HomeMy WebLinkAbout101 Coastline Rd+^ r
t
Whole Building Performance Method for Commercial Buildings
ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Community Affairs
FLA/COM-97 Version 2.2
PROJECT NAME_MACK WAREHOUSE
ADDRESS: _COASTLINE ROAD
SANFORD FL
OWNER: MACK PLUMBING_
AGENT:
Form 400A-97
PERMITTING OFFICE:
_Sanford
CLIMATE ZONE: 5
PERMIT NO: 6 '—)
JURISDICTION NO: 6915i10
BUILDING TYPE: _Business (Office)
CONSTRUCTION CONDITION: New construction
DESIGN COMPLETION: _Finished Building
CONDITIONED FLOOR AREA: _4900 NUMBER OF ZONES: 1
MAX. TONNAGE OF EQUIPMENT PER SYSTEM: 5
COMPLIANCE CALCULATION:
METHOD A DESIGN CRITERIA RESULT
----------------- -------------- ------
A. WHOLE BUILDING 63.14 100.00 PASSES
PRESCRIPTIVE REQUIREMENTS:
LIGHTING
EXTERIOR LIGHTING
200.00 825.0.0
PASSES
LIGHTING CONTROL REQUIREMENTS
PASSES
HVAC EQUIPMENT
COOL'ING EQUIPMENT
1. SEER
10.00 10.00
PASSES
HEATING EQUIPMENT
1. Et
1.00
N/A
AIR DISTRIBUTION SYSTEM INSULATION
REQUIREMENTS
1. Unventilated
6.00 6.00
PASSES
REHEAT SYSTEM TYPES USED
NO REHEAT SYSTEM is USED
WATER HEATING EQUIPMENT
PIPING INSULATION REQUIREMENTS
----------------------------------------------------------------------------
COMPLIANCE CERTIFICATION:
I hereby certify that the plans and Review of the plans and specifica-
specifications covered by this calcu- tions covered by this calculation
lation are in compliance with the indicates compliance with the
Florida Energy Efficiency CodeFlorida Energy Efficiency Code.
PREPARED BY: �"' 14 'OCT 19 19qp Before construction is completed,
DATE: this building will be inspected
for compliance in accordance with
I hereby certify that this .building is Section 553.908, Fl rida Statutes.
in compliance with the Florida Energy BUILDING O VICTAL: _ (�
Efficiency Code. DATE:—
OWNER/AGENT:
"DATE:
e
f'
,iereby certify(*) that the
/iergy Efficiency Code.
SYSTEM DESIGNER
ARCHITECT :
MECHANICAL:
PLUMBING .
ELECTRICAL:
LIGHTING
system design is in compliance with the Florida
REGISTRATION/STATE
(*) Signature is required where Florida law requires design to be performed
by registered design professionals. Typed names and registration numbers may
be used where all relevant information is contained on signed/sealed plans.
