Plans Review Sheet
Date: May 16, 2002 Business Address: 305 Magoustine Occ. Ch.38 Business
Business Name: Chida Plaza Ph. (407) 321-1415
FAX (407) 321-1597
Contractor: Spolski Construction Ph. (407) 322-8424
FAX (407)322-8436
Reviewed [ ] Reviewed with comment [ X] Rejected [ ]
Reviewed by: Timothy Robles, Fire Protection Inspector/plans Examiner
Comment: Plans reviewed as Business Occupancy. FD reserves right to require applicable code
requirements if occupancy use changes. Sprinkler plans to be submitted for review,
permitting, and inspections Sealed letter from Engineer of Record stating design criteria for
sprinkler system needs to be submitted. Fire Alarm horn strobes and pull stations required.
Please have contractor submit as builds for appliance and low voltage wire specs.
1.1 Application — New Building. Type IV, one (1) story firesprinkler protected; with protection of
trusses. 41) 30o s9 -F: 1.
2 Mixed — N/A 1.
3 Special Definitions — Meets F.F.P.C.- 6.1.11.1 (Record keeping/Business transactions).
1.
4Classification of Occupancy — Business F.F.P. C. 1.
5 Classification of Hazard of Contents — Ordinary/6.2.2.2. 1.
6 Minimum Construction — N/R 2.
2 Means of Egress Components — O.K. 2.
3 Capacity of Egress — One person per 100 sq ft (50 or more occupants shall comply
with 44' isle ways) 2.
4 Number of Exits — O.K. 2.
5 Arrangement of Egress — O.K. , two separate (2) 1
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
2.6 Travel Distance — O.K. with in 200' ft
2.7 Discharge from Exits — Complies with Chapter #7
2.8 Illumination of Means of Egress — O.K.; will field verify
2.9 Emergency Lighting — O.K.; will field verify
2.10 Marking of Means of Egress — O.K.;
2.11 Special Features —
3.1 Protection of Vertical Openings —3.2 Protection from Hazards — N/N
3.3 Interior Finish - Class "A "
3.4 Detection, Alarm and Communications Systems —This is existing (Required per
F.F.P.C. 38-3.4.1-Pull stations at every EXIT, Flow switches& tamper switches
required on fire sprinkler system)
3.5 Extinguishing Requirements — as per NFPA 10 — Two (2) 2A rated fire extinguishers
3.6 Corridors - One -hour fire rated corridors (exception Fire Sprinkler System)
4 Special Provisions
5 Building Services
5.1 Utilities — shall comply with N.F.P.A . #70
5.2 HVAC — shall comply with N.F.P.A. # 90 A & #90B over 2000 C.F.M.
duct detectors required
5.3 Elevators, Escalators, Conveyors: shall meet ANSI safety code for elevators
A17.1
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes — N/A
Sanford City Code — Chapter 9
Fire Sprinklers: blueprints required;
Monitoring: Required by a U.L. listed Central Station for all mandated fire
Sprinklered properties, per city code chapter #9
Other: NFPA 1
3-5.1 Fire Lanes — Not Required
u - '
4•'.
SANFORD FIRE DEPARTMENT
FIRE PRE VENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
3-6.1 Key Box — Not Required
3-7.1 Bldg. Address Number Posted and Legible — Existing