HomeMy WebLinkAbout3705 Orlando Dr 21254FLORIDA FIRE SPRINKLER ASSOCIATION, INC. STANDARD DATA SHEET: PLANS SUBMISSION FOR FIRE PROTECTION DOLLAR VALUATION• OVER $5,000.00 YES: 7,600.00 NO: STATE CERTIFICATE HOLDER: James A. Inman STATE CERTIFICATE NO:0030710181-00 NO: OF HEADS: 106 GEN.CONTRACTORS PERMIT NO: 1). Project Name: McDuff Address: 3705 Orlando Dr. 2). Owner's Name: McDuff Address: 3705 Orlando Dr. Responsible Party: Phone No: 3). Sprinkler Contractor: Vesta Fire Protection, Inc. Address: 1870 N. Rio Grande Av., Orlando, FL 32804 Submitted By: George McKinney Phone No: 425-2548 4). Classification of Hazard: Ordinary Group II Method of Storage: Storage Height: 5). Type of Work: Hydraulic: X Pipe Schedule: Ne;' System: :; n"` 1S' ` Existing System: Lnt. LVia VL Tenant Work: New Building: X Existing Building: minor alterations) 6). Flow Information From Supply Main: Static: 50 PSI Residual: 30 PSI Flow: 790 GPM Other Sources of Water: 7). Sprinklers: Manufacturer: Type: Size: Rating: Model: Viking Pendent 1 2" 1550 Microma-ic Central Upright 1 21t - "All 8). System Features: Combination: Sprinklers: X Standpipe: Wet: X Fire Pump: Underground: Type of Occupancies Covered: Dry: Other: Lead -In Mercantile i HYDRAULIC SUMMARY SHEET NAME G V FiC DATE LOCATION Sir, No e CNTt:"/ BUILDING 3 7044-,oA/ P D PA-, 5,,9-,vFo)e0 SYSTEM NO. CONTRACTOR - sT —i ROTeG r iv lAlG, CONTRACT NO. 8 (05- . CALCULATED BY DRAWING NO. CONSTRUCTION: COMBUSTIBLE -COMBUSTIBLE 'CEILING HEIGHT 0 FT. OCCUPANCY / k0t4-AN -r'iGLr 02 NFPA 13: LT. HAZ. ORD. HAZ. GP. 1 Z2 , 3 EX. HAZ. NFPA 231 NFPA 231C: FIGURE CURVE ZZ c OTHER (Specify) W SPECIFIC RULING MADE BY DATE O w AREA OF SPRINKLER OPERATION _LSOD . SYSTEM TYPE DENSITY 0 WET DRY DELUGE PRE -ACTION AREA PER SPRINKLER f,312 11-04 HOSE ALLOWANCE SPRINKLER OR NOZZLE O // V MODEL 1 NPaid= GPM: INSIDE HOSE ALLOWANCE GPM: OUTSIDE MAKE SIZE IZ" K-FACTO 6742 RACK SPRINKLER ALLOWANCE TEMPERATURE RATING CALCULATION GPM REQUIRED 3 -57 PSI REQUIRED 3g • AT BASE OF RISER. SUMMARY C" FACTOR USED: OVERHEAD UNDERGROUND • WATER FLOW TEST DATE & TIME 7=Z—R(a_ PUMP DATA RATED CAPACITY TANK OR RESERVOIR CAPACITY — CAPACITY IL ILSTATIC. PSI SD AT PSI ELEVATION a C RESIDUAL PSI 30 716 ELEVAT' ION GPM FLOWING WELL w ELEVATION Z'b PROOF FLOW GPM 3 LOCATION N oN SOURCE OF INFORMATION COMMODITY CLASS LOCATION _ w STORAGE HEIGHT AREA AISLE WIDTH Q" STORAGE METHOD: SOLID PILED % PALLETIZED % RACK % SINGLE ROW [j CONVENTIONAL PALLET AUTOMATIC STORAGE ENCAPSULATED co } DOUBLE ROW SLAVE PALLET SOLID SHELVING NON- MULTIPLE ROW OPEN ENCAPSULATED D y FLUE SPACING IN INCHES CLEARAN,C,E FROM TOP OF STORAGE TOCEILING 2 . LONGITUDINAL_______ TRANSVERSE FT. IN. v HORIZONTAL. BARRIERS:PRION.IDEIa A® OREVIATIONS.USBDIN CALCULATIONS 0 - PLOW INCREMENT AT SPECIFIC LOCATION- TEE•PLOW TURNED 90• O . PLOW AT A SPECIFIC LOCATION C. CR080.PLOW TURN60 900 O. P.M. - GALLONO PER MINUTE - - OEL.V. - DEL000.VALVE P. S.I.. POUND PER SQUARE INCH - O.P.V.. DRY PIPE VALVE PT. TOTAL PRESSURE IN P.D.I. - AL.V. ALARM VALVE Pp. PREBBURE LOOS DUE TO FRICTION OV .DATE VALVE PE - PREBSURE CHANGE, OUC TO ELEVATION CV . OWING CHECK VALVE PN PRESSURE NORMAL AV ANGLE VALVE.,. PV . PRESSURE' VELOCITY GLV . GLOBE VALVE; EEC . 