HomeMy WebLinkAbout1801 Airline Ave 07-2689 Parking Garage AirportVACK-BOXES REQUIRED/F.B4O0 • • ° • 2_i/8" 4" SQ. 2-1/8" 1-1/2"ra FM M DEEP DEEP DEEP i A 8 C D E F G H 4" SQ. 1- 1/2" BLANK SINGLE 4-11/16" 4-11/16" OCTAGON MUD DOUBLE GANG EXT. RING PLATE GANG BOX SQ. BOX EXT. RING BOX RING PLASTER RING FIRE ALARM SYSTEM DEVICE LEGEND SYMBOL/DESCRIPTION PART No. MOUNTING HT. BACKBOX REQ2D FACP FIRE ALARM CONTROL PANEL "NEW 4005--9102 72" AFF to Top by SimplexGrinnell NAG NOTIFICATION POWER EXPANDER PANEL "NEW" 4009-9201 60" AFF to Top by SimplexGrinnell SMOKE DETECTOR (Head) (Base) 4098-9601 4098-9682 CEILING (as required) G S -ZX-x SMOKE DETECTOR (IDNET) (Head) (Base) 4098--9714 4098-9792 CEILING (as required) G M1_xX+x kHEAT DETECTOR (IDNET) (Head) (Base) 4098--9733 4098�9792 CEILING (as required) G x M11DUCT DETECTOR (IDNET) (Return) (supply) 4098-9756 4098-9756 DUCT (as required) A, C Flex to Housing Xx+x REMOTE TEST STATION 2098-9806 PER MANUFACTURE INSTRUCTIONS D 't SUPERVISED CONTROL RELAY - MAX 3' FROM AHU CONTROLLER A HORN/STROBE (MULTI -VISUAL) (INDOOR) 4906-9127 80A AFF to Bottom of Lens or B Below Calling A, B WP (OUTDOOR ASWP-2475W°-FR whichever Is Lower DK-3LVLPLV SS SURGE SUPPRESSOR (120vac) DK- 120HW Field Verify E, F and Cover lone DK--3LVLPLV CONSTRUCTION DOCUMENTS PROVIDE BY: WALWrMIK I} PARKING CONSULTANTS 4902 Eisenhower Boulevard Suite 281 Tampa, FL 33634 813,888.5800 Ph. 813.888.5822 Fax BE-0003840 Hoyle, Tanner & Associates, Inc. Hulk 3452 LAKE LYNDA DRIVE, SUITE '151, ORLANDO, FL 32817 tel: (407) 3130-1919 fax: (407) 380-1830 email: htaorlfl®hta--fl.com web: www.hoyletanner.com DISCLAIMER DISCLAIMER: "NOTICE: This drawing and the data thereon shall not be duplicated, used, or disclosed to others for procurement or manufacturing purposes, except us otherwise authorized by contract, without the written permission of SimplexGrinnell. All reproductions shall bear this notice." TECHNICAL INSTALLATION SUPPORT TO ENSURE A SMOOTHER INSTALLATION, SIMPLEXGRINNELL PROVIDES THE INSTALLER WITH TECHNICAL LABOR SUPPORT. PLEASE CALL THE SIMPLEXGRINNELL SERVICE DISPATCHER AT (407) 235-1100 TO SCHEDULE A SITE VISIT BY A SIMPLEXGRINNELL TECHNICIAN. THE TECHNICIAN WILL MEET WITH THE INSTALLER RESPONSIBLE FOR THE INSTALLATION SIMPLEXGRINNELL SUPPLIED EQUIPMENT AND: * Review the project drawings and installation instructions with the responsible installer. Review device and panel termination points with the responsible installer * Review project scope Be present during initial panel start-up Identify shorts, opens and grounds in the field wiring Provide answers to on going project questions * Program system to meet specifications * Provide minor label changes * Assist the installer with one complete test of SimplexGrinnell supplied equipment * Provide one end user training session ADDITIONAL SERVICES ARE AVAILABLE. FOR PRICING AND SCHEDULING, PLEASE CALL THE SIMPLEXGRINNELL INSTALLATION SUPERVISOR, AT (407) 235--1100, 7-#14, 1"C 8-#14, 1•0 SD-Z1 SO--ZI-4 $D-Z1-3 SD-ZI-2 .,. ,,. k-M i-7 PANEL REMOIE TEST/ INDICATOR SAITCH UWTTR NO.1 MAGME ROOM 1_ Vi-•EOL -1 sa-z3-1� v1-�r ELEVATOR CONTROLLER 8-#12 4 ELEVATOR RECALL DIAGRAM N.T.S. TYPICAL RISER DIAGRAM NOTE: 1. COORDINATE DESIGNATED RETURN LEVELS AND ALTERNATE RETURN LEVELS WITH LOCAL AUTHORITY TOP Imo. HAVING JURISDICTiCN. 2. WIRE SMOKE DETECTORS TO ELEVATOR RECALL AND SUPERVISORY PANEL IN ELECTRICAL ROOM. RUN CIRCUIT WITH DRY CONTACT OUTPUTS FROM ELEVATOR RECALL AND SUPERVISORY PANEL TO ELEVATOR SEQUENCING EQUIPMENT. COORDINATE INSTALLATION WITH ELEVATOR INSTALLER. 3. ONE 1" CONDUIT TO ELEVATOR RECALL AND FOLNM LEVEL SUPERVISORY PANEL IN THE ELECTRICAL ROOM FOR ELEVATOR SEQUENCING. 4. WIRE SMOKE DETECTORS TO ELEVATOR RECALL AND SUPERVISORY PANEL IN ELECTRICAL ROOM. RUN CIRCUIT WITH DRY CONTACT OUTPUTS FROM ELEVATOR RECALL AND SUPERVISORY PANEL TO ELEVATOR SEQUENCING EQUIPMENT. COORDINATE INSTALLATION WITH ELEVATOR INSTALLER, 14Rq_ LEVEL. SECOND lRVE1 1 1 IBU�Ii 41 EXISTING FAS OF ,4 �� z4--1 �E04 THE TERMINAL FRCP SIMPLEX 4005 PPAN Polo OF MEL ELEVATOR RECALL & ss SUPERVI P - GROUND L VE 129 I I I I I AtARhI i UIRLE SUPERMSMY I CONNECT TD EXISTING FACP AT TMMINAL NOTIFICATION LOAD CALM/ VOLTAGE DROP CAL CS. PANEL NAME: FACP NAG CIRCUIT NUMBER: AVERAGEALARM CURRENT WALL CEILING TYPE A/V V/O S/V SIV AN V/O S/V I S/V 15 od 0.075 0.033 0.063 0.075 30 CD 0.116 0.094 0.094 10.125 75 CD 2 1 0.221 0.186 0.20510.233 110 CD 1 0.285 10.252 0.226 10.316 Horn Only 0 0.025 DEVICE COUNT TOTAL 0.442 Device type I AiV V/0 S/V HORN Equip, Qty 2 0 0 0 PANEL NAME: I NAG NAG CIRCUIT NUMBER: ALARM CURRENT WALL CEILING TYPE A/V V/O SN S/V AN V/O SiV I S/V 15 cd 2 0,075 0.083 0.083 0,075 30 CD 0.116 0.094 0.094 10.125 75 CD 1 0.221 0.186 0.205 0.233 110 CD 1E= 0.285 0.252 0.226 0.316 Horn Only 0 0.025 DEVICE COUNT TOTAL 0.666 Device type AN V/0 I S/V 1 HORN Equip. Qty 4 0 0 1 0 PANEL NAME :FAPiNAC 1!'I V O JTPIJT VOLTAGE 24 NAG: C I RC U IT TAB DEVICE ON NAC: 2 4 MAX NAC CURRENT j Amp 0.44 0.66 CURRENTAVERAGE Amp 0.221 0.164 WIRE GAUGE f Awg 14 14 100 FT FACTOR. Volts 0.2228 0.8307 Distancefl)from Panel ft 150 150 Voltage without load j Volts 26 26 Voltage last Device`` Volts 25.67 25.50 'G11i £ J � (/ _.ffr4 j*tM'Y11114 ts hay:, a'ro,., ,3k In ! SCOPE OF WORK * PROVIDE AND INSTALL NEW SYSTEM COMPONENTS AS FOLLOW ; ** NEW FIRE ALARM CONTROL PANEL, SIMPLEX 4005. ** NEW NOTIFICATION POWER EXPANDER PANEL, SIMPLEX 4009, ** NEW FIRE ALARM CONVENTIONAL DEVICES THAT INCLUDE: *** INITIATION DEVICE: SMOKE DETECTORS, HEAT DETECTORS AND DUCT DETECTORS. *** NOTIFICATION APPLIANCES: HORN STROBE. ** NEW FIRE ALARM ADDRESSABLE DEVICES THAT INCLUDE: *** INITIATION DEVICE: SMOKE DETECTORS, HEAT DETECTORS AND DUCT DETECTORS. * CONNECT ALL CONVENTIONAL DEVICES PART OF THE GARAGE ELEVATOR RECALL SYSTEMS TO THE SIMPLEX 4005 FIRE PANEL. * CONNECT ALL ADDRESSABLE DEVICES PART OF THE BRIDGE AND TERMINAL LOBBY AREAS TO THE EXISTING 41000 FIRE ALARM SYSTEMS AT THE TERMINAL. * CONNECT THE NEW SIMPLEX 4005 PANEL TO EXISTING ADDRESSABLE 41000 FIRE ALARM SYSTEM AT THE TERMINAL. ALL FIRE ALARM SYSTEM INSTALLATION ACCORDING WITH NFPA 72 2002 EDITION, AND COMPLY WITH THE 2001 FLORIDA BUILDING CODE WITH 2O02/2003 REVISIONS AND THE FLORIDA FIRE PREVENTION CODE (2005). ALSO ALL CONDUIT AND WIRING SHALL BE UNDER NFPA 70 (NEC). 