HomeMy WebLinkAbout1270 Upsala Rd 03-1887 Fire plans reviewF D'
SANFORD FIRE DEPARTMENT
FIRE PREVENTIONDIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
Plans Review Sheet
Date: January 13, 2004 Business Address: 1270 Upsala Road
y,
Occ. Business Ch. #38
Business Name: Upsala Executive Center, Inc. Ph. Not given
Contractor: Anderson Fire Sprinkler Inc.. Ph. (407) 788-2110
Fax. (407) 862-5731
Reviewed[ ] Reviewed with comment [x I Rejected [ ]
Underground Fire Line instillation with two (2) fire hydrants, F.D.C. Back Flow and riser
Reviewed by: Timothy Robles, Fire.Protection Inspector/Plans Examiner
Comment: The Sanford Fire Department has reviewed this submittal and plans our approved
with comments (see below)
1.1 Application — Point of service from 6' ft wet tape off city -line Mixed — NA
1.2 From Tap: 14' (ft) of C-900 DR-18 P. KC & 10' (ft) of DR-18 to back flow prey (6')inch
1.3 Reducer — 6 x 4 reducing to 4 " inch riser for fire sprinkler line
2.2 Four Inch (411-120' ft of 4" c-900 dr pvc
' 03—/C_817
f
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
2.3 FIre Hydrants- Two off 6" line with independent valves paint all fire hydrants red (private
color) and provide pavement markers.
2.4 Fire Hydrant Underground: 272' (ft) of C-900 DR-18 PVC main to hydrants
2.5 Inspection Requirements— 48 notice on fire inspections Ph (407) 302-1022
• Two hour hydro required on all under ground pipe
• Two (2) flushes required 6 min. each and or until water is clear
2
t rAr�
a
J5.
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
Plans Review Sheet
Date: January 13, 2004 Business Address:
Occ. Business Ch. #38
Business Name: Upsala Executive Center, Inc.
Contractor: Anderson Fire Sprinkler Inc. .
1270 Upsala Road
Ph. Not given
Ph. (407) 788-2110
Fax. (407) 862-5731
Reviewed[ ] Reviewed with comment [x I Rejected [ ]
Above Fire Sprinkler instillation of three (3) floors office area (Light Hazard)
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner `
Comment: The Sanford Fire Department has reviewed this submittal and plans our approved
with comments (see below)
1.1 Application — Point of service from 6' ft wet tape off city line
1.2 Design— Per N.F.P.A. #131999 Edition LT Hazard
1.3 Fire Sprinkler- (Two hundred & sixty six heads) 266 total install
1.4 Area #2 — 10 density Tyco 2 " orifice 200 degree heads first floor)
1.5 2.2 Area #1 —10 density Tyco 2 " orifice 155 degree heads (second floor )
2.3 Fire Sprinkler Head types: First (1") floor 55-'/2 orifice Tyco TY FBR Chrome Pnd Rec)
y
1
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
First Floor continued > First (1") floor 9- %2 orifice Tyco TY FBR Brass up right)
First (0) floor 1-% orifice Tyco TY FBR white with head guard
Second Floor: 60 heads total
Second (2nd) Floor %2 orifice Tyco TY FBR Chrome Pnd Rec 155 degrees 60 total
Second (2°d) Floor % orifice Tyco TY FBR Brass up Right 200 degrees 60 total
Third Floor: 141 total heads
66> %2" 5.6 K 155 degree heads chrome pend rec.
75> %" 5.6 K 155 degree heads upright brass no esc.
2
.ay
F D F D
4
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
Plans Review Sheet
Date: May 12„ 2003
Occ. Business
Business Address:
Ch. #38
Business Name: Upsala Executive Center, Inc.
Contractor: Bratfo Building Comp.
Architect: Davis Architect
1270 Upsala Road
Ph. Not given
Ph. (954) 242-4456
Fax. (954) 428-4840
Ph. (954)480-8582
Fax. (954) 480-8466
Fax.
