HomeMy WebLinkAbout1190 W Lake Mary Blvd 95-1294 Classroom AdditionComponent Performance Method for Commercial Buildings
I
ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Community Affairs
FLAICOM-94 Version 2.1A
PROJECT NAME Q#7085 SIN8830-32
ADDRESS:
OWNER: G.E. CAPITAL MODULAR SPACE_
AGENT:
Form 40OB-94
PERMITTING OFFICE:
Sanford
CLIMATE ZONE: 5
PERMIT NO: _
JURISDICTION NO: 691500
BUILDING TYPE: _Business (Office)
CONSTRUCTION CONDITION: New construction
DESIGN COMPLETION: _Finished Building
CONDITIONED FLOOR AREA: _3280.01
MAX. TONNAGE OF EQUIPMENT PER SYSTEM: 4
COMPLIANCE CALCULATION:
NUMBER OF ZONES: 1
METHOD B DESIGN CRITERIA RESULT
ENVELOPE PERFORMANCE 47.79 80.87 PASSES
OTHER ENVELOPE REQUIREMENTS PASSES
LIGHTING
INTERIOR LIGHTING 4104.00 7089.50 G 2$ PASSES
EXTERIOR LIGHTING 720.00 1050.0019/(,'fPASSES LIGHTING
CONTROL REQUIREMENTS 3,- cr plqn O' K 0PASSES HVAC
EQUIPMENT ` d y ETN
COOLING
EQUIPMENT APp 1.
SEER 10.00 ) a PASSES HEATING
EQUIPMENT d v"" U
1.
Et 1.00fil N/A AIR
DISTRIBUTION SYSTEM INSULATION LEVEL yessT3s 1.
Ventilated 6.00 F'6.00 PASSES WATER
HEATING EQUIPMENT PIPING
INSULATION REQUIREMENTS COMPLIANCE
CERTIFICATION I
hereby certify that,the plans and specifications
covered by this calcu- lation
are in complianc with the Florida
Energ Ef cie ode. PREPARED
BY: DATE:
2 I
hereby certify that this building is in
compliance with the Florida Energy Efficiency
Code. OWNER/
AGENT: DATE : .
Review
of the plans and specifica- tions
covered by this calculation indicates
compliance with the Florida
Energy Efficiency Code. Before
construction.is completed, this
building will be inspected for
compliance in accordance with Section
553.908, Florida Statutes. BUILDING
OFFICIAL: DATE:
I
hereby certify(*) that the system design is in compliance with the Florida Energy
Efficiency Code. SYSTEM
DESIGNER REGISTRATION/STATE
ARCHI ECT
MECHANICAL:
PLUMBING
ELECTRICAL :
LIGHTING
Signature is required where Florida law requires design to be performed
Eby registered design professionals.. Typed names and registration numbers may
be used where all relevant information is contained on signed/sealed plans.
BUILDING INFORMATION COMPLIANCE
CHECK
401.------GLAZING--ZONE 1------------------------------------------------ v-
Elevation Type U SC VLT Shading Area(Sgft)
West Commercial 1.13 7 1.0 None 43
East Commercial 1.13 7 1.0 None 43
East Commercial 1.13 7 1.0 None 5
West Commercial 1.13 7 1.0 None 5
Total Glass Area in Zone 1 = 96
Total Glass Area = 96
402.------WALLS--ZONE 1 ------------------------------------------------
Elevation Type U Added R Gross(Sgft)
East Frame Wall + 3" InS. 0.081 0.0 720
West Frame Wall + 3" InS. 0.081 0.0 720
North Frame Wall + 3" InS. 0.081 0.0 369
South Frame Wall + 3" InS. 0.081 0.0 369
Total Wall Area in Zone 1 = 2178
Total Gross Wall Area = 2178!
403.------DOORS--ZONE 1 ------------------------------------------------
Elevation Type U Area(Sgft)
East 1-314 Steel Door -Paper Honeycomb core 0.56 95
West 1-314 Steel Door -Paper Honeycomb core 0.56 95
South 1-314 Steel Door -Paper Honeycomb core 0.56 80
Total Door Area in Zone 1 = 270
Total Door Area = 270
404.------ROOFS--ZONE 1 ------------------------------------------------
Type 't Color U Added R Area(Sgft)
STD. TRUSS Light .0526 0.0 3280
Total Roof Area in Zone 1 = 3280
Total Roof Area = 3280
405.------FLOORS-ZONE 1 ------------------------------------------------
Type R Area (Sgft)
Floor over Unconditioned Space/Insulated 11 3280
Total Floor Area in Zone 1 = 3280
Total Floor Area = 3280
406.------INFILTRATION --------------------------------------------------
Infiltration Criteria in 406.I.ABC.1 have been met. ICHECKI/
407.-=----COOLING SYSTEMS -------------------------
No Efficiency IPLV Tons
1. Single Package 3 10.0 0.0 4.00
408.------HEATING SYSTEMS -----------------------------------------------
Type No Efficiency BTU/hr
1. Electric Resistance 3 1.0 35000
409.------VENTILATION ---------------------------------------------------
CHECK
Ventilation Criteria in 409.1.ABC.1 have been met.
410.-----AIR DISTRIBUTION SYSTEM ----------------------------------------
AHU Type Duct Location R-value
Ventilated 611'. packaged Constant Volume
411.-----PUMPS AND PIPING -ZONE 1 ---------------------------------------
Type R-value/in Diameter Thickness
1. Non -Circulating w/o Heat 3.63 0.75 1.0
412.--- -WATER HEATING SYSTEMS -ZONE 1----------------------------------
Type Efficiency StandbyLoss InputRate Gallons
413.-----ELECTRICAL POWER DISTRIBUTION----------------------------------
CHECK
Metering criteria in 413.1.ABC.1 have been met.
Transformer criteria in 413.I.ABC.2 have been met. WA
414.-----MOTORS ---------------------------------------------------
Motor efficiencies in 414.1.ABC.1 have been met. t--
415.-----LIGHTING SYSTEMS -ZONE 1------------------------------------- -
Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)
Reading, T 1 On/Off 2 None 00 350 285
Reading, T 1 On/Off 2 None 00 350 265
Reading, T 1 On/Off 2 None 00 350 278
Reading, T 1 On/Off 2 None 00 350 278
Reading, T 1 On/Off 2, None 00 350 278
Reading, T 1 On/Off 2 None 00 350 278
Reading, T 1 On/Off 2 None 00 350 278
Reading, T 1 On/Off 2 None 00 350 278
Reading, T 1 On/Off 2 None 00 350 278
Reading, T 1 On/Off 2 None 00 350 278
Toilet and 1- On/Off 2 None 00 180 149
Toilet and 1 On/Off 2 None 00 120 77
Toilet and 1 On/Off 2 None 00 120 77
Toilet and 1 On/Off 2 None 00 180 155
Total Watts for Zone 1 4104
Total Area for Zone 1 3251
Total Watts 4104
Total Area 325I
CHECK
Lighting criteria in 415.1.ABC have been met.
16. HVAC load sizing has been performed. (407.1.ABC.1)
17. Duct sizing and design have been performed. (410.1.ABC.1.2)
18. Testing and balancing will be performed. (410.I.ABC.4)
19. Operation/maintenance manual will be provided to owner.(102.1)