Plans Review Sheet
Date: July 29, 2003 Business Address: 1790 E. Airport Blvd.
occ. Ch. #40 Industrial
Business Name: Super Chips Ph. ( )
Contractor: Buena Vista Fire Protection Inc. Ph. (407 ) 382-5172
FAX (407)275-7384
Reviewed [ ] Reviewed with comment [ XI Rejected [ ]
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner
Comment: Instillation of 153 fire sprinkler heads & two -hundred forty-six 246 —
ft) C-900, 6" P.V.C. pipe.
Ll Application — Per N.F.P.A. #13-1999 ed,
1.2 Manufacturing Area> 12' High max on storage/ ordinary hazard group #1 > (NO
STOGARE ALLOWED OVER 12'(FT) PER DESIGN CRITERIA
1.3 office area>C12' High max on storage/ ordinary hazard group #1 >
Office> Tamper switches required on all outside and inside fire sprinkler
valves, including outside Backflow Prevention valves.
i
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772 , ti s
407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
Riser #1
Fire sprinkler heads >153 new fire sprinkler heads
Fire sprinkler heads > 106 Reliable 1/2................. 155 dg heads (pendant)
Fire Sprinkler Heads> 47 Reliable 1/2 165dg head (pendant)
Two (2) hour hydro and spacing test required for overhead fire sprinkler
system
Two (2) hour hydro required for all under ground c-900 fire line pipe
flush required for under ground pipe , six minutes
Please paint and coat all threaded rode and bolts
Tamper switches are required on all fire sprinkler valves