SANFORD FIKE DEPARTMENT
O FIRE PREVENTION DIVISION
POt 300.N. Park Ave., Sanford, FI. 32771 / P. O. Box 1788, Sanford, Fl. 32772 1 (407 302-2520 IFAX (407) 302-2526
Plans Review Sheet
►-)Sl
Date: October 5, 2004 Business Address: t:5-� W.P Ball Blvd.
Occ. Ch. 36, Mercantile Class `B'
Business Name: Linens & Things
Architect: D.L. Moon
Ph. (770) 643-6560
FAX ( ?) not on application
P H (817) 738-8095 xx 219
Fax. (817) 738-9524
Contractor: T.B.A. (out to bid at time of submittal)
with co'li,ntelt p€'�se reply to comments
Ph. ( )
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner
Comment: Plans reviewed as Mercantile Occupancy. FD reserves right to require
applicable code requirements if occupancy use changes. Sprinkler plans to be submitted for
review, permitting, and inspections. Sealed letter from Engineer of Record stating design
criteria for sprinkler system needs to be submitted with construction plans.
Separate permit required for Fire Alarm.
1.1 Fine Alarm required for monitoring of sprinkler system
1.2Application — New Building (28,418 s. q. ft.)
1.3 Mixed — N/A, over 50 occupancy load
1.4Special Definitions — Class "B" Mercantile Store (Under 30,000 sq ft.)
1.50assification of Occupancy — Mercantile Store Class "B"
1.6 Classification of Hazard of Contents — Ordinary in office areas, and storage area
classified as "High Hazard" per L.S.C. 10,11
1.7 Minimum Construction — Shall comply with Florida Building Code 2001
mercantile occupancy Type IV, UNPROTECTED
I.. -- .... -- _...
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Part: Ave., Sanford, FI. 32771 / 13. O. Box 1788, Sanford, FI. 32772
(407 302-2520 / FAX (407) 302 2526
1.8 2.2 Means of Egress Components — Reai.stora-e exits .EXIT.SHALL BExDILIN°EATS
WITH, 44 '...yellt on floor':leading to EXIT door:
ow pain
2.3 Capacity of Egress — sales floor area based on one (])_person per 30 sq ft., storage area
based on one (1) person per 300 sq. ft.
2.4 Number of Exits — (Minimal of Two (2) required EXITS) Four Provided
2.5 Arrangement of Egress: Travel distance increased up to 200' (ft) do to fire sprinkler system
2.6 Travel Distance — Reai EXIT SH.ALI BE'DII,INEATED oor
leadng;to EXIT door:
2.7 Discharge from Exits — O.K., will field verify
2.8 Illumination of Means of Egress —additional EXIT SIGNS may be required (power shut
down test required at night only)
2.9 Emergency Lighting — (1) foot candle (10 1 x & a minimum at any point of 0.1
foot-candle (1LX) measured along the path of egress at floor level. Therefore
additional emergency lights may be required, (power shut down test required at night
171
only)
Emergency Lighting required inside Main Electrical room and all rest rooms (*).
2.10 Marking of Means of Egress — O.K.; will field verify?
2.11 Special Features —Reserved
3.1 Protection of Vertical Openings — Class (B) mercantile shall have an automatic, are
sprinkler system, design criteria SHALL SHOW storage maximum height
stora eg area M.
3.2 Protection from Hazards — (See exception 36-3.2.1 .LSC 101)
3.3 Interior Finish — Not required, building has an automatic fire sprinkler system
3.4 Detection, Alarm and Communications System: (as per N.F.PA.72- 3-8.3.1.2 (99)
Ed.
• 3.5 Extinguishing Requirements — as her NFPA 10, Ejkht (8) fire extinguishers required
per N.FP.A... #10 See blue prints (lllinimal 4A 60 B.C. Rated) (*).
5.1 Utilities — as per LSC 7-1
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 302-2526
5.2 HVAC — as per LSC 7-2
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
Sanford City Code — Chapter9:
Required; Fire Sprinklers. Tire Department will field verify sight glass at all inspectors
test.
Monitoring: Required for fare sprinkler system and all inside and outside fire sprinkler valves.
Other: NFPA 1
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box— One (1) required see application attached
3-7.1 Bldg. Address Number Posted and Legible — Post address in 6" six inch numbers
contrasting in color (see blue prints).
ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Community Affairs
EnergyGauge F1aCom v1.22 FORM 40OB-2001
Selected Component Compliance for Commercial Buildings
Jurisdiction: SANFORD, SEMINOLE COUNTY, FL (691500)
Short Desc:
040531
Project:
Linens N Things - Sanford
Owner:
Address:
200 Towne Center Circle
Seminole Towne Center
City:
Sanford
State:
Florida
PermitNo:
0
Zip:
32771
Storeys:
1
Type:
Retail (mercantile)
GrossArea:
27761
Class:
Renovation to existing building
Net Area:
27761
Max Tonnage:
16 (if different, write in)
Compliance Summary
Component
WHOLE OR ENVELOPE Compliance
Other Envelope Requirements
LIGHTING POWER
LIGHTING CONTROLS
EXTERNAL LIGHTING
HVAC SYSTEM
PLANT
WATER HEATING SYSTEMS
PIPING SYSTEMS
Met all required compliance from Check List?
Design Criteria Result
39,455.00 80,503.77
Not Requested
Not Requested
PASSES
PASSES
Not Requested
PASSES
Not Requested
PASSES
PASSES
Yes/No/NA
IMPORTANT NOTE: An input report Print -Out from EnergyGauge FlaCom of
this design building must be submitted along with this Compliance Report.
9/16/2004 EnergyGauge FlaCom ,FL"CCSB v1.22 1
COMPLIANCE CERTIFICATION:
I hereby certify that the plans and
specifications covered by this calculation are
in compliance wi
Efficiency Code.
PREPARED BY:
DATE:
I hereby certify that this building is in compliance
with the Florida Energy Efficiency Code.
OWNER AGENT:
DATE:
Review of the plans and specifications covered by this
calculation indicates compliance with the Florida Energy
Code. Before construction is completed, this building will be
inspected for compliance in accordance with Section
553.908, F.S.
BUILDING OFFICIAL: PIA S HAULED
DATE: CITY OF SANF RD
If required by Florida law, I hereby certify (*) that the system design is in REGISTRATION
compliance with the Florida Energy Code.
No.
ARCHITECT:
ELECTRICAL SYSTEM DESIGNER:
LIGHTING SYSTEM DESIGNER:
MECHANICAL SYSTEM DESIGNER:
PLUMBING SYSTEM DESIGNER:
Gregory R. Schnackel PE 0048442 / FL
Gregory R. Schnackel PE 0048442 / FL
Gregory R. Schnackel PE 0048442 / FL
Gregory R. Schnackel PE 0048442 / FL
(*) Signature is required where Florida Law requires design to be performed by registered design professionals.
Typed names and registration numbers may be used where all relevant information is contained on signed/sealed
plans.
9/ 16/2004
EnergyGaugeF7aCam FLCCSB 0.22
2
Project: 040531
Title: Linens N Things - Sanford
Type: Retail (mercantile)
Location: SANFORD, SEMINOLE COUNTY,
FL (691500)
(WEA File: Orlando.TMY)
Lighting Power Compliance
Space Ashrae Description
Area
Height
No. of
AF Design
Effective
Allowance
ID
(sq.ft)
(ft)
Spaces
(W)
(W)
(W)
001 2
Corridor
349
14.0
1
1.00
580
435
279
002 100
Retail Establishments
23,362
14.0
1
1.00
44960
33720
77,095
(Merchandising &
Circulation Area) Applicable
to all lighting, including
accen
003 2
Corridor
108
10.0
1
1.00
180
180
86
009/010 45
Storage & Warehouse -
2,379
14.0
1
1.00
2370
2370
714
Bulky Active Storage
Oil 4
Electrical Mechanical
120
14.0
1
1.00
110
110
84
Equipment Room - General
013 4
Electrical Mechanical
59
14.0
1
1.09
60
60
45
Equipment Room - General
004 4
Electrical Mechanical
30
10.0
1
1.14
60
60
24
Equipment Room - General
005 13
Toilet and Washroom
135
8.0
1
1.00
270
270
108
006 13
Toilet and Washroom
135
8.0
1
1.00
270
270
108
007 7
Food Service - Leisure
265
10.0
1
1.00
540
540
663
Dining
014 2
Corridor
151
8.0
1
1.00
180
180
121
012 28
Offices (Partitions>4.5 ft
125
9.0
1
1.00
360
360
262
below ceiling) Enclosed
offices, all open plan offices
without partitions
016/017 2
Corridor
148
14.0
1
1.00
120
120
118
008 28
Offices (Partitions>4.5 ft
290
9.0
1
1.00
540
540
609
below ceiling) Enclosed
offices, all open plan offices
without partitions
018 2
Corridor
28
9.0
1
1.12
60
60
25
015 28
Offices (Partitions>4.5 ft
