HomeMy WebLinkAbout1701 W 13 St Load Calcs Rescue MissionWALL PLUMING & HEATING, INC
1007 SANFORD AV.
SANFORD, FL. 32771
4 (
305) 322-6562 MANUAL J WHOLE -HOUSE LOADSHEET.
Customer's Name RESCUE MISSION Address
I _''CITY PHONE DATE 03/26/87
WINTER:Inside Temp 75 F-Outside Temp 32 F=Heating Temp Difference 43 F
SUMMER:'Outside Temp 95 F-Inside Temp 78 F=Cooling Temp Difference 17 F
HEATING * COMMON DATA SECTION * COOLING *'
BTU * HEATING * * * COOLING * BTU
LOSS * FACTOR * SUBJECT * SQ. FT. * FACTOR * GAIN *'
GROSS WALL 1056
1380 DOOR & WINDOWS 116 3624
723 .77 NET WALL 940 2.3 2162
954 .53 CEILING 1800 2.5 4500
1069 8.1 FLOOR 132 0. 0
INFILTRATION
VOLUME OF BUILDING BTU/HR.
14400 1795
S
4126 SUB -TOTAL BTU LOSS
X 5 ADJUSTMENT FACTOR
20630 TOTAL BTU LOSS r,
5
PEOPLE 15
X 300 BTU 4500
APPLIANCES BTU 1200
SUB -TOTAL BTU GAIN 17781
X 1.15 DUCT LOSS/GAIN FACTOR X 1.15
SUB -TOTAL BTUH 2O448
MOISTURE REMOVAL X 1.3
23724 TOTAL BTUH LOSS/GAIN 26582
BTU GAIN X ACCA FACTOR = EQUIPMENT CAPACITY @ 95 F ARI RATING
26582 X -1.05 27911 BTUH MINIMUM REQUIRED
ELECTRIC HEATER OR FURNACE DIVIDE USING 3413 BTUH/KW,NATURAL GAS
OR PROPANE FURNACE... SELECT OUTPUT TO BE AS CLOSE TO HEAT LOSS AS
POSSIBLE.
TOTAL LOSS 23724 / 3413 6 KW
iswU 730 ( eS86. 3 l. So el ,4 qT"v Coo,c.i-V FACIJ .S, DL
I7.ati
i
CFM PER ROOM
I
FLEX
ROOM
CFM
I'
WOMMENS DORM 235 X 2 9
BATH
16 X 1 5
93 X 1 6
SHOWER Ili9
MEETING II
TOTAL CFM. 1097
ALL PLUMING & HEATING, INC
1007 SANFORD AV. l
SANFORD, FL. 32771
305) 322-6562 MANUAL J WHOLE -HOUSE LOADSHEET
Customer's Name RESCUE MISSION Address 1701 W. 13TH. ST.
CITY.SANFORD PHONE RICHARD BURKE DATE 03/26/87
WINTER:Inside Temp 75 F-Outside Temp 32 F=Heating Temp Difference 43 F
SUMMER:Outside Temp 95 F-Inside Temp 78 F=Cooling Temp Difference 17 F
04
y *
HEATING * COMMON DATA SECTION * COOLING *
BTU * HEATING * * * COOLING * BTU
LOSS * FACTOR * SUBJECT * SQ. FT. * FACTOR * GAIN
GROSS WALL 736
1666 DOOR & WINDOWS 174 3170
432 77 NET WALL 562 2.3 1292
1102 53 CEILING 2080 2.5 5200
745 8.1 FLOOR 92 0 0
l
INFILTRATION
VOLUME OF BUILDING BTU/HR.
16640 2074
3945 SUB -TOTAL BTU LOSS
X 5 ADJUSTMENT FACTOR •
19725 TOTAL BTU LOSS l
PEOPLE 80
X 300 BTU 24000
APPLIANCES BTU 1200 e
SUB -TOTAL BTU GAIN 36936
X 1.15 DUCT LOSS/GAIN FACTOR X 1.15
SUB -TOTAL BTUH 42477
MOISTURE REMOVAL X,1.3
22683 TOTAL BTUH LOSS/GAIN 55220
BTU GAIN X ACCA FACTOR = EQUIPMENT CAPACITY @ 95 F ARI RATING
55220 X 1.05 = 57981 BTUH MINIMUM REQUIRED t
ELECTRIC HEATER OR FURNACE DIVIDE USING 3413 BTUH/KW,NATURAL GAS
OR PROPANE FURNACE... SELECT OUTPUT TO'BE AS CLOSE TO HEAT LOSS AS
POSSIBLE.
TOTAL LOSS 22683 / 3413
3rD 7(ol4 S.50
Btu 7`0P
6 KW
S 8, o o e 13T
Sc-,E OAF A,), CFIVTF8
i
CFM PER ROOM
ROOM CFM FLEX
KIT 326 X 2 10
7
LANDRY 148 X 2
I NING 525 X 2 12
J DIN
IJ TOTAL CFM 1998
i
lJ i
s
4
WALL PLUMING & HEATING, INC
ram.
