Loading...
HomeMy WebLinkAbout2650 Mellonville Ave 98-2383 Fire protection dataFNECEIVED MAY 0 71998 co FIRE PROTECTION BY COMPUTER_DESIGN EAGLE FIRE PROTECTION, INC. P.O. BOX 121091 13649 GRANVILLE AVE. CLERMONT, FLORIDA 34712 407-656-8387 CONTRACTOR GCI CONSTRUCTION, INC. NAME HILL DERMACEUTICAL LOCATION 2650 MELLONVILLE SANFORD, FL. SYSTEM NO. 1 CONTRACT NO. 98-15 PAGE 001 EAGLE FIRE PROTECTION, INC. CLERMONT, FLORIDA 34712 407-656-8387 HYDRAULIC DESIGN INFORMATION SHEET NAME - HILL DERMACEUTICAL DATE - 5/6/98 LOCATION - 2650 MELLONVILLE SANFORD, FL. BUILDING - NEW ADDITION SYSTEM NO. - 1 CONTRACTOR - GCI CONSTRUCTION, INC. CONTRACT NO. - 98-15 CALCULATED BY'- NATHAN EBNER DRAWING NO. - 1 OF 1 CONSTRUCTION: ( ) COMBUSTIBLE (X) NON-COMBUSTIBLE CEILING HEIGHT EXP. OCCUPANCY - WAREHOUSE S (X) NFPA 13 ( )LT. HAZ . ORD . HAZ . GP . ( ) 1 (X) 2 ( ) 3 ( ) EX . HAZ . Y ( )NFPA 231 ( )NFPA 231C FIGURE CURVE S ( ) OTHER T ( )SPECIFIC RULING MADE BY DATE E M AREA OF SPRINKLER OPERATION 1500 SYSTEM TYPE SPRINKLER/NOZZLE DENSITY-GPM/Ft"2 .2 (X) WET MAKE VIKING D AREA PER SPRINKLER 120-10 ( ) DRY MODEL M E ELEVATION AT HIGHEST OUTLET 16' ( ) DELUGE SIZE 3/4" S HOSE ALLOWANCE GPM -INSIDE 100 ( ) PREACTION K-FACTOR 8.0 I RACK SPRINKLER ALLOWANCE 0 ( ) TEMP.RAT.286 G HOSE ALLOWANCE GPM -OUTSIDE 150 N NOTE CALCULATION GPM REQUIRED 569.78 PSI REQUIRED 28.733 AT SUPPLY SUMMARY C-FACTOR USED: OVERHEAD 120 UNDERGROUND 150 W WATER FLOW TEST: PUMP DATA: TANK OR RESERVOIR: A DATE OF TEST 10-7-97 CAP. T TIME OF TEST 9:00am RATED CAP. 0 ELEV. E STATIC (PSI) 56 @ PSI 0 R RESIDUAL (PSI) 42 ELEV. 0 WELL FLOW (GPM) 1215 PROOF FLOW GPM S ELEVATION 2 C 0 M M S T 0 R A G E LOCATION SEE SITE PLAN SOURCE OF INFORMATION FLOW TEST TAKEN BY SANFORD FIRE DEPT. COMMODITY --------------------- CLASS LOCATION STORAGE HT. AREA AISLE W. STORAGE METHOD: SOLID PILED a PALLETIZED $ RACK o R A C K SINGLE ROW ( ) CONVEN. PALLET ( ) AUTO. STORAGE ( ) ENCAP. DOUBLE ROW ( ) SLAVE PALLET ( ) SOLID SHELF ( ) NON MULT. ROW ( ) OPEN SHELF FLUE SFACING CLEAPUANC:STORAGE TO CEILING LONGITUDINAL TRANSVERSE HORIZONTAL BARRIERS PROVIDED: UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW(GPM) PRESSURE (PSI) J w r PAGE 002 AUTO PEAKING SUMMARY for. HILL DERMACEUTICAL LIST of PIPES for AREA CALCULATED LEFT RIGHT SIDE SIDE FROM TO LENGTH FROM TO LENGTH 