10.00 3
181.5
1815.0
3 Break Room Zo0Sp3
Food Service - Kitchen,
17.00
11.00
10,00 2
374.0
3740.0
4 Offices Z()()sp4
Offices (Partitioris>4.5 ft
41.68
17.50
10.00 1
729.4
7294.0
below ceiling) Enclosed
offices, all open plan offices
without partitions
5 Hangers Zo0Sp5
Storage & Warehouse -
124.03
60,00
16.00 1
7441.8
119068.8
Material Handling
Lighting
No Type
Power
Control Type
No.of
IWI
Ctrl pts
In Zone: Offices
In Space: Lobby
'I Recessed Fluorescent - No vent
210.00
Manual On
On/Off
I
El
2 Compact Fluorescent
17.00
Manual On/Off
I
E]
In Space: Toilets
I Compact Fluorescent
34.00
Exception for One fixture or
I
El
In Space: Break Room
ballast
i Recessed Fluorescent - No vent
210.00
Manual ai/Off
2
In Space: Offices
I Compact Fluorescent
630.00
Manual On/Off
2
In Space: Hangers
6/15/03
EnergyGauge FlaCom FLCCSB v1.22
2
i. Metal Halide
3200.00
Exception for Area used as a 2 ❑
Whole
Walls
No Description Type
Width H (Effec) Multi
Area
DirectionConductance
Beat Dens. R-Value
[ft) [ft] plier,
1811
[Btu/hr. sf. F1
Capacity [lb/cf] jb.sLF/Btuj
[Btu/sf. Fj
In Zone: Offices
I Pr0ZoIWaI Metal
17.50 1.0,00 1.
175.0
North 0.0957
0.7570 16.80 10.4-5
s iding/R 1.1. 13att/0. 5"
Gyp
2 Pr0ZOI Wag Metal
73.50 10.00 1
735.0
West 0.0957
0,7570 16.80 1.0.45 p
siding/R1 lBattJO.S"
Gyp
3 Pr0ZoIWa3 Metal
73.50 14.00 1.
1029.0
North 0.0957
0,7570 16.80 1.0,45
siding/R11 Batt/0. ill
Gyp
Windows
No Description Type
Shaded UCen SC
Vis.Tr
W H (Effec)
Multi Total Arca
[Btu/hr sf F]
[ft) [ftj
plier [gg)
In 'Lane, Offices
In Wall West
1 Pr0Zo 1. Wa2 Wi I SINGLE CLEAR No 1.0018 0,95
0.88
4.00 4.00
4 64.0 El
Doors
No Description Type
Shaded! Width. H (El ffec) Multi
Area Cond.
Dens. Heat Cap. R-Value
IN [ft]
plier
[sf) [Btu/hr. A F1 [ib/cf] [Btu/sE F] [h.sLF/Btu1
In Zone: Offices
----
In Wall: West
1. Pr0Zol Wa2Dr1. Solid core flush
No 3.00 6.66
2
20.0 0.5834
0.00 0.00 1.71 []
In Wall: Interior Partition
6/15/03
EnergyGauge FlaCom FLCCSB v.1-22
3
I PrOZol Wa3Drl Panel with 7/1.6"
No
3.00 6.66
1
20.0
1.1057 0.00
0.00 0.90
panels
Roofs
No Description
Type
Width
If (Effec) Multi
Area
Tilt
Cond. Heat Cap
(lens. R-Value s
[ft1
[ft1 plier
[sf]
[deg] [Btu/hr. Sf. F1 [Btu/sf. F1
[lb/cfj [h.sf.F/Btuj
In zonc: Offices
l PrOZolltfl
Mtl Bldg RoofIR-19
17.50
73,43 1
1285.0
0.00
0.0492 1.34
9.49 20.34 0
Batt
�
Nights .
9
No Description TYPe
UCen Shading Vis.Tran
W
fi (Effec) Multiplier
Area Total Area
[Btu/hr sf F1 Coeff
[Dj
[ft.]
