SANFORD FIRE DEPARTMENT
1
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2520 / FAX (407) 3022526
Plans Review Sheet
Date: November 23, 2004 Business Address: 3715 S. Orlando Drive
Occ. Ch. 36 New Mercantile
Business Name: The Check Cashing Store Ph. (407)
Contractor: Not On Application. Ph. (407) FAX. (407)
Architect: Farmer & Company Ph. (407) 996-3600
Fax. (407) 996-5520
Reviewed ' e
] �l?leW�!>tG0/32ii21?n Rejected [
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner
Comment: Plans reviewed as Mercantile Occupancy Class "C". FD reserves right to require
applicable code requirements if occupancy use changes.
Application — New Building. 1,264 sq. ft. New Mercantile occupancy
1.1 Mixed — NIA
1.2 Special Definitions — N/N
1.3 Classification of Occupancy — Class "C" (LESS THAN 3,000 sq. ft.)
1.4 Classification of Hazard of Contents — Ordinary per 6.2.2.2. F.F.P.C.
1.5 Minimum Construction — N/R (NO SPECIAL REQUIRMENTS)
2.2 Means of Egress Components -isles sdiaZl be=maintainea'=at all.tim
2.3 Capacity of Egress — O T. Less them 4D occupants
1
SA.NFORD FIRE DEPAR711EI!11'
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
(407 302-2.520 / FAX (407) 3022.526
2.8 Illumination of Means of Egress — O.K.; will field verify
2.9 Emergency Lighting — O.K.; will field verify
2.10 Marking of Means of Egress — O.K.; will field verify
2.11 Special Features —Reserved
3.1 Protection of Vertical Openings — Provide a basic degree of compartments
3.2 Protection from Hazards — N/N
3.3 Interior Finish — Class "B" "A" or "C" allowed per 10.2.8.1
3.4 Detection, Alarm and Communications Systems — Not required
3.5 Extinguishing Requirements — as Pet °NFPA 10, 'one (1)3A10 B C' fide„extangirash�rs
recluar d
3.6 Corridors —
4 Special Provisions
- 5 Building Services
5.1 Utilities — as per sec 9-1
5.2 HVAC — as per sec 9-2
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes — N/A
Sanford City Code — Chapter 9
FWeSprinklers: required
Monitoring: required.
Other: NFPA 1
size
3-5.1 Fire Lanes — Not required
3-6.1 Key Box — Not required
3-7.1 Bldg. Address Number Posted and Legible: Post address on building 6" in
2
PROJECT
LOCATION
YV
L bfit ;a.r .F �!
..,
"'�
:y.���4
i
WLYI tQ¢�; tt
-g•.R >r3.
YS
......`YS3 8di"`s'yS
07,
za
Pam::
Xfi£ fir;
,i grhf'
3sF
.„J
Ar„��ryf'Ff•7L
®111111111,11111F T%19V V409F vtmwv
VAOM E 0 0 IN %NW ■ E I%mopv ■ N 11L ■ '® ry ■ '44mor-IL ® M 'I M a ® 111111 ® v
�. t v
v v �. .. \J� \J ` " .,1 ,�/ JL .L
A-1.20
REFLECTED CEILING PLAN
Inc*
A-1.30
DETAILS
S 0 t eminole
Qh
#740
otore
U.S H ghway No.17 & 92'(SR.15-600) ADT`00.49;000
. I
r
%� f� $ °:z$hasdueCa t
f }
IONIA
�'4 t, s t r ftj ii i 1 t` .� (�{
y s fqq '.l)c I tfI t jTl'I"T r r
E ;..j f 3 i p i Ss f i
_FTC t f *�j i a ,. : li} a t pp: I+ F i30i1t3f a ii
iKIf do-4i(ICB 1��� 14tj$ufpP ! Itl ti .y`1 Ti -: it ItPE i f i' vt
t € lilslirf is . i :i� {lii If awiat>re c91 :
4 hrr7afrSlo F L,
� 1 idea �arktas b:4
t 'ClCf S Y, 23 _ it 3h4G4f (jn PEIGv A0 11"9
4j I
_, r^-� �', e .s.. � -5 �I•aEl� t � t E� �It,
tYelter s` r € .:7A4 a[t it Aar
Adva t pica i. ,aoro:R)
+11i+e121s3 y SfifiY?I r t F :: i? r — Fr[ rR8 1 S kt i �l
hR s San,�t_
C
ea
i�2$C2l1fpE1 1 1 i4
a WA
L WAR}l
l
` I ;SUpar Center
f7 Nolncfuded -
y
a�cf�3:p i
REte7mpu f;
15 SITE PLAN
A-0.10 NOT TO SCALE
Sanford, Florida 3mo277
EXISTING ONE (1) HOUR FIRE RATED
DRYWALL PARTITION IN ACCORANCE
W/ UL DESIGN U-465.
EXISTING ONE (1) HOUR FIRE RATED
DRYWALL PARTITION IN ACCORANCE
W/ UL DESIGN U-465.
A LIFE SAFETY PLAN
A— 0.10 SCALE: 1/8°=1' -0"
LIFE SAFETY LEGEND
INDICATES WALL MOUNTED EMERGENCY LIGHT FIXTURE
WITH TWO (2) LAMPS AND BATTERY BACK—UP WIRED
INTO BUILDING EMERGENCY SYSTEM.
INDICATES ILLUMINATED EXIT LIGHT FIXTURE, SHADED
QUARTER(S) DENOTE ILLUMINATED FACE(S). ARROWS
DENOTE DIRECTION.
FEE DENOTES NEW SURFACE MOUNTED FIRE EXTINGUISHER.
0 REFER TO UNREFERENCED PLAN NOTES SHEET A-1.10.
E-1.10 FLOOR PLAN - ELECTRICAL
E-1.20 ELEC. NOTES RISERS
M-1.10 FLOOR PLAN - NVAC
M-1.20 NVAC - DETAILS
P-1.10 FLOOR PLAN - PLUME3ING
■E.P■ ENCINEEIZ
W
iul .,.>ry W�,
7
By:
���Date: � ' -
GAST
ENGINEERING, INC.
_C:316 CYPRESS LANDING DR. LONGWOOD, FL 32779
(407) 774-3188 PHONE
v S Yrri, f 44
5COPE OF WORK:
THE SCOPE OF WORK FOR THIS PROJECT SHALL CONSIST OF THE FOLLOWING
INTERIOR ALTERATIONS: NEW DRYWALL E METAL STUD INTERIOR PARTITIONS, A
SECRITY PARTITION WITH BULLET PROOF TELLER WINDOWS AND DEAL TRAYS,
NEW MILLWORK COUNTERS AND CABINETS, MODIFICATIONS OF THE EXISTING HVAC
DUCT WORK, ELECTRICAL AND VOICE/DATA OUTLETS, AND NEW INTERIOR FINISHES.
ALL PLUMBING FIXTURES INDICATED EXCEPT FOR SERVICE SINK ARE EXISTING TO REMAIN.
GENERAL INFORMATION
APPLICA15LE CODES
BUILDING: FLORIDA BUILDING CODE EDITION: 2001
PLUiv:.','NG: FLORIDA PLUMBING CODE EDITION: 2001
LIFE 5"AAFETY: NFPA LIFE SAFETY CODE EDITION: 2000
ELECTRICAL: FLORIDA ELECTRIC CODE EDITION: 2001
MECHANICAL: FLORIDA MECHAINAL CODE: EDITION: 2001
ENERGY: FLORIDA ENERGY CODE EDITION: 2001
FIRE: FLORIDA FIRE PREVENTION CODE EDITION: 2001
ADA, FLORIDA BUILDING CODE EDITION: 2001
OCCUPANCY
OCCUPANCY(S) / GROUP CLASSIFICATION: BUSINESS - GROUP B
TENANT AREA SQ. FT. 1,264 OCCUPANT / SQ. FT.: 1/100
TOTAL OCCUPANTS: 13
EXITS
MINIMUM NUMBER OF EXITS: I MAXIMUM TRAVEL DISTANCE: 200'-0"
MAX. DEAD END CORRIDOR: 20'-0MIN. CORRIDOR/AISLE WIDTH: 44"
MINIMUM STAIR WIDTH: 44"
CONSTRUCTION
SPRINKLERED OR NON-SPRINKLERED t NON - SPRINKLERED
NUMBER OF STORIES: I CONSTRUCTION TYPE: IV
UNPROTECTED
IF MULTIPLE OCCUPANCY
OCCUPANCY SEPERATION: [-HOUR TENANT SEPERATION. N/A
LIFE SAFETY 5UMMARY
ITEM
REQUIRED
PROVIDED
REMARKS
DOORS
2
2
EXIT DOOR
2.6"
68"
SEE NOTE I E 2
WIDTH
MAX. TRAVEL
200'
58'-8"
COMMON PATH
OF TRAVEL
75'
N/A
DEAD END
20 '
N/A
CORRIDOR
1, 1,264 SQUARE FEET 0 1/100 = 13
13 X .20VOCC = 2.6
2. 2 36" DOOR(S) c 34" CLEAR = 68" CLEAR
TRAVEL DISTANCE
(COMMON PATH)
ARCHITECTURE
■ 1800 33rd Street
■ Suite 202
® Orlando, FL 32839
Phone: (407) 996-3600
® Fax: (407) 996-5520
® License # AA26000783
Seal
J
Daniel H. Farmer - AR1
C)
O
a�
CU
.i
CO
a�
o
U)
O CV
r C`7
V
0
Q
U
I
®
O
C
O
Q�
�
C
(n
M 00
REVISIONS:
�5PD
AI01.117%`:/a
DATE: OCT. 20, 2004
PROJECT NO.: 4077
DRAWN: F. EATON
CHECKED: F. EATON
COVER
514EET
NOTE #16
NOTE #I 004
FE M MOTE V5
o JAN. 003 XIT.
TTjOI E
#14
106 NOTE I I(
co
N
a
6' -03/4"
6UPPLY
104
NOTE #5
3
EQUAL
"`O
z
O
o
_-�
Q
m
+I
N
5' -0"
WORK AF
102
4' -4"
I
I I
NOTE #3
7' -23/8"
r --
-1.30
EQUAL 2' -6"
NOTE #2
I NOTE #7
O
N
NOTE #6
o�
'o
NOTE #5
N
— — — 4,-0' ------ -- �,
6 �
A-1.20 d"
NOTE #16
)� NOTE #5
I
I
NOTE #4'
TELLER AIL_
101
I
3
A-1.20
4'_8. ; o
NOTE #II
NOTE #13
3 ---J
imil'i J
-2` R.O.
10 911
..__._..
DOTE h12
FE
NOTE #17
8.+
9. 3' _0" F.O. �3' -4'
3'-2" R.O. '
002
� I
L - - J
o
..-----. �............f....... _.
NOTE #14 001
A FLOO(� PLAN
—I"IQ Scale- 1/4"=1'-O"
t
FLOOR PLAN LEGEND
INDICATES EXISTING OR BASE BUILDING PARTITION TO
REMAIN, VERIFY EXISTING CONDITIONS IN FIELD.
INDICATES EXISTING ASSUMED ONE (1) HOUR FIRE
RATED DRYWALL ASSEMBLY IN ACCORDANCE WITH U-465.