3701 N. John Young Parkway, Suite 110 Branch 291 Orlando, Florida OFFICE PERMIT # DATE: PLANS REVIEWED OTY OF SANFORD DRAWING LIST DRAWING NUMBER DESCRIPTION REVISION 917872302-01 COVER, DRAWING INDEX, LEGEND, RISER DIAGRAM, GENERAL NOTES 00 917877302-02 FIRE ALARM SYSTEM - GARAGE GROUND LEVEL 00 917872302-03 FIRE ALARM SYSTEM - GARAGE SECOND LEVEL 00 917872302-04 FIRE ALARM SYSTEM - GARAGE THIRD LEVEL 00 917872302-05 FIRE ALARM SYSTEM - GARAGE FOURTH LEVEL 00 917872302-08 FIRE ALARM SYSTEW - GARAGE TOP LEVEL 00 917072302-07 FIRE ALARM 5YSTEN - BRIDGE LOBBY GROUND AND SECOND LEVEL 00 917872302-08 TYPICAL DEVICE DIAGRAM 00 917872301-09 TYPICAL DEVICE DIAGRAM 00 FIRE ALARM SYSTEMS GENERAL NOTES GENERAL NOTES (ALL SHEETS) 0 PROVIDE DEDICATED 120 VAC CIRCUITS, TO FIRE ALARM PANEL, LABEL THE DEDICATED CIRCUIT "FIRE ALARM SYSTEM" AND PLACE LOCK OUT ON CIRCUIT AT ELECTRICAL PANEL. CONNECT ALL FIRE ALARM PANEL OUT PUT TO EXISTING FIRE ALARM SYSTEMS AT THE TERMINAL OMOUNT SMOKE DETECTORS AT THE CEILING, AND NOT ON THE BOTTOMS OF BEAMS OR JOISTS. LOCATE ALL SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM ANY MECHANICAL DIFFUSERS, AND AS REQUIRED BY NFPA 72, SMOKE DETECTOR HEADS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEANUP OF ALL TRADES IS COMPLETE AND FINAL. 0 ALL DUCT DETECTOR SHALL BE PROGRAMMED FOR AHU SHUT DOWN UPON ANY ALARM CONDITION, COORDINATE FIELD LOCATION WITH MECHANICAL CONTRACTOR.DUCT SMOKE DETECTORS INDICATING LAMPS SHALL BE MOUNTED AT 80" AFF AND HAVE AN ENGRAVED COVERPLATE WITH ADDRESS, UNIT SERVED AND DETECTOR LOCATION (IE L1--D30,AHU-XX, SUPPLY). PROVIDE ANY ASSOCIATED CABLING AND CABLING CONNECTIONS BETWEEN DUCT DETECTOR AND REMOTE TEST STATION. COORDINATE EXACT LOCATION WITH THE GENERAL CONTRACTOR AND OWNER PRIOR TO INSTALLATION. ® MINIMUM CABLING REQUIREMENTS SHALL BE AS FOLLOWS: INITIATION CIRCUITS (THHN) CLASS B, SUPERVISORY (THHN) CIRCUITS CLASS B, NOTIFICATION CIRCUITS (THHN) CLASS B, STYLE Y, SIGNALING LINE CIRCUITS (TSP) CLASS B, STYLE 4, AUXILIARY CIRCUITS (THHN) CLASS B ALL FIRE ALARM SYSTEM INSTALLATION ACCORDING WITH NFPA 72 2002 EDITION AND COMPLY WITH THE 2001 FLORIDA BUILDING CODE WITH 2O02/2003 REVISIONS AND THE FLORIDA FIRE PREVENTION CODE (2005). ALSO ALL CONDUIT AND WIRING SHALL BE UNDER NFPA 70 (NEC). RE iyE i E" . sonforci Fi o pf' v Div, Date.: i TYPICAL. DEVICE MOUNTING FIGHTS A/0 SUPPLY 01FFUSER 1-1 ,. SMOKE/HEAT 3' (MIN) k , ruiiiiiirsirriiiillrvlriiirlaii•or!��iviiiiirr�arr�iriiiii��iiir vtsrtGi���ir��rrlwfrrriri���rrrri�r�rrrrrrrirEut�ir!�riresrrri.� Ze MIN HANDICAP .► Mir- VISUAL -ONLY DEVICU HERE E. Q&TECTOR �1 ft TWO APPLIANCES IN ANY FIELD OF VIEW, SPACED A MINIMUM OF 55 FROM EACH OTHER IN ROOMS 80 X 80' OR CREAiFR. NFPA 72 29D2 EDINN �T80" MIN 96' MAX MANVAL NFPA 72 2002 PULL EDMON STAnON MAGNETIC PHONE HOLDER JACK o� - 48- MAX ADA 42- MIN/54- MAX (FPA NFPA 72 200 FINISHED FLOOR FINISHED WALL SIDE WALL. IMPORTANT NOTICE 1. THE INSTALLER SHALL CONTACT THE SIMPLEXGRINNELL SERVICE CENTER AT LEAST 3 DAYS PRIOR TO ANY DESIRED CHECK-OUT DATE TO ALLOW FOR SCHEDULING AVAILABILITY OF OUR TECHNICIANS, NOTE: PHOTOELECTRIC AND IONIZATION DETECTOR HEADS SHOULD NOT BE INSTALLED IN THE BASES UNTIL JUST PRIOR TO THE FINAL SYSTEM TEST. DUST OR PAINTS FROM CONSTRUCTION MAY DAMAGE THESE DEVICES AND REQUIRE FACTORY CLEANING OR REPLACEMENT WHICH IS NOT COVERED UNDER THE SIMPLEXGRINNELL SYSTEM WARRANTY. 2. THE INSTALLER SHALL COMPLETE ALL FIELD DEVICE AND PANEL CONNECTIONS. ALL CIRCUITS SHALL BE CHECKED WITH AN OHMMETER FOR PROPER CONTINUITY. ALL CIRCUITS MUST TEST FREE OF OPENS, GROUNDS AND HIGH RESISTANCE SHORTS. BELL AND BATTERY METHOD OF TESTING IS NOT RECOMMENDED. 3. ALL CIRCUITS SHALL TEST FREE OF INDUCED VOLTAGE, ONLY SYSTEM WIRING SHOULD BE IN THE SAME CONDUIT. IN ANY INSTALLATION WHERE PVC TUBING IS USED IN PLACE OF CONDUIT OR EMT, A COMMON DRAIN (GROUND) WIRE SHALL BE INCLUDED. 4. THE INSTALLING COMPANY SHALL MAKE AVAILABLE THE INSTALLER RESPONSIBLE FOR WIRING THE SYSTEM. THIS PERSON MUST BE PRESENT AT THE FINAL CHECKOUT TO IDENTIFY ALL WIRES LEADING INTO THE CONTROL PANEL, 5. THE INSTALLER WILL NOT CALL FOR FIRE DEPT. WALK-THROUGH UNTiL SIMPLEXGRINNELL COMPLETES THEIR FINAL CHECK-OUT OF THE SYSTEM. DEVICES SHALL BE PERMANENTLY MOUNTED BY THE INSTALLER AFTER FINAL FIRE DEPARTMENT WALK THROUGH, IF REQUIRED BY THE AUTHORITY HAVING JURISDICTION (AHJ). I- oW n CD 0 M __Jz 0 O I---• LLJ o- W F-- C) C� ci� < LLJ 0 (D < < V)u_0 O LL- 0 4 CO C- V) O 2003 "NOTICE: This drawing and the data thereon shall not be duplicated, used, or disclosed to others for procurement or manufacturing purposeo, except as otherwiaa authorized by contract, Nithout tho written permission of 51mplexGrtnnell. All reproductions shall bear this notice.' ONE 1" CONDUIT TO ELEVAI LOBBY AND STAIRS TO FEE] FIRE ALARM DEVICES ONE 1* CONDUIT TO EQUIPMENT ROOM 7—#14, 100 5—#12,r Iwo 5d f14, 1% 11—#14, 1"C ELEC., STORAGE & IRM ROOM PLAN SCALE: 1 /4" = I'm-0" 1 2 3 4 5 8 1 O 11 PAD MOUNM U TRMlSFr7f�AER 312 -0" RTAIR/El �l/AT®R 12'-0' 0-0" 36'-0" 36'-0" 36 -0 TOWER Nat � _0" _p^ 5 0" 5'-0' C.8 x STAIR TOWER Na.3 im 0 1 Vl--02 75 CD n A.2 B o• o- 0 0 0 0 I C a FIRE ALARM SYSTEMS GENERAL DOTES GENERAL NOTES (ALL SHEETS) 0 PROVIDE DEDICATED 120 VAC CIRCUITS, TO FIRE ALARM PANEL. LABEL THE DEDICATED CIRCUIT "FIRE ALARM SYSTEM" AND PLACE LOCK OUT ON CIRCUIT AT ELECTRICAL PANEL, CONNECT ALL FIRE ALARM PANEL OUT PUT TO EXISTING FIRE ALARM SYSTEMS AT THE TERMINAL MOUNT SMOKE DETECTORS AT THE CEILING, AND NOT ON THE BOTTOMS OF BEAM OR JOISTS, LOCATE ALL SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM ANY MECHANICAL DIFFUSERS, AND AS REQUIRED BY NFPA 72. SMOKE DETECTOR HEADS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEANUP OF ALL TRADES IS COMPLETE AND FINAL, ALL DUCT DETECTOR SHALL BE PROGRAMMED FOR AHU SHUT DOWN UPON ANY ALARM CONDITION. COORDINATE FIELD LOCATION WITH MECHANICAL CONTRACTOR.DUCT SMOKE DETECTORS INDICATING LAMPS SHALL BE MOUNTED AT 80" AFF AND HAVE AN ENGRAVED COVERPLATE WITH ADDRESS, UNIT SERVED AND DETECTOR LOCATION (IE L1--D30,AHU--XX, SUPPLY), PROVIDE ANY ASSOCIATED CABLING AND CABLING CONNECTIONS BETWEEN DUCT DETECTOR AND REMOTE TEST STATION. COORDINATE EXACT LOCATION WITH THE GENERAL CONTRACTOR AND OWNER PRIOR TO INSTALLATION, MINIMUM CABLING REQUIREMENTS SHALL BE AS FOLLOWS: INITIATION CIRCUITS (THHN) CLASS B, SUPERVISORY (THHN) CIRCUITS CLASS B, NOTIFICATION CIRCUITS (THHN) CLASS B, STYLE Y, SIGNALING LINE CIRCUITS (TSP) CLASS B, STYLE 4, AUXILIARY CIRCUITS (THHN) CLASS B ALL FIRE ALARM SYSTEM INSTALLATION ACCORDING WITH NFPA 72 2002 EDITION, AND OCOMPLY WITH THE 2001 FLORIDA BUILDING CODE WITH 2O02/2003 REVISIONS AND THE FLORIDA FIRE PREVENTION CODE (2005). ALSO ALL CONDUIT AND WIRING SHALL BE UNDER NFPA 70 (NEC). TYPICAL DETICE MOU14MG HEIGHTS A/O W PLY pfFa9�J1 COLINO MOUNTED"1•liyw-� 1 1 !/i' '%///1//!!!//!!!/!/,U///!!!7/!/!/!!/%lG/LL!!fl!!L/.!f/!!/i HANDICAP ACCEPTED HERE BEDROOM STROBE DIO WALLI MOUNT yD UETECTi .