HomeMy WebLinkAbout2251 WP Ball Blvd (04 2574) (rev) World Market.. , SANFORD F. IRE DEPARTMENT
FIRE PREVENTION DIVISION �*
300 N. Park Ave., Sanford, F1432771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 302-2526
Plans Review Sheet
Date: June 17, 2004 Business Address: 2251 W.P. Ball Blvd.
Occ. Ch. 36, Mercantile . Class W
Business Name: World Market Market Ph. (770) 394-1616
FAX (770)394-1314
Architect: Phillips Partnership
PH (770) 394-1616
Fax. (770) 394-1314
Comment: Plans reviewed as Mercantile Occupancy. FD reserves right to require
applicable code requirements if occupancy use changes. Sprinkler plans to be submitted for
review, permitting, and inspections. Sealed letter from Engineer of Record stating design
criteria for sprinkler system needs to be submitted with construction plans.
Separate permit required for Fire Alarm.
1.1 Fire Alarm required for monitoring of sprinkler system
1.2Application — New Building (18,083 s. q. ft.)
1.3 Mixed — N/A, all restaurants under 50 occupancy load
1 ASpecial Definitions — Class "B" Mercantile Store (Under 30,000 sq ft.)
1.5 Classification of Occupancy — Mercantile Store Class `B"
1.6 Classification of Hazard of Contents — Ordinary in office areas, and storage area
classified as "High Hazard" per L.S.C. 101
1.7 Minimum Construction — Shall comply with Florida Building Code 2001
mercantile occupancy Type IV, UNPROTECTED
4
1
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, FI.32772
(407 302 2520I FAX (407) 302 2526
1.8 2.2 Means of Egress Components SHALL BE DILINEATED'!
WITH 44" el�lowamto'n floor, ead�ri to EXIT.do"or
2.3 Capacity of Egress — sales floor area based on one (])_person per 30 sq ft., storage area
based on one (1) person per 300 sq. ft.
2.4 Number of Exits — (Minimal of four (4) required EXITS)
2.5 Arrangement of Egress: Travel distance increased up to 200' (ft) do to fire sprinkler system
2.6 Travel Distance Rear,: EXIT�SHALLBEDILINEATEDW,,,.,ITH 44'3' yellow pai t on floor
leading to..EXIT door;.
2.7 Discharge from Exits — O.K., will field verify
2.8 Illumination of Means of Egress —additional EXIT SIGNS may be required (power shut
down test required at night only)
2.9 Emergency Lighting — (1) foot candle (101x & a minimum at any point of 0.1
foot-candle (1 LX) measured along the path of egress at floor level. Therefore
additional emergency lights may be required, (power shut down test required at night
only)
Emergency Lighting required inside Main Electrical room and all rest rooms (*).
2.10 Marking of Means of Egress — O.K.; will field verify?
2.11 Special Features —Reserved
3.1 Protection of Vertical Openings — Class () mercantile shall have an automatic fire
sprinkler system. design criteria SHALL SHOW storage maximum height in
storage area M.
3.2 Protection from Hazards — (See exception 36-3.2.1 .LSC 101)
3.3 Interior Finish — Not required, building has an automatic fire sprinkler system
3.4 Detection, Alarm and Communications System: (as per N.F.PA.72- 3-8.3.1.2 (99)
Ed.
• 3.5 Extinguishing Requirements —as per NFPA 10, five (5) fire extinguishers required
per N F RA... #10 See blue prints (Minimal 4A 60 B. C. Rated) M.
2
. ; . SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, FI. 32772
(407 302-2520 I FAX (407) 302-2526
5.1 Utilities — as per LSC 7-1
5.2 HVAC — as per LSC 7-2
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
Sanford City Code — Chapter9:
Required; Fire Sprinklers. Fire Department will field verify sight glass at all inspectors
test.
Monitoring: Required for fire sprinkler system and all inside and outside fire sprinkler valves.
Other: NFPA 1
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box — One (D required see application attached
3-7.1 Bldg. Address Number Posted and Legible — Post address in 6" six inch numbers
contrasting in color (see blueprints).