FIELD VERIFY AND TAKE CORRECTIVE ACTION AS REQ'D,
-1.20 INDICATES NEW NON -FIRE RATED DRYWALL PARTITION,
METAL STUDS AT 24" O.C. MAXIMUM WITH ONE (1)
LAYER GYPSUM BOARD EACH SIDE FROM FLOOR SLAB
TO UNDERSIDE OF SUSPENDED CEILING. REFER TO I/A-1.20.
3 INDICATES NEW SECURITY PARTITION, 6' 16 GA. STEEL
-1.20 STUDS AT 16" O.C. W/ 1/2" GYPSUM BOARD EACH
SIDE OVER 1/2" DURAROCK EACH SIDE TO UNDERSIDE
OF SUSPENDED CEIILING ABOVE. PROVIDE EXPANDED
SECURITY STEEL MESH ON 1 5/8" METAL STUDS FROM
TOP OF WALL TO UNDERSIDE OF ROOF DECK ABOVE.
2 REFER TO SECTION 3/A-1.20.
-1.20
INDICATES NEW LOW HEIGHT DRYWALL PARTITION,
METAL STUDS AT 16' O.C. MAXIMUM WITH ONE (1)
LAYER GYPSUM BOARD EACH SIDE TO 5'-0' ABOVE
FINISHED FLOOR. REFER TO SECTION 2/A-1.20
101 INDICATES ROOM, SPACE, OR AREA NUMBER.
001 DOOR AND HARDWARE DESIGNATION SYMBOL,
REFER TO DOOR SCHEDULE THIS SHEET.
FE INDICATES NEW SURFACE MOUNTED FIRE EXTINGUISHER.
O REFER TO UNREFERENCED PLAN NOTES THIS SHEET.
REFERENCED PLAN NOTES
NOTE #1 NEW SERVICE SINK. REFER TO PLUMBING DRAWINGS.
NOTE: #2 EXISTING HI-LO ADA ACCESSIBLE DRINKING FOUNTAIN TO REMAIN.
NOTE #3 TENANT PROVIDED SAFE UNDER NEW COUNTER TOP. G.C.
TO COORDINATE SIZE OF SAFE WITH MILLWORK OPENING.
NOTE #4 STAINLESS STEEL DEAL TRAYS (TYPICAL).
NOTE #5 PROVIDE 5/8' T S G PLYWOOD FROM FLOOR SLAB TO
UNDERSIDE OF ROOF DECK AT ALL TENANT DEMISING
WALLS IN TELLER AREA, WORK AREA, SUPPLY, JAN., AND
EXISTING TOILET AS INDICATED.
NOTE #6 UNDER COUNTER REFRIG. COORD. SIZE W/ MILLWORK.
NOTE #7 NEW PLASTIC LAMINATE BASE CABINET. REFER TO SECTION
4/A-1.20.
NOTE #8 NEW PLASTIC LAMINATE UPPER CABINET. REFER TO
SECTION 5/A-1.20.
NOTE #4 NEW 18" WIDE PLASTIC LAMINATE ADA ACCESSIBLE SERVICE
COUNTER MOUNTED AT 34" A.F.F. REFER TO SECTION
2/A-1.30.
NOTE 910 NEW 18" WIDE PLASTIC LAMINATE SERVICE COUNTER
MOUNTED 3'-6" A.F.F. REFER TO SECTION I/A-1.30.
NOTE #ll NEW UNDER COUNTER CASH DRAWER. G.C. TO COORDINATE
EXACT SIZE WITH OWNER PROVIDE CASH TRAY. EXACT LOCATION
TO BE DETERMINE IN FIELD BY OWNER.
NOTE #12 PAINTED CLAM SHELL CHAIR RAIL. TOP TO BE AT 41" A.F.F.
NOTE #13 PROVIDE 2" BLACK PLASTIC GROMMETS. LOCATION
TO BE DETERMINE IN FIELD BY OWNER.
NOTE #14 NEW SURFACE MOUNTED FIRE EXTINGUISHER HAVING A
MINIMUM RATING OF 2-A,10-BC FOR EVERY 3,000 SQ. FT..
EXTINGUISHERS SHALL BE CONSPICUOUSLY LOCATED AND
READILY ACCESSIBLE. THE TOP OF THE EXTINGUISHER
SHALL NOT BE MORE THAN 5 FT. ABOVE THE FLOOR AND
THE BOTTOM OF EXTINGUISHER SHALL NOT BE LESS THAN
4 INCHES FROM THE FLOOR. TRAVEL DISTANCE TO AN
EXTINGUISHER SHALL NOT EXCEED 75 FEET.
NOTE #15 PROVIDE 5/8" T E G PLYWOOD ABOVE EXISTING TOILET
CEILING TO UNDERSIDE OF ROOF DECK.
NOTE #16 NEW 1/2" DRYWALL OVER 3 5/8' METAL STUD PLUMBING
CHASE, APPLY T i G PLYWOOD TO DEMISING WALL
PRIOR TO CONSTRUCTION OF PLUMBING CHASE.
NOTE #17 COLUMN FURR-OUT, 1/2' DRYWALL OVER 1 5/8' METAL
STUDS, HOLD STUDS TIGHT TO EXISTING STEEL COLUMN.
REFER TO DETAIL 4/A-1.30.
UNREFERENCED PLAN NOTE5
ALL NEW DRYWALL PARTITION ARE TO BE TAPED, BEDDED, AND SANDED
TO RECIEVE TENANT FINISH AS PER FINISH SCHEDULE.
* DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS SHALL GOVERN,
LARGE SCALE DRAWINGS SHALL GOVERN OVER SMALLER SCALE
DRAWINGS. CONTACT DESIGNER TO CONFIRM ALL DISCREPANCIES.
* ALL INTERIOR DIMENSIONS ARE FROM FACE OF FINISH TO FACE
OF FINISH (F.O.F.) UNLESS OTHERWISE NOTED AS FACE OF STUD
(F.O.S.) OR FACE OF MASONRY (F.O.M.).
* ALL WORK S14ALL CONFORM WITH DRAWINGS AND SPECIFICATIONS
IN ACCORDANCE WITH ALL APPLICABLE GOVERNING MUNICIPAL AND
REGULATORY AGENCIES, CODES AND REQUIREMENTS. IT SHALL BE
UNDERSTOOD THAT ALL INTENDED WORK IS SUBJECT TO REVIEW AND
INTERPRETATION BY THE ADMINISTRATIVE AUTHORITY HAVING JURISDICTION,
AND IN NO CASE SHALL WORK BE PERFORMED WITHOUT THE REVIEW
AND WRITTEN APPROVAL OF SAID AUTHORITY. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR ALL FEES RELATED TO THE ISSUE OF
PERMITS, INSPECTIONS AND CERTIFICATES NECESSARY FOR THE EXECUTION
AND COMPLETION OF THE WORK AND THE OCCUPANCY OF THE AREA OF
WORK.
* PROVIDE FIRE EXTINGUISHERS) HAVING A MINIMUM RATING OF 2-A.
10-B.0 FOR EVERY 3,000 SQ. FT., EXTINGUISHERS SHALL BE
CONSPICUOUSLY LOCATED AND READILY ACCESSIBLE. THE TOP OF
THE EXTINGUISHER SHALL NOT BE MORE THAN 5 FT, ABOVE THE FLOOR
AND THE BOTTOM OF EXTINGUISHER SHALL NOT BE LESS THAN 4
INCHES FROM THE FLOOR. TRAVEL DISTANCE TO AN EXTINGUISHER
SHALL NOT EXCEED 75 FEET.
* REFER TO MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS
FOR ADDITIONAL INFORMATION.
000k v I4AFZDWARE 5CWEDULE
t4ARD\VARE
51ZE
TYPE
MATERIAL
FRAME
5ET
FINI5"
COMMENTS
001
3' -0" X 7' -0" X 1 3/4"
STOREFRONT
ALUM./GLASS
ALUM.
EXIST.
-
EXISTING DOOR FRAME TO REMAIN
PROVIDE BULLET PROOF WINDOW
002
3'-0" X 7'-0" X 1 3/4"
INSUL. CORE
H. METAL
STEEL
SET I
P-2
WITH DEAL TRAY, BOTTOM TO BE AT 34" A.F.F.
003
3'-0" X 6'-8" X 1 3/4"
EXIST.
WOOD
WOOD
EXIST.
P-4
EXISTING DOOR is FRAME TO REMAIN
004
3'-0" X 7'-0" X 1 3/4'
EXIST,
H. METAL
H. METAL
EXIST.
P-4
EXISTING DOOR � FRAME TO REMAIN
I4A[ZPWA1ZE LEC4END
b4AIZDWARE 5ET #1
LOCK
SET
1 1/2 PAIR BUTT HINGES
DOOR
STOP, FLOOR MOUNTED
SILENCERS (3 PER FRAME MIN.)
FIN1514 6CI4EDULE
ROOM
#
ROOM NAME
FLOOR
E5A5E
WALLS
CEILING
COMMENTS
NORT"
50UT14
EA5T
WEST
"C4T.
TYPE
P-1
P-1
P-1
P-1
EXISTING
P-1 ABOVE CHAIR RAIL
100
LOBBY AREA
F-2
8-2
P-3
P-3
P-3
P-3
10'-0"
C-1
P-3 BELOW CHAIR RAIL
101
TELLER AREA
F-I
B-I
P-3
P-3
P-3
P-3
C-1
102
WORK AREA
F-1
B-I
P-3
P-3
P-3
P-3
C-1
103
BREAK
F-2
B-2
P-3
P-3
P-3
P-3
C-1
104
SUPPLY
EXPOSED
B-1
P-3
P-3
P-3
P-3
C-1
105
EXIST. TOILET
F-2
B-2
P-3
P-3
P-3
P-3
EXISTING
C-2
PAINT EXISTING DRYWALL CEILING P-3
EXISTING
lOb
JAN.
F-I B-I
P-3 P-3
P_3 P-3
l0' -0" C-1
FIN1514
LEGEND
PAINT
MATERIAL,
EGGSHELL PAINT
e)A6E
P-1
MANAUFACTURER, SHERWIN WILLIAMS
COLOR,
CUSTOM COLOR BLUE
MATERIAL,
4" CARPET BASE
MATERIAL,
SEMI -GLOSS PAINT
13-1 MANAUFACTURER, -
COLOR,
TO MATCH FLOOR CARPET
P-2
MANAUFACTURER,
COLOR,
SHERWIN WILLIAMS
CUSTOM COLOR BLUE
MATERIAL.