- SYNCHRONIZE MORE THAN TWO,APPIlANC> S IN ANY FIELD OF YfEWI SPZ A MINIOF 80 FROM EACH OTHER IN ROOMS 80' x W IM3 X OR GREATER. NFPA 72 Z002 EDITION eo, MN " 98" MAX MANUAL. NFPA 72 2002 PULL EDITION STATION MArtIE71L FIRE ouoR PHONE HOWER JACK �o 4' NAX AAA)) 42' MIN/0 MAX ( FPA) NFPA 72 200 FINISHED FLOOR FINI�SM 510E WALL m Sa 21 0 a=- V) L" h r 4 i 4 ,.l i I 0 CONSTRUCTION DOCUMENTS PROVIDE BY :.WALICER .... PARKING CONSULTANTS 4902 Eisenhower Boulevard Suite 281 Tampa, FL 33634 813.888.5800 Ph. 813.888.5822 Fax BE-0003840 Hoyle, Tanner Associates, Inc.MOM NNW 3452 LAKE LYNDA DRIVE, SUITE 151, ORLANDO, FL 32817 1" CONDUIT TO ELEVATOR ,ALL AND SUPERVISORY FACP tel: (407) 380-1919 fax: (407) 380-1830 email: htooriflGihta-fl.com web: www,hoyletonner.com aEL IN THE ELECTRICAL,. ROOM I ELEVATOR SEQUENCING 4 /' � " 4 � p; Li D _ _� DRAWN BY: eu��r�-reexirF.� CHECKED BY: X a dr lairruavre DATE: 5 AJPRff 20 DRAWING NAME: 917872302--C SCALE: 1/1611-11p01 PROJECT 07 / PROMPT Nc 917872302 FILE LOCATION: OSIA—GARAGI SHEET: 2 of @ 2003 "NOTICE: This drawing and the data thereon shall not be dupllcotcd, used, or disclosed to athem for procuroment or rnanufaaturing purposes, except as otherwise authorized by contract, without tho written permisslan of SirnplcxGrinnell• All reproductlons shall bear thk notice.' TYPICAL DEVICE MOUNTING HEIGHTS A �Y C&IUNQ MOUNTED — 4, s � TK DRTfGmR 3' SMIN) amaacu�TmaF TNe MIN BE ACCEPTED HERE T I BEDROOM STRO2r ��//AMM + 12 <MAX> �^^ dON5UAL LY DEMICES HEM WALL L MOUNTED IEAT /H I— — 5' SYNCHRONIZE MORE THAN TWO APPUANM IN ANY nELO OF VIEW I '9"AGED A MINIMUM OF 95 FROM EACH OTHER IN x dD' ! OR ORFA GREATER,. �� NFPA 72 2002 EDITION ne WALL 90° MIN PULL NFPA n 2ooz EDITION 0AIIO" MAONETIFIRE OM p PHONE Ld.J UU HOLDER • WALL 42' MIN/ 64�MAXl(NFFPPA) NFPA 7Z 2002 FINISHEDFLOOR STAIR/ELEVATOR NO.1 SECOND LEVEL PLAN SCALE: 1 /4" = 1'— 0" FIRE ALARM SYSTEMS GENERAL NOTES GENERAL NOTES (ALL SHEETS) 0PROVIDE DEDICATED 120 VAC CIRCUITS, TO FIRE ALARM PANEL. LABEL THE DEDICATED CIRCUIT "FIRE ALARM SYSTEM" AND PLACE LOCK OUT ON CIRCUIT AT ELECTRICAL PANEL. CONNECT ALL FIRE ALARM PANEL OUT PUT TO EXISTING FIRE ALARM SYSTEMS AT THE TERMINAL MOUNT SMOKE DETECTORS AT THE CEILING, AND NOT ON THE BOTTOMS OF BEAMS OR JOISTS. LOCATE ALL SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM ANY MECHANICAL DIFFUSERS, AND AS REQUIRED BY NFPA 72. SMOKE DETECTOR HEADS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEANUP OF ALL TRADES IS COMPLETE AND FINAL. ALL DUCT DETECTOR SHALL BE PROGRAMMED FOR AHU SHUT DOWN UPON ANY ALARM CONDITION. COORDINATE FIELD LOCATION WITH MECHANICAL CONTRACTOR.DUCT SMOKE DETECTORS INDICATING LAMPS SHALL BE MOUNTED AT 80" AFF AND HAVE AN ENGRAVED COVERPLATE WITH ADDRESS, UNIT SERVED AND DETECTOR LOCATION (IE L1—D30,AHU—XX, SUPPLY). PROVIDE ANY ASSOCIATED CABLING AND CABLING CONNECTIONS BETWEEN DUCT DETECTOR AND REMOTE TEST STATION. COORDINATE EXACT LOCATION WITH THE GENERAL CONTRACTOR AND OWNER PRIOR TO INSTALLATION. MINIMUM CABLING REQUIREMENTS SHALL BE AS FOLLOWS: INITIATION CIRCUITS (THHN) CLASS B, SUPERVISORY (THHN) CIRCUITS CLASS B, NOTIFICATION CIRCUITS (THHN) CLASS B, STYLE Y, SIGNALING LINE CIRCUITS (TSP) CLASS B, STYLE 4, AUXILIARY CIRCUITS (THHN) CLASS B ALL FIRE ALARM SYSTEM INSTALLATION ACCORDING WITH NFPA 72 2002 EDITION, AND COMPLY WITH THE 2001 FLORIDA BUILDING CODE WITH 2O02/2003 REVISIONS AND THE FLORIDA FIRE PREVENTION CODE (2005). ALSO ALL CONDUIT AND WIRING SHALL BE UNDER NFPA 70 (NEC), CONSTRUCTION DOCUMENTS PROVIDE BY: WALKER ;•:.:, r;;•:;;;,.... PARKING CONSULTANTS 4902 Eisenhower Boulevard Suite 281 Tampa, FL 33634 813.888.5800 Ph. 813.888.5822 Fax BE--0003840 Hoyle, Tanner 8c Associates,Ema Elm Inc. 3452 LAKE LYNDA DRIVE, SUITE 151, ORLANDO, FL 32817 tel: (407) 380-1919 fax: (407) 380-1830 email: htaorlflQYhta—fl.com web: www.hayletanner.com IN PEDESMlj 1 11 DATUM ELEVATION 50.5' = W-0° DOT ISOMETRIC NORTH TOP LEVEL M 0 w cn P= 13- LJ 0 v� ■ =.i Nr iw MR r z - v DRAWN BY: 53 4TH LEVEL a z CHECKED BY: JJ �✓ 3RD LEVEL DATE: DRAWING NAME: 917872302--C SCALE: aC PARIQNG "-�1 '�0 r 1/16 GROUND LEVEL q�pr PROJECT No. / PROMPT NC 917872302 FILE LOCATION: OSIA—GARAGI SHEET: 3 of ■ © 2003 'NOTICE: This drawing and the data thomon shall not be duplicated, used, or dlscloaed to others for procurement or rnanuNoturing purpoeeo, except ae otherwise authorized by contract, without the writton permission of SlrnplexGdnnell, All reproductions shall bear this notice.' TYPICAL DEVICE MOUNTING HEIGHTS O; SUPPLY gFLm CEILING MOUNTED SMOKE $' (MIN) MUNG 24" MIN HANDICAP ACCEPTED HERE BEDROOM STROBE AUDIO VISUAL NEVER l ,� 1 ... __ DEVICE S L-ONLY HERE SYNCHRONIZE MORE THAN TWO APPLIANCES IN ANY FIELD OF VIEW SPACED A MINIMUM OF W FROM EACH OTHER IN RaOMS 00' x OV OR GREATER NFPA 72 2002 EOITION 9V MAX NFPA 72 2002 EDITION MANUAL STATION FIRE PHONE —�('1 JACK - o I 4D" MAX AOA 42" MIN/ 64" MAX ( FPA NFPA 72 2002 5' MAGNETIC DOOR HOLOETt 6 4' WALL MOUNTED SM DE ft OR FINIWSHED LL NOTES MEASUMENTS S1QM ARE TQ 1HE CLO=7 OF THE WEOTOR. 4' 1 1 12' (MAX) SUE WAIL STAIR/ELEVATOR N0. 1 THIRD LEVEL PLAN SCALE: 1 /4" = 1'— 0" FIRE ALARM SYSTEMS GENERAL NOTES GENERAL NOTES (ALL SHEETS) 0 PROVIDE DEDICATED 120 VAC CIRCUITS, TO FIRE ALARM PANEL. LABEL THE DEDICATED CIRCUIT "FIRE ALARM SYSTEM" AND PLACE LOCK OUT ON CIRCUIT AT ELECTRICAL PANEL. CONNECT ALL FIRE ALARM PANEL OUT PUT TO EXISTING FIRE_ ALARM SYSTEMS AT THE TERMINAL MOUNT SMOKE DETECTORS AT THE CEILING, AND NOT ON THE BOTTOMS OF BEAMS OR JOISTS. LOCATE ALL SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM ANY MECHANICAL DIFFUSERS, AND AS REQUIRED BY NFPA 72. SMOKE DETECTOR HEADS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEANUP OF ALL TRADES IS COMPLETE AND FINAL. ALL DUCT DETECTOR SHALL BE PROGRAMMED FOR AHU SHUT DOWN UPON ANY ALARM CONDITION. COORDINATE FIELD LOCATION WITH MECHANICAL CONTRACTOR,DUCT SMOKE DETECTORS INDICATING LAMPS SHALL BE MOUNTED AT 80" AFF AND HAVE AN ENGRAVED COVERPLATE WITH ADDRESS, UNIT SERVED AND DETECTOR LOCATION (IE L1--D30,AHU--XX, SUPPLY). PROVIDE ANY ASSOCIATED CABLING AND CABLING CONNECTIONS BETWEEN DUCT DETECTOR AND REMOTE TEST STATION. COORDINATE EXACT LOCATION WITH THE GENERAL CONTRACTOR AND OWNER PRIOR TO INSTALLATION, MINIMUM CABLING REQUIREMENTS SHALL BE AS FOLLOWS: INITIATION CIRCUITS (THHN) CLASS B, SUPERVISORY (THHN) CIRCUITS CLASS B, NOTIFICATION CIRCUITS (THHN) CLASS B, STYLE Y, SIGNALING LINE CIRCUITS (TSP) CLASS B, STYLE 4, AUXILIARY CIRCUITS (THHN) CLASS B (D ALL FIRE ALARM SYSTEM INSTALLATION ACCORDING WITH NFPA 72 2002 EDITION, AND COMPLY WITH THE 2001 FLORIDA BUILDING CODE WITH 2O02/2003 REVISIONS AND THE FLORIDA FIRE PREVENTION CODE (2005). ALSO ALL CONDUIT AND WIRING SHALL BE UNDER NFPA 70 (NEC), CONSTRUCTION DOCUMENTS PROVIDE BY: .r PARKING CONSULTANTS 4902 Eisenhower Boulevard Suite 281 Tampa, FL 33634 813.888.5800 Ph. 813.888.5822 Fax BE-0003840 Hoyle, Tanner & Associates, Inc. 3452 LAKE LYNDA DRIVE, SUITE 151, ORLANDO, FL 32817 tel: (407) 380-1919 fax: (407) 380-1830 email: htoodfl4hto--fl.com web: www.hoylot<innor.com CA PEDESTRI, 1 !9 DATVM ELEVATION 80.5' = 0'-0" J EAT ISOMETRIC NORTH Tad. P_L 4T�"HLEVEL 3RDLEVEL P 2ND LEVEL. ' EL. - 12'-10" JC PARKING tY L GROUND LEVEL EL. - 0'-0 bill i r y rr v r DRAWN 9Y: J6 SCALE: 1/1611 -11-01 PROJECT No. / PROMPT Nc 917872302 FINISHED D FILE LOCATION: OSIA—GARAGI SHEET: 4 of © 2003 "NOTICE: This drawing and the data thereon shall not be duplicated, used, or disclosed to others for procurement or manufacturing purposes, except ae otherwise authorized by contract, without the written permisslon of SlmplexOrinnell. All reproductions shall bear this notice." TYPICAL DEVICE MOU19WG FIEIGHTS CEILINQ MOUNTED MO !