CITY OF SANFORD
FIRE DEPARTMENT
300 N. Park Ave.
Sanford, FL 32771
407) 302-1091 (407) 330-5677 FAX
Plans Review Sheet
Date: December 21, 1999 Business Address 2RedCleueianel Occ. Ch. 8
Business Name: O.S.I. Ph.
Contractor: Mark Construction Ph. (407) 831-6275
Reviewed [ ] Reulewedwithcornrrrent [ X} Rejected
Reviewed by: Bart Wright, Fire Protection Inspecto
Comment: Review based in part on 12/21/1999 letter (attached) from Nelson
Blankenship
1.1 Application — Renovation to assembly occupancy
1.2 Mixed — N/A
1.3 Special Definitions — N/N
1.4 Classification of Occupancy — Assembly; # sq. ft. 3750
1.5 Classification of Hazard of Contents Ordinary
1.6 Minimum Construction — N/R
1.7 Occupant Load — 1/15 sq. ft. = 250
2.2 Means of Egress Components — O.K.
2.3 Capacity of Egress — O.K.
2.4 Number of Exits — O.K.
2.5 Arrangement of Egress — O.K.,
2.6 Travel Distance — O.K.
2.7 Discharge from Exits — O.K.
2.8 Illumination of Means of Egress — O.K.; will field verify
2.9 Emergency Lighting — O.K.; will field verify
2.10 Marking of Means of Egress — O.K.
2.11 Special Features — O.K.
3.1 Protection of Vertical Openings — N/N
3.3 Interior Finish — Class "C"
3.6 Corridors — N/A
4 Special Provisions
5 Building Services
5.1 Utilities
5.2 HVAC
5.3 Elevators, Escalators, Conveyors (4A-47)
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes
Sanford City Code — Chapter 9
Fire Sprinklers: See 3.5 above
Monitoring: Required for all mandated fire sprinklered properties
Other: NFPA 1
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box - N/A
3-7.1 Bldg. Address Number Posted and Legible — Required; will field verify
Dec-21-99 11:47A BLANKENSHIP MCMILLEN 407-599-0548 P.01
BLANKENSHIP
McMILLEN
330 Crown Oak Centre Drive
Longwood Florida 32750.6149
4O7. j99.0547
Fax 407.599.0548
AAOt)03290
December`21, 1999
Larry Flynn
Mark Construction. Company
1969 Corporate .Square Drive
Longwood, Florida 32750
Re: Sanford Fire -Department fax dated 12-20-9.9
Welcome Center Addition #3
Dear Mr. Flynn
Discrepancy in area:
New Area
Northern (enclosed -including 9117) 1,794sf
Southern (enclosed including #103) 1 734sf
Subtotal (rounded) 3,550sf
Existing Area
Booths 576sf
Total .4126sf
e Classification is "Assembly" in spaces 103 and 117.
e Cc.cupants: @ 15sf/person, North or South equals
120 persons maxi.
120 people x 0.2 = 24..inches required .exit width
Provided for North and South space -each: ,4 .36 leaves =,144
inches
all other doors are 36".
o Ramp is 48" long to accommodate the 4" change in elevation "from
100'-0" on the main floor to 100'-4"for the food prep space car
rentals and booths.
a Equi.pm.ent ,in the food prep .area #110 will be identified by another
tenant improvement permit, which Js to follow. The equipment
in the food. prep work area will be similar to the ,3elway Cafe
across the street.
Dec-21-99 11:47A BLANKENSHIP MCMILLEN 407-599-0548 P.O2
1 c1 y
Response to-.Sanford's fax 12-20-99
Welcome Center #3
Page 2
e Sprinkler:. information will required .by lWiginton.
Awning willbe made with curved gypsum board on studs. It will not
be canvas. The soffit under the awning will be a linear ceiling at
45 degrees as shown on the drawings.
Hope this answers Mr. Wright's questions. If there needs to be any more
explanation, please call.
Sincerely,
Nelson Blankenship, Jr. AIA
Principle
Cc: Bart Wright via fax 407.330.5677
FLORIDA ENERGY EFFICIENCY CODE FOR 3UILDING CONSTRUCTION
CHAPTER 4 — Commercial Buildill-, C,,'mpli,ance Methods
FORM 40OD-97
Administered by the Departmant nF Community Affairs
renovations & Systems Prescriptive Method ALL CLIMATE ZONESrenovations
4 F Na_ me: NBuildingZone:
i6dress: - ,/7 Classification: (":".
City; Zip Co e: Building Permit No.:
Permitting Office: Builder:
Owner: Jurisdiction No.:
BUILDING INFORMATION
WALLS ROOF/CEILING FLOORS DOORS GLASS
TYPE U I AREA TYPEU ARE TYPE U AREA TYPE U AREA TYPE U AREA Concrete
CBS Under Attic i Slab -on -grade Wood Sin le wall Wood
frame Sin le Assembly Raised Wood i Metal Double, wall Metal
frame Other: Raised Concrete Insulated Single, roof Insulation
R-value Insulation R-value Insulation R-value Other Double, roof SYSTEMS
INFORMATION AIR
CONDITIONER. HEATING SYSTEM HOT WATER TYPE
EFFICIENCY TONS TYPE EFFICIENCY BTU/H TYPE Unitary &
Heat Pump Central & Heat Pump Electric 65,
000 Btu/h SEER 65,000 Btu/h HSPF Resistance 65,
000 Btu/h EER _ IPLV 65,000 Btu/h COP Dedicated Heat Pump Water
cooled EER _ IPLV Water cooled COP /y,
Gas
Evaporatively
cooled EER Evaporatively cooled COPil Natural PTAC
EER Electric Resistance COP /i,-rr LPG Chiller
COP _IPLV Gas/Oil (circle one) HRU Gas
heat pump COP 225,000/300,000 Btu/h _ AFUE Other: Other.
