March 11, 2003
Mr. Bob Bott
City of Sanford
Building Code Compliance Office
300 N. Park Avenue
Sanford, Florida 32771
RE: Additions and Renovations to Invacare
2101 E. Lake Mary Blvd.
Sanford Florida
GLE Project No.: 03000-04076
Dear Mr. Bott
This letter responds to your letter of February 24, 2003 regarding Building Code Plan Review for
the above -referenced project.
1.0 Roof Ton Equipment RTV -6
1.1 Comment
Roof top equip. within 10' of roof edge required 42" guardrail RTV-6
Response
A 6' long guardrail will be set on the parapet wall and will be 42" above the roof with a
intermediate rail centered so a 21" sphere will not pass through. Guardrail will be
centered on equipment. Fabrication will be same as interior guardrails. See
supplemental drawing A-101
2.0 Interior Stairs and Guardrail
2.1 Comment
Stairs not accessible to public, guardrails required to prevent passage of 21" sphere
1320 N. Semoran Boulevard - Suite 203 - Orlando, FL 32807 - 407/658-4151 - Fax: 407/658.4410
Architect AA 0002369 - Engineer EB 0005483 - Asbestos ZA 0000034 - Geology GB 0000297
OIAP-11-2003 21:17 GLE ASSOCIATES 407 G5e 4410 P.02i07
Response
Intermediate rail is shown on plans for guardrail but covered with tick mark of dimension
line. Will clarify with sketch. Intermediate rail will be added to stair hand rail. All
intermediate rails will be installed to prevent passage of 21" sphere. See supplemental
drawing A-101
3. 0 Openings in Tilt -up Panels
3.1 Comment
Submit detail of opening in existing tilt -up panels where sawcut, submit re-inforcement.
Response
See attached letter from our structural engineer Glenn Amore, P.E.
4.0 Smoke Detector in Supply and Return
4.1 Comment
Air handler 2,000 CFM or greater smoke detector in supply & return.
Response
Smoke detector will be added if not shown in the supply and return of air Handlers 2000
CFM or greater.
5.0 Life Safeq Plan
5.1 Comment
Submit life safety plan showing exits & travel distances & proximity to burn off ovens.
Response
Exit is within the 250' requirement of a sprinkled building. See supplemental drawings
A-102 (2 pages) Full size drawing can be furnished if required.
MAR-11-2003 21:17
GLE ASSOCIATES 407 GSS 4410
P.03/07
Please do not hesitate to contact us if you have questions concerning any of our responses to
your comments.
Sincerely,
GLE Associates, Inc.
David A. Miller
Project Manager
C. David Strong, Owner Strong Construction
Paul Visnoski, Invacare
R. Quinn Turner, GLE
Project File
WworklArch103000 Projects\04076 Invacare Constniction AdministrationVesponse to City of Sanford review 03-10-0240c
MAR-11-2003 21:17 GLE ASSOCIATES
407 G58 4410
PIPE P05T5 rn
� I
I I
T`"FIGAL 42" HIGH GU,4RD R,41L
STEEL PIPE HAND RAIL
BOTH 51DE5 OF STAIR
WELD TO 5TRIW-,ER 4'-0' OZ
WITH PIPE POSTS
PROVIDE INTERMEDIATE
RAIL IN CENTER
T I'PIGAL 5TAIR HAND RAIL
PROVIDE 4' X 4' X 1/4'
STEEL PLATE WITH 4
5/5' 0 ANCHOR5
TOP OF PARAPET
PIPE P05T5
INTERMEDIATE RAIL
CENTERED ON P05T ,
TOP OP ROOF --
42 " PIG- 4 GU,4}RD R,41 L AT PARAPET
SUF)FLEMENTAL EDfRAUJINe:1
�' aar�r�w�ie.,•a�a
onwiaR��o. wao,Rao�
p.K�:o auuaanetm as" t..rerd�se
4tooa gaia� seen uaJ �w
MAR-11-2003 21:18
Amore Enginee
Structural Enain"rs
ing, Inc.
GLE ASSOCIATES
407 658 4410 P.05i07
To: David Miller (CLE Associates)
CC: Bob Bett (City of Sanford Bldg. Dept)
From: Marc Graper, P.E. (Amore Engineering)
Date: February 26, 2003
Subject: Invacare Addition/Renovation - Bldg Dept Comments
Project #: 02-100
Plans Review Comments.
(3) Submit detail of opening in existing tilt up panels where sawcut, submit reinforcement
Note. comments (1), (2), (4), and (5) do not apply to the structural design, and shall not be addressed
herein.
Response:
Upon review of the existing 7-in, thick concrete tiitwall and the proposed penetrations' sizes and
locations, it has been determined that none of the proposed sawcut penetrations require any additional
structural reinforcemenL
Please call, if there are any questions/concerns.
2277 Lee Read, Suite 225
Wlnttr Park. Florida 32769
rhome (407) 6474 MO
Fax (407) 647.6119
FEB-26 -2003 14 : 00
APO f a7 r; t 1 q
MAR-11-2003 21:18 GLE ASSOCIATES 407 658 4410 P.06i07
II I
X
M
o O
a
I
•I
!•
x
r.•
4'-0'
&PPLEMMAL DRAM
�!!�/11iR11�YKtbl
NVACARE '°'pa 'a GU Anoatte4 IAG
SrMF010,:{.0WA OWmalft. GM Man alP�y. wlAo®r ue�egs
cra�eooaam>Ams� aav��
ai�ffi
fJQR'gdMoIaM�10
®
on
!dam
wsao 4wlo
A-102
MAR-11-2003 21:18 GLE ASSOCIATES 407 Gt>b 441U r.UriUr
110-.t
a
I
�lti • • WeftWWA DRAIUMRam
WACAW a w.ra+r+r /� .r/�
WMV, A fL�MWWAIMW. B+IMI�•B/MYlfi�ihlMliQIwO+ UPA-102
K RA1 �YOl61f�E:[O
013M00. RLRG� ]i001 lYIJ Neil [MKO
TOTAL P.07
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1.788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 330-5677
Pager (407) 918-0395
Plans Review Sheet
Date: February 24„ 2003 Business Address: 2101 E. Lake Mary Blvd.
Occ. Ch. # 40 Industrial
Business Name: INVACARE CORP. Ph. (�
Fax ()
Contractor: G.L.E. Associates Inc. Ph. (407) 658-4151
Fax (407)658- 4410
eviewed with co�m�ment ] Rejected
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner -
New addition to existing Industrial Occupancy 4179 sq. ft.
Comment: Fire department will require the following fire code items to be
addressed prior to permitting.
I.I.- Relocation of existingfire hydrant
1. Provide Sign by fire hydrant stating "NO PARKING FIRE LANE"
2. Paint fire hydrant red
3. Provide "crash ballads" around fire hydrant for protection
4. Provide Blue Reflective fire hydrant marker on pavement in front of fire
hydrant
5. Paint on ground in front of fire hydrant NO PARKING
1.2- Provide Floor Plan
1. Life safety diagram showing path of travel out of building around the
Oven area
2. Fire sprinkler blue prints required for permitting on the 4179 sq. ft. new
addition
1
---------------