[s [S I
In Zone:
In Roof:
i
Floors
No Description
Type
Width
H(Effec) Multi
Area
Cond.
Heat Cap. hens.
It -Value
[ft]
[ft] plier
[st7
[Btu/hr. sf.
F] [Btu/sf. F1 jib/cf]
[h.sf.F/Btu1
In Zone: Offices
l PrOZolrll
Underground wall
1.7.50
73.43 1
1255.0 3.1233
9.33 140.00
0.32 171
6/15/03 EnergyOauge F1aCom FILCCSB vl.22_ 4
A/C-1. System I�
Y Constant Volume .Air Cooled Split
Pdo. Of Units i
System < 65000 Btu/hr
I
Component Cat ory
Capacity Efficiency IPLV
1 Cooling System. (Air Cooled
< 65000 .Btu/h. Cooling 36000.00 10.00 10.00
Capacity)
2 Air Handling System -Supply (Air Handler (Supply) - 1200.00 0.21
El
Constant Volume)
Plant
Equipment
Category Size Inst.No Eff.
IPLV
Water Heaters
W-Ileater,Description
Capacit Cap.Unit I/P Rt. Efficienc
Loss
1 Storage Water Heater - Electric
40 Gal 9 [kW] 0.8900 [EF]
[%/hr]
[�
Ext-Lighting
•
Description
Categories. Area/Len/No. of units
Wattage
[sf/ft/No)
[w]
I Ext Light 1
Entrance (w/ Canopy) High 144.00
500.00
(�
traffic -retail, hotel, airport, theatre etc
2 Ext Light 2
Public drivewayshvalkways 2400.00
1050.00
[�
Piping
.No Type
Operating Insulation Nomonal pipe
Insulation Is Itunout?
Temperature Conductivity Diameter
Thickness
IF] f Btu-in/h.sf.F] fin]
[in]
I
1 Domestic and Service Hot Water Systems 115.00 0.23 0.75
1.00 No
Cj I
6/1.5/03
EnergyGauge FlaCom FLCCSB v1.22
5
2 Cooling Systems (Chilled Water, Brine and 1,35.00 0.23 0.50
Fenestration Used
0.75 No ❑
0
Name Glass Type No. of Grass SC VLT Frame Frame
Panes Conductance Conductance Absorptance
[13tu/h.sf Fj [Btu/h.sf.F]
ApLbWndl. SINGLE CLEAR 1 1.0018 0.9500 0.8810 0.4340 0.7000 ❑
Materials Used
Mat No Acronym Description Only R-Value RValue Thickness Conductivity Density SpecificHea
Used [h.sf.F/Btu] IN [l3tu/h.ful [lb/ctj t
18
Mat118
2 in. Wood
No
264
Mat1264
ALUMINUM; 1/16IN
No
214
Mat1214
POLYSTYRENE, EXP.,
No
1-1/41N.
187
Mat11.87
GYP OR PLA.S
No
BOARD,1/2IN
206
Ma11206
CELLULOSE,FILL,5.5IN R-
No
20
15.1
Mad 1.51
CONC HW, DRD, 1401,13,
No
4IN
1.78
Mat] 1.78
CARPET W/RUBBER PAD
Yes
?65
Mat1265
Soil, 1 It
No
48
Matl48
6 in- Heavyweight concrete
No
123
MatI123
CONC BLOCK
No
MW,8IN,HOLLOW
159
Mall1.59
CONC
No
HW-UND.RD-140LB-41N
57
Matl57
3/4 in. Plaster or gypsum
No
6/15/03
2.3857 ,
0.1670
0.0700
37.00
0.3900
0.0002
0.0050
26.0000
480.00
0.1000
❑
5.2100
0.1042
0,0200
1.80
0.2900
❑
0.4533
0.0417
0.0920
50.00
0,2.000
❑
20,8318
0.4583
0.0220
3.00
0.3300
❑
0.4403
0.3333
0.7570
140.00
0.2000
❑
1.2300
2.0000
1.0000
0,5000
100.00
0.2000
❑
0.5000
0.5000
1,0000
140.00
0.2000
❑
1.7227
0.6667
0.3870
53.00
0.2000
ED
0.3202
0.3333
1.041.0
140.00
0.2000
❑
0,1488
0,0625
0.4200
100.00
0.2000
❑
1EnergyGauge FlaCom FLCCSB v1.22
6
72
Mat172
AIR LAYER; 3/41N OR
Yes
0.9000
LESS, VERT, WALLS
267
Ma11267
0.75" stucco
No
0.1563
266
Mat1266
2x4(u16" oc + RI1 Batt.