225,000/300,000 Btu/h _ Et — LIGHTING
Total Lighting Wattage i SIZING CALCULATION DUCTS R-value Total
Conditioned Floor Area lavrEeIZ Watts/s .ft. B
required) Attached
Location PRESCRIPTIVE
MEASURES (Must be met or exceeded by all buildings.) Components
Section Requirements Chec O
erations Manual 102.1 Operations manual will be provided to owner. Windows
406.1 Maximum of .3 cfm per sq.ft. of window area. Doors
406.1 Maximum of.1:2 cfm per sq.ft. of door area. Joints/
Cracks 406.1 To be caulked, gasketed, weatherstripped or otherwise sealed. Reheat
407.1 Electric resistance reheat prohibited. Ventilation
409.1 Supplied with readily accessible switch for shut-off and/or volume reduction when ventilation is not required. HVAC
Efficiency 407.1, 408.1 Minimum efficiencies— Heating: Tables 4-7, 4-8, 4-9. Cooling: Tables 4-3, 4-4, 4-5, 4-6. HVAC
Controls 407.1 Separate readily accessible manual or automatic thermostat for each system. HVAC
Ducts 410.1 Air ducts, fittings, mechanical equipment and plenum chambers shall be mechanically attached, sealed, insulated and
installed in accordance with the criteria of section 410.1. Balancing
410.1 HVAC distribution system(s) tested and balanced. Piping
Insulation 411.1 In accordance with Table 4-11. Water
Heaters 412.1 Automatic electric storage water heaters 5120 gallons and gas & oil fired storage water heaters 575,000 Btu/h shall meet performance
requirements in Table 4-12. Electric >120 gallons: standby loss <_.30+27NT. Gas >75,000, Oil >105,000: E, .78, Standby
loss15 1.30+114NT. Gas, Oil >155,000: E.78, Standby loss <_ 1.30+95NT. L Swimming Pools
Spas 412.
1
Spas & heated pools must have covers. Non-commercial pools must have pump timer. Gas spa & pool heaters must have a
minimum thermal efficiency of 78%. LI X
LL y!'
j Hot Water
Pipe Insulation 412.
1
Piping heat loss is limited to the levels in Table 4-11 for circulating systems and the first 8' of pipe from a storage tank. Water
Fixtures
412.1 Shower head water flow restricted to maximum of 2.5 gpm at 80 psi. Toilets meet 42CFR 6295(k). Public lavatory fixture maximum flow
of .5 gpm; or if self -closing valve, .25 gallon circulating, .5 gallon non -circulating. Lighting 415.
1 Ballasts shall have Power Factors no less than .90. Code. ARCHITECT:
juWaf2iV=
ELECTRICAL SYSTEM
DESIGNE - LIGHTING SYSTEM
DESIGNER: MECHANICAL SYSTEM
DESIGNER: PLUMBING SYSTEM
DESIGNER: I hereby
certify that the plans and specifications covered by the calculation are incompliance with the Review of plans and specifications covered by this calculation indicates compliance with Florida Energy
Code. the Florida Energy Code. Before construction is completed, this building will be inspected PREPARED BY-
DATE: _ for compliance
in accordance with Section 553.908, F.S. I hereby
certify that ' ui ,rR i/sy' n e th a Florida Energy Code. / BUILDING OFFICIAL OWNER AGENT: !
o %, f DJ/IrI DATE: d .
FORM 40OD-97
stalled
ALL CLIMATE ZONES,
i
Building Component Efficiency Required Value In
1. Code minimums shall be met for components being retrofitted with new equipment.
2. Repairs to equipment need not meet Code and should not be construed to require a replacement of equipment.
3. Where existing components, such as ducts or electrical wiring, are utilized with a replacement system, such
existing components need not be replaced.
ALL CLIMATE ZONES
r— -
FORM 40OD-97
r
e
Building Component Efficiency Required Value Installed
Fenestrations:
Climate zones 1,2,3 U-0.67
Climate zones 4,5,6,7,8,9 7 SC (.61 SHGC)>1'OH
55 SC .48 SHGC no OH
Wall:
Masonry ,
Climate zones 1,2,3
Climate zones 4,5,6,7,8,9
R-7
R-5
Wood frame — all zones R 11
Metal frame — all zones R-13
Roof:
Built-up
Climate zones 1,2,3
Climate zones 4,5,6
R-16
R-14
Climate zones 7,8,9 R-12
Attic or Drop ceiling
All zones R-19
Floor:
Slab-oRased
Grade
Raised Wood
R-
R-19
Raised Concrete R-7
Infiltration Code minimums per
sec.406.1.ABCD.1
Cooling System Code minimums per
sec. 407.1.ABCD.3 l v
Heating System Code minimums per
sec. 408.1.ABCD.3
Ducts Code minimums per
sec. 410.1.ABCD.2 wz'
Piping Code minimums per f
sec. 411.1.ABCD.1
Domestic Hot Water Code minimums per
sec.412.1.ABCDJ/
y
Motors Code minimums per
sec. 413.1.ABCD
Lighting UPD: W/s.f. per Table 4-16
Controls:
1. Two banks per space with r
separate manual controls; or
2.One occupancy
sensor per space (or other
automatic control)
