HomeMy WebLinkAbout2 Red Cleveland Blvd Plans fire inspection Jerry's restaurantr , CITY OF SANFORD FIRE DEPARTMENT 300 N. Park Ave. Sanford, FL 32771 407) 302-1091 (407) 330-5677 FAX Plans Review Sheet Date: December 21, 1999 Business Address 2RedCleueianel Occ. Ch. 8 Business Name: O.S.I. Ph. Contractor: Mark Construction Ph. (407) 831-6275 Reviewed [ ] Reulewedwithcornrrrent [ X} Rejected Reviewed by: Bart Wright, Fire Protection Inspecto Comment: Review based in part on 12/21/1999 letter (attached) from Nelson Blankenship 1.1 Application — Renovation to assembly occupancy 1.2 Mixed — N/A 1.3 Special Definitions — N/N 1.4 Classification of Occupancy — Assembly; # sq. ft. 3750 1.5 Classification of Hazard of Contents Ordinary 1.6 Minimum Construction — N/R 1.7 Occupant Load — 1/15 sq. ft. = 250 2.2 Means of Egress Components — O.K. 2.3 Capacity of Egress — O.K. 2.4 Number of Exits — O.K. 2.5 Arrangement of Egress — O.K., 2.6 Travel Distance — O.K. 2.7 Discharge from Exits — O.K. 2.8 Illumination of Means of Egress — O.K.; will field verify 2.9 Emergency Lighting — O.K.; will field verify 2.10 Marking of Means of Egress — O.K. 2.11 Special Features — O.K. 3.1 Protection of Vertical Openings — N/N 3.3 Interior Finish — Class "C" 3.6 Corridors — N/A 4 Special Provisions 5 Building Services 5.1 Utilities 5.2 HVAC 5.3 Elevators, Escalators, Conveyors (4A-47) 5.4 Rubbish Chutes, Incinerators, and Laundry Chutes Sanford City Code — Chapter 9 Fire Sprinklers: See 3.5 above Monitoring: Required for all mandated fire sprinklered properties Other: NFPA 1 3-5.1 Fire Lanes — Required if building is more than 150' from street; exception: building has fire sprinkler system. 3-6.1 Key Box - N/A 3-7.1 Bldg. Address Number Posted and Legible — Required; will field verify Dec-21-99 11:47A BLANKENSHIP MCMILLEN 407-599-0548 P.01 BLANKENSHIP McMILLEN 330 Crown Oak Centre Drive Longwood Florida 32750.6149 4O7. j99.0547 Fax 407.599.0548 AAOt)03290 December`21, 1999 Larry Flynn Mark Construction. Company 1969 Corporate .Square Drive Longwood, Florida 32750 Re: Sanford Fire -Department fax dated 12-20-9.9 Welcome Center Addition #3 Dear Mr. Flynn Discrepancy in area: New Area Northern (enclosed -including 9117) 1,794sf Southern (enclosed including #103) 1 734sf Subtotal (rounded) 3,550sf Existing Area Booths 576sf Total .4126sf e Classification is "Assembly" in spaces 103 and 117. e Cc.cupants: @ 15sf/person, North or South equals 120 persons maxi. 120 people x 0.2 = 24..inches required .exit width Provided for North and South space -each: ,4 .36 leaves =,144 inches all other doors are 36". o Ramp is 48" long to accommodate the 4" change in elevation "from 100'-0" on the main floor to 100'-4"for the food prep space car rentals and booths. a Equi.pm.ent ,in the food prep .area #110 will be identified by another tenant improvement permit, which Js to follow. The equipment in the food. prep work area will be similar to the ,3elway Cafe across the street. Dec-21-99 11:47A BLANKENSHIP MCMILLEN 407-599-0548 P.O2 1 c1 y Response to-.Sanford's fax 12-20-99 Welcome Center #3 Page 2 e Sprinkler:. information will required .by lWiginton. Awning willbe made with curved gypsum board on studs. It will not be canvas. The soffit under the awning will be a linear ceiling at 45 degrees as shown on the drawings. Hope this answers Mr. Wright's questions. If there needs to be any more explanation, please call. Sincerely, Nelson Blankenship, Jr. AIA Principle Cc: Bart Wright via fax 407.330.5677 FLORIDA ENERGY EFFICIENCY CODE FOR 3UILDING CONSTRUCTION CHAPTER 4 — Commercial Buildill-, C,,'mpli,ance Methods FORM 40OD-97 Administered by the Departmant nF Community Affairs renovations & Systems Prescriptive Method ALL CLIMATE ZONESrenovations 4 F Na_ me: NBuildingZone: i6dress: - ,/7 Classification: (":". City; Zip Co e: Building Permit No.: Permitting Office: Builder: Owner: Jurisdiction No.: BUILDING INFORMATION WALLS ROOF/CEILING FLOORS DOORS GLASS TYPE U I AREA TYPEU