1 100 26.000 103 2 28.000 3 104 26.000 107 4 28.000 5 108 26.000 ill 6 28.000 7 112 26.000 112 8 64.000 FLOW PRESSURE PRESSURE REQUIRED REQUIRED DIFFERENTIAL LEFT 12.000 I 569.79 28.651 0.082 AREA CALCULATED I 569.78 28.733 0.000 RIGHT 12.000 I 569.79 28.665 0.068 TYPICAL DISTANCE BETWEEN HEADS = 12.000 SPLIT POINT USED IN AREA CALCULATED = 102 m PAGE 003 EAGLE FIRE PROTECTION, INC. Water Supply Curve ---------------------------- Static Press.= 56.000 PSI Resid. Press.= 42.000 PSI Resid. Flow = 1215.000 GPM Press Available at ----------------------------------- 569.78 GPM 52.550 PSI I v Safety Margin 23.817 PSI ------- > v Flow Available at Demand x<------------- >*<----- 1742.06 GPM Safety Margin 1172.28 GPM Total System \ \ Demand \ \ 569.78 GPM \ 28.73 PSI \ 1 100 101 K>K>K<K< 48.8 24.3 48.75 3 104 105 K>K>K<K< 48.8 24.4 97.55 5 108 109 K>K>K<K< 49.0 24.5 146.53 7 112 8 K< 15.4 12.5 161.89 9 10 3.3 158.61^ 161.17 11 12 3.5 155.08^ 164.70 13 14 4.4 150.70^ 169.09 15 16 6.2 144.49^ 175.29 17 18 7.9 136.56^ 183.23 19 20 9.7 126.87^ 192.91 21 22 11.3 115.54 24 25 15.7 99.89v 99.89 26 27 13.7 86.24v 86124 28 29 12.8 73.43v 73.43 30 31 v PAGE 004 A-- 102 103 2 2 24.0 48.4 48.39 106 107 4 2 24.0 48.4 96.83 110 111 6 2 24.1 48.6 11.6 61.83v 61.83 32 33 11.0 50.83v 50.83 34 35 10.2 40.59v 40.59 36 37 11.1 29.54v 29.54 38 39 10.7 18.90v 18.90 40 41 I 9.5 9.43v 9.43 42 43 9.4 1 3 5 7 9 11 13 15 17 2 4 6 8 10 12 14 16 18 145.4 157.9 1 23 TASR BASR BK Ul TEST Q<><Q 319.8 319.8 419.8 419.8 419.8 A-- PAGE 005 19 21 24 26 20 22 23 25 204.3 115.5 A 28 30 32 34 36 27 29 31 33 35 IME PAGE 006 I 38 40 42 37 39 41 43 B C-- EAGLE FIRE PROTECTION, INC. JOB- HILL DERMACEUTICAL JOB NO- 98-15 -1 DATE 050698 PAGE 7 FITTING NAME TABLE ABBREV. NAME A Generic Alarm Va B Generic Butterfly Valve C Roll Groove for D Generic Dry Pipe Valve E 90' Standard Elbow F 45' Elbow G Generic Gate Valve K Generic Detector L 90' Long Turn Elbow M 90' Medium Turn Elbow Q Generic Flow Control Val S Generic Swing Ch T 90' Flow thru Tee W Generic Wafer Ch Z Generic Wafer Ch EAGLE FIRE PROTECTION, INC. JOB- HILL DERMACEUTICAL JOB NO- 98715 1 DATE 050698 PAGE 8 HYD. Qa DIA. FITTING PIPE Pt Pt REF C" or FTNG'S Pe Pv NOTES ****** POINT Qt Pf/F Eqv. Ln. TOTAL Pf Pn 48.75 1.752 2T 24.14 26.00 12.10 12.10 1 C=120 0.00 24.14 0.00 0.00 48.75 0.0556 0.00 