i
1. Code minimums shall be met for components being retrofitted with new equipment.
2. Repairs to equipment need not meet Code and should not be construed to require a replacement of equipment.
3. Where existing components, such as ducts or electrical wiring, are utilized with a replacement system, such
existing components need not be replaced.
2.
a
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
CHAPTER 4 — Commercial Building Compliance Methods
Administered by the Department of Community Affairs
FORM 40OD-97
Renovations & Systems Prescriptive Method ALL CLIMATE ZONES
Project Name:
Address: j Bi.lildingClassification: _
City, Zip Code: Building Permit No.:
Builder: Permitting Office:
Owner: Jurisdiction No.:
BUILDING INFORMATION
WALLS ROOF/CEILING FLOORS DOORS GLASS
TYPE U AREA TYPE. ' AREA TYPE U AREA TYPE U AREA TYPE U AREA
Concrete CBS Under Attic Slab -on- rade Wood Sin le, wall
Wood frame Single AssemblyRaised Wood Metal Double, wall
Metal frame Other: Raised Concrete Insulated Single, roof
Insulation R-value Insulation R-value Insulation R-value Other Double, roof
SYSTEMS INFORMATION
AIR CONDITIONER HEATING SYSTEM HOT WATER
TYPE EFFICIENCY" TONS TYPE EFFICIENCY BTU/H TYPE
Unitary & Heat Pump Central & Heat Pump Electric
65,000 Btu/h SEER 65,000 Btu/h HSPF Resistance
65,000 Btu/h EER IPLV 265,000 Btu/h COP Dedicated Heat Pump
Water cooled EER IPLV Water cooled COP Gas
Evaporatively cooled EER. Evaporatively cooled COP _ _, Natural
PTAC EER Electric Resistance COP LPG
Chiller COP IPLV Gas/Oil (circle one) HRU 1 I
Gas heat pump COP 225,000/300,000 Btu/h _ AFUE Other:
Other. 225,000/300,000 Btu/h _ Et —
LIGHTING Total Lighting Wattage r%. SIZING CALCULATION DUCTS R-value
Total Conditioned Floor Area,—. Watts/s A
n required)
Attached Location
PRESCRIPTIVE MEASURES (Must be met or exceeded by all buildings.)
Components Section Requirements Chec
O erations Manual 102.1 Operations manual will be provided to owner.
Windows 406.1 Maximum of .3 cfm per sq.ft. of window area.
Doors 406.1 Maximum of 1.2 cfm per sq.ft. of door area.
Joints/Cracks 406.1 To be caulked, gasketed, weatherstripped or otherwise sealed.
Reheat 407.1 Electric resistance reheat prohibited.
Ventilation 409.1 Supplied with,readily accessible switch for shut-off and/or volume reduction when ventilation is not required.
HVAC Efficiency 407.1, 408.1 Minimum efficiencies — Heating: Tables 4-7, 4-8, 4-9. Cooling: Tables 4-3, 4-4, 4-5, 4-6.
HVAC Controls 407.1 Separate readily accessible manual or automatic thermostat for each system.
HVAC Ducts 410.1 Air ducts, fittings, mechanical equipment and plenum chambers shall be mechanically attached, sealed, insulated
and installed in accordance with the criteria of section 410.1.
Balancing 410.1 HVAC distribution system(s) tested and balanced.
Piping Insulation 411.1 In accordance with Table 4-11.
Water Heaters 412.1 Automatic electric storage water heaters 15120 gallons and gas & oil fired storage water heaters <_75,000 Btu/h shall meet
performance requirements in Table 4-12. Electric >120 gallons: standby loss <.30+27NT. Gas >75,000, Oil >105,000: E, .78,
Standby loss15 1.30+114NT. Gas, Oil >155,000: E,78, Standby loss15 1.30+95NT. Swimming Pools
Spas 412.
1
Spas &heated pools must have covers. Non-commercial pools must have pump timer. Gas spa & pool heaters must have a
minimum thermal efficiency of 78%. Hot Water
Pipe Insulation 412.
1
Piping heat loss is limited to the levels in Table 4-11 for circulating systems and the first 8' of pipe from a storage tank. Water
Fixtures
412.1 Shower head water flow restricted to maximum of 2.5 gpm at 80 psi. Toilets meet 42CFR 6295(k). Public lavatory fixture maximum flow
of .5 gpm; or if self -closing valve, .25 gallon circulating, .5 gallon non -circulating. Lighting 415.