REVISIONS
FERN IT #
(-65T ivw5 LQe--*Lt2 &)CPK Ot-
GATE 21X1
ADDRESS
I- U 19
C" 0 N T R A C T 0 R L)
PH-7- n-' 6 A
1--\
_ _2 __jL _ a�._ F X # '1,67-668-0716
D-
Z) I-, l""'PRI"CION OF REVISIM:
U"T 11LITIE
FIRE _ /
BLDG
c ITY
'604
SEA' I
R�i
REVISIONS
PERMIT # o t4--=Z.5-?L{ DATE $-4 &q
ADDRESS 2.Z 5-1
CONTRACTOR i,��� i�,-�. -�► n �� i
P H # �1 �? a �SZ�-� Z,�o FAX
DESCPRITION OF REVISION: e4
UTILITIES
FIRE
BLDG
PH I LL I P PWTh4F!-l."--: H lFF Fa.,,,: :770-31:14-1314-' Auq-:�18 '04 11 - I I
REVISIONS
4 . PERMIT # "4% DATE't
-
ADDRESS-1,1-5 [-63r, &Lm-o
CONTRACTOR aaumAo- 0
FAX 272
PH ft x #
DF-SCMITIOPI OF REVISION:
1,2
FIRE -
Ed L D \'-'-'j
OF SS Afi, iNf JD
AUG 3 0 2004
,R- EC,EIVEU
6
0
ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Community Affairs
EnergyGaugeFlaCom v1.22 FORM 40OB-2001
Component Performance Method for Commercial Buildings
Jurisdiction: SANFORD, SEMINOLE COUNTY, FL (691500)
Short Dese: Cost +/World Mkt. Project: The Marketplace at Seminole Center
Owner: North American Properties
Address: 1400 Rinehart Road
.Seminole Town Center
City: Sanford
State: Florida PermitNo: 0
Zip: 32771 Storeys: I
Type: Retail (mercantile) GrossArea: 18012
Class: New Shell building Net Area: 18012
Max Tonnage 1 S (if d fferent, write in)
Compliance Summary
Component
Design Criteria Result
1 AJ"ELOPE
379.33 1,556.30 PASSES
Other Envelope Requirements - B
PASSES
LIGHTING POWER
Not Requested
11GHTTNTG C'O:NTTROLS
Not Requested
F__lTER,V4L LIGHTING
Not Requested
111 ,IC SYSTEM
PASSES
I'L,4NT
Not Requested
it _ I TER HEATING SYSTEMS
Not Requested
PIPI_VG SYSTEMS
Not Requested
.1let all required compliance from Check List?
Yes/No/NA
IMPORTANT NOTE: An input report Print -Out from EnergyGauge HaConz of
this design building must be submitted along with this Compliance Report.
N ; 2004
EnergyGauge HaCom FLCCSB v1.22
COMPLIANCE CERTIFICATION:
I hereby certify that the plans and
specifications covered by this calculation are
in compliance with the Florida Energy
Efficiency Code.
I PREPARED BY: Gerald M. Skala. P.E.
Review of the plans and specifications covered by this
calculation indicates compliance with the Florida Energy
Code. Before construction is completed, this building will be
inspected for compliance in accordance with Section
553.908, F.S.
BUILDING OFFICIAL:
DATE: DATE:
i hereby certify that this building is in compliance
with the Florida Energy Efficiency Code.
OWNER AGENT:
DATE:
If required by Florida law, I hereby certify (") that the system design is in
compliance with the Florida Energy Code.
ARCHITECT:
ELECTRICAL SYSTEM DESIGNER:
LIGHTING SYSTEM DESIGNER:
MECHANICAL SYSTEM DESIGNER:
I'LUMBING SYSTEM DESIGNER:
REGISTRATION
No.
Philips Partnership
Charles C. Jordan, Jr., P.E. 45525
Charles C. Jorda, Jr., P.E. 45525
Gerald M. Skala, P.E. 32482
Gerald M. Skala, P.E. 32482
(') Signature is required where Florida Law requires design to be performed by registered design professionals.
TypFA names and registration numbers may be used where all relevant information is contained on signed/sealed
plans.
Project: Cost +/World Mkt.
Title: The Marketplace at Seminole Center
TA pe: Retail (mercantile)
Location: SANFORD, SEMINOLE COUNTY. FL (691500)
(NV E
Envelope Compliance
Design Load Criteria
Zone Heating Cooling Heating Cooling
Zone I (CONDITIONED) 0.00 379.33 -4.44 1,551.86
�TF.AM Loads: Design=379.332 Criteria=1556.297
L
PASSES
1`1.1 '-1004 EnergyGauge FlaCom FLCCSB v1.22 2
Project: Cost +/World Mkt.