•1//!l/// CCC/Ll!/%//I HANDICAP24" MIN BEDROOM STROBE AVDIQ/VI`UAL dc NLY DEAM SYNCHRONIZE MORE THAN TWO APPLIANCES IN ANY FIELD OF VIEW, SPACED A MINIMUM OF W FROM EACH OTHER IN ROOMS W x W OR GREATER NFPA 72 2002 EDITION W MIN 90' MAX NFPA 72 2002 EDITION FINISHED FLOOR MANUAL STATION FlR£ PHONE 0 40' MAX (ADA 42' MIN/34' MAX (NFPA NFPA 72 200 I 4 NOTFa MEASUNEMUM ML TO 1Hc 94M %Qmw W THE ACCEPTED HERE 12' (MAX) NEVER HERE WALL MOUNTED 51 SMOKE /I iEAT DETECTOR 11— MOTH slDa wau MAGNETIC 0009 HOLDER FINISHED WALL FIRE ALARM SYSTEMS GENERAL NOTES GENERAL NOTES (ALL SHEETS) 0 PROVIDE DEDICATED 120 VAC CIRCUITS, TO FIRE ALARM PANEL, LABEL THE DEDICATED CIRCUIT "FIRE ALARM SYSTEM" AND PLACE LOCK OUT ON CIRCUIT AT ELECTRICAL PANEL. CONNECT ALL FIRE ALARM PANEL OUT PUT TO EXISTING FIRE ALARM SYSTEMS AT THE TERMINAL MOUNT SMOKE DETECTORS AT THE CEILING, AND NOT ON THE BOTTOMS OF BEAMS OR JOISTS. LOCATE ALL SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM ANY MECHANICAL DIFFUSERS, AND AS REQUIRED BY NFPA 72. SMOKE DETECTOR HEADS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEANUP OF ALL TRADES IS COMPLETE AND FINAL. ALL DUCT DETECTOR SHALL BE PROGRAMMED FOR AMU SHUT DOWN UPON ANY ALARM �3 CONDITION. COORDINATE FIELD LOCATION WITH MECHANICAL CONTRACTOR.DUCT SMOKE DETECTORS INDICATING LAMPS SHALL BE MOUNTED AT 80" AFF AND HAVE AN ENGRAVED COVERPLATE WITH ADDRESS, UNIT SERVED AND DETECTOR LOCATION (IE L1-D30,AHU-XX, SUPPLY). PROVIDE ANY ASSOCIATED CABLING AND CABLING CONNECTIONS BETWEEN DUCT DETECTOR AND REMOTE TEST STATION. COORDINATE EXACT LOCATION WITH THE GENERAL CONTRACTOR AND OWNER PRIOR TO INSTALLATION. (� MINIMUM CABLING REQUIREMENTS SHALL BE AS FOLLOWS: INITIATION CIRCUITS (THHN) CLASS B, SUPERVISORY (THHN) CIRCUITS CLASS B, NOTIFICATION CIRCUITS (THHN) CLASS B, STYLE Y, SIGNALING LINE CIRCUITS (TSP) CLASS B, STYLE 4, AUXILIARY CIRCUITS (THHN) CLASS B ALL FIRE ALARM SYSTEM INSTALLATION ACCORDING WITH NFPA 72 2002 EDITION, AND 0 COMPLY WITH THE 2001 FLORIDA BUILDING CODE WITH 2O02/2003 REVISIONS AND THE FLORIDA FIRE PREVENTION CODE (2005). ALSO ALL CONDUIT AND WIRING SHALL BE UNDER NFPA 70 (NEC). CONSTRUCTION DOCUMENTS PROVIDE BY: WALm=R ;. PARKING CONSULTANTS 4902 Eisenhower Boulevard Suite 281 Tampa, FL 33634 813.888.5800 Ph. 813.888.5822 Fax BE-0003840 Hoyle, Tanner & Associates, Inc. 3452 LAKE LYNDA DRIVE, SUITE 151, ORLANDO, FL 32817 ti �r k tel: (407) 380-1919 fax: (407) 380-1830 email: htaorifl®hto—fl.com web: www.hoyletanner.com V PEDESTRI, DATUM ELEVATION 50.5' a 0'-0" Da ISOMETRIC NORTH 4 TOP LEVEL.. rkT.. 47'-1O" 4TH LEVEL. DEL. -38 2 ■ 1, r K r � CHECKED BY: 3RD LEVEL OATE: E'-6' 11 195 A.'W 2 0 DRAWING NAME: zNOb--O LEA 917872302-C El. g 12 —10n SCALE: UC PARIQNG / 1 ar — 1 1— 01 I tY GROUNDLEVEL PROJECT No. / PROMPT Nc IL --0r 917872302 FILE LOCATION; OSIA—GARAGI SHEET: 5 Of Y C@ 2003 'NOTICE: This drawing and the data thereon shall not be duplicated, used, or disclosed to others for procurement or manufacturing purposes, except as otherwise authorized by contract, without the written perrnlssion of SlmplexGrfnnell, All reproductions shall bear this notice.' TYPICAL DEVICE MOUNTING HEIGHT'S aMY CEILING MOUNTED 3MOKE/HEAT I.-» 0' (MIN) —� I EIECTI9R 24" MIN HANDICAP OEOROOM STROBE ACCEPTED HERE j^ AUDIO/MSUAL I I DEVICES ONLY 501CHRONIZE MORE THAN Two APPUANCES IN ANY FIELD OF V1EWt WACED A MINIMUM OF 55 FROM EACH OTHER IN Rom aV x aV OR GREATER. NFPA 72 2002 EDITION 80' MIN NFPA 7722.20MAX022 EDITION FINISHED FLOOR MANUALPULL I STATION FIRE PHONE JACK 1 e I RE — 48• MAX ADA)) 4Z MIN/54" MAx ( FPA} NFPA 72 2 MAGNETIC DOOR HOLM N 4"1 NO"WA wAA"T00T !T3 CLO'AN ARE TO THE OWST OF THE 111E 4- I NHS 12" (MAX) WALL MOUNTED SMD= FINISHED WALL WE WALL. STAIR/ELEVATOR NO.1 TOP LEVEL PLAN SCALE: 1/4" = 1'-0" FIRE ALARM SYSTEMS GENERAL NOTES GENERAL NOTES (ALL SHEETS) PROVIDE DEDICATED 120 VAC CIRCUITS, TO FIRE ALARM PANEL. LABEL THE DEDICATED CIRCUIT "FIRE ALARM SYSTEM" AND PLACE LOCK OUT ON CIRCUIT AT ELECTRICAL PANEL. CONNECT ALL FIRE ALARM PANE OUT PUT TO EXISTING FIRE ALARM SYSTEMS AT THE TERMINAL MOUNT SMOKE DETECTORS AT THE CEILING, AND NOT ON THE BOTTOMS OF BEAMS OR JOISTS. LOCATE ALL SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM ANY MECHANICAL DIFFUSERS, AND AS REQUIRED BY NFPA 72. SMOKE DETECTOR HEADS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEANUP OF ALL TRADES IS COMPLETE AND FINAL. ALL DUCT DETECTOR SHALL BE PROGRAMMED FOR AHU SHUT DOWN UPON ANY ALARM CONDITION, COORDINATE FIELD LOCATION WITH MECHANICAL CONTRACTOR.DUCT SMOKE DETECTORS INDICATING LAMPS SHALL BE MOUNTED AT 80" AFF AND HAVE AN ENGRAVED COVERPLATE WITH ADDRESS, UNIT SERVED AND DETECTOR LOCATION (IE L1--D30,AHU-XX, SUPPLY). PROVIDE ANY ASSOCIATED CABLING AND CABLING CONNECTIONS BETWEEN DUCT DETECTOR AND REMOTE TEST STATION. COORDINATE EXACT LOCATION WITH THE GENERAL CONTRACTOR AND OWNER PRIOR TO INSTALLATION. MINIMUM CABLING REQUIREMENTS SHALL BE AS FOLLOWS: INITIATION CIRCUITS (THHN) CLASS B, SUPERVISORY (THHN) CIRCUITS CLASS B, NOTIFICATION CIRCUITS (THHN) CLASS B, STYLE Y, SIGNALING LINE CIRCUITS (TSP) CLASS B, STYLE 4, AUXILIARY CIRCUITS (THHN) CLASS B ALL FIRE ALARM SYSTEM INSTALLATION ACCORDING WITH NFPA 72 2002 EDITION, AND COMPLY WITH THE 2001 FLORIDA BUILDING CODE WITH 2O02/2003 REVISIONS AND THE FLORIDA FIRE PREVENTION CODE (2005). ALSO ALL CONDUIT AND WIRING SHALL BE UNDER NFPA 70 (NEC). CONSTRUCTION DOCUMENTS PROVIDE BY; miff ,..:...:.. PARKING CONSULTANTS 4902 Eisenhower Boulevard Suite 281 Tampa, FL 33634 813.888.5800 Ph. 813.888.5822 Fax BE— 0003840 Hoyle, Tanner & Associates, Inc. 3452 LAKE LYNDA DRIVE, SUITE 151, ORLANDO, FL 32817 11 nuft tel; (407) 380-1919 fax: (407) 380-1830 email: htaor11`10hta--fl.com web: www.hoyletanner.com CA POESTRI4 DATUM ELEVATION 50.5' = 0'-0' I EXIT ISOMETRIC (V NQRTH TOP LEVEL EL. R 0-10" ■ + w DRAWN BY: EL = 38'--2" CHECKED BY: 3RD LEVEL. DATE: EIS' S AJPZM 2 0 DRAWING NAME: 2ND LEVEL 917872302--C EL SCALE: UUC Y PARKING � / � �"— I I — 01 . h GROUND LEVEL EL. - 