1 Ballasts shall have Power Factors no less than .90. t If required
by Florida la I r b ce i that he s esian i5 in com lac wit e F on od 99 ti N ARCHITECT:+/ ` 'i:/=/
1-- &/ ELECTRICAL SYSTEM
ESIGNER: X. LIGHTING
SYSTEM
DESIGNER: MECHANICAL SYSTEM
DESIGNER: PLUMBING SYSTEM
DESIGNER: I hereby
certify that the plans and specifications covered by the calculation are in compliance with the Review of plans and specifications covered by this calculation indicates compliance with Florida Energy
Code. the Florida Energy Code. Before construction is completed, this building will be inspected PREPARED BY:
DATE: for compliance
in accordance with Section 553.908, F.S. I hereby
certify that is b 1 /ys 9 ZIn vn the Flosrida/Energy ode. BUILDING OFFICIAL OWNER AGENT: /// //
A DATE / DATE:
1 FORM 400D-97 ALL CLIMATE ZONES
P •
yI
Building Component Efficiency Required Value Installed
Fenestrations:
Climate zones 1,2,3 U-0.87
Climate zones 4,5,6,7,8,9 7 SC (.61 SHGC)>1'0H'
55 SC (.48 SHGC) no OH
Wall:
Masonry
Climate zones 1,2,3
Climate zones 4,5,6,7,8,9
R-7 j„
R-5
Wood frame — all zones ,. R-11 ;
Metal frame — all zones R-13
Roof:
Built-up
Climate zones 1,2,3
Climate zones 4,5,6
R-16
R-1
Climate zones 7,8,9 R-12
Attic or Drop ceiling
All zones R-19
Floor:'
Slab -on -Grade
Raised Wood
R-0
R-19
Raised Concrete R-7
Infiltration Code minimums per f
sec. 406.1.ABCD.1
Cooling System Code minimums per
sec. 407.1.ABCD.3 l v
Heating System Code minimums per
sec. 408.1.ABCD.3
Ducts Code minimums per
sec. 410.1.ABCD.2
Piping Code minimums per
sec. 411.1.ABCD.1
Domestic Hot Water Code minimums per
sec.412.1.ABCD
i
Motors Code minimums per
sec. 413.1.ABCD
Lighting UPD: W/s.f. per Table 4-16
Controls:
1. Two banks per space with r
separate manual controls; or r% IL /
2. One occupancy
sensor per space (or other
automatic control)
1. Code minimums shall be met for components being retrofitted with new equipment.
2. Repairs to equipment need not meet Code and should not be construed to require a replacement of equipment.
3. Where existing components, such as ducts or electrical wiring, are utilized with a replacement system, such
existing components need not be replaced.
2.
I
FdRM-40013-97 ALL CLIMATE ZONES
Building Component Efficiency Required Value Installed
Fenestrations:
Climate zones 1,2,3 U-0.87
Climate zones 4,5,6,7,8,9 7 SC (.61 SHGC)>1"OH 17V55SC (.48 SHGC) no OH y (j
Wall:
Masonry
Climate zones 1,2,3
Climate zones 4,5,6,7,8,9
R-7
R-5
Wood frame — all zones R-11
Metal frame — all zones R-13
Roof:
Built-up
Climate zones 1,2,3
Climate zones 4,5,6
R-16
R-14'`
Climate zones 7,8,9 R-12
Attic or Drop ceiling
All zones R-19
Floor:
Slab -on -Grade R-0
Raised Wood R-19
Raised Concrete R-7
Infiltration Code minimums per.
sec. 406.1.ABCD.1
Cooling System Code minimums per
sec. 407.1.ABCD.3
Heating System Code minimums per
sec. 408.1.ABCD.3
Ducts Code minimums per
sec. 410.1.ABCD.2
Piping Code minimums per
sec. 411.1.ABCD.1
Domestic Hot Water Code minimums per
sec.412.1.ABCD c
Motors Code minimums per
I
sec.413.1.ABCD
Lighting UPD: W/s.f. per Table 4-16
Controls:
1. Two banks per space with topseparatemanualcontrols; or
2. One occupancy
sensor per space (or other
automatic control)
1. Code minimums shall be met for components being retrofitted with new equipment.
2. Repairs to equipment need not meet Code and should not be construed to require a replacement of equipment.
3. Where existing components, such as ducts or electrical wiring, are utilized with a replacement system, such
existing components need not be replaced.
2-
CITY OF SANFORD
FIRE DEPARTMENT
300 N. Park Ave.
Sanford, FL 32771
407) 302-1091 (407) 330-5677 FAX
Plans Review Sheet
Date: February 28, 2000 Business Address: 92 Red Cleveland BL.
Occ. Ch. #8 New Assembly
Business Name: Jerry's Restaurant Ph. 324-9681
Contractor: Mark Construction Ph.(407)831-6275
Reviewed [ ] Reviewed with comment [X ] Rejected []
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner
Comment: Will require all cooking equipment to meet N.F.P.A. #96 & N.F.P.A
58(Permit required for hood system and fire extinguishing system).
1.1 Application —New Assembly 500 sq ft tenant renovation.
1.2 Mixed — N/A
1.3 Special Definitions — N/N
1.4 Classification of Occupancy —(Assembly) Engineer shall confirm the occupancy
load for dinning eating.
1.5 Classification of Hazard of Contents — Shall meet sec 4-2 L.S.0 (Building will
continue be protected by automatic sprinkler system).