4" CERAMIC TILE
MATERIAL,
EGGSHELL PAINT
B-2 MANAUFACTURER, -
COLOR
TO MATCH FLOOR TILE
P-3
MANAUFACTURER
SHERWIN WILLIAMS
COLOR,
CUSTOM WHITE COLOR
FLO®RING
MATERIAL,
SEMI -GLOSS PAINT
MATERIAL
CARPET
P-4
MANAUFACTURER, SHERWIN WILLIAMS
F-I
MANAUFACTURER,
TBD
COLOR
CUSTOM WHITE COLOR
COLOR,
TO BE SELECTED BY TENANT
MATERIAL,
12" X 12" CERAMIC TILE
CEILING
F-2
MANAUFACTURER,
TBD
COLOR:
TO BE SELECTED BY TENANT
MATERIAL,
2' X 4' ACOUSTICAL PANEL CEILING TILE
C-1
MANAUFACTURER,
EXISTING
COLOR/STYLE,
EXISTING
MATERIAL,
GYPSUM BOARD
C-2
MANAUFACTURER,
EXISTING
COLOR/STYLE:
EXISTING
FINI5" NOTES
I. ALL WALLS TO BE PAINTED SHALL RECIEVE (2) TWO COATS OF
SPECIFIED FINISH PAINT OVER (1) COAT PRIMER OF SIMILAR COLOR.
2. ALL DOOR FRAMES SHALL RECIEVE (2) TWO COATS OF SPECIFIED
OIL BASED ENAMEL OVER (1) COAT FACTORY PRIMER.
3. ALL FLOOR MATERIAL SHALL HAVE A MINIMUM OF CLASS II
INTERIOR FLOOR FINISH RATING AS CLASSIFIED IN ACCORDANCE
WITH NFPA.
DOOR AND WAIZOWARE NOTES
# ALL DOORS AND FRAMES SHALL BE BUILDING STANDARD WITH BUILDING
STANDARD FINISH TO MATCH EXISTING.
* ALL HARDWARE SHALL BE LEVER ACTION.
* PROVIDE DOOR STOPS, HINGES, CLOSERS, AND SILENCERS
AT ALL DOORS AS SPECIFIED IN DOOR SCHEDULE.
* NON -RATED INTERIOR SWINGING DOORS SHALL BE OPENABLE
BY A FORCE OF NOT MORE THAN FIVE (5) POUNDS APPLIED
TO THE LATCH STILE.
* THE FORCES REQUIRED TO FULLY OPEN FIRE -RATED (LABELED)
DOORS SHALL NOT EXCEED A 15 LBF TO RELEASE THE LATCH,
A 30 LBF TO SET THE DOOR IN MOTION AND A 15 LBF TO OPEN
THE DOOR TO THE MINIMUM REQUIRED WIDTH. THESE FORCES BEING
APPLIED TO THE LATCH STILE.
* ALL DOORS SHALL BE INSTALLED TO MEET REQUIRED CLEARANCES
AS SEEN IN PROVISION FOR BARRIER FREE DOORS ON THIS SHEET.
PIZOV1510N5 F01Z 5ARCZIER FREE 00OP-0)
PULL SIDE PUSH SIDE
c 18 min.
E 24 preferred
�
T�
(A) FRONT APPIZOACI4E5
PULL SIDE
x
NOTE, x = 12 IN If -T_L-F- DOOR
HAS BOTH ACLOSER AND A LATCH.
54 min.
1 I
PUSH SIDE
T
i
NOTE, x = 36 IN MINIMUM IF y = 60 IN NOTE, y = 4 MIN. IF DOOR HAS
x = 42 IN MINIMUM IF y = 54 IN. BOTH A LATCH AND A CLOSER.
(b) "INC,E 510E APPIZOAC"ES
PULL SIDE PUSH SIDE
24 min.
24 m n.
x x T E
CD
NOTE, y = 54 IN MINIMUM IF THE DOOR NOTE, y 48 IN'MN IF THE DOOR
HAS A CLOSER, HAS A CLOSER.
(C) LATC4 510E APPIZOACI4E5
NOTE, ALL DOORS IN ALCOVES SHALL COMPLY WITH THE CLEARANCES
FOR FRONT APPROACHES.
ARCHITECTURE
Daniel H. Farmer - AR107501k�,
CD
0
WIMMEJ
s
O
O
It
y
N
O
L
M
r..
CD
co
o
A."
a)
4-4
CIO
.�
(D
4
Q
O
�
O
U-
L_
O
.-
O
c
.E
u
T_
O
C
F�
U)
M
C)
REVISIONS:
DATE: OCT. 20, 2004
PROJECT NO.: 4077
DRAWN: FWE
CHECKED: FWE
SHEET:
FLOOR
PLAN
wow
rrREFLECTED CEILING LEGEND
NOTE #3
'1111010 M
Faiver
SUBSCRIPT 'E' INDICATES EXISTING ITEM TO REMAIN. - (`
- E VERIFY CONDITION AND PROPER OPERATION IN FIELD.
'ZIP-STRIP" (L BEAD) TAPE SPACKLE SMOOTHLY
>4 V
" "
r
k . REFURBISH AS REQUIRED FOR NEW APPEARANCE. I Z ny
E I I SCREW ATTACH CONTINUOUS METAL STUD
<.. «<:.
SUBSCRIPT R INDICATES EXISTING ITEM TO BE "
UNNER TO CLG. SPLINES AT 4 O O.C. MAX. R REMOVED OR RELOCATED AS INDICATED ON PLAN, I R `
E (TYPICAL FOR ALL ITEMS) ;
N Ih i (L-4) Inc
•
SUBSCRIPT "N" INDICATES NEW ITEM TO MATCH
OF —TAIL AT TERMINATION
N EXISTING UNLESS OTHERWISE NOTED. (TYPICAL FOR i
<, n / ARCHITECTURE
R ALL ITEMS) (L-4) BOT. OF . OCKI G
. .....f------......._...... ........."""----........................ k-----------------------I-......._ wa - i 1 /di
INDICATES EXISTING 2 X 4 ACOUSTICAL LAY IN CEILING / FINISHED CEILING ; 6'-6" A.F.F.
F TILE AND GRID, REFER TO FINISH SCHEDULE FOR — — Fly OPENING 1800 33rd Street
N N FINISH SPECIFICATION AND HEIGHT. I / HT. AS NOTED
P. LAMIN TE (L-4) OVER SECURE WITH C UNTERSUNK Suite 202
INDICATES 2 X 4 LAY -IN FLUORESCENT LIGHT FIXTURES. REFER TO DETAIL SHOWN '' SCREWS. PROVE SCREW
2X WOOD LA TOP. SS
ROVE FOR TERMINATION COVERS TO TCH LAMINATE. d0, FL
.....:........__---------- .............------.: H;. .................__..
I A
INDICATES SURFACE MOUNTED LIGHT FIXTURE. I Phone: (407) 996-3600
METAL STUDS AT 24" O.C., MAX. W/ ONE (1) RUBBER SOUID SPACERS
Fax: 407
LAYER GYP. BD. AS SPECIFIED, FROM FLOOR SLAB LAMINATEXPOSED SURFACES
INDICATES WALL MOUNTED EMERGENCY LIGHT FIXTURE I TO UNDERSIDE OF SUSPENDED CEILING ABOVE. AT HE >, JAMB. ) 996-5520
WITH TWO (2) LAMPS AND BATTERY BACK-UP WIRED
�I INTO BUILDING EMERGENCY SYSTEM. License # AA26000783
a N R N METAL_ STUD SIZE /8
2
.-.-...------------------.;�<........._...�....--...-........._'_----------------- i w-..-�--------------- .. ....._...-_..... m ZE � 35 Seal
INDICATES ILLUMINATED EXIT LIGHT FIXTURE SHADED NOTE
QUARTERS) DENOTE ILLUMINATED FACE(S). ARROWS i GYPSUM BOARD THICKNESS, 1/2" `•dam
DENOTE DIRECTION. 1 5/8" METAL TUDS a k
TYPICAL THIS WALL TYPE, 16" O.C. W/ M TAL LATH EXISTING ROOF STRUCTURE
® INDICATES NVAC DIFFUSER (SUPPLY). I UNLESS OTHERWISE NOTED. ONE SIDE TOTRUCTURE.
I:
.... ® INDICATES NVAC DIFFUSER (RETURN).
q..M-...... i CONTINUOUS METAL STUD RUNNER, ANCHOR TO NEW CEILING GRID 15
SLAB WITH POWDER DRIVEN FASTENERS AT 24" O.C. TILE. SEE FINISH SCH.
A I REFLECTED GEILINC, PLAN
A-1.20 Scale- 1/4"=1'-0"
PLASTIC LAMINATE LEGEND
MANAUFACTURER:
NEVAMAR
L-I
COLOR:
PATRIOT BLUE, S-3-48T
L-2
MANAUFACTURER:
NEVAMAR
COLOR:
SUNRAY YELLOW, 5-4-22T
L-3
MANAUFACTURER:
FORMICA
COLOR:
SPECTRUM RED, 845-58
L-4
MANAUFACTURER ,
FORMICA
COLOR:
WHITE, 949-58
® INDICATES EXHAUST FAN (MINIMUM TWO (2) C.F.M.
PER SQUARE FOOT OF FLOOR AREA) WITH ON/OFF
LIGNTED PILOT SWITCH.
�- INDICATES LIGHT SWITCH MOUNTED AT 48" A.F.F.
REFERENCED PLAN NOTES
NOTE #1 EXISTING EMERGENCY LIGHT FIXTURE TO BE RELOCATED
AS INDICATED ON PLAN.
NOTE #2 CUT EXISTING CEILING GRID AND TILE AS REQUIRED
FOR CONSTRUCTION OF SECURITY WALL.
NOTE #3 EXISTING DRYWALL CEILING TO REMAIN. PAINT AS
INDICATED ON FINISH SCHEDULE.
NOTE #4 EXISTING DRYWALL SOFFIT. PAINT TO MATCH ADJACENT
WALLS.
#I REFLECTED CEILING UNREFERENCED PLAN NOTES
* REUSE EXISTING FIXTURES AS POSSIBLE, REPLACE DAMAGED, MISSING
COMPONENTS. VERIFY PROPER OPERATION OF FIXTURES TO BE REUSED.
■ ALL FIXTURES SHALL BE BUILDING STANDARD WITH BUILDING STANDARD
FINISH. ALL LIGHT FIXTURES SHALL BE EQUIPPED WITH BUILDING STANDARD
LENS.
* EXISTING SUSPENDED CEILING SHALL REMAIN AT 10'-O'± ABOVE
FINISHED FLOOR (A.F.F.) UNLESS NOTED OTHERWISE ON PLAN.
* MODIFY EXISTING CEILING TO REMAIN IN CONFORMANCE WITH
NEW PARTITION AND LIGHTING LAY -OUT. RELOCATE EXISTING
FLUORESCENT FIXTURES AS INDICATED.
* EXISTING NVAC SYSTEM SHALL REMAIN. LOCATIONS OF
RELOCATED EXISTING DIFFUSERS ARE SUGGESTED ONLY. THE
CONTRACTOR SHALL TEST AND BALANCE SYSTEM AS REQUIRED.
* CONTRACTOR TO VERIFY EXISTING INSULATION ABOVE EXISTING
CEILING TILES. FURNISH AND INSTALL 6" BATT INSULATION IF
REQUIRED. PROVIDE NEW INSULATION OT MATCH EXISTING OVER
NEW CEILING.
NOTE:
ALL EXPOSED CABINET SURFACES TO RECEIVE PLASTIC LAMINATE
FINISH. INTERIOR CABINET SURFACES TO RECEIVE WHITE CABINET
LINER (PLASTIC LAMINATE).
4" P. LAMINATE BACKSPLASH
PLASTIC LAMINATE (L-4) OVER 3/4"
PARTICULE BOARD COUNTERTOP.
