HomeMy WebLinkAbout1111 Rinehart Rd 02-1332, 02-1334 Fire prevention division Sam's gas stationSANFORD FIRE bEPA TMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
Plans Review Sheet
Date: February 21, 2002 Business Address: I101 Rinehart Road
Occ. Ch. 28 &11 Special structures/refueling center
Business Name: Sam's Ph. (479 ) 273-7780 ext #222
Architect: Harrision French Architect FAX (479) 273-9436
Contractor: Out to bid Ph. ()
µ
Reu><ewed [x ] Reviewed with comment [ ] Rejected [ ]
Reviewed by: Timothy Robles, Fire Protection Inspector
1
Comment: Plans reviewed as "Special” Occupancy. FD reserves right to require applicable
code requirements if occupancy use changes.
1.1 Application — New Building; 4,949 sq ft. one (1) story canopy with (6) six dispensers &
three (3) 20,000 gallon tanks
1.2 Mixed — N/A
1.3 Special Definitions — Yes per FFP.C.
1.4 Classification of Occupancy — Refueling Center
1.5 Classification of Hazard of Contents - Special Structure
1.6 Minimum Construction — N/R
2.2 Means of Egress Components — O.K.
2.3 Capacity of Egress — O.K.
2.4 Number of Exits — O.K.
2.5 Arrangement of Egress — O.K.,
2.6 Travel Distance — O.K.
2.7 Discharge from Exits — O.K.,
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
2.8 Illumination of Means of Egress - exempt fy'om marking exit (F ER Q.
2.9 Emergency Lighting — O.K.
2.10 Marking of Means of Egress — O.K.
2.11 Special Features — O.K.
3.1 Protection of Vertical Openings — N/N
3.2 Protection from Hazards — N/N
3.3 Interior Finish — N/N
3.4 Detection, Alarm and Communications Systems —
3.5 Extinguishing Requirements — as per NFPA 10; 40B.0 rated fire extinguishers required by
fuel dispencers. One (1) 5 l.b. C o 2 fire extinguisher required in electrical /phone room
3.6 Corridors — N/A
4 Special Provisions
5 Building Services
5.1 Utilities —N/N/
5.2 HVAC — N/N
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes — N/A
Sanford City Code — Chapter 9
Fire Sprinklers: N/N
Monitoring: N/N
Other: NFPA 1
3-5.1 Fire Lanes — N/N
3-6.1 Key Box —
3-1.1 Bldg. Address Number Posted and Legible — Required; See blue prints for
location of numbers
n h rl- 12cP
Sams (I as Sf rJ4 ();"
0-- -- / -- 1 33Y