1.6 Minimum Construction — N/R
2.2 Means of Egress Components — O.K.
2.3 Capacity of Egress — O.K.
2.4 Number of Exits — O.K.
2.5 Arrangement of Egress —complies with sec 5-5 L.S.C.
2.6 Travel Distance — O.K. meets the minimal L.S.0
2.7 Discharge from Exits — O.K.
2.8 Illumination of Means of Egress — O.K.; will field verify
2.9 Emergency Lighting — O.K.; will field verify
2.10 Marking of Means of Egress— O.K.
2.11 Special Features — O.K.
3.1 Protection of Vertical Openings —Shall meet the requirements found in
N.F.P.A.#96(Roof penetration for hood system).
3.2 Protection from Hazards — N/N Auto Sprinkler System O.K.
3.3 Interior Finish — Shall meet sec 6-5 of the L.S.C.
3.4 Detection, Alarm and Communications Systems Provide continued coverage for
this tenant space. (This will require fire alarm to be tied into the hood extinguishing
system).-
3.5 Extinguishing Requirements — 40 B.C. Ratted fire extinguisher required in kitchen.
3.6 Corridors — N/R;
Special Provisions
5 Building Services
5.1 Utilities Gas appliances shall meet N.F.PA. #58
5.2 HVAC
5.3 Elevators, Escalators, Conveyors (4A-47)
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes
Sanford City Code — Chapter 9
Fire Sprinklers: Required; see 3.5 above
Monitoring:
Sprinkled properties
Other: NFPA 1
3-5.1 Fire Lanes —
3-6.1 Key Box —
3-7.1 Bldg.
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407 302-1022 / FAX (407) 330-5677
Pager (407) 918-0388
Plans Review Sheet
Date: 4/11/01 Business Address: # 2 Red Cleveland Blvd Occ. Ch. 8
Premium Passenger Lounge)
Business Name: Orlando — Sanford Airport Ph. (407) 324-9681
Contractor: Mark Construction Ph. (407) 831-6275
Reviewed [ ] Reviewed with comment [ X ] Rejected [ ]
Reviewed by: H. A. "Pete" Tucker, Fire Protection Inspector
Comment: Plans reviewed as Assembly Occupancy. FD reserves right to require applicable code
requirements if occupancy use changes. Alterations to Sprinkler and/or Fire Alarm systems
require plans to be submitted for review, permitting, and inspections.
1.1 Application — Interior renovation. Type IV Const. 4920 sq.ft.
1.2 Mixed — N/A
1.3 Special Definitions — N/N
1.4 Classification of Occupancy — Assembly
1.5 Classification of Hazard of Contents — Ordinary
1.6 Minimum Construction — N/R
2.2 Means of Egress Components — O.K.
2.3 Capacity of Egress — O.K.
2.4 Number of Exits — O.K.
2.5 Arrangement of Egress — O.K., will field verify
2.6 Travel Distance — O.K.
2.7 Discharge from Exits — O.K., will field verify
2.8 Illumination of Means of Egress — O.K.; will field verify
2.9 Emergency Lighting — O.K.; will field verify
2.10 Marking of Means of Egress — O.K.; will field verify
2.11 Special Features — N/A
1
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI. 32771 / P. O. Box 1788, Sanford, FI. 32772
407 302-1022 / FAX (407) 330-5677
Pager (407) 918-0388
3.1 Protection of Vertical Openings — N/N
3.2 Protection from Hazards — N/N
3.3 Interior Finish — Class "B"
3.4 Detection, Alarm, and Communications Systems — see comments
3.5 Extinguishing Requirements — as per NFPA 10
3.6 Corridors — O.K.
4 Special Provisions
5 Building Services
5.1 Utilities — as per LSC 7-1
5.2 HVAC — as per LSC 7-2
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes — N/A
Sanford City Code — Chapter 9
Fire Sprinklers: see comments
Monitoring: Required by a U.L. listed Central station for all mandated fire
sprinklered properties
Other: NFPA 1
3-5.1 Fire Lanes — N/A to renovation
3-6.1 Key Box — N/A to renovation
3-7.1 Bldg. Address Number Posted and Legible — N/A to renovation
2
le Building Performance Method for Commercial Buildings
ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Community Affairs
FLA/COM-94 Version 2.1A
Form 40OA-94
OJECT NAME WELCOME CENTER/SANFORD PERMITTING OFFICE:
DRESS: Red Clevland Blvd. r _SanfordOne
Sanford, Florida 32772 CLIMATE ZONE: 5
NER: SANFORD AIRPORT PERMIT NO: _0000
ENT: JURISDICTION NO:_691500
LDING TYPE: _Business (Office)
STRUCTION CONDITION: Existing Building
IGN COMPLETION: _Renovation
DITIONED FLOOR AREA: _16375
TONNAGE OF EQUIPMENT PER SYSTEM:
CE CALCULATION:
6
NUMBER OF ZONES: 6
ETHOD A DESIGN CRITERIA
WHOLE BUILDING 72.51 100.00
SCRIPTIVE REQUIREMENTS:
LIGHTING
EXTERIOR LIGHTING 26.00 100.00.