50.14 2.79 0.00 Vel 6.49 24.41 1.752 0.00 12.00 9.31 9.31 K = 8 100 C=120 0.00 0.00 0.00 0.00 24.34 0.0158 0.00 12.00 0.19 0.00 Vel 3.24 24.16 1.752 0.00 11.92 9.12 9_12 K = 8 101 C=120 0.00 0.00 0.00 0.00 0.18 0.0000 0.00 11.92 0.00 0.00 Vel 02 24.17 1.752 0.00 12.08 9.12 9.12 K = 8 102 C=120 0.00 0.00 0.00 0.00 23.99 0.0157 0.00 12.08 0.19 0.00 Vel 3.19 24.40 1.752 2T 24.14 28.00 9.31 9.31 K = 8 103 C=120 0.00 24.14 0.00 0.00 48.39 0.0548 0.00 52.14 2.86 0.00 Vel 6.44 2 48.39 12.17 K = 13.872 48.80 1.752 2T 24.14 26.00 12.12 12.12 3 C=120 0.00 24.14 0.00 0.00 48.80 0.0556 0.00 50.14 2.79 0.00 Vel 6.49 24.43 1.752 0.00 12.00 9.33 9.33 K = 8 104 C=120 0.00 0.00 0.00 0.00 24.37 0.0158 0.00 12.00 0.19 0.00 Vel 3.24 24.19 1.752 0.00 11.92 9.14 9.14 K = 8 105 C=120 0.00 0.00 0.00 0.00 0.18 0.0000 0.00 11.92 0.00 0.00 Vel 02 24.19 1.752 0.00 12.08 9.14 9.14 K = 8 106 C=120 0.00 0.00 0.00 0.00 24.01 0.0149 0.00 12.08 0.18 0.00 Vel 3.20 24.43 1.752 2T 24.14 28.00 9.32 9.32 K = 8 107 C=120 0.00 24.14 0.00 0.00 48.44 0.0550 0.00 52.14 2.87 0.00 Vel 6.45 4 48.44 12.19 K 13.873 UNITS - DIAMETER INCH) LENGTH FOOT) FLOW GPM) PRESSURE (PSI) EAGLE FIRE PROTECTION, INC. JOB- HILL DERMACEUTICAL JOB NO- 98-15 1 DATE 050698 PAGE 9 HYD. Qa DIA. FITTING PIPE Pt Pt REF licit or FTNG'S Pe Pv NOTES ****** POINT Qt Pf/F Eqv. Ln. TOTAL Pf Pn 48.98 1.752 2T 24.14 26.00 12.21 12.21 5 C=120 0.00 24.14 0.00 0.00 48.98 0.0562 0.00 50.14 2.82 0.00 Vel 6.52 24.52 1.752 0.00 12.00 9.39 9.39 K = 8 108 C=120 0.00 0.00 0.00 0.00 24.46 0.0150 0.00 12.00 0.18 0.00 Vel 3.26 24.27 1.752 0.00 11.92 9.21 9.21 K = 8 109 C=120 0.00 0.00 0.00 0.00 0.19 0.0000 0.00 11.92 0.00 0.00 Vel 03 24.28 1.752 0.00 12.08 9.21 9.21 K = 8 110 C=120 0.00 0.00 0.00 0.00 24.09 0.0149 0.00 12.08 0.18 0.00 Vel 3.21 24.51 1.752 2T 24.14 28.00 9.39 9.39 K = 8 111 C=120 0.00 24.14 0.00 0.00 48.60 0.0554 0.00 .. 52.14 2.89 0.00 Vel 6.47 6 48.60 12.28 K 13.871 15.35 1.752 2T 24.14 26.00 12.41 12.41 7 C=120 0.00 24.14 0.00 0.00 15.35 0.0065 0.00 50.14 0.33 0.00 Vel 2.04 27.81 1.752 2T 24.14 64.00 12.08 12.08 K = 8 112 C=120 0.00 24.14 0.00 0.00 12.46 0.0045 0.00 88.14 0.40 0.00 Vel 1.66 8 12.46 12.48 K 3.528 3.27 1.752 4T 48.29 90.00 12.68 12.68 9 C=120 0.00 48.29 0.00 0.00 3.27 0.0003 0.00 138.29 0.05 0.00 Vel 44 10 3.27 12.73 K 916 3.53 1.752 4T 48.29 90.00 12.94 