IX4 HARDWOOD WEB FRAME.
2'-10" A.F.F. o BREAK AREA. Ah
3' -6" A.F.F. AT TELLER AREA
WIRE PULLS. COLOR TO BE
SELECTED BY TENANT.
PLASTIC LAMINATE (L-4) BASE
CABINET,
3/4' PLASTIC LAMINATE SHELF
ON RECESSED ADJ. STANDARDS.
FIRE TREATED WOOD BLOCKING
AS REQUIRED.
FULLY CONCEALED PIVOT HINGES
(180 DEG. SWING) PROVIDE DOOR
SILENCERS.
CONTINUOUS BASE TO MATCH
P.LAMINATE CAB. BASE (L-4)
4 CABINET 6 CTION
A-1.20 Scale- 1"=I'—O'
I WALL 5CTION
A®1.20 Scale: 11/2'-1'-0"
5' -0" A.F.F.
PROVIDE NAILER IF REQUIRED TO SECURE
DECORITIVE MOTIF (SIMILAR AT BASE)
COORDINATE IN FIELD.
METAL STUDS AT 16" O.C., MAX. W/ ONE (D
LAYER GYP. BD. AS SPECIFIED FROM FLOOR SLAB.
i NOTE: METAL STUD SIZE, 3.5/8"
I I.
GYPSUM BOARD THICKNESS: 1/2'
I I`
TYPICAL THIS WALL TYPE,
UNLESS OTHERWISE NOTED.
I I'.
T i STEEL KNEE BRACE (24" LONG FOOT x 36" HT. x
1/4' TNK.) AS REQUIRED AT FREE STANDING ENDS.
COORDINATE LOCATIONS OF USE IN FIELD.
I
I I:
CONTINUOUS METAL STUD RUNNER, ANCHOR TO
I I.
2 WALL 6CTION
A-1.20 Scale: 1 1/2"=I'-O"
7'=0" A.F.F. �
PROVIDE FIRE TREATED
WOOD BLOCKING AS REQ'D
3/4" TNK. SHELF
ON RECESSED
ADJ. STANDARDS
3/4' TNK. PARTICLE BD.
DOOR, TYP.
EXPOSED CAB. SURFACES TO
RECEIVE PL. LAM. FINISH
(L-4).
INTERIOR CAB. SURFACES TO
RECEIVE WH, PLAS. LAM. FINISH
FULLY CONCEALED
PIVOT HINGES,
AMOUNT AS REQ' D
TYP.
4 `6" A.F.F.
CAINET 6ECTION
A-1.20 Scale- 1 I/2'=1'-0"
3 5/8' METAL STUE
BRACING. SECURE
STEEL STRUCTURE.
PLASTIC LAMINATE OVER
3/4" INDUSTRIAL BOARD
TRIM. I I
2X6 FIRETREATED WOOD
BLOCK. LAMINATE EXPOSED
SURFACE AT HEAD E JAMB.
P. LAMINATE_ (L-D OVER 3/4"
INDUSTRIAL BOARD COUNTER
TOP AT 42' A.F.F.
1 1/2" X 42" STEEL ANGLE
SUPPORTS.
_L 3'-3" A.F.F.
'tY TOP OF BLOCKING
(L-2)
(L-3) I�
CONT. METAL STUD RUNNER
ANCHOR TO SLAB W/ POWER
DRIVEN FA STNERS a 12" O.C.
4" CERAMIC TILE BASE.
CERAMIC TILE FLOORING.
6" METAL STUD TRACK
CONTINUOUS,
6'-7" A.F.F.
BOT. OF BLOCKING
6-6" A.F.F.
FIN. OPENING
6" 16GA. METAL STUDS
16' O.C.
1 1/4" THICK SECURITY
GLASS IN ALUM. CHANNEL.
STAINLESS STEEL MONEY
TRAYS.
`--�--' I 3'-4" A.F.F.
0_
_._.._....._..-------- ._--- ._._._,_ T.O. COUNTER
CJ
I/2" DRYWALL OVER I/2"
NIGH DEN. INDUST. ON 6"
16 GA. MTL. STUDS o 16' O.C.
3 WALL 6ECTION
A-1.20 Scale, 3/4"=1'-0"
FILL VOIDS IN PARTITION
WALL WITH SMALL PEA
GRAVEL TO 7'-0" A.F.F.
4" COVED VINYL BASE.
CARPET.
NOTE:
ALL EXPOSED CABINET SURFACES TO RECEIVE PLASTIC LAMINATE
FINISH, INTERIOR CABINET SURFACES TO RECEIVE WHITE CABINET
LINER (PLASTIC LAMINATE).
PLASTIC LAMINATE (L-D OVER 3/4'
2'-7" IPARTICULE BOARD COUNTERTOP.
1X4 HARDWOOD WEB FRAME.
Lf,", 3'-6-
A.F.F.
6"
DRAWER
BASE CABINET TO BE (L-4).
2.-6"
P. LAMINATE LA I 2'-6"
A.F.F.
ZS'ELEEDL5EC3Y
COLOR TO BE
TENANT.
LAMINATE SHELF
D ADJ. STANDARDS.
PLASTIC LAMINATE (L-D OVER 3/4'
PART, BOARD ANGLE SUPPORT
o MAX. 3'-0" APART.
CONTINUOUS BASE TO MATCH
ADJ. WALL BASE,
FULLY CONCEALED PIVOT HINGES
(180 DEG. SWING) PROVIDE DOOR
SILENCERS.
L
Daniel H. Farmer - AR10750
C)
It
AM all
0
Mimi
vi
■
O
O
U)
O
®
O
O
�
C6
-
Q
U
_®
LL
O
®
O
U)
C
(n
M
W
REVISIONS:
DATE: OCT. 20, 2004
PROJECT NO.: 4077
DRAWN: FWE
CHECKED: FWE
REFLECTED
CEILINC4 PLAN
2'-5" 1 1 5'-3" 1 2'-4' 1 5'-3y 11'-6'
II'-10'
F_, F—IF —JF—IF--IF-1 F--If— Jr—JF—JF—IF—Jr—J
iLD
L_JL_IL_JIL_JL_JL_J I__ IL_ A—JL_JL_JL_JL_J
CLAM SHELL CHAIR
RAIL ®3' tea" A.F.F.
2S
�.
2 I
1.30 (A-- 05
INTERIOR ELEVATION
A-1.30Scale- 1/4"-I'-0"
V BACKSPLASH (LA.
'LASTIC LAMINATE (L-1) OVER 3/4"
'ARTICULE BOARD COUNTERTOP.
42" A.F.F.
P. LAMINATE LA
P. LAMINATE L-2.
P. LAMINATE L-3
FIRE TREATED WOOD BLOCKING
AS REQUIRED.
1X4 HARDWOOD WEB FRAME.
PLASTIC LAMINATE (L -1) OVER 3/4"
PART. BOARD ANGLE SUPPORT
o MAX. 3'-0' APART.
BASE AS SPECIFIED
FLOOR FINISH AS SPECIFIED
I COUNTER 6ECTION
A—J.�o Scale= I"=r-O"
2'-5"
'LASTIC LAMINATE (L-1) OVER 3/4"
'ARTICULE BOARD COUNTERTOP.
34" A.F.F. (q�_
4" BACKSPLASH.
FIRE TREATED WOOD BLOCKING
AS REQUIRED.
IX4 HARDWOOD WEB FRAME.
PLASTIC LAMINATE OVER 3/4"
PART. BOARD ANGLE SUPPORT
c MAX. 3' -0" APART.
BASE AS SPECIFIED
FLOOR FINISH AS SPECIFIED
2 ADA COUNTER SECTION
Q-1.30 Scale, 1 1/2"ml'-O"
IRE TREATED WOOD BLOCKING
,S REQUIRED.
t" P. LAMINATE (L-1) BACKSPLASH
'LASTIC LAMINATE (L-1) OVER 3/4"
'ARTICULE BOARD COUNTERTOP.
2'-6 1/2"�
A.F.F.
K4 HARDWOOD WEB FRAME.
'LASTIC LAMINATE (L-1) OVER 3/4"
'ART. BOARD ANGLE SUPPORT
® MAX. 3'-0" APART.
CONTINUOUS BASE TO MATCH
ADJ. WALL BASE.
COUNTER O
A-130I Scale 3"=1'-0"
EXISTING STEEL
COLUMN.
1/2' GYP. BOARD
1 5/8" METAL
STUDS
_A_F C_.. _L .l_t'�ll lea C "U 1 IA..
® 1800 33rd Street
® Suite 202
Orlando, FL 32839
Phone: (407) 996-3600
® Fax: (407) 996-5520
License # AA26000783
Seal
Daniel H. Farmer - AR10750
U)
c)
CD
stoo
(Y)
U)
r
C
®
a)
w
0C)
.0
a)
4-1
n
LL
r
a
M
U
U)
REVISIONS:
DATE: OCT. 20, 2004
PROJECT NO.: 4077
DRAWN: FWE
CHECKED: FWE
SHEET:
1 0
DETAILS
INS', ELEVATION6
- SINGLE POLE TOGGLE SWITCH - MOUNTED 42" AFF TO
CENTERLINE UNLESS OTHERWISE NOTED
(3) 3 WAY
(4) 4 WAY
DUPLEX RECEPTACLE - MOUNTED 18" AFF TO CENTERLINE
UNLESS NOTED OTHERWISE
(GFI) GROUND FAULT INTERRUPTING
(REF) REFRIGERATOR
(WP) WEATHERPROOF
(EWC) ELECTRIC WATER COOLER
DOUBLE DUPLEX RECEPTACLE — MOUNTED 18" AFF TO CENTERLINE
UNLESS NOTED OTHERWISE
DUPLEX RECEPTACLE — MOUNTED HORIZONTAL 6" ABOVE COUNTER
BACKSPLASH UNLESS NOTED OTHERWISE
COMMUNICATIONS OUTLET — MOUNTED 18" AFF TO C.L. U.N.O. TYPICAL —
STUB 1" CONDUIT TO ACCESSIBLE CEILING SPACE. PROVIDE 2 GANG
BOX WITH ONE GANG RING (TYPICAL).
Q SPECIAL PURPOSE OUTLET OR EQUIPMENT CONNECTION
MOTOR
[� DISCONNECT SWITCH
ELECTRICAL PANEL
^ INDICATES DESIGNATION
�j SEE NOTE SYMBOL
l—� SOLID LINE INDICATES EQUIPMENT ON COMMON BRANCH CIRCUIT
AND/OR CONTROLLED BY COMMON SWITCH. EACH CIRCUIT SHALL
CONSIST OF A PHASE CONDUCTOR, NEUTRAL AND GROUND
CONDUCTOR. CONTRACTOR SHALL PROVIDE NECESSARY SWITCH
LEGS IN CONDUIT TO ATTAIN SWITCHING ARRANGEMENTS
INDICATED ON PLANS. CONTRACTOR MAY COMBINE CIRCUITS
INTO COMMON HOMERUN(S) CONSISTING OF A COMMON
NEUTRAL AND GROUND CONDUCTOR AND THREE PHASE
CONDUCTORS (A, B, AND C PHASE).