ARE TYPE U AREA TYPE U AREA TYPE U AREA Concrete CBS Under Attic i Slab -on -grade Wood Sin le wall Wood frame Sin le Assembly Raised Wood i Metal Double, wall Metal frame Other: Raised Concrete Insulated Single, roof Insulation R-value Insulation R-value Insulation R-value Other Double, roof SYSTEMS INFORMATION AIR CONDITIONER. HEATING SYSTEM HOT WATER TYPE EFFICIENCY TONS TYPE EFFICIENCY BTU/H TYPE Unitary & Heat Pump Central & Heat Pump Electric 65, 000 Btu/h SEER 65,000 Btu/h HSPF Resistance 65, 000 Btu/h EER _ IPLV 65,000 Btu/h COP Dedicated Heat Pump Water cooled EER _ IPLV Water cooled COP /y, Gas Evaporatively cooled EER Evaporatively cooled COPil Natural PTAC EER Electric Resistance COP /i,-rr LPG Chiller COP _IPLV Gas/Oil (circle one) HRU Gas heat pump COP 225,000/300,000 Btu/h _ AFUE Other: Other. 225,000/300,000 Btu/h _ Et — LIGHTING Total Lighting Wattage i SIZING CALCULATION DUCTS R-value Total Conditioned Floor Area lavrEeIZ Watts/s .ft. B required) Attached Location PRESCRIPTIVE MEASURES (Must be met or exceeded by all buildings.) Components Section Requirements Chec O erations Manual 102.1 Operations manual will be provided to owner. Windows 406.1 Maximum of .3 cfm per sq.ft. of window area. Doors 406.1 Maximum of.1:2 cfm per sq.ft. of door area. Joints/ Cracks 406.1 To be caulked, gasketed, weatherstripped or otherwise sealed. Reheat 407.1 Electric resistance reheat prohibited. Ventilation 409.1 Supplied with readily accessible switch for shut-off and/or volume reduction when ventilation is not required. HVAC Efficiency 407.1, 408.1 Minimum efficiencies— Heating: Tables 4-7, 4-8, 4-9. Cooling: Tables 4-3, 4-4, 4-5, 4-6. HVAC Controls 407.1 Separate readily accessible manual or automatic thermostat for each system. HVAC Ducts 410.1 Air ducts, fittings, mechanical equipment and plenum chambers shall be mechanically attached, sealed, insulated and installed in accordance with the criteria of section 410.1. Balancing 410.1 HVAC distribution system(s) tested and balanced. Piping Insulation 411.1 In accordance with Table 4-11. Water Heaters 412.1 Automatic electric storage water heaters 5120 gallons and gas & oil fired storage water heaters 575,000 Btu/h shall meet performance requirements in Table 4-12. Electric >120 gallons: standby loss <_.30+27NT. Gas >75,000, Oil >105,000: E, .78, Standby loss15 1.30+114NT. Gas, Oil >155,000: E.78, Standby loss <_ 1.30+95NT. L Swimming Pools Spas 412. 1 Spas & heated pools must have covers. Non-commercial pools must have pump timer. Gas spa & pool heaters must have a minimum thermal efficiency of 78%. LI X LL y!' j Hot Water Pipe Insulation 412. 1 Piping heat loss is limited to the levels in Table 4-11 for circulating systems and the first 8' of pipe from a storage tank. Water Fixtures 412.1 Shower head water flow restricted to maximum of 2.5 gpm at 80 psi. Toilets meet 42CFR 6295(k). Public lavatory fixture maximum flow of .5 gpm; or if self -closing valve, .25 gallon circulating, .5 gallon non -circulating. Lighting 415. 1 Ballasts shall have Power Factors no less than .90. Code. ARCHITECT: juWaf2iV= ELECTRICAL SYSTEM DESIGNE - LIGHTING SYSTEM DESIGNER: MECHANICAL SYSTEM DESIGNER: PLUMBING SYSTEM DESIGNER: I hereby certify that the plans and specifications covered by the calculation are incompliance with the Review of plans and specifications covered by this calculation indicates compliance with Florida Energy Code. the Florida Energy Code. Before construction is completed, this building will be inspected PREPARED BY- DATE: _ for compliance in accordance with Section 553.908, F.S. I hereby certify that ' ui ,rR i/sy' n e th a Florida Energy Code. / BUILDING OFFICIAL OWNER AGENT: ! o %, f DJ/IrI DATE: d . FORM 40OD-97 stalled ALL CLIMATE ZONES, i Building Component Efficiency Required Value In 1. Code minimums shall be met for components being retrofitted with new equipment. 2. Repairs to equipment need not meet Code and should not be construed to require a replacement of equipment. 