----------------------------------------------------------------------------
----------------------------------------------------------------------------
BUILDING
ENVELOPE SYSTEMS
COMPLIANCE
CHECK
40-•1.------GLAZING--ZONE 1------------------------------------------------
v-
Elevation
---------
Type
---------------
U SC VLT Shading
---- ---- ----
Area(Sgft)
North
Commercial
--------------
1.26 1 1 None
----------
48
West
Commercial
1.26 1 1 None
96
South
Commercial
1.26 1 1 None
48
South
Commercial
1.26 1 1 None
16
Total Glass Area in Zone 1 =
208
Total Glass Area =
208
402.------WALLS--ZONE
1------------------------------------------------
---
Elevation
---------
Type
U Insul R
Gross(Sgft)
North
--------------------------------
5/8"Stco/8"CMU/3/4"ISO
----- -------
BTWN24"oc 0.149 4
-----------
840
West
5/8"Stco/8"CMU/3/4"ISO
BTWN24"oc 0.149 4
950
South
5/8"Stco/8"CMU/3/4"ISO
BTWN2411oc 0.149 4
410
East
5/8"Stco/8"CMU/3/4"ISO
13TWN24"oc 0.149 4
250
Adjacent
3/4"Stco/2x4@16"oc+RllBatt/""Gyp
0.080 11
1160
Total Wall Area in Zone 1 =
3610
Total Gross Wall Area =
3610
403.------DOORS--ZONE 1------------------------------------------------
---
Elevation
Type
------------------------------------------
U
Area(Sgft)
---------
West
1-3/4 Steel Door-Fiberglass/Mineral
-----
woo 0.60
----------
42
North
1-3/4 Steel Door-Fiberglass/Mineral
woo 0.60
168
East
1-3/4 Steel Door-Fiberglass/Mineral
woo 0.60
168
Adjacent
1-3/4 Steel Door-Fiberglass/Mineral
woo 0.60
21
Total Door Area in Zone 1 =
399
Total Door Area =
399
404.------ROOFS--ZONE
1------------------------------------------------
---
Type
------------------------------------
Color U Insul R
Area(Sgft)
Mtl Bldg Roof/R-11 Batt
------ ------------
Medium .084 11
----------
4900
Total Roof Area in Zone 1 =
4900
Total Roof Area =
4900
405-------
FLOORS -ZONE 1------------------------------------------------
---
Type
------------------------------------------------
Insul R
Area(Sgft)
Slab on Grade/Uninsulated
-------
0
----------
4900
Total Floor Area in Zone 1 =
4900
Total Floor Area =
4900
406------- INFILTRATION --------------------------------------------------
---
CHECK
Infiltration Criteria in
406.1.ABCD have been meta
MECHANICAL SYSTEMS
------------------------------------------------------------------
CHECK
HVAC load sizing has been performed. (407.1.ABCD)
----
---
407-------
COOLING SYSTEMS-----------------------------------------------
---
Type
----------------------------
No Efficiency IPLV
Tons
1. Split
System
------------- -------------------
3 10 0
5.00
408-------
HEATING SYSTEMS-----------------------------------------------
---
Type
No Efficiency
BTU/hr
F .
Electric Resistance 3
1 51195
j!09.------VENTILATION
---------------------------------------------------
Ventilation Criteria in 409.1.ABCD have been met. (CHECK
410.-----AIR DISTRIBUTION SYSTEM__________________________________
---------------------------
CHECK
--------------------------------- -
Duct sizing and design have been performed. (410.1.ABCD) ----- ----- ---
AHU Type Duct Location R-value
---------------------- -------
1. Air Conditioners Unventilated
CHECK
------------------------------------------------------------------
Testing and balancing will be performed. (410.1.ABCD)
411.-----PUMPS AND PIPING -ZONE _________________________________________ ---
Basic prescriptive requirements in 411.1.ABCD have been met.
PLUMBING SYSTEMS
411------ PUMPS AND PIPING -ZONE 1--------------------------------------- ---
Type __ -_-- _--- -
R-value/in Diameter Thickness
-
------------------
412
-----WATER HEATING SYSTEMS -ZONE 1__________________________________
Type Efficiency y In Standb Loss utRate Gallons
P
ELECTRICAL SYSTEMS
413.-----ELECTRICAL POWER DISTRIBUTION_________________________CHECK
___
Metering criteria in 413.1.ABCD have been met.
414.-----MOTORS
---------------------------------------------------
Motor efficiencies in 414.1.ABCD have been met.
415.-----LIGHTING SYSTEMS -ZONE 1______________________________
--------- ---
pace Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)
---------- ----------------- --- ----------------
Reading, T 1 On/Off 10 None 0 8575 4900
Total Watts for Zone 1 = 8575
Total Area for Zone 1 = 4900
Total Watts = 8575
Total Area = 4900
Lighting criteria in 415.1.ABCD have been met. CHECK
--------------------
------------------------
1 . Operation/maintenance manual will be provided to owner.(102.1)
----------------------------------