0 -O PROJECT No. / PROMPT Nc , 917872302 FILE LOCATION: OSIA--GARAGI SHEET: 6 of © 2001 "NOTICE: This drowfng and the data thereon shall not be duplfcated, used, or disclosed to others for procurement or manufacturing purpooes, except ae otherwise authorized by contract, without the written permission of SimplexGrinnell. All reproductions shall bear this; notice." TYPICAL DEVICE MOUNTING HEIGHTS A/0 SUPPLY DIFFUSER GM! ING MOUNTW SMOKE/HEAT 3' CMIN) — «� DETECTOR ) I � OM W MIN HANDICAP ACCEPTED HERE BEDROOM STROBE AUDIO VISUAL DEVI�AL—ONLY SYNCHRONIZE MORE THAN TWO APPL IANCIES IN ANY FIELD OF VIEW SPACED A MINIMUM OF W FROM EACH OTHER IN ROOMS BW x W OR GREATER. NFPA 72 2002 EDITION $O" MI 90" MANX NFPA 72 2002 EDITION FINISHED FLOOR MANUAL PULL STATION FIRE PHONE JA�F 48" MAX (ADD 42' MIN/84' MAX (NFPA) NFPA 72 2092 a MAGNETIC DOOR HOMER NOM MEASUREMENTS 4" RHONN ARE TO THE CLO$M OF THE onmlexl. NEVER 12" CMAX) HEE WALL MOUNTED 5MOKE/FIEAT DE CTOR FINISHED WALL SIDE WALL GROUND LEVEL PLAN SCALE: 1 /8" = V-0" EXISTING TERMINAL EXTERIOR WALL EXISTING DOOR OPENING TO REMAIN DECK TOWER SECOND LEVEL PLAN SCALE: 1 /8" = V-0" )ECK )WER FIRE ALARM SYSTEMS GENERAL NuTES GENERAL NOTES (ALL SHEETS) 0 PROVIDE DEDICATED 120 VAC CIRCUITS, TO FIRE ALARM PANEL. LABEL THE DEDICATED CIRCUIT "FIRE ALARM SYSTEM" AND PLACE LOCK OUT ON CIRCUIT AT ELECTRICAL PANEL, CONNECT ALL FIRE ALARM PANEL OUT PUT TO EXISTING FIRE ALARM SYSTEMS AT THE TERMINAL MOUNT SMOKE DETECTORS AT THE CEILING, AND NOT ON THE BOTTOMS OF BEAMS OR JOISTS. LOCATE ALL SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM ANY MECHANICAL DIFFUSERS, AND AS REQUIRED BY NFPA 72. SMOKE DETECTOR HEADS SHALL NOT BE INSTALLED UNTIL AFTER THE CONSTRUCTION CLEANUP OF ALL TRADES IS COMPLETE AND FINAL. ALL DUCT DETECTOR SHALL BE PROGRAMMED FOR AHU SHUT DOWN UPON ANY ALARM !dJ CONDITION. COORDINATE FIELD LOCATION WITH MECHANICAL CONTRACTOR.DUCT SMOKE DETECTORS INDICATING LAMPS SHALL BE MOUNTED AT 80" AFF AND HAVE AN ENGRAVED COVERPLATE WITH ADDRESS, UNIT SERVED AND DETECTOR LOCATION (IE L1-D30,AHU-XX, SUPPLY), PROVIDE ANY ASSOCIATED CABLING AND CABLING CONNECTIONS BETWEEN DUCT DETECTOR AND REMOTE TEST STATION, COORDINATE EXACT LOCATION WITH THE GENERAL CONTRACTOR AND OWNER PRIOR TO INSTALLATION. MINIMUM CABLING REQUIREMENTS SHALL BE AS FOLLOWS: INITIATION CIRCUITS (THHN) CLASS B, SUPERVISORY (THHN) CIRCUITS CLASS B, NOTIFICATION CIRCUITS (THHN) CLASS B, STYLE Y, SIGNALING LINE CIRCUITS (TSP) CLASS B, STYLE 4, AUXILIARY CIRCUITS (THHN) CLASS B ALL FIRE ALARM SYSTEM INSTALLATION ACCORDING WITH NFPA 72 2002 EDITION, AND COMPLY WITH THE 2001 FLORIDA BUILDING CODE WITH 2O02/2003 REVISIONS AND THE FLORIDA FIRE PREVENTION CODE (2005). ALSO ALL CONDUIT AND WIRING SHALL BE UNDER NFPA 70 (NEC). CONSTRUCTION DOCUMENTS PROVIDE BY: MW Isom WALM-M K "`"' PARKING CONSULTANTS 4902 Eisenhower Boulevard Suite 281 Tampa, FL 33634 813.888.5800 Ph. 813.888.5822 Fax BE-0003840 191111111110 Hoyle, Tanner Associates, Inc. ul 3452 LAKE LYNDA DRIVE, SUITE 151, ORLANDO, FL 32817 tel: (407) 380-1919 fax: (407) 380-1830 email: htaarlfl®hta•-fl.com web: www.hoyietanner.com C w r + T " D 2003 'NOTICE; This drawing and the data thereon shall not be duplicated, used, or disclosed to others for mourement or manufacturing purposes, except as otherwise authorized by contract, without the written mmission of SimplaxGrinnell. All reproductions shall bear this notice," 4098--9682 4 WIRE BASE, WITH SMOKE DETECTORS, LED OUTPUT AND AUXILIARY ALARM RELAY PRQQUQT INFORMATION FEATURES: d UL LISTED TO STANDARD 268 4' X 2 1/2' DEEP OCTAGONAL PATH 1 1/2' EXTENSION RING e MULTI -FUNCTION INDICATOR LED: e SQUARE X 1 1/2"DEEPOWITH i I/Y EXTENSION RING — INDICATES NORMAL AND ALARM CONDITIONS AND A 4090-9832 ADAPTER PLATE (6 3/8 X 1/4') — PROVIDES DETAILED DIAGNOSTIC INFORMATION FOR Box SUPPLIED BY CONTRACTOR SERVICE EVALUATION — IDENTIFIES DIRTY DETECTORS, ASSISTING WITH MAINTENANCE PRIORITIES A FUNCTIONAL CHAMBER ENCLOSURE: — LOUVERED DESIGN ENHANCES SMOKE CAPTURE BY DIRECTING FLOW TO CHAMBER — ENTRANCE AREAS ARE MINIMALLY VISIBLE WHEN CEILING MOUNTED O MAGNETICALLY OPERATED FUNCTIONAL TEST — INITIATES ALARM AND VERIFIES PERFORMANCE n — IDENTIFIES GENERAL SENSITIVITY STATUS USING DETECTOR LED DETECTOR HEADS 4098-9801 PHOTOELECTRIC STANDARD (2.89) SMOKE DETECTOR (� • DETECTOR MODELS AVAILABLE IN TWO SENSITIVITY SETTINGS: 4088-9805 PHOTOEIECTPoC (3.M SMOKE DETECTOR o 0 - 4908-9601, STANDARD SENSITIVITY, NOMINAL 2.8%/FT. OBSCURATION - 4900-9605, SPECIAL APPLICATION SENSITIVITY, NOMINAL 3.5%/FT, OBSCURATION ® AUXILIARY ALARM RELAY CONTACTS: - SINGLE FORM "C" RATED 2A 0 26VOC, FOR TRANSIENT SUPPRESSED LOADS. o - RELAY CONNE011ONS COLOR CODED #18 AWG LEADS o REMOTE ALARM INDICATING LED OUTPUT • MOUNTING: CEILING OR WALLL e COLOR : FROST WHITE FLUSH MOUNTING (BOX TO BE FLUSH OR RECESSED 1/4' MAXIMUM). SPECIFICATIONS: 4 VOLTAGE: 15 TO 32 VDC 4 INPUT RIPPLE VOLTAGE: 25% MAX. o ALARM CURRENT: 86 mA 0 24 VDC 4 SURGE CURRENT: 200uA 0 24 VDC a STANDBY CURRENT: 1OOUA 0 24 VDC + AIR VELOCITY RANGE: 0-2000 FT/MIN (0-610 M/MIN) . ALTITUDE: 8,000 FT. (2438m) ® UL LISTED TEMPERATURE RANGE: 32'F TO 107F • OPERATING TEMPERATURE RANGE: 15'F TO 122E • HUMIDITY RANGE: 107. TO 95% RH IN DIMENSIONS WITH HEAD: 4 7/8' 0 X 1 7/8" H DESCRIPTION: TRUEALARM PHOTOELECTRIC DETECTORS PROVIDE MANY OF THE PROVEN TRUEALARM ANALOG SENSING FEATURES FOR APPLICATIONS WHERE DETECTORS ARE CONNECTED TO CONVENTIONAL INITIATING DEVICE CIRCUITS (ID05). EACH TRUEALARM DETECTOR HAS AN ON —BOARD MICROPROCESSOR THAT EVALUATES ITS PHOTOELECTRIC LIGHT SCATTERING CHAMBER FOR ACTIVITY AND MAKES AN INTELLIGENT DECISION BASED ON LIGHT OBSCVRATION HISTORY AS TO WHETHER AN ALARM CONDITION IS PRESENT. TRUEALARM DETECTORS ARE PACKAGED IN A PATENTED HOUSING THAT MINIMIZES THE VISIBILITY OF THE AIR INTAKE LOUVERS FROM THE NORMAL VIEWING LOCATIONS WHILE MAINTAINING A HIGH PERFORMANCE SMOKE + FROM 24VDC �-- — — POWER SOURCE F , CAPTURE ABILITY, OPTIONS: 4098-9830 REMOTE ALARM INDICATOR, PROVIDES A REMOTE RED ALARM LED STATUS INDICATOR MOUNTED ON A SINGLE GANG STAINLESS STEEL PLATE, + IORG 2098-9735 24 VDC END —OF —LINE RELAY, PLATE MOUNTED (ONE REQUIRED PER CIRCUIT) FROM PREVIOUS DEVICE OR 2095-9739 4 VDC END —OF —LINE RELAY, ENCAPSULATED FIRE ALARM CONTROL PANEL �GRN ()NE REQUIRED PER CIRCUIT) WIRING: 1. ALL WIRING TO COMPLY WITH LOCAL CODE. 2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS. 3. IF USED, 4098-9830 REMOTE LED IS POLARIZED MAINTAIN CORRECT POLARITY 4, REFER TO APPLICATION MANUAL (574-709) 5, REFER TO INSTALLATION INSTRUCTIONS (574-706) RELAY MODULE MOUNTS BEHIND SMOKE DETECTOR BASE IN SAME BOX. R1 TO REMOTE ALARM INDICATOR 4098-083( (IF USED) SEE WIRING NOTE 3 RELAY MODULE MOUNTS BEHIND SMOKE DETECTOR BASE