3. Where existing components, such as ducts or electrical wiring, are utilized with a replacement system, such existing components need not be replaced. ALL CLIMATE ZONES r— - FORM 40OD-97 r e Building Component Efficiency Required Value Installed Fenestrations: Climate zones 1,2,3 U-0.67 Climate zones 4,5,6,7,8,9 7 SC (.61 SHGC)>1'OH 55 SC .48 SHGC no OH Wall: Masonry , Climate zones 1,2,3 Climate zones 4,5,6,7,8,9 R-7 R-5 Wood frame — all zones R 11 Metal frame — all zones R-13 Roof: Built-up Climate zones 1,2,3 Climate zones 4,5,6 R-16 R-14 Climate zones 7,8,9 R-12 Attic or Drop ceiling All zones R-19 Floor: Slab-oRased Grade Raised Wood R- R-19 Raised Concrete R-7 Infiltration Code minimums per sec.406.1.ABCD.1 Cooling System Code minimums per sec. 407.1.ABCD.3 l v Heating System Code minimums per sec. 408.1.ABCD.3 Ducts Code minimums per sec. 410.1.ABCD.2 wz' Piping Code minimums per f sec. 411.1.ABCD.1 Domestic Hot Water Code minimums per sec.412.1.ABCDJ/ y Motors Code minimums per sec. 413.1.ABCD Lighting UPD: W/s.f. per Table 4-16 Controls: 1. Two banks per space with r separate manual controls; or 2.One occupancy sensor per space (or other automatic control) i 1. Code minimums shall be met for components being retrofitted with new equipment. 2. Repairs to equipment need not meet Code and should not be construed to require a replacement of equipment. 3. Where existing components, such as ducts or electrical wiring, are utilized with a replacement system, such existing components need not be replaced. 2. a FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION CHAPTER 4 — Commercial Building Compliance Methods Administered by the Department of Community Affairs FORM 40OD-97 Renovations & Systems Prescriptive Method ALL CLIMATE ZONES Project Name: Address: j Bi.lildingClassification: _ City, Zip Code: Building Permit No.: Builder: Permitting Office: Owner: Jurisdiction No.: BUILDING INFORMATION WALLS ROOF/CEILING FLOORS DOORS GLASS TYPE U AREA TYPE. ' AREA TYPE U AREA TYPE U AREA TYPE U AREA Concrete CBS Under Attic Slab -on- rade Wood Sin le, wall Wood frame Single AssemblyRaised Wood Metal Double, wall Metal frame Other: Raised Concrete Insulated Single, roof Insulation R-value Insulation R-value Insulation R-value Other Double, roof SYSTEMS INFORMATION AIR CONDITIONER HEATING SYSTEM HOT WATER TYPE EFFICIENCY" TONS TYPE EFFICIENCY BTU/H TYPE Unitary & Heat Pump Central & Heat Pump Electric 65,000 Btu/h SEER 65,000 Btu/h HSPF Resistance 65,000 Btu/h EER IPLV 265,000 Btu/h COP Dedicated Heat Pump Water cooled EER IPLV Water cooled COP Gas Evaporatively cooled EER. Evaporatively cooled COP _ _, Natural PTAC EER Electric Resistance COP LPG Chiller COP IPLV Gas/Oil (circle one) HRU 1 I Gas heat pump COP 225,000/300,000 Btu/h _ AFUE Other: Other. 225,000/300,000 Btu/h _ Et — LIGHTING Total Lighting Wattage r%. SIZING CALCULATION DUCTS R-value Total Conditioned Floor Area,—. Watts/s A n required) Attached Location PRESCRIPTIVE MEASURES (Must be met or exceeded by all buildings.) Components Section Requirements Chec O erations Manual 102.1 Operations manual will be provided to owner. Windows 406.1 Maximum of .3 cfm per sq.ft. of window area. Doors 406.1 Maximum of 1.2 cfm per sq.ft. of door area. Joints/Cracks 406.1 To be caulked, gasketed, weatherstripped or otherwise sealed. Reheat 407.1 Electric resistance reheat prohibited. Ventilation 409.1 Supplied with,readily accessible switch for shut-off and/or volume reduction when ventilation is not required. HVAC Efficiency 407.1, 408.1 Minimum efficiencies — Heating: Tables 4-7, 4-8, 4-9. Cooling: Tables 4-3, 4-4, 4-5, 4-6. HVAC Controls 407.1 Separate readily accessible manual or automatic thermostat for each system. HVAC Ducts 410.1 Air ducts, fittings, mechanical equipment and plenum chambers shall be mechanically attached, sealed, insulated and installed in accordance with the criteria of section 410.1. Balancing 410.1 HVAC distribution system(s) tested and balanced. Piping Insulation 411.1 In accordance with Table 4-11. Water Heaters 412.1 Automatic electric storage water heaters 15120 gallons and gas & oil fired storage water heaters <_75,000 Btu/h shall meet performance requirements in Table 4-12. Electric >120 gallons: standby loss <.30+27NT. Gas >75,000, Oil >105,000: E, .78, Standby loss15 1.30+114NT. Gas, Oil >155,000: E,78, Standby loss15 1.30+95NT. Swimming Pools Spas 412. 