DOTTED LINE INDICATES EQUIPMENT ON COMMON BRANCH CIRCUIT
BUT NOT CONTROLLED BY SAME SWITCH OR OTHER SIMILAR DEVICE.
THE FOLLOWING ABBREVIATION NEXT TO A SYMBOL INDICATES:
E EXISTING
ER EXISTING TO BE REMOVED
EL EXISTING TO BE RELOCATED
EP EXISTING TO BE REPLACED
RE/CKT REUSE EXISTING CIRCUIT
RAI REMAIN AS IS
R EXISTING RELOCATED
NOTE: NOT ALL SYMBOLS MAY BE USED.
ELECTRICAL KEYED NOTES: (Z)
1. (RT-1) PROVIDE 6OA/3P FUSIBLE DISCONNECT
SWITCH AT UNIT (NEMA 3R) WITH DE FUSES SIZED
PER EQUIPMENT MANUFACTURES RECOMMENDATIONS.
BRANCH WIRING SHALL BE 3#8, 1 #10 GND. -1" C.
PROVIDE WATER PROOF, GFI SERVICE RECEPTICAL AS
INDICATED ON PLANS.
LIGHTING FIXTURE SCHEDULE
MARK
LAMP DATA
DESCRIPTION
FIXTURE MODEL NUMBER
MOUNT
VOLT
NOTES
#1
QTY
TYPE
MANUFACTURER
CATALOG NUMBER
N
4
F32—T8
2'X4' RECESS FLUOR ACRYLIC
LITHONIA
2GT8-4-32—A12125-120—GLR
REC GRID
120
C
1
F25—T8-35K
2' BATHROOM LIGHTING FIXTURE
LITHONIA
WC-225-120—GEB
SURF WALL
120
5
E
EXISTING FIXTURE
EXISTING
TO REMAIN
120
6
R
EXISTING FIXTURE
EXISTING
TO BE RELOCATED
120
5
X
INC
INC
UNIVERSAL LED EMERGENCY EXIT
LITHONIA
LQMSW3REL
UNIVERSAL
120
2,3
BU
INC
INC
EMERGENCY BATTERY UNIT
LITHONIA
BELM2
UNIVERSAL
120
2,3,4
LIGHTING FIXTURE NOTES:
1. GENERAL
SCHEDULE NOTES (APPLIES TO ALL FIXTURES):
A)
CONTRACTOR SHALL CORRDINATE FIXTURE MOUNTING WITH ARCHITECTURAL REFLECTED CEILING PLAN(S)
AND SHALL PROVIDE FIXTUREMOUNTING AS REQUIRED TO MATCH CEILING TYPE.
B)
ALL FIXTURES BALLASTS SHALL BE HIGH POWER FACTOR TYPE.
C)
ALL FLUORESCENT BALLASTS SHALL BE ENERGY SAVING TYPE.
D)
ALL ELECTRICAL FIXTURES MUST BE INDEPENDENTLY SUPPORTED OF CEILING GRID.
2. FIXTURES
TO BE PROVIDED WITH INTEGRAL EMERGENCY BATTERY BACK—UP.
3. FIXTURES
SHALL BE CONNECTED TO CONSTANT NORMAL ROOMLIGHTING BRANCH CIRCUIT OF AREA SERVED
(I,e,
LOAD SIDE OF BREAKER, LINE SIDE OF ANY SWITCHING/CONTROLLING DEVICES).
4. FIXTURE
TO BE WALL MOUNTED 7'—G" AFF TO TOP.
5. FIXTURE
TO BE WALL MOUNTED ABOVE MIRROR.
6. EXISTING FIXTURE TO BE CLEANED. RELAMPED AND NEW BALLAST AS REQUIRED FOR A COMPLETE OPERATING SYSTEM.
ii!4 4811
48" P
A--23
d
'48"
4
'q
P
3/4" CONDU I T
STUBBED 6"
ABOVE CEILING
FOR SECURITY
J
Inc.
An Nirr-E C'T'U7� F
1800 33rd Street
Suite 202
® Orlando, FL 32839
Phone: (407) 996-3600
® Fax: (407) 996-5520
Seal
N
C:)
(U
U)
0
f�
00
O
LL
--
L
W
(y)
U)
v
REVISIONS:
FLOOR PLAN POWER & DATA C9 FLOOR PLIGHTING N00
NORTH SCALE: 1/4"=1' —0" NORTH SCALE: 1/4"=1' —0" 0 r_ z
_j 0
``nE-
a
G IV
aIx.�- x o
a a
W
��0
'' 1 0.-W
16.1611 0 DATE: 10/20/04
z I`
z 9X
PROJECT NO.: 4077
® v a C DRAWN: LJY
Ex CHECKED: DWG
a. W Fz
Z
U0O
z a.
< wSHEET:
FLOOR FLAN
ELECTRICAL
ELECTRICAL REQUIREMENTS:
1. DRAWINGS ARE DIAGRAMMATIC AND SHALL NOT BE SCALED.
REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT
LOCATION OF ALL EQUIPMENT. ELECTRICAL CONTRACTOR SHALL
FURNISH AND INSTALL ALL ITEMS REQUIRED FOR A COMPLETE AND
ACCEPTABLE WORKING INSTALLATION.
2. ALL WORK SHALL COMPLY WITH THE LATEST EDITION OF THE
NATIONAL ELECTRICAL CODE AND SHALL COMPLY WITH ALL LOCAL
RULES AND ORDINANCES HAVING JURISDICTION.
3. MINIMUM WIRE SIZE SHALL BE #12 AWG. UNLESS OTHERWISE
NOTED ALL CONDUCTORS SHALL BE COPPER WITH THWN OR THHN
INSULATION.
4. ALL MATERIAL SHALL BE NEW AND BEAR THE UNDERWRITES
LABORATORIES LABEL (U.L.) WHERE APPLICABLE.
5. THE ELECTRICAL SYSTEM SHALL BE COMPLETELY AND
EFFECTIVELY GROUNDED AS REQUIRED IN ARTICLE 250 OF THE
NATIONAL ELECTRICAL CODE.
6. THE ELECTRICAL, TELEPHONE, AND CABLE TELEVISION
INSTALLATIONS SHALL MEET ALL REQUIREMENTS BY THE LOCAL
UTILITY COMPANIES.
7. ALL DISCONNECT SWITCHES SHALL BE RATED FOR 100,000
A. I. C. UNLESS OTHERWISE NOTED. ALL FUSES SHALL BE RATED FOR
200,000 A. I . C. AND SHALL BE CURRENT LIMITING.
8. ALL ELECTRICAL SWITCHGEAR SHALL BE BY SQUARE D, ITE,
GE, OR CHALLENGER. SUBSTITUTES MUST BE APPROVED BY THE
ENGINEER.
9. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS.
PLASTIC BOXES MAY BE USED IN LIEU OF THE STEEL BOX WHERE
PERMITTED BY LOCAL CODES. IN DAMP OR WET LOCATIONS BOXES
SHALL BE MADE FROM CAST ALLOY WITH THREADED HUBS. SPECIAL
ENCLOSURES ARE REQUIRED FOR OTHER CLASSIFIED AREAS.
10. SEPARATE WIRE AND CONDUIT SYSTEM MAY BE SUBSTITUTED
WITH FACTORY FABRICATE❑ ASSEMBLY OF INSULATED CONDUCTORS IN
A FLEXIBLE METALLIC ENCLOSURE WHERE PERMITTED BY LOCAL
CODES.
11. MOTOR STARTERS SHALL BE MANUAL OR MAGNETIC WITH
OVERLOAD RELAYS IN EACH HOT LEG. IT SHALL BE THE ELECTRICAL
CONTRACTOR TO PROVIDE ALL STARTERS WHERE REQUIRED.
12. FURNISH AND INSTALL DISCONNECT SWITCHES, OVER CURRENT
PROTECTION, AND WIRING FOR THE AIR CONDITIONING SYSTEM AS
PER MANUFACTURER RECOMMENDATIONS. CONTROLS ARE TO BE
SUPPLIED BY THE AIR CONDITIONING CONTRACTOR AND CONNECTED BY
THE ELECTRICAL CONTRACTOR.
13, ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL
CONTRACOR IN A FIRST CLASS WORKMANLIKE MANNER. THE COMPLETE
SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTED BY THE ENGINEER
OR ARCHITECT.
14. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO
AVOID INTERFERENCE WITH THE PROGRESS OF CONSTRUCTION..
15. THE ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL MATERIALS
AND WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT LESS
THAN (1) ONE YEAR FROM THE DATE OF ACCEPTANCE. CORRECTION 'OF
ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND
SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF
THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY.
16. ALL REQUIRED INSURANCE SHALL BE PROVIDED FOR PROTECTION
AGAINST PUBLIC LIABILITY OR PROPERTY DAMAGE FOR THE DURATION
OF THE WORK.
17. ALL WIRING TO BE " THWN" CU, IN "EMT" CONDUIT.
18. EQUIPMENT SPECIFIED IN THESE DRAWINGS ARE TO SET THE MINIMUM
LEVEL OF QUALITY. PROVIDE EQUIPMENT AND PRODUCTS EQUAL TO
THAT SPECIFIED.
- - - - - - - - - - - - - - - - - - - - - - -
EXISTING
MAIN i ------ j --
r--1
120/208 3PH I `T�
I I I
I I I
I I
I I r---1___l
I 1 �
I I
I I
I i J_
I OTHER
GND
TENANTS
I
PER NEC
-----------------------,
I
I
I
-------.--------r---------
I
EXIST
I
METER
T
E X I S T
( 4) #3/0,
r---! ---�
-- I
r xIS
( 1) #6 GND
i EXIST i
1 200A
IN 2" C.
200A
I PNL "A" I
FUSED
NEMA 1
DISC I
I I
I I
I 1
I NEMA 3R I
I I
EXIST
I
I
( 4) #3/0,
( 1) #6 GND
IN2" C.
'------------------------�
- -
--------J POWER RISER DIAGRAM
NOTE : ALL WIRING SHALL BE COPPER TYPE "THW" UNLESS NOTED OTHERWISE .
PANEL
IPA"
VOLTAGE:
BUS RATING:
MAINS:
MOUNTING:
A. I . C. RATING
208Y 12OV,3PH,4W
200 AMP
NONE
SEE PLANS
LOADS (WATTS)
CKT
C N PHASE
C N
CKT
LOADS
(WATTS)
LOAD SERVED
BRKR
K 0
K 0
BRKR
LOAD SERVED
LTS
RECPT
MOTOR
HEAT
AMP P
T . A B C
T .
AMP P
LTS RECPT
MOTOR
HEAT
TIME CLOCK
360
20/1
1 * - -
2
H45/3
650
3000
RT-1
RECPT
360
20/1
3 - * -
4
----
650
3000
----
REFRIG
1000
20 1
5 - - *
6
----
650
3000
----
MICRO
1000
20/1
7 * - -
8
COFFEE
1000
20/1
9 - -
10
20/1
1000
SIGN
RECPT
1080
20/1
11 - - *
12
20/1
1080
RECPT - CEILING
RECPT
1080
20/1
13 * - -
14
20/1
1080
RECPT - CEILING
RECPT
1080
20/1
15 - * -
16
20/1
1080
RECPT - SERVICE
RECPT
1080
20/1
17 - - *
18
20 1
2000
EWH
RECPT
1080
20/1
19 * - -
20
20/1
1080
LTS
RECPT
1080
20/1
21 - * -
22
20/1
1370
LTS
RECPT
1080
20 1
23 - -
24
20/1
1640
LTS
RECPT
1080
20/1
25
*
-
-
26
20/1
27
-
*
-
28
20/1
29
-
-1*
30
20/1
-..-.
