SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407 302-2.520 / FAX (407) 302-2.526
Pager (407) 918-0395
Plans Review Sheet
Date: November 18, 2003 Business Address: 330 E. Seminole Ave.
Occ. Ch. 36 New Mercantile
Business Name: Trail Head Building Ph. ()
Contractor: E.D.C. Ph. (407) 771-4442
FAX. (407) 771-4452
Comment: Plans reviewed as Mercantile Occupancy Class "C". Fl) reserves right to require
applicable code requirements if occupancy use changes.
Application — New Building. 2,910 sq. ft. New Mercantile occupancy
1.1 Mixed — N/A
1.2 Special Definitions — N/N
1.3 Classification of Occupancy — Class "C" (LESS THAN 3,000 sq. ft.)
1.4 Classification of Hazard of Contents — Ordinary per 6.2.2.2. F.F.P.C.
1.5 Minimum Construction — N/R (NO SPECIAL REQUIRMENTS)
2.2 Means of Egress Components -isles shall be maintained at all tames
2.3 Capacity of Egress — O K Less than 40occupants
2.4 Number of Exits — One (1) See exception #36- 2.4. Less than 75' (ft) Maximum according to
blueprints 60' (ft)
2.5 Arrangement of Egress — O.K., will field verify, per section 7.5>F.F.P. C.
2.6 Travel Distance — Shall not exceed 75' 36- 2.4.
t Y
SANFORD FIRE DEPARTMENT
SA
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407 302-2520 / FAX (407) 302-2526
Neer (407) 918-0395
2.8 Illumination of Means of Egress — O.K.; will field verify
2.9 Emergency Lighting — O.K.; will field verify
2.10 Marking of Means of Egress — O.K.; will field verify
2.11 Special Features -Reserved
3.1 Protection of Vertical Openings — Provide a basic degree of compartments
3.2 Protection from Hazards — N/N
3.3 Interior Finish — Class "B" "A" or "C" allowed per 10.2.8.1
3.4 Detection, Alarm and Communications Systems — Not required
3.5 Extinguishing Requirements — aer NFPA10, two (2)` 3A10 B C fire"extznguashers requiresp
3.6 Corridors —
4 Special Provisions
5 Building Services
5.1 Utilities — as per sec 9-1
5.2 HVAC — as per sec 9-2
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes — N/A
Sanford City Code — Chapter 9
FireSprinklers:E Not required
Monitoring: Not required.
Other: NFPA 1
3-5.1 Fire Lanes — Not required
3-6.1 Key Box — Not required
3-7.1 Bldg. Address Number Posted and Legible: Post address on building 6" in size
see blueprints)
2