1 Spas &heated pools must have covers. Non-commercial pools must have pump timer. Gas spa & pool heaters must have a minimum thermal efficiency of 78%. Hot Water Pipe Insulation 412. 1 Piping heat loss is limited to the levels in Table 4-11 for circulating systems and the first 8' of pipe from a storage tank. Water Fixtures 412.1 Shower head water flow restricted to maximum of 2.5 gpm at 80 psi. Toilets meet 42CFR 6295(k). Public lavatory fixture maximum flow of .5 gpm; or if self -closing valve, .25 gallon circulating, .5 gallon non -circulating. Lighting 415. 1 Ballasts shall have Power Factors no less than .90. t If required by Florida la I r b ce i that he s esian i5 in com lac wit e F on od 99 ti N ARCHITECT:+/ ` 'i:/=/ 1-- &/ ELECTRICAL SYSTEM ESIGNER: X. LIGHTING SYSTEM DESIGNER: MECHANICAL SYSTEM DESIGNER: PLUMBING SYSTEM DESIGNER: I hereby certify that the plans and specifications covered by the calculation are in compliance with the Review of plans and specifications covered by this calculation indicates compliance with Florida Energy Code. the Florida Energy Code. Before construction is completed, this building will be inspected PREPARED BY: DATE: for compliance in accordance with Section 553.908, F.S. I hereby certify that is b 1 /ys 9 ZIn vn the Flosrida/Energy ode. BUILDING OFFICIAL OWNER AGENT: /// // A DATE / DATE: 1 FORM 400D-97 ALL CLIMATE ZONES P • yI Building Component Efficiency Required Value Installed Fenestrations: Climate zones 1,2,3 U-0.87 Climate zones 4,5,6,7,8,9 7 SC (.61 SHGC)>1'0H' 55 SC (.48 SHGC) no OH Wall: Masonry Climate zones 1,2,3 Climate zones 4,5,6,7,8,9 R-7 j„ R-5 Wood frame — all zones ,. R-11 ; Metal frame — all zones R-13 Roof: Built-up Climate zones 1,2,3 Climate zones 4,5,6 R-16 R-1 Climate zones 7,8,9 R-12 Attic or Drop ceiling All zones R-19 Floor:' Slab -on -Grade Raised Wood R-0 R-19 Raised Concrete R-7 Infiltration Code minimums per f sec. 406.1.ABCD.1 Cooling System Code minimums per sec. 407.1.ABCD.3 l v Heating System Code minimums per sec. 408.1.ABCD.3 Ducts Code minimums per sec. 410.1.ABCD.2 Piping Code minimums per sec. 411.1.ABCD.1 Domestic Hot Water Code minimums per sec.412.1.ABCD i Motors Code minimums per sec. 413.1.ABCD Lighting UPD: W/s.f. per Table 4-16 Controls: 1. Two banks per space with r separate manual controls; or r% IL / 2. One occupancy sensor per space (or other automatic control) 1. Code minimums shall be met for components being retrofitted with new equipment. 2. Repairs to equipment need not meet Code and should not be construed to require a replacement of equipment. 3. Where existing components, such as ducts or electrical wiring, are utilized with a replacement system, such existing components need not be replaced. 2. I FdRM-40013-97 ALL CLIMATE ZONES Building Component Efficiency Required Value Installed Fenestrations: Climate zones 1,2,3 U-0.87 Climate zones 4,5,6,7,8,9 7 SC (.61 SHGC)>1"OH 17V55SC (.48 SHGC) no OH y (j Wall: Masonry Climate zones 1,2,3 Climate zones 4,5,6,7,8,9 R-7 R-5 Wood frame — all zones R-11 Metal frame — all zones R-13 Roof: Built-up Climate zones 1,2,3 Climate zones 4,5,6 R-16 R-14'` Climate zones 7,8,9 R-12 Attic or Drop ceiling All zones R-19 Floor: Slab -on -Grade R-0 Raised Wood R-19 Raised Concrete R-7 Infiltration Code minimums per. sec. 406.1.ABCD.1 Cooling System Code minimums per sec. 407.1.ABCD.3 Heating System Code minimums per sec. 408.1.ABCD.3 Ducts Code minimums per sec. 410.1.ABCD.2 Piping Code minimums per sec. 411.1.ABCD.1 Domestic Hot Water Code minimums per sec.412.1.ABCD c Motors Code minimums per I sec.413.1.ABCD Lighting UPD: W/s.f. per Table 4-16 Controls: 1. Two banks per space with topseparatemanualcontrols; or 2. One occupancy sensor per space (or other automatic control) 1. Code minimums shall be met for components being retrofitted with new equipment. 