IN SAME BOX. 24VDC END -OF -LINE RELAY ONE PER CIRCUIT REQUIRED 2098-9735, PLATE MOUNTED 2098-9739, ENCAPSULATED DIAGRAMS PROVIDED A PANEL FOR PROPER SISTOR VALUES, 4098---9756 ADDRESSABLE 4--WIRE DUCT SENSOR MAPNET II/IDNet WITH 24VDC RELAY EROUQCTIER ATI N DUCT DETECTOR SELECTION CHART FEATURES: COMPACT AIR DUCT SENSOR HOUSING WITH CLEAR COVER TO MONITOR FOR THE PRESENCE OF SMOKE INCLUDES FACTORY INSTALL TRUEALARM PHOTOELECTRIC SMOKE DETECTOR AND FEATURES: • INDIVIDUAL SENSOR INFORMATION PROCESSED BY THE HOST CONTROL PANEL TO DETERMINE SENSOR STATUS • DIGITAL TRANSMISSION OF ANALOG SENSOR VALUES VIA MAPNET it OR IDNet 2-WIRE COMMUNICATIONS • PROGRAMMABLE SENSITIVITY, CONSISTENT ACCURACY, ENVIRONMENTAL COMPENSATION, STATUS TESTING, AND MONITORING OF SENSOR DIRT ACCUMULATION MODEL: + DUCT SENSOR HOUSING WITHSUPERVISEDOUTPUT FOR ULTIPLE REMOTE RELAYS, REQUIRES SEPARATE 24 VDC A VOTE M NU AOf 8Y AN SEPARATDE ALAi�M/INPUT) GENERAL FEATURES: • UL LISTED TO STANDARD 268A • CLEAR COVER ALLOWS VISUAL INSPECTION • TEST PORTS PROVIDE FUNCTIONAL SMOKE TESTING ACCESS WITH COVER IN PLACE • MOUNTS TO RECTANGULAR DUCTS OR ROUND DUCTS (MINIMUM SIZE 8' SQUARE OR 18" DIAMETER) • MAGNETIC TEST FEATURE FOR ALARM INITIATION AT HOUSING • OPTIONAL WE THERPROOF ENCLOSURE IS AVAILAB E SEPARATELY 2REFER TO DATA SHEET S4098-0032 DIAGNOSTIC LEOS (ON INTERFACE BOARD): • RED ALARM/TROUBLE LED FOR SENSOR STATUS AND COMMUNICATIONS POLUNG DISPLAY • YELLOW LED FOR OPEN OR SHORTED TROUBLE INDICATION OF SUPERVISED RELAY CONTROL SAMPLING TUBES (ORDERED SEPARATELY): r AVAILABLE IN MULTIPLE LENGTHS TO MATCH DUCT SIZE • INSTALLED AND SERVICED WITH HOUSING IN PLACE REMOTE MODULE OPTIONS (ORDERED SEPARATELY): • RED STATUS/ALARM LED (2098-9808) • TEST STATION WITH LED (2098-9806) • RELAYS USED (4098-9843) SPECIFICATIONS: DUCT SMOKE SENSOR HOUSING WITH PHOTOELECTRIC SENSOR MODEL DESCRIPTION COMPATIBILITY DUCT HOUSING WITH SUPERVISED MULTIPLE RELAY CONTROL FOR UP 4098-9756 TO 15, 4098-9843 RELAYS ORDERED SEPARATELY), REQUIRES SIMPLEX FIRE ALARM CONTROL MODELS SEPARATE 24 VDC FIRE ALARM POWER AND RELAY END —OF —LINE 4010, 4020, 4100, AND 4120. RESISTOR REMOTE LED INDICATOR AND TEST STATION, SELECT ONE IF REQUIRED MODEL DESCRIPTION MOUNTING 2098-9808 RED LED STATUS INDICATOR USE SINGIaE GANG BOX, 76 mm X 51 mm X D mm ( ) 2098-9806 TEST STATION WITH KEYSWITCH AND RED LED STATUS TURNING SWITCH TO TEST INITIATES ALARM FOR SYSTEM TESTING O 2098-9808 REMOTE STATUS/ALARM INDICATOR GENERAL SPECIFICATIONS AIR VELOCITY RANGE LINEAR FT MIN 300 TO 4000 FT min 91 TO 1220 m min ALTITUDE UP TO 8000 FT. 2.4 km SENSOR SENSITIVITY RANGE 0.2% TO 3.77 PER FOOT OF OBSCURATION, SELECTABLE AT HOST CONTROL PANEL L "ITED TEMPERATUREN 'F "C TO 3' OPERATING TEMPERATURE RANG 32" F ' F 0' C TO 50' STORAGE TEMPERATURE RANGE 0' F TO 140' F —18' C TO 60' C HUMIDITY RANGE 10% TO 9 % RH, NON —CONDENSING HOUSING COLOR BLACK BASE WITH CLEAR COVER WIRING CONNECTIONS TERMINAL BLOCKS, 18 TO 12 AWG REMOTE STATUS/ALARM LED AND TEST STATION WITH REMOTE STATUS/ALARM LED REMOTE ALARM LED CURRENT 1.2m ' 'NO IMPACT TO ALARM -CURRENT _(2 8-98139 OR 2095-9806 TEST STATION KEYSWITCH CURRENT 3,3 mA NO IMPACT TO ALARM CURRENT 2098-9806 REMOTE ALARM LED AND TEST STATION DISTANCE 250 FT, (76m) MAXIMUM ADDRESSABLE OPERATION DATA COMMUNICATIONS MAPNET II OR IDNet COMMUNICATION, AUTO —SELECT 1 ADDRESS PER HOUSING, PROVIDES OPERATING POWER TO MODEL 4095--9755 MODEL 4098-9756 WITH SUPERVISED MULTIPLE RELAY CONTROL, REQUIRES SEPARATE FUSED 24 VDC FROM FIRE ALARM POWER SUPPLY INPUT VOLTAGE 18-32 VDG(24 VDC NOMINAL) STANDBY CURRENT 2.4 mA 0 24 VDC ALARM CURRENT 15 mA 0 24 VDC, ADD 15 mA ADDITIONAL FOR EACH 4098-9843 RELAY 4098-9843 RELAY OUTPUT RATINGS, SINGLE FORM C COIL CURRENT 15 mA_ V L C N L OUTPUT T RELAY CONTACTS, RESISTIVE RATINGS 7 A 9 26 VDC; 10 A 0 120 VAC; 250 UA 0 5 VDC LOCATION DISTANCE 500 FT, (152m)) MAX. TO RELAY COILS, RELAY MUST BE WITHIN 3 FT, (1m) OF DEVICE BEING CONTROLLED PER NFPA 72, SECTION 3-9.2.1 2098-9806 TEST STATION (OPTIONAL) 2095-9808 ALARM INDICATOR RED ALARM LED SEE NOTES TUBE SUPPORT HOLE SHALL BE USED FOR DUCTS MORE THAN 3 FEET WIDE -----rINSERT RUBBER PLUG EXHAUST TUBE CUT TO 1/2 OF DUCT WHEN < 24" DO NO INSERT RUBBER PLUG FOR DUCT WIDTHS I FOR DUCT WIDTHS 3' TO 95" 8" TO 3' 4098-8758 4-WIRE DUCT SENSOR SMr2 2 t» 3 C� 5 am= aEmm A,SD.RTESS BLK UL LISTED CONTROL PANEL SIMPLEX 4010, 4020 4100+ OR 4120 MAPNET II/IONot (OPTION`A`L) SEE NOTE 1 POWER CIRCUIT + 24 VDC +24V 124C (OPTIONAL) 4098-8758 2098-9806 4-MARE DUCT SENSOR REMOTE OR/RM SW2 1 g KEYSWITCH 2 am= RED 5 � ALARM e 7 8 ASM�ATCH 1 F-- TEST TB1 SEE NOTES 3,4 0, o, 0a ra 0 SHIELD L m WHT-r �---+ �-WH7 OPTIONAL _ BLU—C 4098-9843 4098-28 PAW -SO YEL—N.0 PAW -SC RELAY CRC—N.O. RELAY + + RED BLK zz SHIELD SI$TOR EOL 81-9008 WIRING NOTES: 1, DUCT SENSOR WIRING IS 12 TO 18 AWG, 2. MAXIMUM QUANTITY OF DEVICES PER CIRCUIT IS 127 FOR 4020, 4100+, OR 4120, AND 250 FOR THE 4010 PANEL 3. THE 2098-9806 AND 2098-9808 ARE POLARIZED, OBSERVE COLOR -CODED WIRING. 4. MAXIMUM WIRE LENGTH TO TEST TERMINALS AND REMOTE LED IS 250 FEET. 5. 4095-9843 PAM-SD RELAY (AIR PRODUCTS & CONTROL LIMITED) ARE RATED AT 7 AMPS 28 VDC/10 AMPS 0 115 VAC. MAXIMUM WIRE LENGTH TO PAM—SD RELAYS IS 500 FT. 15 PAM—SD RELAYS MAX.). WIRING FROM THE RELAY TO THE DEVICE IT IS CONTROLLING HOULD BE NO MORE THAN 3 FT, (PER NFPA 72). +24V 124C TO OTHER _ MAPNET II/IDNat OEMICES SEE NOTE 2 OR RETURN TO FACP FOR STYLE 8 %0 4098-9792 STANDARD SENSOR BASE PRODUCT INFORMATION FEATURES: • UL LISTED, FM APPROVED o TRUEALARM ANALOG SENSING PROVIDES DIGITAL TRANSMISSION OF ANALOG SENSOR VALUES VIA MAPNET II, OR IDNet TWO WIRE COMMUNICATIONS r FIRE ALARM CONTROL PANEL PROVIDES: -INDIVIDUAL SENSITIVITY SELECTION FOR EACH SENSOR -PEAK VALUE LOGGING ALLOWING ACCURATE ANALYSIS FOR SENSITIVITY SELECTION -AUTOMATIC ENVIRONMENTAL COMPENSATION -DISPLAY OF SENSITIVITY IN PERCENT PER FOOT -MULTISTAGE ALARM OPERATION -ABILITY TO DISPLAY AND PRINT DETAILED SENSOR INFORMATION IN PLAIN ENGLISH LANGUAGE s PHOTOELECTRIC SMOKE SENSOR 4098-9714: SEVEN LEVELS OF SENSITIVITY FROM 0.2% TO 3.7% a IONIZATION SMOKE SENSOR 4098-9717: FOUR LEVELS OF SENSITIVITY FROM 0.5% TO 13%. • HEAT SENSOR 4098-9733; -RATE-OF-RISE TEMPERATURE DETECTION IS SELECTABLE AT THE CONTROL PANEL FOR EITHER 157 OR ZO'F PER MINUTE -FIXED TEMPERATURE SENSING IS INDEPENDENT OF RATE -OF -RISE AND PROGRAMMABLE TO OPERATE AT 135F OR 155E -TRUEALARM HEAT SENSORS CAN BE PROGRAMMED AS A UTILITY DEVICE TO MONITOR FOR TEMPERATURE EXTREMES IN THE RANGE FROM 32' F TO 120' F. * UL STANDARD SPACING: -60 FT SPACING FOR 135' F -40 FT SPACING FOR 155' F • INTEGRAL RED LED FOR POWER -ON (PULSING), OR ALARM OR TROUBLE (STEADY ON) * BASE MOUNTED ADDRESS SELECTION: -ACCESSIBLE FROM FRONT (DIP