HomeMy WebLinkAbout500 Gordon St- SANFORD FIRE DEPA!T�TM*,,NT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
F D
Plans Review Sheet
Date: September 19, 2002 Business Address: 500 Gordon Street Occ. Ch. 42
Business Name: Blue Belle Creameries Ph. ()
Contractor: K.C. Petroleum Ph. ( 407) 399-4630
Fax. (407) 469-2994
Reviewed Reviewed with comment [XI Rejected [ 1
Reviewed by: Timothy Robles, Fire Protection Inspector
Comment: Instillation on one(]) 10, 000 gallon diesel tank (underground)
1.1 Application — The Sanford Fire Department will require the following items to be field
verified prior to C/0.
1.2 Fuel Dispensers: Shear Valves
1.3 Main Shut Off: Function Test with fuel dispensing
1.4 Fuel Dispensers: Verify Ballard's in front of all fuel dispensers
1.5 Fire Protection: One (1) 201b "Purple" Kfire extinguisher required inside cabinet at Fuel Island.
1
J - ,
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
Plans Review Sheet
Date: 7118102 Business Address: 500 Gordon Street
Occ. Ch. (#38)Business (#40) Warehouse
Business Name: Blue Bell Creameries Ph. ()
Contractor: Brasfield & Gorrie Ph. (904) 49.3-6101
Fax. (904) 493-6066
Reviewed [ ] Reviewed with comment [ X ] Rejected [ ]
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner
Comment: Plans reviewed as BusinesslWarehouse Occupancy. FD reserves right to require
applicable code requirements if occupancy use changes. Sprinkler plans to be submitted for
review, permitting, and inspections. If separate certified contractor does underground fireline,
plans to be submitted for review, permitting, and inspections. Sealed letter from Engineer of
Record stating design criteria for sprinkler system needs to be submitted with construction plans.
Fire Alarm plans to be submitted for review, permitting, and inspections. Fire sprinkler system
shown as, -'-'.Class #2 commodity; maximum storage 18' (ft) hivh. Dry and Wet pipe
system
1.1 Application — New Metal Building, 12,523 (sq, ft)building with fire sprinkler system
1.2Mixed — N/A (warehouse 8,953 sq ft,) & ( office 3, 570 sq ft)
1.3 Special Definitions — None
1.4 Classification of Occupancy — Business(iow) , Warehouse (ordinary)
1.5 Classification of Hazard of Contents — Ordinary
1.6 Minimum Construction — N/R
2.2 Means of Egress Components —,Door, 101 B- shall comply with L. S. C. 2000
SECTLON 7.2.1.6.1 (Ti, door Into fire alarm)
2.3 Capacity of Egress — O.K.
1
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI.32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
2.4 Number of Exits — O.K.
2.5 Arrangement of Egress — O.K., will field verify
2.6 Travel Distance — O.K.
2.7 Discharge from Exits — O.K., will field verify
2.8 Illumination of Means of Egress — O.K.; will field verify
2.9 Emergency Lighting -Fire Department will field verify (6) six inside cooler area
2.10 Marking of Means of Egress — O.K.; will field verify
2.11 Special Features - Reserved
3.1 Protection of Vertical Openings — N/N (single story building)
3.2 Protection from Hazards — Per section 8.4.1> sec 9.7 (mechanical room shall be
protected by fire sprinkler system)
3.3 Interior Finish — Class I,II, per 10.2.7
3.4 Detection, Alarm and Communications Systems — as per NFPA 72 (submit plans for
review)
3.5 Extinguishing Requirements — as per NFPA 10, see page "A-U" one (1) 51b, CO -2, fire
extinguisher, two (2) 3A40BC fire extinguishers required in office area. Two (2) 4A rated fire
extinguishers outside cooler area (truck bays) SEE PAGE A-O
3.6 Corridors — Fire sprinklers in lieu of (1) hour rating
- 4 Special Provisions:
- 5 Building Services: Fuel tanks will require site plan permit & plans review to
meet N.F.P.A. #30
5.1 Utilities — as per LSC 9-1
5.2 HVAC — as per LSC 9-2= All A/C units over 2,000 C.F.M. require duct detectors to
tie into fire alarm panel as "trouble" alarm only
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes — N/A
2
SANFORD FIRE DEPARTMENT
FIRE PREVENTIONDIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
Sanford City Code — Chapter 9
Fire Sprinklers: Required; also see 3.5 above
Monitoring: Required by a U.L. listed Central Station for all mandated fire
sprinklered properties
Other: NFPA 1
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box — Required; will field verify See page FP -I FOR LOCATION
(application attached)
3-7.1 Bldg. Address Number posted and legible — Required; will field verify
(see pag,�e A-5 for location)
3
` c f# AE
BP208I01 CITY OF SANFORD 1/17
Global Location Inquiry - Building Permit Applications 1 07
Property address . . . . . . 500 GORDON ST
Parcel Number . . . . . . . . 27.19.30.504-0000-0050
Type options, press Enter.
2=Application inq 3=Structure inq 4=Permit inq 5=Inspection inq
Opt Appl Nbr Type Stat Date Tenant Nbr/Name
03 00001213 FRAL CL 2/28/03
03 00001121 FRAL CL 2/14/03
03 00000041 MECH CL 10/08/02
_ 02 00002280 UDGS CL 9/27/02
02 00002244 FRSP CL 9/19/02
02 00002236 FSUP CL 9/19/02
02 0000210.3 FRSP CL 8/28/02
02 00001940 SDVP AP 8/05/02
02 00001933 NIND CO 8/01/02
_ 02 00001294 ENGR AP 5/16/02
02 00001293 SITE AP 5/16/02
F3=Exit F12=Cancel
e»
BP401I01
N
CITY OF SANFORD 1/17/06
Permit Inquiry 13:23:28
Parcel Number . . . . . .
. 27.19.30.504-0000-0050
Property address . . . .
. 500 GORDON ST
Application, str, pmt nbr
. 02 00001933 000 000 BLCA 00
Application type . . . .
. NEW INDUSTRIAL
Permit type . . . . . . .
. BLDG PERMIT - NEW CONST/ALTER
Permit status, date . . .
. . C.O. ISSUED 4/30/03
Issue date . . . . . . .
. . 8/06/02
Expiration date . . . . .
. . 2/03/03
Reissue date . . . . . .
. .
Permit value . . . . . .
. . 1200000
Permit square footage . .
. . 0
Property owner . . . . .
. . BLUE BELL CREAMERIES LP
Contractor . . . . . . .
. . BRASFIELD & GORRIE GENERAL
Additional permit desc
Phone interface number
309757
Permit pin number . . . .
. . 605503
Last maintained by . . .
. . DUNKLINM 4/30/03 12:45:48
F3=Exit FS=Land inq
F6=Sub-contractors F8=Permit fees F9=Req'd insp
F12=Cancel