Reviewed[ ] Reviewed with comment [XJ Rejected []
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner �.
Comment: The Sanford Fire Department will require the following addendums prior to further
review. Fire permits required for the following construction. Underground fire lines, fire alarm
system for occupant notification. Fire Sprinkler System. The Sanford Fire Department will
require other code applications if building usage changes.
1. Provide Life Safety Page showing design criteria of the Automatic Fire Sprinkler sprinkler
r----
�yst(n
1.1 Application — New_23,1 9 sq ft. 3 story Building Type IV
1.2 Mixed — NA
1.3 Special Definitions — NA
1.4 Classification of Occupancy — Business
1.5 Classification of Hazard of Contents — Ordinary Hazard per 6.2.2.3
1.6 Minimum Construction — Provide fire chalk around all fire sprinkler penetrations.
2.2 Means of Egress Components— One(]) person per 100 sq. ft. see table (7.3.1.2>1)
1
TF D,
SANFORD FIRE DEPARTMENT -''—
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
2.3 Capacity of Egress - One (1) person per 100 sq. ft
2.4 Number of Exits- Two separate per floor
2.5 Arrangement of Egress - Exits within 38' ft. (2) two
2.6 Travel Distance - 38' ft. (2) two
2.7 Discharge from Exits - Life Safety plan shown in revisions
2.8 Illumination of Means of Egress Required
2.9 Emergency Lighting - Required in all stair wells
2.10 Marking of Means of Egress - Shall comply with Fla. Fire Prevention Code 20011
2.11 Special Features- Mark doors to the following ROOMS (elevator; main electrical, fire
alarm room, "Label all Doors"
3.1 Protection of Vertical Openings - N/A
3.2 Protection from Hazards -
3.3 Interior Finish - ;Class A only
3.4 Detection, Alarm and Communications Systems Required full fire alarm with pull stations
at each exit and fire sprinkler monitoring.
3.5 Extinguishing Requirements - One: (1) 5_pound Fire Extinguisher per. Office with a
State Cert. service tag.
3.6 Corridors - N/A
- 4 Special Provisions -NA
- 5 Building Services -NA
5.1 Utilities - as per LSC 9-2
5.2 HVAC -'as-per LSC 9-2 / NFPA 90A & 90B
5.3 Elevators, Escalators, Conveyors (4A-47) - N/A
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes - N/A
Sanford City Code - Chapter 9
Fire Sprinklers':: Required submit design criteria for building
Monitoring: Required submit design criteria for building
2
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
Other: NFPA 1> FIRE HYDRANT REQUIRED WITH IN 250'FT FROM PRINCIPLE
BUILDING
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box — Required, place Key's for exterior door, and all service rooms inside
Knox box
3-7.1 Bldg. Address Number Posted and Legible — Required;will field ver fy_(6") six
inch in size
3
7
V4 F aD aD
SANFORD FIRE DEPARTMENT
FIRE PRE VENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
Plans Review Sheet
Date: February 26„ 2003 Business Address: 1270 Upsala Road
Occ. Business Ch. #38
Business Name: Upsala Executive Center, Inc
Contractor: Bratfo Building Comp.
Architect: Davis Architect Ph.
Fax.
Ph. Not given
Ph. (954) 242-4456
Fax. (954) 428-4840
(954)480-8582
(954) 480-8466
Fax.
Reviewed[ ] Reviewed with comment [ ] 'Rejected _ x]
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner �—
Comment: The Sanford Fire Department will require the following addendupts prior to further
review.
