SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl 32771 / P.O. Box 1788, Sanford, Fl. 32772
407 302-2520 / FAX (407) 302-2526
Plans Review Sheet
Date: August 5, 2005 Business Address: 100 North Entrance Road.
Occ. Ch. 36, Mercantile Class "A"
Business Name: Joann Fabrics P H (305) 573-9700
Fax. O
Architect: Design Form Mike Twinggs PH (937) 312-8853
Fax. (937) 439-7247
Contractor: T.B.A. Out to bid at submittal time Ph. ()
Revtwed vita comet plea reply torrent
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner
Comment: Plans reviewed as Mercantile Occupancy. FD reserves right to require
applicable code requirements if occupancy use changes. Sprinkler plans to be submitted for
review, permitting, and inspections. Sealed letter from Engineer of Record stating design
criteria for sprinkler system needs to be submitted with construction plans. Fire alarm
system required, with monitoring and horn strobes
through out.
Application — New Building (42,929 s. q. ft.)
1.1 Mixed — N/A,
Special Definitions — Class "A" Mercantile Store (42,929 s. q. ft.)
Classification of Occupancy — Mercantile Store Class "A"
1.2 Classification of Hazard of Contents — Ordinary in office areas, and storage area
classified as "High Hazard" per L.S.C. 101
1.3 Minimum Construction — Shall comply with Florida Building Code 2001
mercantile occupancy
1
2.3 Capacity of Egress — sales floor area based on one (])_person per 30 sq ft., storage area
based on one (1) person per 300 sq. ft.
2.4 Number of Exits — (5) EXITS
2.5 Arrangement of Egress O.K. — Five remotely locatedfrom the other five (5) exits
2.6 Travel Distance —.:A. III FILL I3 .DIMl 1 1E "' el rnl n .obr
2.7 Discharge from Exits — O.K., will field verify
2.8 Illumination of Means of Egress —additional EXIT SIGNS may be required (power shut
down test required at night only)
2.9 Emergency Lighting — (1) foot candle (10 Ix & a minimum at any point of 0.1
foot-candle (1LX ) measured along the path of egress at floor level.Therfore
additional emergency lights may be required, (power shut down test required at night
only) Emergency Lights required In all rest rooms & Main Electrical Room (*).
2.10 Marking of Means of Egress — O.K.; will field verify
2.11 Special Features —Reserved
3.1 Protection of Vertical Openings — Class () mercantile shall have an automatic fire
sprinkler system, design criteria shows rack storage maximum height in storage
area * >
3.2 Protection from Hazards — (See exception 36-3.2.1 .LSC 10 1)
3.3 Interior Finish — Not required, building has an automatic fire sprinkler system
3.4 Detection, Alarm and Communications System: (as per N.F.PA.72- 3-8.3.1.2 (99)
Ed.
3.5 Extinguishing Requirements - as per NFPA 10, (10) ten 4A60
rated fire extinguishers required per N.F.PA. # 10 (see blue
2
P!/ 4
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407 302-2520 / FAX (407) 302-2526
prints for locations).One 5 pound CO 2 fire extinguisher
required in electrical room.
5.1 Utilities — as per LSC 7-1
5.2 HVAC — as per LSC 7-2
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
Sanford City Code — Chapter9:
Required; Fire Sprinklers. Fire Department will field verify with hydro test
Monitoring: Required on all fire sprinkler valves (includes
inside and out)
Other: NFPA 1
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box - One (]) required already (application
attached)
3-7.1 Bldg. Address Number Posted and Legible — Post address in 6" six inch numbers
contrasting in color (see blue prints).
3