.Title: The Marketplace at Seminole Center
Ti pe: Retail (mercantile)
Location: SANFORD, SEMINOLE COUNTY, FL (691500)
(WE
Other Envelope Requirements
Item Zone Description
Design Limit Meet Req.
Zone 1 % SAylight - Max % Limit
0.00 6.70 Yes
PrOZo1)?f1 Zone 1 Exterior Roof- Max Uo Limit
0.05 0.07 Yes
:Meets Other Envelope Requirements
Project: Cost +/World Mkt.
Title: The Marketplace at Seminole Center
Type: Retail (mercantile)
Location: SANFORD, SEMINOLE COUNTY, FL (691500)
(WE
System Report Compliance
Pk-OSy2 System 2
Constant Volume Packaged No. of Units
System 4
Component Category Capacity
Design Eff Design IPLV Comp-
Eff Criteria IPLV Criteria liance
c 'oolin System Air Cooled 135000 to 760000
9.90 8.50 8.00 7.50 PASSES
Btu/h Cooling Capacity
iir Handling SrstemAir Handler (Supply) -
0.80 0.80 PASSES
-5'1fppl1' Constant Volume
PASSES
S"5 '004 EnergyGauge FlaCom FLCCSB 0.22
ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Community Affairs
EnergyGauge FlaCom v1.22
INPUT DATA REPORT
Project Information
Project Name:
Cosh +%World Mki.
Orientation:
North
Project Title:
The Marketplace at Seminole Center
Building Type
Retail ("mercantile)
Address:
Seminole Toivn Center
Building Classification:
Nevi, Shell building
1400 Rinehart Road
State:
Florida
No.of Storeys:
1
Zip:
32771
GrossArea:
18012
Owner: North American Properties
Zones
No Acronym Description Type Load Profile Area Multiplier Total Area
JsfJ JsfJ
I Zone 1 Cost Plus/World Market CONDITIONED FlaCom retail 18012.0 1 18012.0 ❑
building
8/5/2004 EnergyGauge FlaCom FLCCSB v1.22 1
Spaces
No Acronym Description Type Depth Width Height Multi Total Area Total Volume
Iftl Ifti Iftl plier lsfl lcfl
In Zone: Zone 1
l Spacel Zo1Sj)l
Retail Establlshmenis
(Merchandising K
Circulation Area) Applicable
to all lighting, including
accen
158. 00 11-1. (Ill 20.00 1
l S012.0 360240.0 ❑
Lighting
No
Type
Power
Control Type
No.of
I W I
Ctrl pts
In Zone: Zone 1
In Space: Spacel
1
Compact Fluorescent
1000.00
None
1
Walls
No
Description
Type
Width H (Effec) Multi
Area
DirectionConductance
Heat
Dens.
R-Value
Ifti
IN plier
jsfj
I Btu/hr. sf. FJ
Capacity
jib/cfl
Ih.sf.F/Btul
l Btu/sf. Fl
In Zone: Zone
I
PrOZoI WaI
Exterior Wall 1
36.00
24.00 1
864.0
North Wes 0.0616
1.0862
10.69
16.24
t
2
PYOZol Wag
Exterior 141all2
78.00
24.00 1
1872.0
NorthOles0.2963
5.4862
38.71
3.37
t
3
PrOZoI WO
Exterior N,a/l 2
114.00
20.00 1
2280.0
5outhEast 0.2963
5.4862
38.71
3.37
4
PYOZOI Wa4
Exterior Wall 2
173.00
22.00 1
3806.0
East-Nort 0.2963
5.4862
38.71
3.37
hEast
8/5/2004 EnergyGauge FlaCom FLCCSB v1.22 2
Windows
No Description Type
Shaded UCen SC
Vis.Tr
11/ H (Effec) Multi
Total Area
IBtu/hr sf FI
Iftl Iftl plier
[sf)
In Zone: Zone I
In Wall: PrOZolWal
1 P/'OZoI1,Ya10ii1 DOUBLECLEAR No 0.6514 0.88
0.81
35.00 12.00 1
420.0
IG
Doors
No Description Type
Shaded? Width H (Effec) Multi
Area
Cond. Dens. Heat Cap. R-Value
[ftl Iftl
plier
Isfl
[Btu/hr. sE FI llb/cfl IBtu/sf.