2. Repairs to equipment need not meet Code and should not be construed to require a replacement of equipment. 3. Where existing components, such as ducts or electrical wiring, are utilized with a replacement system, such existing components need not be replaced. 2- CITY OF SANFORD FIRE DEPARTMENT 300 N. Park Ave. Sanford, FL 32771 407) 302-1091 (407) 330-5677 FAX Plans Review Sheet Date: February 28, 2000 Business Address: 92 Red Cleveland BL. Occ. Ch. #8 New Assembly Business Name: Jerry's Restaurant Ph. 324-9681 Contractor: Mark Construction Ph.(407)831-6275 Reviewed [ ] Reviewed with comment [X ] Rejected [] Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner Comment: Will require all cooking equipment to meet N.F.P.A. #96 & N.F.P.A 58(Permit required for hood system and fire extinguishing system). 1.1 Application —New Assembly 500 sq ft tenant renovation. 1.2 Mixed — N/A 1.3 Special Definitions — N/N 1.4 Classification of Occupancy —(Assembly) Engineer shall confirm the occupancy load for dinning eating. 1.5 Classification of Hazard of Contents — Shall meet sec 4-2 L.S.0 (Building will continue be protected by automatic sprinkler system). 1.6 Minimum Construction — N/R 2.2 Means of Egress Components — O.K. 2.3 Capacity of Egress — O.K. 2.4 Number of Exits — O.K. 2.5 Arrangement of Egress —complies with sec 5-5 L.S.C. 2.6 Travel Distance — O.K. meets the minimal L.S.0 2.7 Discharge from Exits — O.K. 2.8 Illumination of Means of Egress — O.K.; will field verify 2.9 Emergency Lighting — O.K.; will field verify 2.10 Marking of Means of Egress— O.K. 2.11 Special Features — O.K. 3.1 Protection of Vertical Openings —Shall meet the requirements found in N.F.P.A.#96(Roof penetration for hood system). 3.2 Protection from Hazards — N/N Auto Sprinkler System O.K. 3.3 Interior Finish — Shall meet sec 6-5 of the L.S.C. 3.4 Detection, Alarm and Communications Systems Provide continued coverage for this tenant space. (This will require fire alarm to be tied into the hood extinguishing system).- 3.5 Extinguishing Requirements — 40 B.C. Ratted fire extinguisher required in kitchen. 3.6 Corridors — N/R; Special Provisions 5 Building Services 5.1 Utilities Gas appliances shall meet N.F.PA. #58 5.2 HVAC 5.3 Elevators, Escalators, Conveyors (4A-47) 5.4 Rubbish Chutes, Incinerators, and Laundry Chutes Sanford City Code — Chapter 9 Fire Sprinklers: Required; see 3.5 above Monitoring: Sprinkled properties Other: NFPA 1 3-5.1 Fire Lanes — 3-6.1 Key Box — 3-7.1 Bldg. SANFORD FIRE DEPARTMENT FIRE PREVENTION DIVISION 300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772 407 302-1022 / FAX (407) 330-5677 Pager (407) 918-0388 Plans Review Sheet Date: 4/11/01 Business Address: # 2 Red Cleveland Blvd Occ. Ch. 8 Premium Passenger Lounge) Business Name: Orlando — Sanford Airport Ph. (407) 324-9681 Contractor: Mark Construction Ph. (407) 831-6275 Reviewed [ ] Reviewed with comment [ X ] Rejected [ ] Reviewed by: H. A. "Pete" Tucker, Fire Protection Inspector Comment: Plans reviewed as Assembly Occupancy. FD reserves right to require applicable code requirements if occupancy use changes. Alterations to Sprinkler and/or Fire Alarm systems require plans to be submitted for review, permitting, and inspections. 1.1 Application — Interior renovation. Type IV Const. 