LIGHTING CONTROL REQUIREMENTS
HVAC EQUIPMENT
COOLING EQUIPMENT
1. SEER _. 10.25 10.00
2. SEER 10.05 10.00
3. SEER 10.20 10.00
4. SEER 10.05 10.00
5. EER 9.00 8.90
IPLV 9.00 8.30
6. SEER 10.05 10.00
HEATING EQUIPMENT
1. Et 1.00
2. Et 1.00
3. Et 1.00
4. Et 1.00
5. Et 1.00
6. Et 1.00
AIR DISTRIBUTION SYSTEM INSULATION LEVEL
1. With Insulated Roof 6.00 4.20
2. With Insulated Roof 6.00 4.20
3. With Insulated Roof 6.00 4.20
4. With Insulated Roof 6.00 4.20
5. With Insulated Roof 6.00 6.00
6. With Insulated Roof 6.00 6.00
WATER HEATING EQUIPMENT
1. EF 1.00 0.89
PIPING INSULATION REQUIREMENTS
1. Non -Circulating 1.00 0.56
RESULT
PASSES
PASSES
PASSES
PASSES
PASSES
PASSES
PASSES
PASSES
PASSES
PASSES
N/A
N/A.
N/A
N/A
N/A
N/A
PASSES
PASSES
PASSES
PASSES
PASSES
PASSES
PASSES
PASSES
i 1
COMPLIANCE CERTIFICATION:
I hereby certify that the plans and
specifications covered by this calcu-.
lation are in compliance with the
Florida Energy 57/4iency ode.
PREPARED BY:
DATE: i`% 97
I hereby certify that this building is
in compliance with the ;Florida Energy
Efficiency Code.
OWNER/AGENT:
DATE:
Review of the plans and specifica-
tions covered by this calculation
indicates compliance with the
Florida Energy Efficiency Code.
Before construction is completed,
this building will be inspected
for compliance in accordance with
Section 553.908, Florida Statutes.
BUILDING OFFICIAL:
DATE:
I hereby certify(*) that the system design is in compliance with the Florida
Energy Efficiency Code.
SYSTEM DESIGNER REGISTRATION/STATE
ARCHITECT : NPlcnn R1ankanshin 4rrhitart/Flnriria
MECHANICAL: M R Varrandn P F /Florida
PLUMBING :r,4gVe^ranrin P E ! Fa on da
ELECTRICAL: R Varrand, P F1 on da
LIGHTING
Signature is required where Florida law requires design to be pet -formed
by registered design professionals. Typed names and registration numbers may
be used where all relevant information is contained on signed/sealed plans.
BUILDING INFORMATION COMPLIANCE
CHECK
401.------GLAZING--ZONE 1---------------------------------------------v-
Elevation Type U SC VLT Shading Area(Sqft East
Commercial 1.31 1.00 1.00 None 40 Total
Glass Area in Zone 1 = 40 401.------
GLAZING--ZONE 2------------------ -----------------------(-q----
v-
Elevation
Type U SC VLT Shading Area S ft South
Commercial 1.31 1.00 1.00 None 40 Total
Glass Area in Zone 2 = 40 401--------
GLAZING --ZONE 3-------------------------------- ---------`-q----
v-
Elevation
Type U SC VLT Shading Area S ft South
Commercial 1.31 1.00 1.00 None 125 Total
Glass Area in Zone 3 = 125 401.------
GLAZING--ZONE 4------------------------------------------------ V- Elevation
Type U Sc VLT Shading Area(Sgft) North
Commercial 1.31 1.00 0.78 None 280 lEast
Commercial 1.31 1.00 0.78 None 60 South
Commercial 1.31 1.00 0.78 None 80 West
Commercial 1.31 1.00 0.78 None 100 Total
Glass Area in Zone 4 = 520 5-------------------------------------------------
v- i401.------
GLAZING--ZONE Elevation
Type U SC VLT Shading Area(Sgft) East
Commercial 1.31 1.00 0.78 None 285 West
Commercial 1.31 1.00 0.78 None 285 Total
Glass Area in Zone 5 = 57.0 401.------
GLAZING--ZONE 6------------------------------------------------ v- Elevation
Type U SC VLT Shading Area(Sgft) North
Commercial 1.31 1.00 0.78 None 0 Total
Glass Area in Zone 6 = 0 Total
Glass Area = 1295 402.------
WALLS--ZONE 1------------------------------------------------ Elevation
Type U Added R Gross(Sgft) East
Frame Wall + 3" InS. 0.081 11 375 South
Frame Wall + 3" InS. 0.081 11 219 Total
Wall Area in Zone 1 = 594 402.