31
*
-
-
32
33
-
*
-
34
35
-
-
*
36
37
*
-
-
38
39
-
*
-
40
41
142
LTS
RECPT
MOTORS
HEAT
LTS RECPT
1
MOTOR
HEAT
0
11360
1000
0
SUB TOTALS
5090
3249L
1950
11000
PHASE LOADING
LTS
RECPT MOTORS
HEAT
LTS
RECPT
MOTORS
HEAT
NOTES:
F ]
5. 1 14.6
1.25 12. 3
6. 4 12. 3
INDICATES NON -CONCURRENT A/C
SIZES BASED ON LARGEST LOAD.
3. 0
1.00
3. 0
LOAD.
11. 0
CONNECTED KW TOTALS
PHASE A
1080
5660
650
3000
1. 00
DEMAND
PHASE B
2370
4600
650
3000
11. 0
ADJUSTED KW TOTALS
PHASE C
1640
4320
1650
5000
33.6
TOTAL CONNECTED KW
A
B
C
32.6
TOTAL
ADJUSTED KW
208
THREE
PHASE VOLTAGE
PHASE TOTALS
1 104101
10620
12610
"H"
"G"
INDICATES
INDICATES
HACR
GFI
RATED BREAKER.
BREAKER.
10/20/04 :DATE JOB NAME:
TOTAL
PANEL
01:39 PM
:TIME
CCS - SEMINOLE CENTS
1 911
AMPERAGE:
Im
AHCHITECT'UR.E
1800 33rd Street
Suite 202
■ Orlando, FL 32839
® Phone: (407) 996-3600
■ Fax: (407) 996-5520
Seal
C)
tU
a-�
U)
®
U)
O
70
CV
®
a)
-Ca
(C5
4_4
i
O
-0
O
LL
a
.0
Chi
M
U)
(y-)
U)
OZ v
REV LIONS:
m
0
In o
0 L0
rngom
� � I
N r, z
J 0
1i-nt=
Q
N
d �jz
0 0
fr i�0 X 1—0 a
w J
I I I 00W
�" DATE. 10/20/04
z I W_
PROJECT NO.: 4077
a DRAWN: I JY
ryv� GHECKEa: DWG
n �
Z N
U Q
< Ujr� � SHEET:
L-102
ELECTRICAL
N®TE,6 AND IZ16EIZ
P
ROOFTOP SCHEDULE
MARK
RT-1
AREA SERVED
SEE
PLANS
SYSTEM TYPE
CLG HEAT
CONFIGURATION
DOWNFLOW
MANUFACTURER
TRANE
MODEL NO.
TCDO60C
OPERATING WT LBS W FAC CURB
1000
INDOOR FAN DATA:
CFM TOTAL
1700
CFM 0. A.
175
E. S. P. ( " W. G. )
50
H. P.
60/5. 3
RPM SPEED
LOW
COOLING DATA 95 DEG F AMB
TOTAL CAPACITY (TMBH)
62.5
SENSIBLE CAPACITY ( SMBH)
43.7
ENT. AIR TEMP. F D8 WB
80 67
HEATING CAPACITY DATA:
BTUH (30 DEG F AMBIENT)
-
KW (@ RATED VOLTAGE)
9.0
HEATER STAGES
2
CONDENSING DATA:
NO. COMPRESSORS
1
NO. COOLING STAGES
0/100
COMP. F. L. A. ( EA. )
18. 6
COMP. L. R. A. ( EA. )
118
NO. COND. FANS
1
COND. FAN H. P. /F. L. A.
40 2. 7
ELECTRICAL DATA:
V/PH/60
208/3/60
MCA
37.9
MAX FUSE
45
ENERGY EFFICIENCY DATA:
EER / I PL V ( ® AR I STD.)
-/-
SEER ( C AR I STD.)
10.0
COP HEATING
1.0
REMARKS:
SEE BELOW
ROOFTOP NOTES:
1. PROVIDE A/C UNITS WITH PROGRAMMABLE HEATING AND COOLING
THERMOSTAT WITH FAN ON -OFF -AUTO SWITCH, AND NIGHT SETBACK
MODE. SET STAT FOR FAN IN AUTO MODE. FAN SHALL NOT RUN
UNLESS THE COMPRESSOR OR HEATER IS ON.
2. PROVIDE TWO SETS OF 1" OR 2" 40% FILTERS TRI-DIM ES60M
THROW AWAY FILTERS (561-287-3839).
3. PROVIDE 0- 25% MANUAL OUTSIDE DAMPERS.
4. VERIFY THAT EXISTING ROOF CURB IS INSULATED.
5. PROVIDE ANTI -SHORT CYCLE PROTECTION.
6. PROVIDE ELECTRIC HEATERS AS SCHEDULED, VERIFY MINIMUM CFM
WITH MANUFACTURE.
7. E. S. P. DOES NOT INCLUDE COIL, OR CABINET LOSSES.
8. UNLESS OTHERWISE NOTED CAPACITIES AND EFFICIENCIES ARE AT
ARI CONDITIONS. OUTSIDE AIR DESIGN CONDITIONS: 95 DEGREES
FDB 80 DEGREES FWB. ENTERING AIR DESIGN CONDITIONS: 80
DEGREES FDB 67 DEGREES FWB.
9. COORDINATE WITH ELECTRICAL CONTRACTOR BEFORE BIDDING OR
ORDERING ANY EQUIPMENT.
10. PROVIDE CONDENSER COIL GUARDS.
HVAC KEYED NOTES: #O
1. EXISTING DUCTWORK TO REMAIN. CONTRACTOR SHALL VERIFY
DUCT SIZE AND REPORT ANY DISCREPANCIES TO ARCHITECT AND
ENGINEER.
2. EXISTING GRILLE TO REMAIN. BALANCE FOR CFM INDICATED.
3. RELOCATE EXISTING GRILLE. EXTEND OR REPLACE FLEX
DUCT AS REQUIRED. BALANCE FOR CFM INDICATED.
4. PROVIDE NEW GRILLE AND DUCTWORK AS SHOWN. BALANCE FOR
CFM INDICATED.
5. EXISTING RTU CURB TO REMAIN. EXISTING RTU WILL BE REMOVED
AND RETURNED TO OWNER FOR POSSIBLE FUTURE USE. INSTALL
NEW RTU ON TO EXISTING CURB ACCORDING TO SPECIFICATIONS.
6. EXISTING EXHAUST FAN TO REMAIN.
A/C LEGEND
SD
SMOKE DETECTOR
TO
THERMOSTAT
RS
REMOTE SENSOR
O
KEYED NOTE:
EF
1
EQUIPMENT TAG: ( ex. EF-1)
SUPPLY AIR DIRECTION
-�
RETURN AIR DIRECTION
U
UNDER CUT DOOR
1" MIN UNLESS INDICATED
® INDICATES SUPPLY AIR
INDICATES RETURN AIR
INDICATES EXHAUST AIR
CD GRILLE MARKER: INDICATES
12X 12 TYPE "CD" GRILLE WITH 12" X 12"
300 NECK, BALLANCE FOR 300 CFM.
SUPPLY AIR GRILLE IN T-BAR
CEILING SEE ARCHITECT'S
REFLECTIVE CEILING PLAN
® SUPPLY AIR GRILLE SURFACE
MOUNTED INTO CEILING TILE
OR DRYWALL CEILING.
WALL CAP
DW DRYWELL SEE DETAIL
FLEXIBLE DUCT: SIZE TO MATCH
*m'< DIFFUSER NECK SIZE, UNLESS
OTHERWISE INICATED.
7 = FLEX DUCT COLLAR W/OBD
SPLITTER DAMPER
45 DEG TAP WITH DAMPER
DUCT TRANSITION
OPPOSED BLADE DAMPER (OBD)
- v FIRE DAMPER V11TH ACCESS DOOR
------ EXISTING DUCTWORK
- Xis EXISTING DUCTWORK TO BE REMOVED
0/
•
A.RCI3ITECTURE
1890 33rd Street
Smite 202
Orlando, FL 32839
Phone: (407) 996-3600
® Fax: (407) 996-5520
Seal
v
O
C7
.1�r
N
Q
0
(D
c:
0
0
LL
L_
0
ow
U)
(y)
(f)
in
Ln
_. ...... ::. V
_
REVISIONS.
m
0
®
�rn�4
tf7 0
o�
Inwo
rn
h
ASHRAE 62-1989 REQUIREMENTS:
APPLICATION
AREA
SF
OCCUPANCY
SF / PERS
OUTSIDE AIR
CFM/PER
INTERMITTENT
OCCUPANCY
OUTSIDE AIR
REQUIRED
OFFICE AREAS
NONOCCUP I ED AREAS, WALLS, MECH, ELEC RMS
1,170
97
143.0
400.0
20
0
100%
100%
1_6"
0
TOTAL
1,267
164
EQUIPMENT DESIGNATION
NOMINAL
TONS
SUPPLY
CFM
OUTSIDE AIR
CFM
RT-1
5.0
1, 700
175
TOTALS
175
a
a
XAc
z
a a
FLOOR PLAN � HV � � �_
o lf) t--
NOM SCALE: 1/4"=1' -0"
n L DATE: 10/20/04
z cm
n p PROJECT NO.: 4077
® v, DRAWN: LJY
�a CHECKED: DWG
V/ r�'0
QM SHEET:
r� w
(D
Farber
GASKET
UNIT SUPPORT RAIL
JROOFTOP,
SECURE STRAP TO UNIT
WITH (2) 3/4" #10
SHEETMETAL SCREWS
CANT STRIP W/ OUTSIDE AIR INTAKE
FLASHING OPENING W\ DAMPER
PROVIDE 1-1/2"WIDE
16 GA GALV.STEEL
AND RAIN COVER.
STRAP EVERY 24"O. C.
CONDENSATE DRAIN
SECURE STRAP TO CURB
W/TRAP & CLEANOUT
W/ (2) 2-1/2" #10 SCREWS
RETURN AIR DUCT
WOOD NAILER
SUPPLY AIR DUCT TRANSITION AS REQ'D.
ROOF CURB BY
TRANSITION AS REQ'D.
UNIT MANUFACTURER
COUNTER FLASHING
RIGID INSULATION
i
CANT STRIP
ROOF COVERING
SECURE ROOFCURB TO ----\
ROOF STRUCTURE WIT,
RIGID INSULATION
BRANCH TAKEOFF
3/8" S.S. BOLTS
WITH VOLUME DAMPER
AND (2) 1" S. S.
r
WASHERS EVERY
24" 0. C.
