Plans Review Sheet
Date: April 22, 2002 Business Address: 1200 Central Park Drive
Occ. Ch. 38 New Business/Warehouse
Business Name: Cinema Designs Ph. ()
Contractor: .lames Bethune Ph. (407) 363-5733
FAX (407) 352-6673
Reviewed: [ ] Revaewed with Comment [X Rejected: [ .]
Reviewed By: T. L. Robles, Fire Inspector/Plans Examiner IfL
Comments: Plans reviewed as Business/Warehouse Occupancy. FD reserves right to
require applicable code requirements if occupancy use changes. Fire sprinkler plans
to be submitted for review, permitting and inspections. If separate certified
contractor does underground fireline, plans to be submitted for review, permitting, and
inspections. Sealed letter from Engineer of Record stating the design
criteria for sprinkler system needs to be submitted with construction
plans. Fire alarm plans to be submitted for review, permitting, and
inspections.
1.1 Application — New Building, Type VI Const., 11,700 sq.ft.
1.2 Mixed — N/A (6.1:14 does not apply)
1.3 Special Definitions — None
1.4 Classification of Occupancy — Business/Warehouse
1.5 Classification of Hazard of Contents — Ordinary
1.6 Minimum Construction — N/R
2.2 Means of Egress Components — O.K. meets L.S.C.
2.3 Capacity of Egress — O.K., in accordance with section7.3
2.4 Number of Exits — O. K. (2 separate exits in each occupied space required)
1
SANFORD FIRE DEPARTMENT
FIRE PREVENTIONDIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P."O. Box`1788, Sanford Fl. 32772
Office (407) 302-2520 /FAX (407) 330-5677
Pager (407) 918-0395
2.5 Arrangement of Egress — O.K., will field verify
2.6 Travel Distance — O.K.
2.7 Discharge from Exits — O.K. , will field verify
2.8 Illumination of Means of Egress — O.K., will field verify
2.9 Emergency Lighting — O.K. , will field verify
2.10 Marking of Means of Egress — O.K., will field verify
2.11 Special Features - No Require
3.1 Protection of Vertical Openings — N/N
3.2 Protection from Hazards — N/N
3.3 Interior Finish — No requirements
3.4 Detection, Alarm, and Communications — as per NFPA 72, required since
building will have a automatic fire sprinkler system
3.5 Extinguishing Requirements — as per NFPA 10, Fire extinguishers of a 2A1 OBC
rating required every 75' ft.
3.6 Corridors — Provisions of 7.1.3.1 shall not apply
4 Special Provisions —
5 Building Services
5.1 Utilities — as per LSC 7-1
5.2 HVAC — as per LSC 7-2
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes— N/A
SANFORD CITY CODE — CHAPTER 9
Fire Sprinklers — Required, also see 3.5 above
Monitoring —Required by UL Listed Central Station for all mandated fire
sprinklered properties
OTHER — NFPA 1
FA
SANFORD FIRE; DEPARTMENT
FIRE PREPI, N& ON,DIVISION
300 N. Park Ave., Sanford, Fl. 32771''.'%''P.'O: Boz 1788; Sanford Fl. 32772
Office (407) 302-2520 /FAX (407) 330-5677
Pager (407) 918-0395
3-5.1 Fire Lanes — Required if building is more than 150' from street,
exception: building has a fire sprinkler system
3-6.1 Key Box — Required, will field verify
3-7.1 Bldg. Address Number Posted & Legible — Required, will field verify,
numbers of a contrasting color to background, please see front page
of blue prints