WALLS --ZONE 2------------------------------------------------ Elevation
Type U Added R Gross(Sgft) South
Frame Wall + 3" InS. 0.081 11 288 Total
Wall Area in Zone 2 = 288 402 ------
WALLS--ZONE 3------------------------------------------------ Elevation
Type U Added R Gross(Sgft) South
Frame Wall + 3" InS. 0.081 11 442 Total
Wall Area in Zone 3 = 442 402-------
WALLS --ZONE 4------------------------------------------------ Elevation
Type U Added R Gross(Sgft) East
Frame Wall + 3" InS. 0.081 11 402
Type Color U Added R Area(Sgft)
Steel Sheet with 1" Insulation Medium 0.213 11 1834
Total Roof Area in Zone 3 = 1834
404.------ROOFS--ZONE 4------------------------------------------------
Type Color U Added R Area(Sgft)
Steel Sheet with i" Insulation Medium 0.213 11 9964
Total Roof Area in Zone 4 = 9964
404.------ROOFS--ZONE 5 -------------------
Color U Added R Area(Sgft)
Steel Sheet with 1" Insulation Medium 0.213 11 0
Total Roof Area in Zone 5 = 0
404.------ROOFS--ZONE 6 ------------------------------------------------
Type Color U Added R Area(Sgft)
Steel Sheet with i" Insulation Medium 0.213 11 0
Total Roof Area in Zone 6 = 0
Total Roof Area = 14196
405.------FLOORS-ZONE 1 ------------------------------------------------
Type R Area(Sgft)
Floor over Conditioned Space/Uninsulated 0 0
Total Floor Area in Zone 1 = 0
405.------FLOORS-ZONE 2------------------------------------------------
Type R Area (Sgft )
iFloor over Conditioned Space/Uninsulated 0 1319
Total Floor Area in Zone 2 = 1319
405.------FLOORS-ZONE 3 ------------------------------------------------
Type R Area(Sq
Floor over Conditioned Space/Uninsulated 0 1834
Total Floor Area in Zone 3 = 1834
405.------FLOORS-ZONE 4------------------------------------------------
Type R Area(Sgft)
Floor over Conditioned Space/Uninsulated 0 9964
Total F1oor.Area in Zone 4 = 9964
405.------FLOORS-ZONE 5------------------------------------ ------------
Type R Area(Sgft)
Floor over Unconditioned Space/Insulated 6.0 0
Total Floor Area in Zone 5 = 0
405.------FLOORS-ZONE 6------------------------------------------------
Type
R Area(Sgft)
Floor over Unconditioned Space/Insulated 4.0 668
Total Floor Area in Zone 6 = 668
Total Floor Area = 13785
406.------INFILTRATION --------------------------------------------------
ICHECKInfiltrationCriteriain406.1.ABC.1 have been met.
i 407.------COOLING SYSTEMS---------------------------------------------
Type No Efficiency IPLV Tons
1. Split System 1 10.25 10.25 4.88
2. Split System 1 10.05 10.05 2.97
3. Split System 1 10.20 10.20 3.58
4.. Split System 4 10.05 10.05 4.00
5. Air Cooled ( >= 65,000 Btu/h 1 9.0 9.0 5.83
6. Split System 1• 10.05 10.05 2.40
408.------HEATING SYSTEMS-----------------------------------------------
Type No Efficiency BTU/hr
1. Electric Resistance 1 1 41000
2. Electric Resistance 1 1 20500
3. Electric Resistance 1 1 20500
4. Electric Resistance 4 1 41000
5. Electric Resistance 1 1.0 41000
6. Electric Resistance 1 1.0 20500
409.------VENTILATION
CHECK
Ventilation Criteria in 409.1.ABC.1 have been met. I
410.-----AIR DISTRIBUTION SYSTEM ---------------------------------
AHU Type Duct Location R-value
1. Split / PTAC Air Conditioner With Insulated Roof 6
2. Split / PTAC Air Conditioner With Insulated Roof 6
3. Split / PTAC Air Conditioner With Insulated Roof 6.0
4. Split / PTAC Air Conditioner With Insulated Roof 6.0
5. Split / PTAC Air Conditioner With Insulated Roof 6
6. Split / PTAC Air Conditioner With Insulated Roof 6
411.-----PUMPS AND PIPING -ZONE 1----------------------------------------
Type R-value/in Diameter Thickness
1. Non -Circulating 0 0 0
411.-----PUMPS AND PIPING -ZONE 2 ---------------------------------------
Type
1. Circulating
411.-----PUMPS AND PIPING -ZONE
Type
1. Circulating
411.-----PUMPS AND PIPING -ZONE
Type
1. Non -Circulating
411.-----PUMPS AND PIPING -ZONE
Type
1. Circulating
411.-----PUMPS AND PIPING -ZONE
Type
1. Circulating
R-value/in Diameter Thickness
0 0 Cal
3 ---------------------------------------
R-value/in Diameter Thickness
0 0 0
4 ---------------------------------------
R-value/in Diameter Thickness
6.5 1 1
5 ---------------------------------------
R-value/in Diameter Thickness
0 0 0
6 ---------------------------------------
R-value/in Diameter Thickness
0 0 W
412.-----WATER HEATING SYSTEMS -ZONE 1 ----------------------------------
Type Efficiency StandbyLoss InputRate Gallons
412.-----WATER HEATING SYSTEMS -ZONE 2 ----------------------------------
Type Efficiency StandbyLoss InputRate Gallons
412.-----WATER HEATING SYSTEMS -ZONE 3 ----------------------------------
Type Efficiency StandbyLoss InputRate Gallons
412.-----WATER HEATING SYSTEMS -ZONE 4----------------------------------
Type Efficiency StandbyLoss InputRate Gallons
1. <=12 kW 1.. 0 0 6 30
412.-----WATER HEATING SYSTEMS -ZONE 5 ----------------------------------
Type Efficiency StandbyLoss InputRate Gallons
412.-----WATER HEATING SYSTEMS -ZONE 6----------------------------------
Type Efficiency StandbyLoss InputRate Gallons
413.-----ELECTRICAL POWER DISTRIBUTION----------------------------------
CHECKMeteringcriteriain413._l.ABC.1 have been met.