12.94 11 C=120 0.00 48.29 0.00 0.00 3.53 0.0004 0.00 138.29 0.06 0.00 Vel = .47 UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI) I 1 EAGLE FIRE PROTECTION, INC. JOB- HILL DERMACEUTICAL JOB NO- 98-15 1 DATE 050698 PAGE 10 HYD Qa DIA FITTING PIPE Pt Pt REF licit or FTNG'S Pe Pv NOTES ****** POINT Qt Pf/F Eqv. Ln. TOTAL Pf Pn 12 3.53 13.00 K = 979 4.39 1.752 4T 48.29 90.00 13.19 13.19 13 C=120 0.00 48.29 0.00 0.00 4.39 0.0006 0.00 138.29 0.09 0.00 Vel = 58 14 4.39 13.28 K = 1.205 6.20 1.752 1F 3.02 90.00 13.42 13.42 15 C=120 2T 24.14 27.16 0.00 0.00 6.20 0.0011 0.00 117.16 0.14 0.00 Vel = 83 16 6.20 13.56 K = 1.683 7.94 1.752 1F 3.02 90.00 13.61 13.61 17 C=120 2T 24.14 27.16 0.00 0.00 7.94 0.0019 0.00 117.16 0.23 0.00 Vel = 1.06 18 7.94 13.84 K = 2.134 9.68 1.7523E 18.11 92.00 13.81 13.81 19 C=120 3T 36.22 54.32 0.00 0.00 9.68 0.0028 0.00 146.32 0.41 0.00 Vel = 1.29 20 9.68 14.22 K = 2.567 11.33 1.752 3E 18.11 91.00 13.98 13.98 21 C=120 3T 36.22 54.32 0.00 0.00 11.33 0.0037 0.00 145.32 0.54 0.00 Vel = 1.51 22 11.33 14.52 K = 2.973 15.65 1.752 4E 24.14 92.00 14.08 14.08 24 C=120 2T 24.14 48.29 0.00 0.00 15.65 0.0068 0.00 140.29 0.96 0.00 Vel = 2.08 UNITS - DIAMETER INCH) LENGTH FOOT) FLOW GPM) PRESSURE (PSI) EAGLE FIRE PROTECTION, INC. JOB- HILL DERMACEUTICAL JOB NO- 98-15 1 DATE 050698 PAGE 11 HYD. Qa DIA. FITTING PIPE Pt Pt REF C° or FTNG'S Pe Pv NOTES ****** i POINT Qt Pf/F Eqv. Ln. TOTAL Pf Pn 25 15.65 15.04 K = 4.036 13.65 1.752 4E 24.14 92.00 14.19 14.19 26 C=120 2T 24.14 48.29 0.00 0.00 13.65 0.0052 0.00 140.29 0.74 0.00 Vel = 1.82 27 13.65 14.93 K = 3.533 12.81 1.752 4E 24.14 92.00 14.23 14.23 28 C=120 2T 24.14 48.29 0.00 0.00 12.81 0.0047 0.00 140.29 0.66 0.00 Vel = 1.70 29 12.81 14.89 K = 3.320 11.60 1.752 4E 24.14 92.00 14.28 14.28 30 C=120 2T 24.14 48.29 0.00 0.00 11.60 0.0039 0.00 140.29 0.55 0.00 Vel = 1.54 r 31 11.60 14.83 K = 3.012 11.00 1.752 4E 24.14 92.00 14.31 14.31 32 C=120 2T 24.14 48.29 0.00 0.00 11.00- 0.0035 0.00 1.40.29 0.50 0.00 Vel = 1.46 33 11.00 14.81 K = 2.859 10.24 1.752 4E 2'4_.14 4------------------------------------------ 92.00 14.34 14.34 34 C=120 2T 24.14 48.29 0.00 0.00 10.24 0.0031 0.00 140.29 0.44 0.00 Vel = 1.36 35 10.24 14.78 K = 2.664 11.05 1.7 -52 2T 24.14 88.00 14.36 14.36 36 C=120 0.00 24.14 0.00 0.00 11.05 0:0035 0.00 112-14 0,40 0.00 Vel = 1.47 