ROOF STRUCTURE
{{
3X3 METAL CHANNEL
TYPICAL
SUPPORT ON ALL
SPLITTER DAMPER
FOUR SIDES OF OPENING
ROOFTOP UNIT DETAIL
ROOFTOP UNIT
CURE DETAIL
2
N. T. S.
RT-CURB1
N. T. S. RT-1B M-10F
NOTE: ALL STRAP SHALL BE
A MINIMUM OF 1-1/2", 26 GA
GALVINIZED STEEL.
HANGER WIRE SHALL BE A
MINIMUM OF 22 GA.
INSULATED
PLENUM BOX
������
HANGER WIRE OR STRAP
5' -0" MAX DISTANCE
INSULATED DUCT
BETWEEN SUPPORTS.
MAX. SAG 1 /2" PER FOOT
ALTERNATE FOR LOW CLEARANCE
OF SUPPORT SPACING.
N. T. S.
SPIN -IN W/
MANUAL DAMPER
1-1/2" GALV. STEEL SAND
CLAMP TO MATCH DUCT
RIGID AIR DUCT:
"METHODS
DIAMETER
SEE OF
/
HANGING DUCTS"
BLANKET INSULATION
- 6' SHEETMETAL EXTENSION COLLAR
REQUIREMENTS
_,,INSULATEDFOR
I FLEXIBLE DUCT
11 W/H UL-181 CLASS 1
WITH ZIP TIE
AROUND COLLAR
26 GAUGE COLLAR
AIR DIFFUSER
FIN. CILING
INSTALL STAINLESS STEEL DUCT
CEILING TILE
CLAMPS ON BOTH INNER AND OUTER
JACKETS. SEAL INNER JACKET AIR
SUSPENDED T-BAR
TIGHT WITH MASTIC. NYLON DRAWBANDS
CEILING GRID
SUPPLY AIR GRILLE
MAY BE USED IN NON PLENUM AREAS.
FLEXIBLE DUCT DETAIL
SUPPLY AIR GRILLE
3
4
N. T. C. FLEXDUCT
IW102
N. T. S.
CD-1
M--102
SEE DUCTWORK AND ACCESSORIES NOTES FOR
SPECIFICATION OF DUCT MATERIALS, FASTENING
SYSTEM, AND SEALING METHODS.
II II
i
TYPICAL HANGING TYPICAL CHANNEL
AND STRAP DUCT
STRAP AND SADDLE HANGING DETAIL
HANGING DETAIL
NOTE: ALL STRAP SHALL BE
A MINIMUM OF 1-1/2,26 GA
GALVINIZED STEEL. WITH A
6 FT MAXIMUM SPACING.
METHODS OF HANGING
RIGID FIGERGLASS DUCTS
N. T. S. HANGDUCT-FG M-102
GENERAL NOTES:
DUCTWORK &
ACCESSORIES NOTES:
1.
THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS,
1.
ALL DUCTWORK
SHALL BE AS FOLLOWS OR APPROVED EQUAL:
EQUIPMENT, ACCESS PANELS, CONTROL SYSTEMS, DEVICES, PERMITS
AND SERVICES NECESSARY FOR FURNISHING AND INSTALLING OF A
a)
SUPPLY - MANVILLE SUPERDUCT 1-1/2"
3/4 LB FIBERGLASS
nc,,
COMPLETE SERVICEABLE MECHANICAL SYSTEM.
DUCTBOARD R=6.0.
b)
RETURN - MANVILLE SUPERDUCT 1-1/2"
3/4 LB FIBERGLASS
A R CHIr!'F C'rUIE.E
2.
ALL MECHANICAL SYSTEMS ARE TO BE INSTALLED IN
DUCTBOARD R=6.0.
ACCORDANCE WITH ALL APPLICABLE SECTIONS OF THE NFPA
c)
FLEX DUCT - THERMAFLEX G-KM R=6.0,
UL-181 CLASS 1.
STANDARDS, ANSI STANDARDS, THE LOCAL BUILDING CODE, PLANS
d)
EXHAUST - GALV. SHEETMETAL 28 GA MINIMUM.
®
1800 33rd Street
AND SPECIFICATIONS.
2.
ASSEMBLE, INSTALL, AND SEAL DUCTWORK IN
ACCORDANCE WITH
SUlte 202
3.
ALL MATERIALS SHALL BE NEW( UNLESS OTHERWISE INDICATED)
SMACNA "HVAC DUCT CONSTRUCTION STANDARD".
UNLESS OTHERWISE
Orlando, FL 32839
AND ANY DAMAGED EQUIPMENT SHALL BE REPLACED.
NOTED
ON PLANS CONSTRUCT DUCTWORK TO 2"
DUCT CLASS, SEAL TO
100%
CLOSURE.
Phone: (407) 996-3600
4.
CONTRACTOR WILL WARRANTY ALL MECHANICAL SYSTEMS,
Fax: (407) 996-5520
EQUIPMENT, PARTS AND LABOR, INSTALLED UNDER HIS CONTRACT,
3.
SEAL
ALL SHEETMETAL DUCTS JOINTS WITH RCD #8 MASTIC.
FOR A PERIOD OF ONE (1) YEAR AFTER C. 0.
mm
4.
MAKE
JOINTS FOR DUCT WRAP AND DUCTBOARD
WITH GLASS
Seal
5.
PROVIDE 6 SETS OF SUBMITTALS FOR REVIEW BY ARCH/ENGR
FABRIC AND VAPOR BARRIER COATING TO 30 MILL DRY FILM
PRIOR TO PURCHASING ANY EQUIPMENT OR MATERIALS. SUBMITTALS
THICKNESS, RCD #9.
.`
SHALL INCLUDE ALL ITEMS AND MATERIALS SUPPLIED BY
v
CONTRACTOR. SUBMITTALS SHALL HAVE A SUMMARY SHEET SHOWING
5.
CONTRACTOR SHALL PROTECT ALL FIBERGLASS INSULATION
ALL SCHEDULED INFORMATION. ANY EQUIPMENT OR MATERIALS
PRODUCTS FROM DAMAGE. INSULATION PRODUCTS SHALL NOT BE
INSTALLED WITHOUT REVIEWED SUBMITTALS SHALL BE REMOVED AND
ALLOWED TO GET WET. INSULATION DAMAGED AS A RESULT OF
REINSTALL AT ARCH/ENGR DISCRETION WITH NO ADDITIONAL
MOISTURE, VANDALISM, OR CONSTRUCTION TRAFFIC SHALL BE
COMPENSATION TO CONTRACTOR.
REPLACED.
6.
PROVIDE 2 SETS OF MAINTENANCE AND OPERATION MANUALS ON
6.
INSULATE NECKS AND BELLS OF OF ALL SUPPLY AIR DIFFUSERS
ALL MECHANICAL EQUIPMENT OR SYSTEMS.
WITH 1-1/2" R=6.0 BLANKET INSULATION. SECURE INSULATION TO
DIFFUSER NECK WITH ZIP LOCK TIE STRAP.
7.
ALL CUTTING, PATCHING, STRUCTURAL STEEL, WEATHER
PROOFING, PAINTING, AND WALL OPENINGS SHALL BE BY THE
7.
USE RADIUS RECTANGULAR FITTINGS OR TURNING VANES IN ALL
GENERAL CONTRACTOR.
SUPPLY DUCT ELBOWS, CONICAL BRANCH TAKE -OFFS, SPLITTER
8.
ALL LOUVERS, GRILLES, PIPING, ETC. SHALL BE PAINTED TO
DAMPERS WHERE INDICATED ON DRAWINGS AND VOLUME CONTROL
EXTRACTORS IN ALL BRANCH DUCTS OR DIFFUSER CONNECTIONS.
C)
MATCH SURROUNDING COLOR AND TEXTURES AS REQUIRED BY
ARCHITECT. VERIFY COLOR AND TEXTURE WITH ARCHITECT. PAINT
8.
ALL DUCT SIZES ARE CLEAR INSIDE DIMENSIONS.
ALL EXPOSED MECHANICAL EQUIPMENT WITH BENJAMIN MOORE EPDXY
ENAMEL 182.
9.
PLANS ARE DIAGRAMMATIC. IN GENERAL DUCT OFFSETS HAVE
NOT BEEN SHOWN. A/C CONTRACTOR SHALL COORDINATE THESE AS
9.
ALL OPENINGS IN BUILDING STRUCTURE, FOR DUCTWORK,
REQUIRED WITH BUILDING STRUCTURE AND OTHER TRADES.
PIPING, ETC. TO BE 1 /2" LARGER( ON ALL S I DES) THEN THE
OUTSIDE DIMENSIONS. FILL VOIDS WITH FIRE RETARDANT SILICONE
10.
TERMINAL AIR DISTRIBUTION DEVICES SHALL BE AS FOLLOWS
FOAM (I.E. CHASE -FOAM CTC PR-855 BY CHASE TECHNOLOGY CORP.).
OR APPROVED EQUAL:
a) CD CEILING DIFFUSER MODEL TDC-AA, TYPE 1 BORDER, WITH
SQUARE OR ROUND NECK. PROVIDE 4-WAY AIR PATTERNS UNLESS
MECHANICAL
EQUIPMENT NOTES:
OTHERWISE SHOWN ON PLANS.
0
b) RAG RETURN AIR GRILLE MODEL 50F W/1/2X1/2X1/2 GRID.
1.
ALL MECHANICAL EQUIPMENT SHALL BE ARI & U.L. LISTED
4-4
WHERE APPLICABLE AND RATED FOR THE REQUIRED SERVICE,
11.
PAINT DUCTWORK VISIBLE BEHIND AIR DISTRIBUTION DEVICES
40
PRESSURES, TEMPERATURES, AND SHALL BE PROVIDED WITH ALL
MATTE BLACK.
NECESSARY TRANSFORMERS, SEALS, VALVES, CONNECTIONS, ETC. TO
FUNCTION PROPERLY.
2.
INSTALL ALL EQUIPMENT TO COMPLY WITH THE MANUFACTURERS
COORDINATION NOTES:
SPECIFICATIONS AND CLEARANCE REQUIREMENTS.
1.
A/C CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE HIS
3.
ALL INSULATION WILL HAVE FIRE/SMOKE RATING LESS THAN
WORK FOR SIZE, LOCATION, CLEARANCE, ACCESS AND ELECTRICAL
e
25/50,
CHARACTERISTICS WITH ALL OTHER TRADES AND TO PROVIDE SHOP
DRAWINGS TO THE ENGINEER FOR REVIEW BEFORE INSTALLATION OF
4.
PROVIDE A MIN. OF 3' CLEARANCE IN FRONT OF ALL 120-240
DUCTWORK OR EQUIPMENT. SHOP DRAWING WILL INCLUDE BEAM OR
VOLT RATED AND 4' CLEARANCE IN FRONT OF ANY 480 VOLT RATED
STRUCTURE ELEVATION & REQUIRED EQUIPMENT ACCESS AREAS.
PANELS AND DISCONNECTS. PROVIDE ADEQUATE SIDE CLEARANCE PER
NEC.
2.
WALL, ROOF, AND CEILING OPENINGS INDICATED ON
CONTRACTOR DRAWINGS ARE NOMINAL DIMENSIONS ONLY AND ALL
,®
5.
PROVIDE MOTOR STARTERS FOR ALL MOTORS.
DUCT, PIPE OR EQUIPMENT PENETRATIONS SHALL BE SLEEVED AND
�-
FIRE RATED AS REQUIRED, ADJUST OPENINGS
�y
6.
