SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
Plans Review Sheet
Date: October 15, 2003 Business Address: 2353 JEWETT Lane
Occ. Ch. Business Occupancy 38
Business Name: Sanford Auto Dealers Exchange, Ph. (407) 322-1755
FAX O
Contractor: McKee Construction Ph. (407) 323-1150
FAX (407) 323-9304
Architect: Architectural Dynamics
Reviewed [] Ket eW,ed Wlth C011rileri tWX Rejected []
Reviewed by: Timothy Robles, Fire Protection Inspector/plans Examiner —/;;
Comment: Plans reviewed as Business Occupancy. FD reserves right to require applicable code
requirements if occupancy use changes. Sprinkler System require per local city ordinance.
Fire sprinkler system shall be monitored per City of Sanford local ordinance. Fire sprinkler
contractor to submit design criteria for sprinkler system.
1.1 Application — New Building. 13,400 sq. ft. , Type IV- fire sprinkler protected
1.2 Mixed — N/A
1.3 Special Definitions — Meets F.F.P.C.- 6.1.11.1 (Record keeping/Business
transactions).
1.40assification of Occupancy — Business F.F.P. C.
1.5 Classification of Hazard of Contents — Ordinary/6.2.2.2.
1.6 Minimum Construction — N/R
2.2 Means of Egress Components —
2.3 Capacity of Egress — One person per 100 sq ft (50 or more occupants shall
comply with 44' isle ways)
2.4 Number of Exits — O.K.
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI.32771 / P. O. Box 1788, Sanford, FI. 32772 `
407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
2.5 Arrangement of Egress — Two separate EXITS
2.6 Travel Distance — O.K., Does not exceed 129' ft 4" inches
2.7 Discharge from Exits — O.K., will field verify
2.8 Illumination of Means of Egress — O.K.; will field verify
2.9 Emergency Lighting =0k, will field verify
2.10 Marking of Means of Egress — O.K.; will field verify
2.11 Special Features —N/A
3.1 Protection of Vertical Openings — Shall be constructed as a smoke barrier with
degree of compartments
3.2 Protection from Hazards — N/N
3.3 Interior Finish - Class "A "or 'T "
3.4 Detection, Alarm and Communications Systems Required fire sprinkler monitoring
per City Fire Code
3.5 Extinguishing Requirements — as per NFPA 10 — Three (3) 4A rated fire extinguishers
required in this building mounted at 36" from floor to bottom one (1) 2A IObc fire
extinguisher required in brake room. (See blue prints)
3.6 Corridors - One -hour fare rated corridors (exception Fire Sprinkler System)
4 Special Provisions
5 Building Services
5.1 Utilities — Additional fare hydrant required per L.D.R. (250' FTfrom
principle building
5.2 HVAC - shall comply with N.F.P.A. # 90 A & #90B over 2000 C.F.M.
duct detectors required (blue prints show none over 1,200 c. f )
5.3 Elevators, Escalators, Conveyors: 5.4 Rubbish Chutes, Incinerators, and
Laundry Chutes — N/A
Sanford City Code — Chapter 9
Fire Sprinklers: blue prints required;
2
t, SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI.32771 / P. O. Box 1788, Sanford, Fl. 32772 a
407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
Monitoring: Required by a U.L. listed Central Station for all mandated fire
Sprinklered properties, per city code chapter #9
Other: NFPA 1
3-5.1 Fire Lanes — Not Required
3-6.1 Key Box —Required; will field verify, see application, and see blue prints
for location
3-7.1 Bldg. Address Number Posted and Legible — Required; will field veri , see
blue print for visible location