77
10.0
1
1.00
180
180
162
below ceiling) Enclosed
offices, all open plan offices
without partitions
Design
50840 (W)
PASSES
Effective:
39455 (V)
Allowance:
80503.77 (V)
9/16/2004 EnergyGauge F1aCom FLCCSB v1.22
Project: 040531
Title: Linens N Things - Sanford
Type: Retail (mercantile)
Location: SANFORD, SEMINOLE COUNTY, FL (691500)
(WEA File: Orlando.TMY)
Fighting Controls Compliance
Acronym
Ashrae
Description
Area
No. of
Design
Min
Compli-
ID
(sq.ft)
Tasks
CP
CP
ance
001
2
Corridor
349
0
10
1
PASSES
002
100
Retail Establishments
23,362
0
115
30
PASSES
(Merchandising & Circulation
Area) Applicable to all lighting,
including accen
003
2
Corridor
108
0
1
1
PASSES
009/010
45
Storage & Warehouse - Bulky
2,379
0
2
2
PASSES
Active Storage
Oil
4
Electrical Mechanical Equipment
120
0
1
1
PASSES
Room - General
013
4
Electrical Mechanical Equipment
59
0
1
1
PASSES
Room - General
004
4
Electrical Mechanical Equipment
30
0
1
1
PASSES
Room - General
005
13
Toilet and Washroom
135
0
1
1
PASSES
006
13
Toilet and Washroom
135
0
1
1
PASSES
007
7
Food Service - Leisure Dining
265
0
1
1
PASSES
014
2
Corridor
151
0
1
1
PASSES
012
28
Offices (Partitions>4.5 ft below
125
0
1
1
PASSES
ceiling) Enclosed offices, all open
plan offices without partitions
016/017
2
Corridor
148
0
1
1
PASSES
008
28
Offices (Partitions>4.5 ft below
290
0
1
1
PASSES
ceiling) Enclosed offices, all open
plan offices without partitions
018
2
Corridor
28
0
1
1
PASSES
015
28
Offices (Partitions>4.5 ft below
77
0
1
1
PASSES
ceiling) Enclosed offices, all open
plan offices without partitions
PASSES
9/16/2004 EnergyGauge FlaCom FLCCSB v1.22
Project: 040531
Title: Linens N Things - Sanford
Type: Retail (mercantile)
Location: SANFORD, SEMINOLE COUNTY, FL (691500)
(WEA File: Orlando.TMY)
System Report Compliance
RTU-1 RTU-1 Thru RTU-6
Constant Volume Packaged No.
of Units
Thru
RTi1-6
System
6
Component Category Capacity
Design Eff Design IPLV
Comp-
Eff Criteria IPLV Criteria
liance
Cooling System Air Cooled 135000 to
11.80 8.50 13.30 7.50
PASSES
760000 Btu/h Cooling
Capacity
Air Handling Air Handler (Supply) -
0.37 0.80
PASSES
System -Supply Constant Volume
7 RTU-7
Component Category
Cooling System Air Cooled < 65000 Btu/h
Cooling Capacity
Air Handling Air Handler (Supply) -
System -Supply Constant Volume
Constant Volume Air Cooled No. of Units
Single Package System < 1
Capacity Design
Eff
Design IPLV Comp-
Eff
Criteria
IPLV Criteria liance
12.00
9.70
8.00 PASSES
0.56
0.80
PASSES
PASSES
Project: 040531
Title: Linens N Things - Sanford
Type: Retail (mercantile)
Location: SANFORD, SEMINOLE COUNTY, FL (691500)
(WEA File: Orlando.TMY)
Water Heater Compliance
Description Type Category Design
Min Design Max Comp
Eff
Eff Loss Loss liance
Water Heater Storage Water Heater - <=120 [gal] & <= 0.99
0.91 PASSES
Electric 12 [kW]
PASSES
9/16/2004 EnergyGauge F1aCom FLCCSB v1.22 5
Project: 040531
Title: Linens N Things - Sanford
Type: Retail (mercantile)
Location: SANFORD, SEM
Piping System Compliance
Category
Pipe Dia Is Operating Ins Cond Ins Req Ins Compliance
[inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in]
[F] .SF.FJ
Domestic and Service Hot Water
0.50 False 105.00 0.28 1.50 1.38 PASSES
Systems
PASSES
9/16/2004 EnergyGauge FlaCom FLCCSB v1.22
ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Community Affairs
EnergyGauge FlaCom v1.22
INPUT DATA REPORT
Project Name: 040531
Project Title: Linens N Things - Sanford
Address: Seminole Towne Center
200 Towne Center Circle
State: Florida
Zip: 32771
Owner:
Project Information
Orientation: North
Building Type: Retail (mercantile)
Building Classification: Renovation to existing building
No.of Storeys: 1
GrossArea: 27761
Zones
No Acronym Description-
Type Load Profile
Area Multiplier
Total Area
[sq
[sq