4920 sq.ft. 1.2 Mixed — N/A 1.3 Special Definitions — N/N 1.4 Classification of Occupancy — Assembly 1.5 Classification of Hazard of Contents — Ordinary 1.6 Minimum Construction — N/R 2.2 Means of Egress Components — O.K. 2.3 Capacity of Egress — O.K. 2.4 Number of Exits — O.K. 2.5 Arrangement of Egress — O.K., will field verify 2.6 Travel Distance — O.K. 2.7 Discharge from Exits — O.K., will field verify 2.8 Illumination of Means of Egress — O.K.; will field verify 2.9 Emergency Lighting — O.K.; will field verify 2.10 Marking of Means of Egress — O.K.; will field verify 2.11 Special Features — N/A 1 SANFORD FIRE DEPARTMENT FIRE PREVENTION DIVISION 300 N. Park Ave., Sanford, FI. 32771 / P. O. Box 1788, Sanford, FI. 32772 407 302-1022 / FAX (407) 330-5677 Pager (407) 918-0388 3.1 Protection of Vertical Openings — N/N 3.2 Protection from Hazards — N/N 3.3 Interior Finish — Class "B" 3.4 Detection, Alarm, and Communications Systems — see comments 3.5 Extinguishing Requirements — as per NFPA 10 3.6 Corridors — O.K. 4 Special Provisions 5 Building Services 5.1 Utilities — as per LSC 7-1 5.2 HVAC — as per LSC 7-2 5.3 Elevators, Escalators, Conveyors (4A-47) — N/A 5.4 Rubbish Chutes, Incinerators, and Laundry Chutes — N/A Sanford City Code — Chapter 9 Fire Sprinklers: see comments Monitoring: Required by a U.L. listed Central station for all mandated fire sprinklered properties Other: NFPA 1 3-5.1 Fire Lanes — N/A to renovation 3-6.1 Key Box — N/A to renovation 3-7.1 Bldg. Address Number Posted and Legible — N/A to renovation 2 le Building Performance Method for Commercial Buildings ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Community Affairs FLA/COM-94 Version 2.1A Form 40OA-94 OJECT NAME WELCOME CENTER/SANFORD PERMITTING OFFICE: DRESS: Red Clevland Blvd. r _SanfordOne Sanford, Florida 32772 CLIMATE ZONE: 5 NER: SANFORD AIRPORT PERMIT NO: _0000 ENT: JURISDICTION NO:_691500 LDING TYPE: _Business (Office) STRUCTION CONDITION: Existing Building IGN COMPLETION: _Renovation DITIONED FLOOR AREA: _16375 TONNAGE OF EQUIPMENT PER SYSTEM: CE CALCULATION: 6 NUMBER OF ZONES: 6 ETHOD A DESIGN CRITERIA WHOLE BUILDING 72.51 100.00 SCRIPTIVE REQUIREMENTS: LIGHTING EXTERIOR LIGHTING 26.00 100.00. LIGHTING CONTROL REQUIREMENTS HVAC EQUIPMENT COOLING EQUIPMENT 1. SEER _. 10.25 10.00 2. SEER 10.05 10.00 3. SEER 10.20 10.00 4. SEER 10.05 10.00 5. EER 9.00 8.90 IPLV 9.00 8.30 6. SEER 10.05 10.00 HEATING EQUIPMENT 1. Et 1.00 2. Et 1.00 3. Et 1.00 4. Et 1.00 5. Et 1.00 6. Et 1.00 AIR DISTRIBUTION SYSTEM INSULATION LEVEL 1. With Insulated Roof 6.00 4.20 2. With Insulated Roof 6.00 4.20 3. With Insulated Roof 6.00 4.20 4. With Insulated Roof 6.00 4.20 5. With Insulated Roof 6.00 6.00 6. With Insulated Roof 6.00 6.00 WATER HEATING EQUIPMENT 1. EF 1.00 0.89 PIPING INSULATION REQUIREMENTS 1. Non -Circulating 1.00 0.56 RESULT PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES N/A N/A. N/A N/A N/A N/A PASSES PASSES PASSES PASSES PASSES PASSES PASSES PASSES i 1 COMPLIANCE CERTIFICATION: I hereby certify that the plans and specifications covered by this calcu-. lation are in compliance with the Florida Energy 57/4iency ode. PREPARED BY: DATE: i`% 97 I hereby certify that this building is in compliance with the ;Florida Energy Efficiency Code. OWNER/AGENT: DATE: Review of the plans and specifica- tions covered by this calculation indicates compliance with the Florida Energy Efficiency Code. Before construction is completed, this building will be inspected for compliance in accordance with Section 553.908, Florida Statutes. BUILDING OFFICIAL: DATE: I hereby certify(*) that the system design is in compliance with the Florida Energy Efficiency Code. SYSTEM DESIGNER REGISTRATION/STATE ARCHITECT : NPlcnn R1ankanshin 4rrhitart/Flnriria MECHANICAL: M R Varrandn P F /Florida PLUMBING :r,4gVe^ranrin P E ! Fa on da ELECTRICAL: R Varrand, P F1 on da LIGHTING Signature is required where Florida law requires design to be pet -formed by registered design professionals. Typed names and registration numbers may be used where all relevant information is contained on signed/sealed plans. BUILDING INFORMATION COMPLIANCE CHECK 401.------GLAZING--ZONE 1---------------------------------------------v- Elevation Type U SC VLT Shading Area(Sqft East Commercial 1.31 1.00 1.00 None 40 Total Glass Area in Zone 1 = 40 401.