FI Ih.sf.F/Btul
In Zone:
In Wall:
El
Roofs
No Description Type
Width H (Effec) Multi
Area
Tilt
Cond. Heat Cap
Dens. R-Value
IN Iftl plier
Isfl
Idegl
[Btu/hr. Sf. Fl [Btu/sE FI
Ilb/cfl Ih.sLF/Btul
In Zone: Zone 1
I PrOZoIRfl membrane roof
114.00 158.00 1
18012.0
0.00
0.0470
21.28
❑
w/R-20 rigid
insulation
Skylights
No Description Type
UCen Shading Vis.Trans
W
H (Effec) Multiplier
Area Total Area
[Btu/hr sf Fj Coeff
Iftl
Iftl
ISfI IS11
In Zone:
In Roof:
El
8/5/2004 EncrgyGauge FlaCom FLCCSB v1.22
Floors
No Description Type Width H (Effee) Multi Area Conti. Heat Cap. Dens. R-Value
IN Iftl plier Isfl lBtu/hr. sf. F1 jBtu/sf. Fj jib/cfl Ih.sf.F/Btul
In Zone: Zone
I 1'rOZoll11 Concretc_Jloor, 114.00 158.00 1 18012.0 0.5987 9.33 140.00 1.67 ❑
carpet and rubber
pad
Systems
PrOSy2 System 2
Constant Volume Packaged System,
No. Of Units 4
Component Category
Capacity
Efficiency IPLV
I Cooling System (Air Cooled 135000 to 760000 Btu/h
Coolh?g Capacity)
2 Air Handling System -Supply (Air Handler (Suppl}) -
Constant Volume,)
180000.00
6000.00
9.90 8.00
0.80
❑
❑
Plant
Equipment
Category
Size
Inst.No Eff.
IPLV
Water Heaters
W-Heater Description
Capacit Cap.Unit
1/P Rt.
Efficienc
Loss
I Storage Water Heater - Electric
10 Cal
2 [klv]
0.9700 [EF]
[%/h�� ❑
8/5/2004 EnergyGauge FlaCom FLCCSI3 v1.22 4
Ext-Lighting
Description
Categories.
Area/Lcn/No. of writs
Wattage
I
[sf/ft/No J
[ W ]
I Ext Light I
Entrance (ivy Canopy) High
384.00
600.00
❑
trcr. ic-retail, hotel, airport, theatre etc
2 Ext Light 2
Evil 0vilh or withow Canop}J
3.00
175.00
❑
3 Ext Light 3
Exit (with or without Canopy)
3.00
175.00
❑
Piping
No Type
Operating Insulation
Nomonal pipe
Insulation
Is Runout?
Temperature Conductivity
Diameter
Thickness
1171 [ Btu-in/h.sf.Fl
linj
[in[
I Domestic and Service Hot Water Systems
105.00 0.23
0.75
1.00
No ❑
2 Domestic and Service Hot Water Systems
105.00 0.23
1.00
1.00
No ❑
Fenestration Used
Name
Glass Type No. of
Panes
Glass SC VLT
Conductance
[Btu/h.sf.Fl
Frame
Conductance
[Btu/h.sf.F1
Frame
Absorptance
ApLbWnd6
DOUBLE CLEAR IG 2
0.6514 0.8800 0.8120
0.4340
0.7000 ❑
Materials Used
Mat No Acronym
Description
Only R-Value RValue Thickness
Used Ih.sf.F/Btu[ [ft[
Conductivity Density
[Btu/h.ft.F[ [Ib/cfl
SpecificHeat
[Btu/Ib.F[
264 A1at1264
ALU,411NUA1, 1116IN
No 0.0002 0.0050
26.0000 480.00
0.1000 ❑
8/5/2004 EnergyGauge FlaCom FLCCSB v1.22 5
214
,llull2 i -1
POLYSTYRENE. ",STYRENE. E,A"P. •
A'o
5.2 i 00
0.11042
0. 0'00
/. so
0.2900
❑
1-li41N.