UNITS - DIAMETER ,(INCH) T - - - LENGTH ROOT) FLOW GPM) PRESSURE (PSI) i 1 JOB- HILL DERMACEUTICAL EAGLE FIRE PROTECTION, INC. JOB NO- 98-15 -1 DATE 050698 PAGE 12 HYD Qa DIA. FITTING PIPE Pt Pt REF C" or FTNG'S Pe Pv NOTES ****** POINT Qt Pf/F Eqv. Ln. TOTAL Pf Pn 37 11.05 14.76 K = 2.876 10.65 1.752 2T 24.14 90.00 14.37 14.37 38 C=120 0.00 24.14 0.00 0.00 10.65 0.0033 0.00 114.14 0.38 0.00 Vel 1.42 39 10.65 14.75 K = 2.773 9.46 1.752 3E 18.11 93.50 14.37 14.37 40 C=120 1F 3.02 45.27 0.00 0.00 9.46 0.0026 2T 24.14 138.77 0.37 0.00 Vel 1.26 41 9.46 14.74 K = 2.464 9.43 1.752 3E 18.11 93.50 14.37 14.37 42 C=120 1F 3.02 45.27 0.00 0.00 i------------------------------------------------------------------------------- 9.43 0.0026 2T 24.14 138.77 0.37 0.00 Vel 1.25 43 9.43 14.74 K = 2.456 48.75 3.352 0.00 10.00 12.10 12.10 1 C=120 0.00 0.00 0.00 0.00 48.75 0.0020 0.00 10.00 0.02 0.00 Vel 1.77 48.80 3.352 0.00 10.00 12.12 12.12 3 C=120 0'.00 0.00 0.00 0.00 97.55 0.0090 0.00 10.00 0.09 0.00 Vel 3.55 48.98 3.352 0.00 11.25 12.21 12.21 i 5 C=120 0.00 0.00 0.00 0.00 146.53 0.0177 0.00 11.25 0.20 0.00 Vel 5.33 15.36 3.352 0.00 12.25 12.41 12.41 7 C=120 0.00 0.00 0.00 0.00 161.89 0.0220 0.00 12.25 0.27 0.00 Vel 5.89 3.28 3.352 0.00 12.50 12.68 12.68 9 C=120 0.00 0.00 0.00 0.00 158.61 0.0208 0.00 12.50 0.26 0.00 Vel 5.77 UNITS - DIAMETER INCH) LENGTH FOOT) FLOW GPM) PRESSURE (PSI) JOB- HILL DERMACEUTICAL EAGLE FIRE PROTECTION, INC. JOB NO- 98-15 -1 DATE 050698 PAGE 13 HYD. Qa DIA. FITTING PIPE Pt Pt REF V'C" or FTNG'S Pe Pv NOTES ****** POINT Qt Pf/F Eqv. Ln. TOTAL Pf Pn 3.53 3.352 0.00 12.50 12.94 12.94 11 C=120 0.00 0.00 0.00 0.00 155.08 0.0200 0.00 12.50 0.25 0.00 Vel 5.64 4.38 3.352 0.00 12.00 13.19 13.19 13 C=120 0.00 0.00 0.00 0.00 150.70 0.0191 0.00 12.00 0.23 0.00 Vel 5.48 6.21 3.352 0.00 11.00 13.42 13.42 15 C=120 0.00 0.00 0.00 0.00 144.49 0.0172 0.00 11.00 0.19 0.00 Vel 5.25 7.93 3.352 0.00 12.33 13.61 13.61 17 C=120 0.00 0.00 0.00 0.00 136.56 0.0162 0.00 12.33 0.,20 0.00 Vel 4.96 9.69 3.352 0.00 12.00 13.81 13.81 19 C=120 0.00 0.00 0.00 0.00 126.87 0.0141 0.00 12.00 0.17 0.00 Vel 4.61 11.33 3.352 0.00 9.00 13.98 13.98 21 C=120 0.00 0.00 0.00 0.00 115.54 0.0111 0.00 9.00 0.10 0.00 Vel 4.20 15.65 3.352 0.00 12.00 14.08 14.08 24 C=120 0.00 0.00 0.00 0.00 99.89 0.0091 0.00 12.00 0.11 0.00 Vel 3.63 13.65 