1007 SANFORD AV.
SANFORD, FL. 32771
305) 322-6562 MANUAL J WHOLE -HOUSE LOADSHEET
Customer's Name RESCUE MISSION Address
1 ` _`'CITY PHONE DATE 03/26/87
I
WINTER:Inside Temp 75 F-Outside Temp 32 F=Heating Temp Difference 43 F
SUMMER:Outside Temp 95 F-Inside Temp 78 F=Cooling Temp Difference 17 F
HEATING * COMMON DATA SECTION * COOLING *'
BTU * HEATING * * * COOLING * BTU
LOSS * FACTOR * SUBJECT * SQ. FT. * FACTOR * GAIN * i
GROSS WALL 1056
1380 DOOR & WINDOWS 116 :3624
723 .77 NET WALL 940 2.3 2162
954 .53 CEILING 1800 2.5 4500
j 1069 8.1 FLOOR 132 0. 0
I
INFILTRATION
VOLUME OF BUILDING BTU/HR.
14400 1795
4126 SUB -TOTAL BTU LOSS
X 5 ADJUSTMENT FACTOR
20630 TOTAL BTU LOSS
S PEOPLE, 15
X 300 BTU 4500
APPLIANCES BTU 1200
SUB -TOTAL BTU GAIN 17781
X 1.15 DUCT LOSS/GAIN FACTOR X 1.15
SUB -TOTAL BTUH 2O44.8
MOISTURE REMOVAL X 1.3
23724 TOTAL BTUH LOSS/GAIN 26582 r..
BTU GAIN X ACCA FACTOR = EQUIPMENT CAPACITY @ 95 F ARI RATING i
26582 X 1.05 = 27911 BTUH MINIMUM REQUIRED
ELECTRIC HEATER OR FURNACE DIVIDE USING 3413 BTUH/KW,NATURAL GAS
OR PROPANE FURNACE... SELECT OUTPUT TO BE AS CLOSE TO HEAT LOSS AS ` r
POSSIBLE.
TOTAL LOSS 23724 / 3413 6 KW
O w D 730 f 7 4S P' 9 l/. Fo o ,d 77V Co o
cv r' s '
1'e c O c2L
r4C J .
CFM PER ROOM
ROOM CFM FLEX
WOMMENS DORM 235 X 2 9
BATH 16 X 1 5
SHOWER 93 X 1 6
MEETING 259 X 2 9
TOTAL CFM. 1097
1- 1
WALL PLUMING & HEATING, INC
1007 SANFORD AV.
SANFORD, FL. 32771
305) 322-6562 MANUAL J WHOLE -HOUSE LOADSHEET
Customer's Name RESCUE MISSION Address 1701 W. 13TH. ST.
CITY SANFORD PHONE RICHARD BURKE DATE 03/26/87
WINTER:Inside Temp 75 F-Outside Temp 32 F=Heating Temp Difference 43 F
SUMMER:Outside Temp 95 F-Inside Temp 78 F=Cooling Temp Difference 17 F
HEATING * COMMON DATA SECTION * COOLING *
BTU * HEATING * * * COOLING * BTU
e * LOSS * FACTOR * SUBJECT * SQ. FT. * FACTOR * GAIN *
GROSS WALL 736
1666 DOOR & WINDOWS 174 3170
432 77 NET WALL 562 2.3 1292
1102 53 CEILING 2080 2.5 5200
745 8.1 FLOOR 92 0 0
INFILTRATION
VOLUME OF BUILDING BTU/HR.
16640 2074
L:
I
J
3945 SUB -TOTAL BTU LOSS
X 5 ADJUSTMENT FACTOR
19725 TOTAL BTU LOSS
PEOPLE 80 -
X 300 BTU 24000
APPLIANCES BTU 1200
SUB -TOTAL BTU GAIN 36936
X 1.15 DUCT LOSS/GAIN FACTOR X 1.15
SUB -TOTAL BTUH 42477
MOISTURE REMOVAL X,1.3
22683 TOTAL BTUH LOSS/GAIN 55220
BTU GAIN X ACCA FACTOR = EQUIPMENT CAPACITY @ 95 F ARI RATING i
55220 X 1.05 57981 BTUH MINIMUM REQUIRED L
i
ELECTRIC HEATER OR FURNACE DIVIDE USING 3413 BTUH/KW,NATURAL GAS
OR PROPANE FURNACE... SELECT OUTPUT TO BE AS CLOSE TO HEAT LOSS AS
POSSIBLE.
TOTAL LOSS 22683 / 3413 6 KW
AY6:
3T D 7 6 o/4 .50 S ep,
4 cv 76 o P FNTE. srSri.aAl ...
L.i S.E 2.
CFM PER ROOM
ROOM CFM FLEX
KIT 326 X 2 10
LANDRY 148 X 2 7
DINNING 525 X 2 12
lTOTAL CFM 1998