I S7
1111/0 `"T
G) P (")fZ 1'1.AS
vo
!J, l
0.041 i
0.0920'
50.00
0.=000
❑
BOARD, 112/N
206
Mat1206
CELL UL OSE, FILL, 5.5/N, R-2
No
10.8318
0.4583
0.0220
3.00
0.3300
❑
0
151
Mut1151
CONC HW DRD, 140LB,
No
0.4403
0.3333
0.7 570
140.00
0.2000
❑
41N
178
Mut1178
CARPET IV/RUBBER PAD
Yes
1.2300
❑
265
Matl265
Soil, I ft
No
2.0000
1.0000
0.5000
100.00
0.2000
❑
48
Mat148
6 in. Heavyweight concrete
No
0.5000
0.5000
1.0000
140.00
0.2000
❑
123
Mat1123
CONC BLOCK
No
1.7227
0.6667
0.3870
53.00
0.2000
❑
MW, 81N, HOLLOW
159
Mat1159
CONC
No
0.3202
0.3333
1.0410
140.00
0.2000
❑
HW-UNDRD-140LB-41N
57
A4at157
3/4 in. Plaster or gypsum
No
0.1488
0.0625
0.4200
100.00
0.2000
❑
72
Mat172
AIR LAYER, 3141N OR LESS,
Yes
0.9000
❑
VERT. WALLS
267
Mad267
0.75"stucco
No
0.1563
0.0625
0.4000
16.00
0.2000
❑
266
Ma11266
2x4(a.16" oc + RI I Butt
No
8.3343
0.2917
0.0350
9.70
0.2000
❑
215
Mat1215
POLYSTYRENE, EXP., 21N,
No
8.3350
0.1667
0.0200
1.80
0.2900
❑
105
Mall105
CONC BLK HW, 81N,
No
1.1002
0.6667
0.6060
69.00
0.2000
❑
HOLLOW
256
Mat1256
WOOD, SOFT, 1-112IN
No
1.8939
0.1250
0.0660
32.00
0.3300
❑
268
Mat1268
0.625"stucco
No
0.1302
0.0521
0.4000
16.00
0.2000
❑
42
Mutl42
8 in. Lightweight concrete
No
2.0212
0.6670
0.3300
38.00
0.2000
❑
block
269
A4at1269
.75" ISO BTWN24" oc
No
2.2321
0.0625
0.0280
4.19
0.3000
❑
86
Mat186
BRICK, COMMON, 41N
No
0.8012
0.3333
0.4160
120.00
0.2000
❑
211
Mat12/I
POLYSTYRENE,EXP.,1/21N,
No
2.0850
0.0417
0.0200
1.80
0.2900
❑
12
Mat112
3 in. Insulation
No
10.0000
0.2500
0.0250
2.00
0.2000
❑
218
Mat1218
POL YURETHA NE, EXP., 1121
No
3.2077
0.0417
0.0130
1.50
0.3800
❑
n
23
AfatI23
6 in. Insulation
No
20.0000
0.5000
0.0250
5.70
0.2000
❑
4
A4atl4
Steel siding
No
0.0002
0.0050
26.0000
480.00
0.1000
❑
271
A4at1271
2x4(--24" oc + RI I Batt
No
10.4179
0.2917
0.0280
7.11
0.2000
❑
272
Matl272
Panel with 7/16"panels
Yes
0.9044
❑
273
Ma11273
Ho//ow core flesh (1.37.5")
Yes
1.2777
❑
274
AfatI274
Solid core flush (1.375°)
Yes
1.7141
❑
8/5/2004 EnergyGauge HaCom FLCCSB v1.22 6
275
;1 h02-5
Palle/ frith '.'l6" puncl.�
] cs
1.0019
(1.375")
'-6
Mull_'-6
li,ir'l<�ir�vrc/irrshil.^5"J
Ycs
i.3_'i9
❑
277
Alatl277
Panel frith 1-118"panels
Y'c:c
1.7141
❑
(1.75')
278
A4at1278
Solid core flush (1.75')
Yes
1.6500
❑
279
Allutl279
,Solid core flush (2.25')
Yes
2.8537
❑
280
Mat1280
Fibergluss/Alineral wool core
Yes
0.8167
❑
281
Matl281
Paper Honeycomb core
Yes
0.9357
❑
282
Mat1282
Solid Urethane foam core
Yes
1.6500
❑
283
Mat1283
Solid mineral fiberboard core
Yes
1.7816
❑
284
Mati284
Polystyrene core (18 ga steel)
Yes