Transformer criteria in 413.1.ABC.2 have been met.
414.-----MOTORS ---------------------------------------------------
Motor efficiencies in 414.1.ABC.1 have been met.
415.-----LIGHTING SYSTEMS -ZONE 1 ---------------------------------
Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)
Reading, T 1 No visual task 8 No visual task 1 2440 1079
Total Watts for Zone 1 = 2440
Total Area for Zone 1 = 1079
SYSTEMS -ZONE 2 --------------------------------------- 415.-----LIGHTING
Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)
Reading, T 1 No visual task 13 None 0 4240 680
Toilet and 1 No visual task 4 None 0 1280 639
Total Watts for Zone 2 = 5520
Total Area for Zone 2 = 1319
415.-----LIGHTING SYSTEMS -ZONE 3 ---------------------------------------
Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)
Reception 1 No visual task 2 None 0 2040 1834
Total Watts for Zone 3 = 2040
Total Area for Zone 3 = 1834
415.-----LIGHTING SYSTEMS -ZONE 4 ---------------------------------------
Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)
Reception 1 No visual task 4 None . 0 5880 9964
Total Watts for Zone 4 = 5880
Total Area for Zone 4 = 9964
415.-----LIGHTING SYSTEMS -ZONE 5---------------------------------------
Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)
Corridor 1 No visual task 2 None 0 2160 1511
Total Watts for Zone 5 = 2160
Total Area for Zone 5 = 1511
415.-----LIGHTING SYSTEMS -ZONE 6---------------------------------------
Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft)
Toilet and 1 No visual task 1 None 0 1440 668
Total Watts for Zone 6 = 1440
Total Area for Zone 6 = 668
Total Watts = 19480
Total Area = 16375
Lighting criteria in 415.1.ABC have been met.
CHECK
v-
116. HVAC load sizing has been performed. (407.1.ABC.1) f
1-1-7.---D-u-ct-sizing--and--design-have--been-perf-o-r-m-d.-e(410_1_ABC_1_2)--- - - ---
i----
i18. Testing and balancing will be performed. (410.1.ABC.4)
19. Operation/maintenance manual will be provided to owner.(102.1)
A
s
CITY OF SANFO, RD
r4 FIRE DEPARTMENT
1303 South French Avenue
v
Sanford, Florida 32771
407) 302-1091 (407) 302-1097 FAX ,,
Plans Review Sheet
Date: April 13, 1999 Business Address: 2 Red Cleveland Occ. Chap. 8
Business Name: Orlando Sanford Airport Ph.
Contractor: Mark Construction Ph. 831-6275
Reviewed [ ] Reviewed with comment [ X ] Rejected [
Reviewed by: Bart Wright, Fire Protection Inspector
Comment: Cover page errors: wrong edition of LSC (should be 1994); occupant load notes figure
based on gross square footage (should be net square footage); wrong notation regarding sprinkler
requirement (should note required and provided for existing system)
f
1.1 Application — addition to an existing assembly airport passenger terminal
1.2 Mixed - N/A
1.3 Special Definitions - N/A
1.4 Classification of Occupancy - Ordinary
Sub -classification: Class "A" > 1,000
1.5 Classification of Hazard of Contents - Ordinary
1.6 Minimum Construction — Applicant submitted type IV u.p. SBCCI; type 11(000) NFPA
1.7 Occupant Load — for addition only 3750 sq. ft.: 15 = 250
2.2 Means of Egress Components - O.K.
2.3 Capacity of Egress - O.K.
2.4 Number of Exits - O.K.
2.5 Arrangement of Egress - O.K.
2.6 Travel Distance - O.K.
2.7 Discharge from Exits - O.K.
2.8 Illumination of Means of Egress - O.K.
2.9 Emergency Lighting - O.K.; will field verify
i 2.10 Marking of Means of Egress - O.K. for all uses; will field verify
2.11 Special Features -None noted
3.1 Protection of Vertical Openings —None noted
3.2 Protection from Hazards — N/A
3.3 Interior Finish - Class "B"
3.4 Detection, alarm and Communications Systems — N/R
3.5 Extinguishing Requirements — N/R
3.6 Corridors - N/A
4 Special Provisions - None noted
5 Building Services - No comment
5.1 Utilities
5.2 HVAC
5.3 Elevators, Escalators, Conveyors (4A-47)
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes
Sanford City Code - Chapter 9
Fire Sprinklers: Required and provided; see cover page note
Monitoring: Required by a U.L. listed central station company
Other: NFPA 1
3-5.1 Fire Lanes — N/A for addition
3-6.1 Key Box — N/A for addition
3-7.1 Bldg. Address Number Posted and Legible — N/A for addition
DATE: January 8, .2001
TO: Building Official
FROM: Utility Director f i
RE: Wiginton Fire Sprinklers Inc. Plans
Jerry's Restaurant - Sanford Airport
Dan -
I have reviewed the above referenced plans. The plans show a tie in to the city
line to be done by Wiginton. The Utility Department needs to see details on this
connection with appropriate materials. A City inspector needs to witness the tap.
A minimum of forty-eight (48) hours notice is needed to schedule inspections.
Thank You.
PM/ap