------ GLAZING--ZONE 2------------------ -----------------------(-q---- v- Elevation Type U SC VLT Shading Area S ft South Commercial 1.31 1.00 1.00 None 40 Total Glass Area in Zone 2 = 40 401-------- GLAZING --ZONE 3-------------------------------- ---------`-q---- v- Elevation Type U SC VLT Shading Area S ft South Commercial 1.31 1.00 1.00 None 125 Total Glass Area in Zone 3 = 125 401.------ GLAZING--ZONE 4------------------------------------------------ V- Elevation Type U Sc VLT Shading Area(Sgft) North Commercial 1.31 1.00 0.78 None 280 lEast Commercial 1.31 1.00 0.78 None 60 South Commercial 1.31 1.00 0.78 None 80 West Commercial 1.31 1.00 0.78 None 100 Total Glass Area in Zone 4 = 520 5------------------------------------------------- v- i401.------ GLAZING--ZONE Elevation Type U SC VLT Shading Area(Sgft) East Commercial 1.31 1.00 0.78 None 285 West Commercial 1.31 1.00 0.78 None 285 Total Glass Area in Zone 5 = 57.0 401.------ GLAZING--ZONE 6------------------------------------------------ v- Elevation Type U SC VLT Shading Area(Sgft) North Commercial 1.31 1.00 0.78 None 0 Total Glass Area in Zone 6 = 0 Total Glass Area = 1295 402.------ WALLS--ZONE 1------------------------------------------------ Elevation Type U Added R Gross(Sgft) East Frame Wall + 3" InS. 0.081 11 375 South Frame Wall + 3" InS. 0.081 11 219 Total Wall Area in Zone 1 = 594 402. WALLS --ZONE 2------------------------------------------------ Elevation Type U Added R Gross(Sgft) South Frame Wall + 3" InS. 0.081 11 288 Total Wall Area in Zone 2 = 288 402 ------ WALLS--ZONE 3------------------------------------------------ Elevation Type U Added R Gross(Sgft) South Frame Wall + 3" InS. 0.081 11 442 Total Wall Area in Zone 3 = 442 402------- WALLS --ZONE 4------------------------------------------------ Elevation Type U Added R Gross(Sgft) East Frame Wall + 3" InS. 0.081 11 402 Type Color U Added R Area(Sgft) Steel Sheet with 1" Insulation Medium 0.213 11 1834 Total Roof Area in Zone 3 = 1834 404.------ROOFS--ZONE 4------------------------------------------------ Type Color U Added R Area(Sgft) Steel Sheet with i" Insulation Medium 0.213 11 9964 Total Roof Area in Zone 4 = 9964 404.------ROOFS--ZONE 5 ------------------- Color U Added R Area(Sgft) Steel Sheet with 1" Insulation Medium 0.213 11 0 Total Roof Area in Zone 5 = 0 404.------ROOFS--ZONE 6 ------------------------------------------------ Type Color U Added R Area(Sgft) Steel Sheet with i" Insulation Medium 0.213 11 0 Total Roof Area in Zone 6 = 0 Total Roof Area = 14196 405.------FLOORS-ZONE 1 ------------------------------------------------ Type R Area(Sgft) Floor over Conditioned Space/Uninsulated 0 0 Total Floor Area in Zone 1 = 0 405.------FLOORS-ZONE 2------------------------------------------------ Type R Area (Sgft ) iFloor over Conditioned Space/Uninsulated 0 1319 Total Floor Area in Zone 2 = 1319 405.------FLOORS-ZONE 3 ------------------------------------------------ Type R Area(Sq Floor over Conditioned Space/Uninsulated 0 1834 Total Floor Area in Zone 3 = 1834 405.------FLOORS-ZONE 4------------------------------------------------ Type R Area(Sgft) Floor over Conditioned Space/Uninsulated 0 9964 Total F1oor.Area in Zone 4 = 9964 405.------FLOORS-ZONE 5------------------------------------ ------------ Type R Area(Sgft) Floor over Unconditioned Space/Insulated 6.0 0 Total Floor Area in Zone 5 = 0 405.------FLOORS-ZONE 6------------------------------------------------ Type R Area(Sgft) Floor over Unconditioned Space/Insulated 4.0 668 Total Floor Area in Zone 6 = 668 Total Floor Area = 13785 406.------INFILTRATION -------------------------------------------------- ICHECKInfiltrationCriteriain406.1.ABC.1 have been met. i 407.------COOLING SYSTEMS--------------------------------------------- Type No Efficiency IPLV Tons 1. Split System 1 10.25 10.25 4.88 2. Split System 1 10.05 10.05 2.97 3. Split System 1 10.20 10.20 3.58 4.. Split System 4 10.05 10.05 4.00 5. Air Cooled ( >= 65,000 Btu/h 1 9.0 9.0 5.83 6. Split System 1• 10.05 10.05 2.40 408.