2.0071
[]
1
285
Mat1285
Polyurethane core (18 ga
Yes
2.5983
❑
steel) 2
286
Mat1286
Polyurethane core (24 ga
Yes
2.5983
❑
steel) 1
287
Mat1287
Polyurethane core (24 ga
Yes
4.1500
❑
steel) 2
288
Matl288
Solid Urethane foam core
Yes
4.1500
❑
81
Mail81
ASPHALT -ROOFING, ROLL
Yes
0.1500
❑
244
Mat1244
PLYWOOD, 1121N
No
0.6318
0.0417
0.0660
34.00
0.2900
❑
185
Ma11185
CLAYTILE, PAVER, 3181N
No
0.0301
0.0313
1.0410
120.00
0.2000
❑
82
Nfat182
ASPHALT -SHINGLE AND
Yes
0.4400
❑
SIDING
11
Matll1
2 in. Insulation
No
6.6800
0.1670
0.0250
2.00
0.2000
❑
47
Mat147
2 in. Heavyweight concrete
No
0.1670
0.1670
L0000
140.00
0.2000
❑
95
Mat195
CONC BLOCK
No
0.7107
0.3333
0.4690
101.00
0.2000
❑
HiV 41N-HOLLOW
248
A-1atl248
ROOF GRA VEL OR
No
0.0500
0,0417
0.8340
55.00
0.4000
❑
.SLAG 112IN
94
Mat194
BUILT-UP ROOFING, 318IN
No
0.3366
0.0313
0.0930
70.00
0.3500
❑
1001
ApLbMat1001
Concrete Block, 12-inch,
No
1.6502
1.0000
0.6060
69.00
0.2000
❑
1002
ApLbMat1002
CA9U core fill insulation
Yes
4.0000
❑
1003
ApLbA4atI003
Rigid insulation
Yes
20.0000
❑
Constructs Used
8/5/2004 GnergyGauge HaCom FLCCSB v1.22 7
No
Name
Simple
Massless
Conductance
Heat Capacity
Density
RValue
Construct
Con Str(Ict
�lit ulh.sf.FI
IBtu/sf.F]
IIb/ef1
jh.sf.F/Btu1
1004
Concrete /loor, cagy/ and r'ubbel. pad
No
No
U.6U
�J.33
/ IO.OiI
1.6703
❑
Layer Material Material
Thickness
Framing
No.
I ft i
Factor
1 151 CONC NW, DRD,
140LB, 41N
0.3333
0.00
❑
2 178 CARPET W/RUBBER PAD
0.00
❑
Simple
Massless
Conductance
Heat Capacity
Density
RValue
No
Name
Construct
Construct
I Btu/h.sf.Fl
lBtu/sf.Fl
jib/cfl
Ih.sf.F/Btul
1049
membrane roof w/R-20 rigid insulalion
Yes
Yes
0.05
21.2766
❑
U
Simple
Massless Conductance
Heat Capacity
Density RValue
No Name
Construct
Construct I Btu/h.sf.Fl
IBtu/sf.FI
alb/cfl [h.sf.F/Btul
1054 Exterior Wall 1
No
No 0.06
1.09
10.69 16.2374 ❑
Layer
Material
Material
Thickness
Framing
No.
(ft i
Factor
1
267
0.75"stucco
0.0625
0.00
❑
2
214
POLYSTYRENE, EXP., 1-1/41N,
0.1042
0.00
❑
3
271
2x4(n.24" oc + RI1 Ball
0.2917
0.00
❑
4
187
GYP OR PLAS BOARD,112IN
0.0417
0.00
❑
8/5/2004 EnergyGauge FlaCom FLCCSB v1.22 8
No Name
Simple Massless
Construr_t Construct
1055 Exterior Wall 2 Ao ,1'0
Layer
Material
Material
No.
1
42
8 in. Lightweight concrete block
2
72
AIR LAYER, 3141N OR LESS, VERT.
WALLS
3
187
GYP OR PLAS BOARD,112IN
Conductance
Heat Capacity
Density
RValue
jBtn/h.sf.Fj
113tu/sf.F1
jib/ct'l
Jh.sf.F/Btuj
0.30
5.49
3,�.71
3.3.145 ❑
Thickness
Iftl
0.6670
0.0417
Framing
Factor
0.00
0.00
0.00
8/5/2004 EnergyGauge FlaCom FLCCSB vl.22 9