No
8.3343
215
Mat1215
POLYSTYRENE, EXR,
No
8.3350
2IN,
105
Mat1105
CONC BLK: HW, 8IN,
No
1.1002
HOLLOW
256
Mat1256
WOOD, SOFT, 1-1/2IN
No
1.9939
268
Matl268
0.625" stucco
No
0.1302
42
Matl42
8 in. Lightweight concrete
No
2.0212
block
269
Mat1269
.75" ISO BTWN24" oc
No
2.2321
86
Matl86
BRICK:, COMMON, 4IN
No
0.8012
211
Mat121,1
POLYSTYRENE,EXPJ/21
No
2.0850
N
12
Matf 12
3 in. Insulation
No
10.0000
218
Mat1.218
POLY-URETHANE,E1eP.,1/2
No
3.2077
IN,
23
Mat123
6 in. Insulation
No
20.0000
4
Matl4
Steel siding
No
0.0002
27.1
Mat1271
2x4L24" oc + RI i Batt
No
10.4179
272
Mat1272
Panel with 7/16" panels
Yes
0.9044
273
Mat1273
Hollow core flush (1.375")
Yes
1.2777
274
Matl274
Solid core flush (1.375")
Yes
1.7141
275
Mdat1275
Panel with 7/16" panels
Yes
1.0019
(1.375")
276
M:at1276
Hollow core Rush (1.75")
Yes
1.3239
277
Mat1277
Panel with 1-1/8" panels
Yes
1..7141
(1.75")
278
Matl278
Solid core flush (1.75")
Yes
1.6500
279
Mat1279
Solid core flush (2.25")
Yes
2.8537
280
Mat1280
Fiberglass/Mineral wool core
Yes
0.8167
281
M:at1281,
Paper Honeycomb core
Yes
0.9357
282
Matl282
Solid Urethane foam core
Yes
1.6500
283
Ma11283
Solid mineral fiberboard core
Yes
1.781.6
284
Mat1284
Polystyrene core (18 ga steel)
Yes
2.0071
1
F9
0.0625
0.4000
1.6.00
0.2000
❑
0.2917
0.0350
9.70
0.2000
❑
0.1667
0.0200
1.80
0.2900
❑
0.6667
0,6060
69.00
0.2000
❑
0.1250
0.0660
32.00
0.3300
❑
0.0521
0.4000
16.00
0,2000
❑
0.6670
0.3300
38.00
0.2000
E]
0.0625
0.0280
4.19
0.3000
0
0.3333
0.4160
.120.00
0.2000
El
0.0417
0.0200
1.80
0.2900
❑
0.2500
0.0250
2.00
0.2000
0
0.0417
0.0130
1.50
0.3800
1:1
0.5000
0.0250
5.70
0.2000
❑]
0.0050
26.0000
480.00
0.1000
❑
0.2917
0.0280
7.11.
0.2000
❑
U
Ell
6/15/03 EnergvGauge FlaCom FLCCSB v1.22 7
�o:�
iviat;�a
rotiurethane core (18 ga
'sres
2.5983
steel) 2
286
Mat1.286
Polyurethane core (24 ga
Yes
2.5983
steel) 1
287
Mat1287
Polyurethane core (24 ga
Yes
4.1.500
steel) 2
288
Mat1288
Solid Urethane foam core
Yes
4.1500
81.