1 RTU-1 Thru RTU-1 Thru RTU-6
CONDITIONED Uses Building Load
26377.4 1
26377.4 ❑
RTU-6
Profile
2 RTU-7 RTU-7
CONDITIONED Uses Building Load
1384.1 1
1384.1 ❑
Profile
9/16/2004 EnergyGauge F1aCom FLCCSB v1.22 1
Spaces
No
Acronym
Description
Type
Depth
Width
Height
Multi
Total Area
Total Volume
IN
IN
[ft]
plier
[sf]
[cf]
In Zone: RTU-1 Thru RTU-6
1
001
Vestibule
Corridor
26.89
12.98
14.00
1
349.0
4886.5
Q
2
002
Sales
Retail Establishments
143.67
162.61
14.00
1
23362.2
327070.5
❑
(Merchandising &
Circulation Area) Applicable
to all lighting, including
accen
3
003
Corridor
Corridor
6.76
15.97
10.00
1
108.0
1079.6
❑
4
009/010
Stock/Receiving
Storage & Warehouse -
20.87
114.00
14.00
1
2379.2
33308.5
❑
Bulky Active Storage
5
011
Electrical Room
Electrical Mechanical
8.51
14.10
14.00
1
120.0
1679.9
❑
Equipment Room - General
6
013
Sprinkler Room
Electrical Mechanical
6.56
9.00
14.00
1
59.0
826.6
❑
Equipment Room - General
In Zone: RTU-7
1
004
Janitors Closet
Electrical Mechanical
3.70
8.10
10.00
1
30.0
299.7
El
Equipment Room - General
2
005
Women's Toilet
Toilet and Washroom
10.66
12.67
8.00
1
135.1
1080.5
El
3
006
Men's Toilet
Toilet and Washroom
7.64
17.67
8.00
1
135.0
1080.0
❑
4
007
Break Room
Food Service - Leisure
13.24
20.02
10.00
1
265.1
2650.6
❑
Dining
5
014
Passage
Corridor
15.98
9.45
8.00
1
151.0
1208.1
❑
6
012
G.M. Office
Offices (Partitions>4.5 ft
9.95
12.56
9.00
1
125.0
1124.7
❑
below ceiling) Enclosed
offices, all open plan offices
without partitions
7
016/017
Stairs/Vestibule
Corridor
9.34
15.85
14.00
1
148.0
2072.5
8
008
Office
Offices (Partitions>4.5 ft
15.13
19.17
9.00
1
290.0
2610.4
below ceiling) Enclosed
offices, all open plan offices
without partitions
9/16/2004 EnergyGauge FlaCom FLCCSB v1.22 2
9 018
Closet Corridor
4.47 6.26
9.00 1 28.0
251.8
10 015
Counting Room Offices (Partitions>4.5 ft
7.76 9.92
10.00 1 77.0
769.8
below ceiling) Enclosed
offices, all open plan offices
without partitions
Lighting
No
Type
Power
Control Type
No.of
[W]
Ctrl pts
In Zone: RTU-1 Thru RTU-6
In Space:
001
1
Metal Halide
580.00
Programmable timer with
2
❑
Daylighting 4 step
In Space:
002
1
Metal Halide
2900.00
Programmable timer with
2
Daylighting 4 step
2
Suspended Fluorescent
42060.00
Programmable timer with
21
❑
Daylighting 4 step
In Space:
003
1
Recessed Fluorescent - No vent
180.00
Manual On/Off
1
In Space:
009/010
1
Suspended Fluorescent
1870.00
Manual On/Off
1
2
Incandescent
500.00
Manual On/Off
1
In Space:
011
1
Suspended Fluorescent
110.00
Manual On/Off
1
El
In Space:
013
1
Suspended Fluorescent
60.00
Manual On/Off
1
❑
In Zone: RTU-7
In Space:
004
1
Suspended Fluorescent
60.00
Manual On/Off
1
El
In Space:
005
1
Recessed Fluorescent - No vent
270.00
Manual On/Off
1
El
In Space:
006
1
Recessed Fluorescent - No vent
270.00
Manual On/Off
1
❑
9/16/2004 EnergyGauge F1aCom FLCCSB v1.22 3
In Space:
007
1
Recessed Fluorescent - No vent
540.00
Manual On/Off
1
❑
In Space:
014
1
Recessed Fluorescent - No vent
180.00
Manual On/Off
1
❑
In Space:
012
1
Recessed Fluorescent - No vent
360.00
Manual On/Off
1
❑
In Space:
016/017
1
Suspended Fluorescent
120.00
Manual On/Off
1
In Space:
008
1
Recessed Fluorescent - No vent
540.00
Manual On/Off
1
❑
In Space:
018
1
Recessed Fluorescent - No vent
60.00
Manual On/Off
1
In Space:
015
1
Recessed Fluorescent - No vent
180.00
Manual On/Off
1
❑
Wails
No Description
Type
Width H (Effec) Multi
Area
DirectionConductance
Heat
Dens. R-Value
IN [ft] plier
[sfJ
[Btu/hr. sf. F]
Capacity
[lb/cf] [h.sf.FBtu]
[Btu/sf.F]
In Zone:
Windows
No
Description Type
Shaded UCen SC Vis.Tr
W H (Effec)
Multi
Total Area
[Btu/hr sf F]
IN [ft]
plier
[Sf]
In Zone:
In Wall:
9/16/2004 EnergyGauge F1aCom FLCCSB v1.22 4
Doors
No Description Type
Shaded? Width H (Effec) Multi
[ft] IN plier
Area
[sf]
Cond. Dens. Heat Cap.