SWITCH UNDER SENSOR) -ADDRESS REMAINS WITH ITS PROGRAMMED LOCATION e FOR USE WITH SIMPLEX 4010, 4100, 4020, AND 4120 SERIES CONTROL PANELS, • MAXIMUM QUANTITY OF DEVICES: -127 FOR 4020, 4100, 4120 -250 FOR 4010 *MOUNTING: CEILING OR WALL • COLOR : FROST WHITE e BASE DIMENSIONS: 15/10' X 4-7/8' SPECIFICATIONS: • UL LISTED TEMPERATURE RANGE: 327 TO 100'F • OPERATING TEMPERATURE RANGE: 327 TO 120E • HUMIDITY RANGE: 10% TO 95% RH • PHOTOELECTRIC SENSOR AIR VELOCITY RANGE: 0-2000 FT/MIN • IONIZATION SENSOR AIR VELOCITY RANGE, 0-300 FT/MIN a WIRING CONNECTIONS: SCREW TERMINALS FOR IN/OUT WIRING, #18 TO #14 AWG o COMMUNICATIONS MAPNET II/IDNet: 1 ADDRESS PER BASE VOLTAGE (MAPNET 11/I1)Net): 24-40VDC CURRENT: 400uA TYPICAL DESCRIPTION: TRUEALARM SENSOR BASES CONTAIN INTEGRAL ADDRESSABLE ELECTRONICS THAT CONSTANTLY MONITOR THE STATUS OF THE DETACHABLE PHOTOELECTRIC, IONIZATION, OR HEAT SENSORS. EACH SENSOR'S OUTPUT IS DIGITIZED AND TRANSMITTED TO THE SYSTEM FIRE ALARM CONTROL PANEL EVERY FOUR SECONDS. SINCE TRUEALARM SENSORS USE THE SAME BASE, DIFFERENT SENSOR TYPES CAN BE EASILY INTERCHANGED TO MEET SPECIFIC LOCATION REQUIREMENTS. THIS FEATURE ALLOWS INTENTIONAL SENSOR SUBSTITUTION DURING BUILDING CONSTRUCTION, WHEN CONDITIONS ARE TEMPORARILY DUSTY, INSTEAD OF COVERING THE SMOKE SENSORS. HEAT SENSORS MAY BE INSTALLED WITHOUT REPROGRAMMING THE CONTROL PANEL, ALTHOUGH THE CONTROL PANEL WILL INDICATE AN INCORRECT SENSOR TYPE, THE HEAT 4098-9714 4098-9717 4098-9733 HEAT SUM MAPNET II/IDN•t ADDRESS DI SEE BASE INSTALLATION INS' 574-709 FOR SETTINGS I ►.:-.,ITell-'�l- mw I�,ol V X 1 1/2' DEEP OCTAGONAL OR 4" SQUARE X 1 1/2" DEEP, WHICH REQUIRES A 4098-9832 ADAPTER PLATE (8-3/8' X 1/4') FLUSH MOUNTING (BOX TO BE FLUSH OR RECESSED 1/4" MAXIMUM) SENSOR WILL OPERATE AS A DEFAULT SENSITIVITY PROVIDING HEAT DETECTION FOR BUILDING PROTECTION AT THAT LOCATION. WIRING: J 1. ALL WIRING TO COMPLY WITH LOCAL CODE. — — — IL — — 2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS. TO ADDITIONAL MAPNET II/10Net DEVICES 3. MAINTAIN CORRECT POLARITY FROM PREVIOUS MAPNET il/ 0Net DEVICE SHIELD SHIELD — ` SHIELD OR RETURN TO FIRE ALARM CONTROL 4. MAPNET II/IDNet WIRING TO BE #18 AWG TWISTED SHIELDED PAIR OR FIRE ALARM CONTROL PANEL \ PANEL FOR A STYLE 6 APPLICATION 5. IF SHIELD IS USED, TWIST SHIELD WIRES TOGETHER AND CAP WITH WIRE NUT, SHIELD SHOULD BE INSULATED FROM ELECTRICAL BOX. 6. REFER TO INSTALLATION INSTRUCTIONS (574-707) 7. REFER TO APPLICATION MANUAL (574-709) PRODUCT INFORMATION FEATURES: • UL LISTED MOUNTING: FLUSH • FINISH: CHROME OR STAINLESS STEEL SPECIFICATIONS: • ALARM CURRENT: 1.2 mA Y DIMENSIONS OF BOX: 2 "W X 3"H X 2"D DESCRIPTION: 4098--9830 REMOTE ALARM INDICATOR, PROVIDES A REMOTE RED ALARM LED STATUS INDICATOR MOUNTED ON A SINGLE GANG STAINLESS STEEL OR CHROME PLATE. WIRING: MINIMUM 18 AWG OR TO LOCAL CODE, 0 CONDUCTORS MUST TEST FREE OF ALL GROUNDS. 0 POLARIZED: OBSERVE COLOR CODED WIRING, * ONE INDICATOR MAY BE INSTALLED PER DETECTOR. » DO NOT USE REMOTE RELAY IF REMOTE LED 1S USED. 4098---9880 REMOTE ALARM INDICATOR FLUSH MOUNTING CONNECT TO REMOTE RED ALARM LED OUTPUT OF APPROPRIATE INITIATING — DEVICESBLAC — — BACK VIEW STANDARD SINGLE GANG BOX 2" X 3" MINIMUM DEPTH 2" SUPPUED BY CONTRACTOR KM 4r 1 r j. T f DRAWN BY: CHECKED BY: DATE: 25 AJP2006 DRAWING NAME; 917872302-008 SCALE; 1/16„-i1_00$ PROJECT No. / PROMPT NO. 917872302 FILE LOCATION: OSIA-GARAGE SHEET: 8 of 9 Q 2003 "NOTICE; This drawing and the data thereon shall nut be duplicated, used, or disclosed to others for procurement or manufacturing purposes, except as othermise authorized by contract, without the written permission of SimplexGrinnell. All reproductions shall bear this notice,' PRODUCT INFORMATION MAPNET II ADDRESSABLE MONITOR ZAM 2190— 9155 FEATURES: T1/8°" DEEP9BOX 11/16'SQUARE SUPPLIED BY CONTRACTOR • UL LISTED • (RAGO NO, 203 f(TENSION RING 44SUPE�UEDXBY 1 FM APPROVED ONTR� R • CALIFORNIA STATE FIRE MARSHAL LISTING NUMBERS: 2199-9155 MONITOR ZAM: 7300-0026:182 • ZONE ADAPTER MODULES (ZAMS) PROVIDE o AODRESSABILITY TO CONVENTIONAL CIRCUITS • FOR USE WITH SIMPLEX MAPNET ii COMMUNICATIONS o °D • NFPA STYLE 4 MAPNET COMMUNICATIONS "T" 2 #s SCREWS (FLAT HEAD °n • STYLE 4 MAPNET WIRING MAY BE EITHER TAPPED OR IN/OUT • DIP SWITCH ADDRESS SELECTION, 8 SWITCHS v • MOUNTING: SURFACE SPECIFICATIONS: • DEVICE QTY. MAXIMUM 127 MAPNET II DEVICES ON A SINGLE PAIR OF WIRES • MAPNET II INPUT: 24 TO 40 VDC WITH DATA 2 SCREWS SIMPLEX P/N 412-779 • OPERATING TEMPERATURE RANGE: 32' F TO 120' F • HUMIDITY RANGE: 85% NON -CONDENSING 0 86' F MAPNET A ADDRESS Of SWITCHES • • ALARMVDCORY DC CURRENT: 90N mA MAX mA MAX LOAD PER ZZM PPEER 21 T0188 (574-888) FORTION aSET11NGS DESCRIPTION: SIMPLEX SURFACE COVER MONITOR ZAMS ARE USED WHEN THE FIRE DETECTING DEVICE OR SUPERVISORY SWITCH IS MOUNTED SEPARATELY FROM THE ADDRESSABLE ELECTRONICS. IT PROVIDES STATUS MONITORING AND SUPERVISION TO THE DEVICE CIRCUIT ZONE. WHEN SURFACE MOUNTING INTERFACED TO MAPNET II COMMUNICATION LINES, IT IS USED SEE WIRING NOTES FOR CIRCUITS WITH CONVENTIONAL DETECTORS, WATERFLQW, AND 2, 3, 4 & 7 TAMPER SWITCHES. WIRING: foam--- 1. CONDUCTORS MUST TEST FREE OF ALL GROUNDS. 2. MAPNET II LINES ARE TO BE #18 AWG TWISTED SEE WIRING NOTES SHIELDED PAIR (CONSULT SIR SALES ENGINEERING 51 6 FOR EXCEPTIONS). 3. MAXIMUM ALLOWABLE LINE RUN FROM '�'`° -saw 4020, 4100 OR 4120 TO FARTHEST DEVICE NOT TO EXCEED 2600 FEET. "� 1p ' ' " ' '� '�" °' '�' 4. MAXIMUM TOTAL WIRE (INCLUDING ALL T—TAPS ) ON MAPNET CIRCUIT FROM 4020, 4100 OR 4120 NOT TO EXCEED 10,000 FEET TOTAL. 5. FOR MAXIMUM VOLTAGE DROP, ETC., REFER TO R(+) SIR SALES ENGINEERING'S 4020 OR 4100 OR R + 28VDC 0 2 28VDC 4120 FIELD WIRING GUIDE 900-082. B _ 6. MINIMUM NO, 14 AWG WIRE FOR 28 VDC WIRING, - -g - e 3 OV L:h _ 0 3 OV OR TO LOCAL CODE. SEE WIRING NOTES c(+ 1 _-.__ �•• c(+) 7. MINIMUM NO. 18 AWG WIRE, OR TO LOCAL CODE. 5, 6 8. IF ZONE IS WIRED FOR ALARM VERIFICATION, WIRE ONLY SMOKE DETECTORS TO THAT ZONE. DO NOT B(—> USE ANY OTHER TYPE OF DEVICES ON THE SAME 28VDC ZONE. PREVIOUSFROM R(+) OR FIRE ALACONTROL CONTR 9, IF ZONE 15 NOT USED, CONNECT A 3.3K 1/2 W PANEL RESISTOR ACROSS ZONE TERMINALS TB1-11 AND MAPNET a(-) TB1-12, SHEILD C(+) 10, REFER TO FIELD WIRING DIAGRAMS 841--804 OR 841-996, SEE WIRING 11 1 11. REFER TO INSTALLATION INSTRUCTION (574-668). 