1. Life Safety Plan reflecting travel distance to all EXITS, Fire Extinguisher locations.
2. Provide Life Safety Page showing design criteria of the Automatic Fire Sprinkler sprinkler
System
3. Provide Life Safety Plan calculating EXIT egress capacity for each flog
1.1 Application — New_23,169,, sq ft. 3 story Building Type IV
1.2 Mixed — NA
1.3 Special Definitions — NA -
1.4 Classification of Occupancy — Business
1.5 Classification of Hazard of Contents — Ordinary Hazard per.,6.2.2.3
1.6 Minimum Construction — N/R
I o: oo bi lHHL I hA Cx H �Ul•1 I t
Wa
LANNING/INTERIOR DESIGN
14F;7 West Hill�borC 61vd
bel`ifield Leach. F. 554421
teI.95(1 480.8582
May 5, 2003
To: Sanford Building Department
1101 East First Street
Sanford, FL 32771
Re: 1270 Upsala Rd
3 Story
Attn: Robert Bott
1. Building will move 4,5" to South; 20'-1" from North Property Line. See Engineer's revised Site
Plan.
2. Construction type is 5 Unprotected with firesprinkler (maximum 5 story; 28,000 per Floor.
Table 500 with "B" occupancy).
3. As per table 600:
a. 1 hr bearing wall (actual is 8" CMU)
b. Actual percentage of window opening (unprotected) is 23%; 40is allowed.
r. Designer is directed to FBC 705.1.1. for "protection requirement'' indicating that not all
openings require protection.
d. As per 705.1.1.2 protection is required of openings with 15' of property line; we are 20'-
1".
Please v e
Sincerely Yours,
�. DAVIS ARCHITECTURE INC.
Allen. Davis, Architect
' -JAD/nap
JOB#2291 ,PLDG-LTF
F D F AD
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
Plans Review Sheet
Date: May 12„ 2003 Business Address: 1270 Upsala Road
Occ. Business Ch. #38
Business Name: Upsala Executive Center, Inc
Contractor: Bratfo Building Comp.
Architect: Davis Architect
Ph. Not given
Ph. (954) 242-4456
Fax. (954) 428-4840
Ph. (954)480-8582
Fax. (954) 480-8466
Fax.
Reviewed[ 1 Reviewed with comment - _[X Rejected
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner
Comment: The Sanford Fire Department will require the following addendums prior to further
review. Fire permits required for the following construction. Underground fire lines, fire alarm
system for occupant notification. Fire Sprinkler System. The Sanford Fire Department will
require other code applications if building usage changes.
Is Provide Life Safety Page showing design criteria of the Automatic Fire Sprinkler -sprinkler
�'Systerr
1.1 Application - New;_23,169 sq ft. 3 story Building Type IV
1.2 Mixed - NA
1.3 Special Definitions - NA
1.4 Classification of Occupancy - Business
1.5 Classification of Hazard of Contents - Ordinary Hazard per 6.2.2.3
1.6 Minimum Construction - Provide fire chalk around all fire sprinkler penetrations.
2.2 Means of Egress Components- One(]) person per 100 sq. ft. see table (7.3.1.2>1)
1
r�
J
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
2.3 Capacity of Egress — One (1) person per 100 sq. ft
2.4 Number of Exits— Two separate per floor
2.5 Arrangement of Egress — Exits within 38' ft. (2) two
2.6 Travel Distance — 38' ft. (2) two
2.7 Discharge from Exits — Life Safety plan shown in revisions
2.8 Illumination of Means of Egress � Required
2.9 Emergency Lighting - Required in all stair wells
2.10 Marking of Means of Egress —Shall comply with Fla. Fire Prevention Code 2001I
2.11 Special Features — Mark doors to the following ROOMS (elevator; main electrical, fire
alarm room, "Label all Doors"
3.1 Protection of Vertical Openings — N/A
3.2 Protection from Hazards —
3.3 Interior Finish — ,Class A only
3.4 Detection, Alarm and Communications Systems —Required full fire alarm with pull stations
at each exit and fire sprinkler monitoring.
3.5 Extinguishing Requirements — OneL(1) 5_pound Fire Extinguisher per. Office with a
State Cert. service tag.