[Btu/hr. sf. F] [lb/cf] [Btu/sf. F]
R-Value
[h.sf.F/Btu]
In Zone:
In Wall:
Roofs
No Description Type
Width H (Effec) Multi
[ft] IN plier
Area
[sf]
Tilt
[deg]
Cond. Heat Cap
[Btu/hr. Sf. F] [Btu/sf. F]
Dens.
[lb/cf[
R-Value
[h.sf.FBtu]
In Zone:
Skylights
No Description Type
UCen Shading Vis.Trans
[Btu/hr sf F] Coeff
W
IN
H (Effec) Multiplier
IN
Area
[Sf]
Total Area
[Sf]
In Zone:
In Roof:
Floors
No Description Type
Width H (Effec) Multi
[ft] IN plier
Area
[sf]
Cond. Heat Cap. Dens.
[Btu/hr. sf. F] [Btu/sf. F] [lb/cf]
R-Value
[h.sf.FBtu]
In Zone:
9/16/2004 EnergyGauge F1aCom FLCCSB v1.22 5
Systems
RTU-1 Thru RTU-6 RTU-1 Thru RTU-6
Constant Volume Packaged System No. Of Units 6
Component Category
Capacity Efficiency IPLV
1 Cooling System (Air Cooled 135000 to 760000 Btu/h
Cooling Capacity)
2 Air Handling System -Supply (Air Handler (Supply) -
Constant Volume)
188100.00 11.80 13.30
6000.00 0.37
RTU-7 RTU-7
Constant Volume Air Cooled Single No. Of Units 1
Package System < 65000 Btu/hr
Component Category
Capacity Efficiency IPLV
1 Cooling System (Air Cooled < 65000 Btu/h Cooling
Capacity)
2 Air Handling System -Supply (Air Handler (Supply) -
Constant Volume)
63900.00 12.00 8.00
2000.00 0.56
Plant
Equipment Category
Size Inst.No Eff. IPLV
Water Heaters
W-Heater Description Capacit Cap.Unit
UP Rt. Efficienc Loss
1 Storage Water Heater - Electric 19 Gal
5 [kW] 0.9900 [EF] [%/hr]
Ext-Lighting
Description Categories. Area/Len/No. of units Wattage
11 [sf/ft/No] [W]
9/16/2004 EnergyGauge F1aCom FLCCSB v1.22 6
Piping
No Type Operating
Temperature
[F]
Insulation
Conductivity
[ Btu-in/h.sf.F]
Nomonal pipe
Diameter
[in]
Insulation Is Runout?
Thickness
[in]
1 Domestic and Service Hot Water Systems 105.00
0.28
0.50
1.50 No ❑
Fenestration Used
Name Glass Type No. of Glass SC VLT Frame Frame
Panes Conductance Conductance Absorptance
[Btu/h.sf.F] [Btu/h.sf.F]
Materials Used
Mat No Acronym Description Only R-Value RValue Thickness Conductivity Density SpecificHeat
Used [h.sf.FBtu] [ft] [Btu/h.ft.F] [lb/cf] [Btu/lb.F]
Constructs Used
9/16/2004 EnergyGauge FlaCom FLCCSB v1.22 7
i
W.
No Name Simple Massless Conductance Heat Capacity Density RValue
Construct Construct [Btu/h.sf.F] [Btu/sf.F] [lb/cf] [h.sf.F/Btu]
Layer Material Material Thickness Framing
No. [ft] Factor
9/16/2004
EnergyGauge F1aCom FLCCSB v1.22
EI
8
J