2, 3, 4 & 3.3K 1 W PRODUCT INFORMATION FEATURES: • UL LISTED • FM APPROVED • CALIFORNIA STATE FIRE MARSHAL LISTING NUMBERS: 2098-9163 CONTROL ZAM: 7300-0020:182 • ZONE ADAPTER NODULES (ZAMS) PROVIDE ADDRESSABILITY TO CONVENTIONAL CIRCUITS • FOR USE WITH SIMPLEX MAPNET 11 COMMUNICATIONS • NFPA STYLE 4 OR 6 COMMUNICATIONS • STYLE 4 WIRING MAY BE EITHER Or TAPPED OR IN/OUT • DIP SWITCH ADDRESS SELECTION, 8 SWITCHES • MOUNTING: SURFACE SPECIFICATIONS: • DEVICE CITY: 127 MAPNET II DEVICES ON A SINGLE PAIR OF WIRES • OPERATING TEMPERATURE RANGE: 32" F TO 120' F • HUMIDITY RANGE: 85% NON -CONDENSING 0 86' F • CONTROL ZAM RELAY CONTACTS ARE RATED AT .5A 0 120 VAC OR 2A 0 28 VDC, RESISTIVE • SUPERVISORY DC CURRENT: 10 mA MAX LOAD PER, Z69 • ALARM DC CURRENT: 40 mA JJJ _MAPNET II ADDRESSABLE CONTROL ZAM 2(RACO NO. 190-91�3 2 P DEEP800X 11/16-SQUARE SU PLIED BY CONTRACTOR RACO NO. 203) EXTENSION 1/2" DEEP i UPPLIED BY CONTRACTOR WWNET u ADORESS DIP SWTCHES — SEE INSTALLATION INSTRUCTIONS PER-21-021 (575-279) FOR SETTINGS 2 WIG SCREW 8-32 FHMS-- 2 SCREWS SIMPLEX P/N 412-779 SIMPLEX SURFACE COVER DESCRIPTION: SURFACE MOUNTING CONTROL ZAMS ARE USED TO PROVIDE ADDRESSABLE SHEILD DTO ADOITIONAL EVICES OR MAPNET CONTROL FUNCTIONS SUCH AS ELEVATOR CAPTURE, HVAC CONTROL, PRESSURIZATION FAN CONTROL, DAMPER CONTROL TO ADDITIONAL MAPNET II PANEL E ALARM CONTROL FOR STYLE 6 1(C) SHIELD DEVICES OR RETURN TO MAPNET — 8 MAPNET PAFIRNEL FOR STYLE 8L SYSTEM APPLICATION WIRING: SYSTEM APPLICATION 28VDC TO NEXT DEVICE 1. ALL WIRING TO COMPLY WITH LOCAL CODE. Rt+� 2, CONDUCTORS MUST TEST FREE OF ALL GROUNDS. 3. MAPNET 11 LINES ARE TO BE #18 AWG TWISTED +(R) SHIELDED PAIR (CONSULT STR SALES ENGINEERING TO NEXT DC FOR EXCEPTIONS). 28VDC POWERED DEVICE 4. MAXIMUM ALLOWABLE LINE RUN FROM _(B) 4020 OR 4100 OR 4120 TO FARTHEST DEVICE NOT TO EXCEED 2500 FEET. B 1 �� SHIELD 1D0 _ ® 1 W® SHIELD 100 Pj _ B 5. FOR MAXIMUM VOLTAGE DROP,ETC.,REFER TO 2 ro STIR SALES ENGINEERING'S 4020 OR 4100 ( ) OR 4120 FIELD WIRING GUIDE. 4 "m MAPNET- - B 0 3 u� MAPNET- 8 - B 6. MINIMUM NO. 14 AWG WIRE FOR 28 VDC WIRING, 0 4 m� 7 TO LOCAL CODE. B 6NC •� MAPNET+ 5 +(a)___ Q 6NC a MAPNETI- —6— OR +(c) 7. CONTRACTOR WIRING TO RELAY CONTACTS IS SEE WIRING NOTES 7NO — B) 0 7 N 0 —(e) UNSUPERVISED. USE NO, 14 AWG, OR TO 7, 8, 9 8C OV 3 810 OV 3 ga LOCAL CODE. 49NC 2 (g, - 9NC 2 ® + R 8. RELAY CONTACTS RATED 2A, 28 VDC. FOR DC 28VDC + R 28VDC +(R)^��— m� LOADS. POWER MUST BE PROVIDED FROM F.A. 0 10N0 1 0 1ONO 1 CONTROL 4020 OR 4100 OR POWER SUPPLY LISTED T 2 TF TB Ty FOR FIRE PROTECTIVE SIGNALING USE, DERATE CONTROL 4020 OR 4100 OR POWER SUPPLY LISTED CURRENT RATING BY 50% FOR INDUCTIVE LOADING. 9. REFER TO INSTALLATION INSTRUCTIONS 575-279 OR 575-592. FUSE 21 J FUSE 1 , FUSE 2 FUSE 1 10, REFER TO FIELD WIRING DIAGRAMS 841-804 OR 841-996. +(R) SEE WIRING NOTES 28VDC I 3, 4, 5 _(B) � � � soon r� �. a�ra®r r ram• � e�m FROM PREVIOUS DEVICES SEE WIRING NOTES ' OR ARE ALARM CONTROL PANEL +(C) 5, 6 SEE WIRING NOTES NUMNIIII �, � .OW mom ME= MAPNET _ B 3, 4, 5 SHIELD : x== �' NJ SEE WIRING NOTES 5, 6 !, TrueAlertTIN0N--ADDRESSABLE MULTI —CANDELA AUDIO/VISIBLE NOTIFICATION APPLIANCE WHEELOCK ASWP-2475W—FR WEATHERPROOF AUDIO VISUAL PRODUCT INFORMATION FEATURES: (ELECTRONIC HORN W/STROBE) WHEN SURFACE MOUNTINGUSE RED SKIRT 05 9937 (RED • CLASS B (STYLE Y) OPERATION REQUIRES CONNECTION WHITE SKIRT NO. 4905-91 (WHITE 10 A COMPATIBLE SMARTSYNC NAC OR TO 4" SQUARE x 1 1/2' DEEP BOX SMARTSYNC CONTROL MODULE (SCM) 4905-9938 • CLASS A (STYLE Z) OPERATION WHEN CONNECTED TO THE C=_) 2975-9145 BOX 4905-9938 SCM OR 41000 SERIES FIRE ALARM v CONTROL PANEL NAC'S I ER 00 SPECIFICATIONS: 0 00 I •HOUSING DIMENSIONS (INCLUDING LENS) : 5 1/8"H X 5" W X 2 3/4"0 4905-8961 OPTIONAL WIRE i TEMPERATURE RANGE: 32' F TO 122' F 0' TO 60' C GUARD (SHOWN HERE FOR o� ( ) REFERENCE ONLY, CAN BE USED ON OTHER MOUNTING • HUMIDITY RANGE: 107, TO 93% NON -CONDENSING AT 100' F (38' C) OPTIONS) o p • TERMINAL BLOCKS FOR 18 AWG TO 12 AWG; TWO WIRES PER o TERMINAL FOR IN/OUT WIRING. STROBE nn ALTERNATE BACK BOXES -- RATED VOLTAGE RANGE: UL: REGULATED 24VDC PER UL 1971 u 1. 2 GANG 1 1/2' DEEP BOX ULC: 24VDC TO 3OVDC PER ULC S526-M878 0 L 2, SINGLE GANG 1 1/2' DEEP BOX -FLASH RATE: 1 Hz - SYNCHRONIZED MODE NAG LOADING: MAXIMUM OF 35 SYNCHRONIZED STROBES PER NAC CIRCUIT. Eq "CURRENT DRAWS REFLECT STROBE FLASHING AND HORN ON. 'INITIATING DEVICES CIRCUIT, STYLE B (CLASS B) WIRING SEE WIRINGS NOTE 7, 8, 9 SEMI -FLUSH MOUNTING HOUSING LETTERING STROBE RMS CURRENT 0 MODEL NUMBER COLOR COLOR RATING 16 VDC 18 VDC 24 VDC 4906-9127 RED WHITE 15cd 75 mA 70 mA 60 mA TO ADDITIONAL NOTIFICATION 30cd 116 mA 101 mA 84 mA -- ---- — --Z TPPLIANCDEVICE FACP FOR STYLE Z APPLICATION 75cd 221 mA 184 mA 143 mA IF LAST DEVICE ON CIRCUIT IN A 110od 285 mA 243 mA 185 mA ---' — — — -- --- STYLE Y APPLICATION PLACE A 4906-9125 WHITE RED 15cd 75 mA 70 mA 1 80 mA I TERMINALS S & 4 ARE NOT USED10K 1/2W END —OF UNE RESISTOR 30od 116 mA 101 mA 84 mA 75cd 221 mA 184 mA 143 mA I I ( I I 110od 285 mA 243 mA 185 rnA HORN - SOUND OUTPUT CHARACTERISTICS: 2400 TO 3700 Hz SWEEP, MODULATED AT 120 Hz RATE HORN SOUND OUTPUT RATINGS 0 10 FT. (3m) VOLTAGE 16 VDC STEADY CODED 24 VDC STEADY CODED 33 VDC STEADY CODED SOUND TYPE * REVERBERATE CHAMBER UL 464 TEST $6 dBA 82 dBA 88 dBA 84 dBA 90 dBA 86 dBA ANECHOIC CHAMBER 92 dBA 91 dBA 94 dBA 95 dBA [;6 d A 96 dBA * CODED VALUES ARE TYPICAL OF THE OUTPUT MEASURED WITH A TEMPORAL CODED OR A M/RCH TIME CODED PULSE AND WITH A SOUND LEVEL METER READING ON A FAST" SETTING. UNDER THE SAME TEST CONDITIONS, CODED HORN OUTPUT "PEAK" SOUND LEVEL READINGS ARE TYPICALLY 4 dBA HIGHER. FROM A COMPATIBLE SIMPLEX �+ --- SMARTSYNC NAC OR FROM SMARTSYNC CONTROL MODULE (SCM) 4905-9938 INTEHSTTY SFIECTION PLVO, MCESMLE CHLY _ FROM REAR OF HCAISING; FACTORY SETTING IS 15M TIME INTENSITY MEYANG SLOT SPECIFICATIONS INFORMATION INPUT REGULATED MODEL VOLTAGE VOLTAGE STRQBE NUMBER RANGE CANDELA VDC/FWR ASWP-2475W-FR 24 16.0-33.0 75 AVERAGE CURRENT AVERAGE CURRENT RATINGS (AMPS) SERIES ASWP VOLTAGE HIGH dBA SETTING (99) dBA MED dBA SETTING (95) dBA LOW dBA SETTING (90) dBA 16.0 VDC .219 .203 .201 24.0 VDC .157 .133 .126 33.0 VDC .138 1 .106 1 .094 dBA RATINGS FOR ASWP DESCRIPTION VOLUME REVERBERANT dBA PER VL 04 0 10ft, ANECHOIC dQA 9 10 ft. 24 VDC 24 VDC CONTINUOUS HORN HIGH 91 99 MED 88 95 LOW 83 90 CODE 3 HORN HIGH 87 99 MED 84 95 LOW 79 90 WARNING: TO PREVENT ELECTRIC SHOCK, DO NOT REMOVE THIS COVER. NO USER SERVICEABLE PARTS INSIDE BMX w 11 #6-20 X 1-3/4" SCREW (SUPPLIED) WHEELOCK WPBB-R BACK BOX UNIVERSAL MOUNTING PLATE (SUPPLIED) —\ v p \ \ X 1/2" TRUSS TRUSS HEAD SCREWS (SUPPLIED) WARNING: TO PREVENT ELECTRIC SHOCK, DO NOT REMOVE THIS COVER. NO USER SERVICEABLE PARTS INSIDE "a 0 FROM FACP 24VDC NOTIFICATION — — — — T — APPLIANCE CIRCUIT OR — — TO ADDITIONAL NAC DEVICES OR RETURN FROM FACP 24VDC NON -CODED — I — T T T _ TO FIRE ALARM CONTROL PANEL FOR STYLE Z APPLICATION. WITH WHEELOCK SM OR NOTIFICATION APPLIANCE CIRCUIT _ ��,/ -� .p F LAST DEVICE ON CIRCUIT IN A STYLE Y DSM SYNC MODULE APPUCATION, PLACE A IOK 1/2W END -OF - OR PRECEDING DEVICE. LINE RESISTOR. 4 00 liftb L0 Lo J 00 Z < a. i1 r r f r,. Ar w If