3.352 0.00 6.00 14.19 14.19 26 C=120 0.00 0.00 0.00 0.00 86.24 0.0066 0.00 6.00 0.04 0.00 Vel 3.14 12.81 3.352 0.00 11.00 14.23 14.23 28 C=120 0.00 0.00 0.00 0.00 73.43 0.0045 0.00 11.00 0.05 0.00 Vel 2.67 11.60 3.3`52 0.00 7.00 14.28 14.28 30 C=120 0.00 0.00 0.00 0.00 61.83 0.0042 0.00 7.00 0.03 0.00 Vel 2.25 11.00 3.352 0.00 12.00 14.31 14.31 32 C=120 0.00 0.00 0.00 0.00 50.83 0.0025 0.0b 12.00 0.03 0.00 Vel 1.85 10.24 3.352 0.00 10.50 14.34 14.34 34 C=120 0.00 0.00 0.00 0.00 40.59 0.0019 0.00 10.50 0 02 0.00 Vel 1.48 UNITS - DIAMETER INCH) LENGTH FOOT) FLOW GPM) PRESSURE (PSI) J JOB- HILL DERMACEUTICAL EAGLE FIRE PROTECTION, INC. JOB NO- 98-15 -1 DATE 050698 PAGE 14 HYD. Qa DIA. FITTING PIPE Pt Pt REF C" or FTNG'S Pe Pv NOTES ****** POINT Qt Pf/F Eqv. Ln. TOTAL Pf Pn 11.05 3.352 0.00 10.50 14.36 14.36 36 C=120 0.00 0.00 0.00 0.00 29.54 0.0009 0.00 10.50 0.01 0.00 Vel 1.07 10.64 3.352 0.00 11.00 14.37 14.37 38 C=120 0.00 0.00 0.00 0.00 18.90 0.0000 0.00 11.00 0.00 0.00 Vel 69 9.47 3.352 0.00 10.00 14.37 14.37 40 C=120 0.00 0.00 0.00 0.00 9.43 0.0000 0.00 10.00 0.00 0.00 Vel 34 42 9.43 14.37 K = 2.487 48.39 3.352 0.00 10.00 12.17 12.17 2 C=120 0.00 0.00 0.00 0.00 48.39 0.0020 0.00 10.00 0.02 0.00 Vel 1.76 48.44 3.352 0.00 10.00 12.19 12.19 4 C=120 0.00 0.00 0.00 0.00 96.83 0.0090 0.00 10.00 0.09 0.00 Vel 3.52 48.61 3.352 0.00 11.25 12.28 12.28 6 C=120 0.00 0.00 0.00 0.00 145.44 0.0177 0.00 11.25 0.20 0.00 Vel 5.29 12.46 3.352 0.00 12.25 12.48 12.48 8 C=120 0.00 0.00 0.00 0.00 157.90 0.0204 0.00 12.25 0.25 0.00 Vel 5.74 3.27 3.352 0.00 12.50 12.73 12.73 10 C=120 0.00 0.00 0.00 0.00 161.17 0.0216 0.00 12.50 0.27 0.00 Vel 5.86 3.53 3.352 0.00 12.50 13.00 13.00 12 C=120 0.00 0.00 0.00 0.00 164.70 0.0224 0.00 12.50 0.28 0.00 Vel 5.99 4.39 3.352 0.00 12.00 13.28 13.28 14 C=120 0.00 0.00 0.00 0.00 169.09 0.0233 0.00 12.00 0.28 0.00 Vel 6.15 6.20 3.352 0.00 11.00 13.56 13.56 16 C=120 0.00 0.00 0.00 0.00 175.29 0.0254 0.00 11.00 0.28 0.00 Vel 6.37 UNITS - DIAMETER INCH) LENGTH FOOT) FLOW GPM) PRESSURE (PSI) EAGLE FIRE PROTECTION, INC. JOB- HILL DERMACEUTICAL JOB NO- 98-15 -1 DATE 050698 PAGE 15 HYD. Qa DIA. FITTING PIPE Pt Pt REF liC" or FTNG'S Pe Pv NOTES ****** POINT Qt Pf/F Eqv. Ln. TOTAL Pf Pn 7.94 3.352 0.00 13.83 13.84 13.84 18 C=120 0.00 0.00 0.00 0.00 183.23 0.0274 0.00 13.83 0.38 0.00 Vel 6.66 9.68 