3.6 Corridors — N/A
- 4 Special Provisions -NA
- 5 Building Services -NA
5.1 Utilities —'as per LSC_ 932,
5.2 HVAC —as per LSC 9-2 / NFPA 90A & 90B:
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes — N/A
Sanford City Code — Chapter 9
Fire Sprinklers Required submit design criteria for building
Ls
Monitoring: Required submit design criteria for building
y
2
( t
F D F 4D
z
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395_
Other: NFPA 1> FIRE HYDRANT REQUIRED WITH IN 250'FT FROM PRINCIPLE
oBUILDING)
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box — Required, place Key's for exterior door, and all service rooms inside
Knox box
3-7.1 Bldg. Address Number Posted and Legible — 6equire4; will field verify_(6") six'
irch in size
SANFORD FIRE DEPARTMENT E
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
Plans Review Sheet
Date: May 12„ 2003 Business Address: 1270 Upsala Road
Occ. Business Ch. #38
Business Name: Upsala Executive Center, Inc. Ph. Not given
Contractor: Bratfo Building Comp. Ph. (954) 242-4456
Fax. (954) 428-4840
Architect: Davis Architect Ph. (954)480-8582
Fax. (954) 480-8466
Fax.
Reviewed[ ] Reviewed with comment ,[Xji Rejected []
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner
Comment: The Sanford Fire Department will require the following addendums prior to further
review. Fire permits required for the following construction. Underground fire lines, fire alarm
system for occupant notification. Fire Sprinkler System .The Sanford Fire Department will
require other code applications if building usage changes.
1. Provide Life Safety Page showing design criteria of the Automatic Fire Sprinkler sprinkler;
1.1 Application — New, 23,169,, sq ft. 3 story Building Type IV
1.2 Mixed — NA
1.3 Special Definitions — NA
1.4 Classification of Occupancy — Business
1.5 Classification of Hazard of Contents — Ordinary Hazard per 6.2.2.3
1.6 Minimum Construction — Provide fire chalk around all fire sprinkler penetrations.
2.2 Means of Egress Components— One(]) person per 100 sq. ft. see table (7.3.1.2>1)
1
I_.-J�
D,
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
2.3 Capacity of Egress — One (])person per 100 sq. ft
2.4 Number of Exits — Two separate per floor
2.5 Arrangement of Egress — Exits within 38' ft. (2) two
2.6 Travel Distance — 38' ft. (2) two
2.7 Discharge from Exits — Life Safety plan shown in revisions
2.8 Illumination of Means of Egress u Required
2.9 Emergency Lighting - Required in all stair wells
2.10 Marking of Means of Egress — Nall comply with Fla. Fire Prevention Code 002 1
2.11 Special Features — Mark doors to the following ROOMS (elevator; main electrical, fire
alarm room, "Label all Doors.
3.1 Protection of Vertical Openings — N/A
3.2 Protection from Hazards —
3.3 Interior Finish — Class A only
3.4 Detection, Alarm and Communications Systems —Required full fire alarm with pull stations
at each exit and fire sprinkler monitoring.
3.5 Extinguishing Requirements — One`(1) 5 pound Fire Extinguisher per. Office with a
State Cert. service tag.
3.6 Corridors — N/A
- 4 Special Provisions -NA
- 5 Building Services -NA
5.1 Utilities —'as per LSC 9-2
5.2 HVAC — 'per LSC 9-2 / NFPA 90A & 90B
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes — N/A
Sanford City Code — Chapter 9
Fire Sprinklers:; Required submit design criteria for building
Monitoring: Required submit design criteria for building
N
F -D F D
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
_ Pager (407) 918-0395
Other: NFPA 1> FIRE RANT REQUIRED WITH IN 250'FT FROM PRINCIPLE
BUILDING.�
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box — Required, place Key's for exterior door, and all service rooms inside
Knox box
3-7.1 Bldg. Address Number Posted and Legible — Required; will field verify —(C) s x
inch in size
3