HomeMy WebLinkAbout700 Aero Ln 00-2778 Aero ProductsCITY OF SANFORD
FIRE DEPARTMENT
300 N. Park Ave.
Sanford, FL 32771
407) 302-1022 (407) 330-5677 FAX
Plans Review Sheet
Date: 4/20/00 Business Address: 700 Aero Lane Occ. Ch. 28
Business Name: American LaFrance / Aero Products Ph. 1-800-292-2376
Contractor: Unknown Ph.
Reviewed [ ] Reviewed with comment [ X ] Rejected
Reviewed by: H. A. "Pete" Tucker, Fire Protection Inspector r"
Comment: Type of Construction not noted, appears to be Type IV, site plan does not
reflect water supply / FDC / hydrants. If separate contractor does underground fire line,
must have proper certification & pull separate permit for it. Contractors for fire sprinkler
and alarm systems to submit plans for permits, etc.(If over $5,000 must be engineer
sealed and approved by engineer of record.)
1.1 Application — New Buildings & Additions 33, 466 sf
1.2 Mixed — N/A
1.3 Special Definitions — N/N
1.4 Classification of Occupancy — Industrial
1.5 Classification of Hazard of Contents — Ordinary
1.6 Minimum Construction — N/R
2.2 Means of Egress Components — O.K.
2.3 Capacity of Egress — O.K.
2.4 Number of Exits — O.K.
2.5 Arrangement of Egress —
2.6 Travel Distance — O.K.
2.7 Discharge from Exits — D.K.
2.8 Illumination of Means of Egress — O.K.; will field verify
2.9 Emergency Lighting — O.K.; will field verify
2.10 Marking of Means of Egress — O.K.
2.11 Special Features — O.K.
3.1 Protection of Vertical Openings — N/N
3.2 Protection from Hazards — N/N
3.3 Interior Finish — Class `B"
3.4 Detection, Alarm and Communications Systems — as per LSC 7.6, NFPA 72
3.5 Extinguishing Requirements — as per NFPA 10
3.6 Corridors — N/A
4 Special Provisions
5 Building Services
5.1 Utilities
5.2 HVAC
5.3 Elevators, Escalators, Conveyors (4A-47)
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes
Sanford City Code — Chapter 9
Fire Sprinklers: Required; also see 3.5 above
Monitoring: Required by a U.L. listed Central Station for all mandated fire
sprinklered properties
Other: NFPA 1
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box — Required; will field verify
3-7.1 Bldg. Address Number Posted and Legible — Required; will field verify