PROVIDE FLEXIBLE DUCT CONNECTORS, RATED AS REQUIRED, TO
ALL FANS, A/C UNITS, OR MECHANICAL EQUIPMENT, EXCEPT FANS
3.
COORDINATE LOCATION OF CEILING DIFFUSERS, GRILLES AND
USED FOR GREASE EXHAUST.
REGISTERS IN THE FIELD WITH LIGHTS, SPRINKLERS AND
u)
ARCHITECTURAL ELEMENTS.
&
7.
PROVIDE VIBRATION ISOLATORS ON ALL MECHANICAL EQUIPMENT
>
AS CALLED FOR IN THE SPECIFICATIONS. IF NOT SPECIFIED, AS
4.
COORDINATE LOCATION OF A/C UNITS, THERMOSTATS, FANS AND
Cr)
RECOMMENDED BY MANUFACTURER FOR QUIET AND VIBRATION FREE
DUCTWORK WITH BUILDING STRUCTURE AND OTHER TRADES SO THAT NO
r'-
OPERATION.
INTERFERENCES OCCUR.
4�
0
U)
C11
S.
PROVIDE A MIN. OF 10' CLEARANCE BETWEEN O/A INTAKES AND
5.
IN GENERAL, DUCT OFFSETS HAVE NOT BEEN SHOWN. A/C
VTR OR EXHAUST OPENINGS.
CONTRACTOR TO COORDINATE THESE AS REQUIRED.
'4-�
9.
HVAC CONTRACTOR SHALL TEST AND BALANCE ALL MECHANICAL
6.
MECHANICAL PLANS IN GENERAL, ARE DIAGRAMMATIC IN
EQUIPMENT AND AIR DEVICES, EXTRACTORS, DAMPERS, A/C UNITS,
NATURE, AND ARE TO BE READ IN CONJUNCTION WITH ARCH.
L-
FANS, ETC. TO PROVIDE THE DESIGN QUANTITIES AS SHOWN ON THE
PLUMBING, ELECTRICAL AND STRUCTURAL PLANS. DUCT AND PIPING
<
9 0 1fl1
PLANS OR SCHEDULES.
OFFSETS, BENDS AND TRANSITIONS WILL BE REQUIRED TO PROVIDE
0 �
W
AND INSTALL A COMPLETE FUNCTIONAL SYSTEM AND SHALL BE
0
(NNW_
10.
RUN CONDENSATE DRAINS ROOF DRAIN AS REQUIRED.
PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE
CONDENSATE DRAINS SHALL BE A MINIMUM OF 3/4" UP TO 10 TONS,
OWNER.
(ay
1-1/4" UP TO 50 TONS, 1-1/2" UP TO 100 TONS, SIZES ARE FOR
W Cy) W
TOTAL CONNECTED TONNAGE. CONDENSATE DRAINS SHALL BE
7.
THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR
SCHEDULE 40 PVC.
TO BIDDING, ORDERING, FABRICATION OR INSTALLATION OF
r 1LO
MATERIALS OR EQUIPMENT.
REVISIONS:
11.
MOUNT ALL ROOFTOP EQUIPMENT FOR WIND LOADS AND MOUNTING
z
,cc
HEIGHTS AS REQUIRED BY LOCAL CODES, ALL CURBS SHALL EXTEND
..�
0
)rn .4
12" MIN. ABOVE FINISHED ROOF.
o
aco v�
12.
PROVIDE STRANDED COPPER CONTROL WIRING AND COPPER
r
CAn Z
PNEUMATIC CONTROL TUBING.
V
Q
n
0-4
13.
ALL PIPING AND DUCTWORK SHALL BE SLEEVED THRU WALLS,
o' o
BEAMS, SLABS, ETC, AS REQUIRED AND COORDINATED WITH THE
fr
3:x G
STRUCTURAL ENGINEER. PROVIDE NECESSARY TRANSITIONS AS
o a
REQUIRED FOR DUCTWORK INSTALLATION.
J I.L.
�m0
14.
CONTRACTOR WILL PROTECT THE AIR-CONDITIONING UNITS AND
W
DUCTWORK IN THE FOLLOWING MANNER. PRE -FILTER ALL RETURN AIR
n
DArE:10/20/04
GRILLES WITH ROLL TYPE FILTER MEDIA AND REPLACE IT AS NEEDED
r` F=-
^�
PROJECT NO.: 4077
THROUGHOUT THE CONSTRUCTION PERIOD. EQUIPMENT MUST NOT BE
N to-Y b
DRAWN: LJ
STARTED FOR ANY PURPOSE UNTIL THE DRYWALL SANDING, ETC. IS
a ��
CHECKED:
DWG
COMPLETED. ONCE DRYWALL SANDING IS COMPLETED, THE UNITS MAY
n
n-Z -
BE STARTED ONCE THE ABOVE PRE -FILTERING IS COMPLETED.
V!
" o
w T
1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN STRICT
ACCORDANCE WITH APPLICABLE LOCAL CODES, RULES AND
ORDINANCES.
2. ALL MATERIALS SHALL BE NEW.
3. ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING
CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER. THE
COMPLETED SYSTEM SHALL BE FULLY OPERATIVE.
4. REQUIRED INSURANCE SHALL BE PROVIDED BY THE CONTRACTOR
FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE
FOR THE DURATION OF WORK.
5. CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES,
INSPECTION AND TESTS.
6. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE FOR THE EXACT
LOCATION OF FIXTURES, PIPING, EQUIPMENT, ETC.
7. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO
AVOID INTERFERENCE WITH THE PROGRESS OF CONSTRUCTION.
8. CONTRACTOR SHALL GUARANTEE ALL MATERIALS & WORKMANSHIP
FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR
FROM DATE OF ACCEPTANCE. CORRECTION OF ANY DEFECTS SHALL BE
COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE
REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION
WHICH MAY HAVE BEEN DAMAGED.
I am
AftC, 1'_rEC'_rURE
® 1800 33rd Street
Suite 202
Orlando, FL 32839
Phone: (407) 996-3600
® Fax: (407) 996-5520
Seal
9. PROVIDE 6 SETS OF SUBMITTALS FOR REVIEW BY ARCH/ENGR
PRIOR TO PURCHASHING ANY EQUIPMENT OR MATERIALS. SUBMITTALS
SHALL INCLUDE ALL ITEMS AND MATERIALS SUPPLIED BY
CONTRACTOR. ANY EQUIPMENT OR MATERIALS INSTALLED WITHOUT EWH
REVIEWED SUBMITTALS SHALL BE REMOVED AND REINSTALL AT
ARCH/ENGR DISCRESTION WITH NO ADDITIONAL COMPENSATION TO
CONTRACTOR.
.........
10. PROVIDE 2 SETS OF MAINTENANCE AND OPERATION MANUALS ON WATER '010METRIC
�'°`
ALL MECHANICAL EQUIPMENT OR SYSTEMS.
NTS
11. VERIFY LOCATION, SIZE, INVERTS AND ALL EXISTING
UTILITIES PRIOR TO BEGINNING CONSTRUCTION. ADVISE ENGINEER
OF ANY DISCREPANCIES.
12. ALL FIXTURES MUST BE PROVIDED WITH READILY ACCESSIBLE
CONTROL VALVES AND ACCESS PANELS.
13. DIELECTRIC COUPLINGS ARE REQUIRED BETWEEN ALL
DISSIMILAR METAL IN PIPING AND EQUIPMENT CONNECTIONS.
s
14. ISOLATE COPPER PIPE FROM HANGER OR SUPPORTS WITH
ISOLATOR PAD (HAIR FELT LINING) SUPER STRUT MODEL C/15/16.
FILL VOIDS BETWEEN PIPE & WALL/FLOOR SLEEVES WITH FIRE RATED '
FOAM. <, E 3 s S r ��,�7 �' i� E�:�Sy!+ti' D F'•�I Y*y �rx ,fi� • it:�:,;�'`Y7 1�`{� � �
2
15. PROVIDE ACCESS PANELS FOR ALL CONCEALED VALVES. ACCESScz
PANELS IN RATED WALLS MUST MAINTAIN THE SAME RATING. ALL
ACCESS PANELS MUST MATCH THE FINISH OF THE WALL IN WHICH IT
IS INSTALLED. I JS
16. NO WATER, SANITARY OR DRAINAGE PIPING PERMITTED IN
ELECTRICAL EQUIPMENT ROOMS.
2"AmEmw
17. ALL HOT WATER PIPES UNDER SINKS SHALL BE WRAPPED AND
WITH HANDI-SHIELD WRAP OR EQUAL.
INSULATED �
18. INSULATE ALL HOT WATER LINES WITH - 1" THICK
FIBERGLASS.
19. WATER PIPING SHALL BE TYPE " L" COPPER ABOVE GROUND AND SANITARY ISOMETRIC�
TYPE " K" BELOW GROUND.
NTS
20. WATER PIPING AND FITTINGS SHALL BE SCHEDULE 40 "CPVC"
C'7
WITH A RATING OF 100 PSI AT 180 DEG. F. 0
21. SOIL, WASTE, AND, VENT PIPING SHALL BE SCHEDULE 40 U CO
PVC-DWV PIPE AND FITTINGS WITH NSF SEAL OF APPROVAL, ASTM
D2665-82 ( PVC) AND ASTM D2661-84 ( DWV) , AS MANUFACTURED BY O �3
G. S. R. , CHARLOTTE PLASTIC PIPE & FOUNDRY CO., OR EQUAL. Q}
t�
MAKE PVC JOINTS WITH PVC-DWV SOLVENT CEMENT, ASTM D2564-88
LL
" UN I -WELD" 1200 UP TO 6" PIPE DIAMETER.
< 0
70
22. CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY
FAMILIARIZE HIMSELF WITH ALL EXISTING CONDITIONS PRIOR TO L
BID. r
(0
Cn (Y)
• ua
................... ............ ............ ..................... _
r 1Ln
FIXTURE SCHEDULE: �f
REVISIONS:
m
0
PROVIDE FIXTURES AS LISTED BELOW OR EQUAL FROM THE FOLLOWING colt
to
MANUFACTURES:
AMERICAN STANDARD, KOHLER, ELDER, SLOAN, ZURN, CHICAGO FAUCETS, T&S, n
TAILOR, RHEEM N n Z
SPERZEL, OLSON I TE, JOSAM, ACORN, ELKAY, HALSEY AIL W' n z
J o
LOCH I NVAR, A. 0. SMITH, WADE, SMITH.
Wit"
a
o 0
JS SERVICE SINK FLOOR MOUNT FIAT FL-1
S
0
EWH ELECTRIC WATER HEATER POINT OF USE RHEEM 81VP10S
10 GAL, 2.0 KW, 120/1 VAC C� FLOOR PLANPLUMBING� M
NORTH SCALE: 1 4" =1' —0" w � 1
DATE: 10/20/04
�ni—
" � PROJECT NO.: 4077
o DRAWN: UY
ELIo CHECKED: DWG
;W�
z
ca®o
cp2�
w a SHEET:
Vp 10 1
FLOOR PLAN
PLUM!51144�
/Lez,� S;-4,