400 ELBOW ST . STRAINER E . 90" ELBOW BPP . 13ACKPLOW PREVENTED L. T.E.. LONG TURN ELBOW DCV - DETECTOR CHECK VALVE TW . THIN.WALL PIPE - - BV BUTTERFLY VALVE - II u. c.v___w A.ir cA_:C M.E C.K V.A.L.V.E 100 200 300 600 MULTIPLY SCALE BY D a 0 GPM v 3 z i m--4 500 600 TOo m 800 80U IOOo IV i'- ---!- r---r------:---- 1' r..1._-! Wit. T_}.t. 1 r_ T' T _ T_-'- rit ti 2.s- 4- GPM I i 0O D 0 1 W D C rnU)m rn a oa o a t O I I O A>TYPE K FIRENET HYDRAULIC ANALYSIS OF A FIRE PROTECTION SPRINKLER SYSTEM VERSION 1 = JULY 1984 , DATE FOR THIS COMPUTER RUN ID FOR. THIS COMPUTER RUN a Mc DUFF INPUT DATA FILE NAME _ 8653 s OUTPUT DATA FILE NAME MCDUFF t** SPRINKLER SYSTEM'.DATA.SUMMARY Xc WATER SUPPLY CHARACTERISTICSs, STATIC PRESSURE = ' 50 PSI RESIDUAL PRESSURE _ 30 PSI RESIDUAL FLOW _ 790GPM ELEVATION OF.PRESSURE GAGE _ Q FT. FLOW REQUIREMENTS: OUTSIDE HOSE FLOW REQUIREMENT,(AT SUPPLY). 250 GPM INSIDE HOSE FLOW REQUIREMENT CAT LOCATION 0 ) 0 GPM TOTAL SPRINKLER SYSTEM ,FLOW REQUIRED (BASE OF RISER) O GPM SPRINKLER INFORMATION: MAXIMUM SPACING OF SPRINKLER HEADS - 10 FT. MAXIMUM SPACING OF BRANCH LINES 12 FT. REQUIRED MINIMUM FLOW (PER SPRINKLER) 22_R RPM r . I'• L b .jt .::'. .. ) u'r..4..W.•li`MT•h'•.f'u^. r •Sh •T •'M•Sk iT P AFT M+Mf %+N•TT+TM1T•T•xFT N N'•W.TAL•'MMTTT•A!M T AK••i s .Y. , cXnK` c SUMMARY OF HYDRAULIC CALCULATIONS c Cic C Cc C c c NODES FLOW...,,,,. PIPE EGlV. M dJ DIA. PSI/ V. T. RT :...END DIFE.. FROM--T0 GFM) .. FT:. a.:FT:....o0-TFT.n,:PSI.-r PSI. PSI. 1 2 350.91 110.00 102.80 150 6.09 0.33 0.00 34.82 47 I: 070 2 3 350.91 10.30 22.00 120 4.26 2.84 4.46 34.113 III 5..38 I E 3 4 350.91 73.00 20.00 120 4.26 2.84 0.00 28.73 26.09 2.64 4 5 245.99 12.00 0.00 120 4.26, 1.47 0.00 26.09. 25.92 0.18 5 6 122.93 12.00 0.00 120 4.26 0.41 0.00 25.92 25.87 0.05 4 14 104.92 0.58 10.00 120 2.15 8.48 0.25 26.09 24.94 1.15 5 15 123.05 0.58 10.00 120. 2.15 11.40 0.25 25.92 24.46 1.46 6 16 122.93 0.58 10.00 120 2.15 11.38 0.25 25.87 24.41 1.46 I 14 98 104.92 r6.00 10.00 120. 2.15 8.48 0.00 24.94 23.59 1.36 15 99 123.05 6.00 10.00 120 2.15 11.40 0.00 24.46 22.63 1.82 16 100 122.93 6.00 10.00 120 2.15 11.38 0.00 24.41 22.59 1.82 98 101 104.92 10.00 0.00 120 2.15 8.48 0.00 23.59 22.74 0.85 99 102 123.05 10.00 0.00 120 2.15 11.40 0.00 22.63 21.49 1.14 100 103 122.93 10.00 0.00 120 2.15 11.38 0.00 22.59 21.45 1.14 101 104 78.23 0.00 0.00 120 2.15 4.93 0.00 22.14 22.34 0.39 102 105 97.11 8.00 0.00 120 2.15 7.35 0.00 21.49 20.91 0.59 103 106 97.01 8.00 0.00 120 2.15 7.34 0.00 21.45 20.87 0.59 104 107 51.78 10.00 0.00 120 1.69 7.41 0.00 22.34 21.60 0.74 105 108 71.51 10.00 0.00 120 1.69 13.47 0.00 20.91 19.56 1.35 106 109 71.44 10.00 0.00 120 1.69 13.45 0.00 20.87 19.52 1.34 107 110 25.76 10.00 0.00 120 1.45 4.29 0.00 21.60 21.17 0.43 108 ill 46.75 10.00 0.00 120 1.45 12.93 0.00 19.56 18.27 1.29 109 112 46.71 10.00 0.00. 120 1.45 1291 0.00 19.52 18.23 1.29 111 113 22.82 10.00 0.00 120 1.05 16..57 0.00 18.27 16.61 1.66 112 114 22.80 10.00 0.00 120 1.05 16.54 0.00 18.23 16.58 1.65 THE MAXIMUM VELOCITY OF 10.87 FT/S OCCURS BETWEEN NODES 99 AND 102 I 3 --7 05 Orlando Dr porm ftt ala5 k tz% ,