Matl81
ASPHALT-l"XING,
Yes
0.1500
ROLL
244
Mat1244
PLYWOOD, 1/21N
No
0.6318
185
Mat] 185
CLAY TILE, PAVER, 3/81:N
No
0.0301.
82
MatI82
ASPHALT -SHINGLE .AND
Yes
0.4400
SIDING
1.1
Mail11.
2 in. Insulation
No
6.6800
47
Matl47
2 in. Heavyweight concrete
No
0.1,670
95
Matl95
CONC BLOCK
No
0.7107
H W-41N-HG.LLOW
248
Mat1248
ROOF GRAVEL OR
No
0.0500
SLAG 1/21N
94
Mat194
BIJILT-UP ROOFING,
No
0.3366
3/81N
!
ii
FR I
0.0417
0.0660
34.00
0.2900
[�
0.0313
1.0410
120.00
0.2000
�.7
0.1670
0.0250
2..00
0,2000
0.1.670
1.0000
140.00
0.2000
[�
0.3333
0.4690
101.00
0.2000
L]
0.0417
0.8340
55.00
0.4000
E]
0.0313
0.0930
70.00
0.3500
m
No Name Simple Massless Conductance heat Capacity ]Density RValue
Construct Construct [Btu/h.sf.1F] [Btu/sf.F] [lb/cf] [h.sEF/Btu]
1.007 Underground wall in basement, 4 in. h.tiw, No No 3.12 9.33 140.00 0.3202
cone .
Layer Material Material Thickness Framing
Ito, [ftj Factor
1 159 CONIC HW-U-NDRD-.140LB-4IN 0.3333 0.00
6/13/03
El nergyGauge FlaCom FLCCSB `•1.22
8
No Name Simple
Massless
Conductance
Meat Capacity
Density
. RValue
_ Construct
Construct
[Btu/h.sf.Fj
[]Btu/sLF]
[ib/cf]
(h.sf.F/Btuj
1020 Metal siding/R1lBatt/0.5"Gyp No
No
0.10
0.76
1.6.80
.10.4535 []
Layer Material
Material
No,
1 4
Steel siding
2 12
3 in. Insulation
3 187
GYP OR PLAS BOARD,
Thickness
Framing;
IN
Factor
0.0050
0.00
0,2500
0.00
0.0417
0.00
❑
No Dame Simple Massless -Conductance Heat Capacity Density 1SValue
Construct Construct lBtu/h.st:Fj lBtu/si:14-1 [ib/cfj lh.sf.F/Btuj
1021 Panel with 7/16" panels No Yes 1. l 1 0.9044
.Layer Material Material Thickness Framing
No. IN Factor
1 272 Panel Nvith 7/16" panels 0.00
No Name Simple Massless Conductance .Heat Capacity Density 12Value
— C211struct Construct lBtt►/h.sf.Fj [Btu/st:F'j [lb/cfj lh.sf.FllBtu)
1023 Solid core flush No Yes 0.58
1.7141
C/ l 5/03
La
yer Material Material "Thickness Framing
No.
lftj Factor
1 274 Solid core flush (1.375°j 0.00
EnergyGauge F1aCom FLCCSB V1.22
w
91
No Name
Simple
Density RValue
Massless Conductance Heat Capacity
Construct
Construct [Btu/h.sf.F] [Btu/s1:F]
[lb/cf] [h.sf.F/Btuj
I047 . Mtl Bldg Roof/R-I9 Bait
No
No 0.05 L34
9.49 20,3366 A
� I
Layer Material
Material ~�
Thicimess Framing
No.
[ft] Factor
1 94
BUILT-UP ROOFING, 3/8W
0.0313 0.00
'
I
2 23
6 in. Insulation
0.5000 0,00
6/15/03 EnergyGauge FlaCom JF.LCCSB ,,,1.22
1.0 i
I