3.352 0.00 10.00 14.22 14.22 20 C=120 0.00 0.00 0.00 0.00 192.91 0.0300 0.00 10.00 0.30 0.00 Vel 7.01 11.34 3.352 1T 23.09 2.67 14.52 14.52 22 C=120 0.00 23.09 0.00 0.00 204.25 0.0333 0.00 25.76 0.86 0.00 Vel 7.43 319.79 3.352 2E 21.55 8.17 15.38 15.38 23 C=120 0.00 21.55 0.00 0.00 115.54 0.0114 0.00 29.72 0.34 0.00 Vel 4.20 15.65 3.352 0.00 12.00 15.04 15.04 25 C=120 0.00 0.00 0.00 0.00 99.89 0.0091 0.00 12.00 0.11 0.00 Vel 3.63 13.65 3.352 0.00 6.00 14.93 14.93 27 C=120 0.00 0.00 0.00 0.00 86.24 0.0066 0.00 6.00 0.04 0.00 Vel 3.14 12.81 3.352 0.00 11.00 14.89 14.89 29 C=120 0.00 0.00 0.00 0.00 73.43 0.0054 0.00 11.00 0.06 0.00 Vel 2.67 11.60 3.352 0.00 7.00 14.83 14.83 31 C=120 0.00 0.00 0.00 0.00 61.83 0.0028 0.00 7.00 0.02 0.00 V--1 2.25 11.00 3.352 0.00 12.00 14.81 14.81 33 C=120 0.00 0.00 0.00 0.00 50.83 0.0025 0.00 12.00 0.03 0.00 Vel 1.85 10.24 3.352 0.00 10.50 14.78 14.78 35 C=120 0.00 0.00 0.00 0.00 40.59 0.0019 0.00 10.50 0.02 0.00 Vel 1.48 11.05 3.352 0.00 10.50 14.76 14.76 37 C=120 0.00 0.00 0.00 0.00 29.54 0.0009 0.00 10.50 0.01 0.00 Vel 1.07 10.64 3.352 0.00 9.50 14.75 14.75 39 C=120 0.00 0.00 0.00 0.00 18.90 0.0010 0.00 9.50 0.01 0.00 Vel 69 UNITS - DIAMETER INCH) LENGTH FOOT) FLOW GPM) PRESSURE (PSI) a EAGLE FIRE PROTECTION, INC. JOB- HILL DERMACEUTICAL JOB NO- 98-15 1 DATE 050698 PAGE 16 HYD. Qa DIA. FITTING PIPE Pt Pt REF C" or FTNG'S Pe Pv NOTES ****** POINT Qt Pf/F Eqv. Ln. TOTAL Pf Pn 9.47 3.352 0.00 12.00 14.74 14.74 41 C=120 0.00 0.00 0.00 0.00 9.43 0.0000 0.00 12.00 0.00 0.00 Vel = 34 43 9.43 14.74 K = 2.456 319.78 4.352 7----------------------------------------------------- lE 5.83 25.00 15.38 15.38 23 C=120 0.00 5.83 3.17 0.00 319.78 0.0217 0.00 30.83 0.67 0.00 Vel = 6.90 0.00 4.352 0.00 8.67 19.22 19.22 TASR C=120 0.00 0.00 2.89 0.00 319.78 0.0207 0.00 8.67 0.18 0.00 Vel = 6.90 100.00 8.040 3E 84.61 70.00 22.29 22.29 Qa = 100 BASR C=150 2F 28.20 112.82 6.00 0.00 Fixed Loss = +6.00 419.78 0.0012 0.00 182.82 0.22 0.00 Vel = 2.65 0.00 8.040 2F 28.20 35.00 28.51 28.51 BK C=150 1G 6.27 89.31 0.00 0.00 419.78 0.0012 1T 54.84 124.31 0.15 0.00 Vel = 2.65 0.00 8.450 1G 2.90 40.00 28.66 28.66 U1 C=140 1T 28.99 31.89 0.00 0.00 419.78 0.0009 0.00 71.89 0.07 0.00 Vel = 2.40 150.00 Qa = 150.00 TEST 569.78 28.73 K = 106.295 UNITS - DIAMETER INCH) LENGTH FOOT) FLOW GPM) PRESSURE (PSI) i