------HEATING SYSTEMS----------------------------------------------- Type No Efficiency BTU/hr 1. Electric Resistance 1 1 41000 2. Electric Resistance 1 1 20500 3. Electric Resistance 1 1 20500 4. Electric Resistance 4 1 41000 5. Electric Resistance 1 1.0 41000 6. Electric Resistance 1 1.0 20500 409.------VENTILATION CHECK Ventilation Criteria in 409.1.ABC.1 have been met. I 410.-----AIR DISTRIBUTION SYSTEM --------------------------------- AHU Type Duct Location R-value 1. Split / PTAC Air Conditioner With Insulated Roof 6 2. Split / PTAC Air Conditioner With Insulated Roof 6 3. Split / PTAC Air Conditioner With Insulated Roof 6.0 4. Split / PTAC Air Conditioner With Insulated Roof 6.0 5. Split / PTAC Air Conditioner With Insulated Roof 6 6. Split / PTAC Air Conditioner With Insulated Roof 6 411.-----PUMPS AND PIPING -ZONE 1---------------------------------------- Type R-value/in Diameter Thickness 1. Non -Circulating 0 0 0 411.-----PUMPS AND PIPING -ZONE 2 --------------------------------------- Type 1. Circulating 411.-----PUMPS AND PIPING -ZONE Type 1. Circulating 411.-----PUMPS AND PIPING -ZONE Type 1. Non -Circulating 411.-----PUMPS AND PIPING -ZONE Type 1. Circulating 411.-----PUMPS AND PIPING -ZONE Type 1. Circulating R-value/in Diameter Thickness 0 0 Cal 3 --------------------------------------- R-value/in Diameter Thickness 0 0 0 4 --------------------------------------- R-value/in Diameter Thickness 6.5 1 1 5 --------------------------------------- R-value/in Diameter Thickness 0 0 0 6 --------------------------------------- R-value/in Diameter Thickness 0 0 W 412.-----WATER HEATING SYSTEMS -ZONE 1 ---------------------------------- Type Efficiency StandbyLoss InputRate Gallons 412.-----WATER HEATING SYSTEMS -ZONE 2 ---------------------------------- Type Efficiency StandbyLoss InputRate Gallons 412.-----WATER HEATING SYSTEMS -ZONE 3 ---------------------------------- Type Efficiency StandbyLoss InputRate Gallons 412.-----WATER HEATING SYSTEMS -ZONE 4---------------------------------- Type Efficiency StandbyLoss InputRate Gallons 1. <=12 kW 1.. 0 0 6 30 412.-----WATER HEATING SYSTEMS -ZONE 5 ---------------------------------- Type Efficiency StandbyLoss InputRate Gallons 412.-----WATER HEATING SYSTEMS -ZONE 6---------------------------------- Type Efficiency StandbyLoss InputRate Gallons 413.-----ELECTRICAL POWER DISTRIBUTION---------------------------------- CHECKMeteringcriteriain413._l.ABC.1 have been met. Transformer criteria in 413.1.ABC.2 have been met. 414.-----MOTORS --------------------------------------------------- Motor efficiencies in 414.1.ABC.1 have been met. 415.-----LIGHTING SYSTEMS -ZONE 1 --------------------------------- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft) Reading, T 1 No visual task 8 No visual task 1 2440 1079 Total Watts for Zone 1 = 2440 Total Area for Zone 1 = 1079 SYSTEMS -ZONE 2 --------------------------------------- 415.-----LIGHTING Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft) Reading, T 1 No visual task 13 None 0 4240 680 Toilet and 1 No visual task 4 None 0 1280 639 Total Watts for Zone 2 = 5520 Total Area for Zone 2 = 1319 415.-----LIGHTING SYSTEMS -ZONE 3 --------------------------------------- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft) Reception 1 No visual task 2 None 0 2040 1834 Total Watts for Zone 3 = 2040 Total Area for Zone 3 = 1834 415.-----LIGHTING SYSTEMS -ZONE 4 --------------------------------------- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft) Reception 1 No visual task 4 None . 0 5880 9964 Total Watts for Zone 4 = 5880 Total Area for Zone 4 = 9964 415.-----LIGHTING SYSTEMS -ZONE 5--------------------------------------- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft) Corridor 1 No visual task 2 None 0 2160 1511 Total Watts for Zone 5 = 2160 Total Area for Zone 5 = 1511 415.-----LIGHTING SYSTEMS -ZONE 6--------------------------------------- Space Type No Control Type 1 No Control Type 2 No Watts Area(Sgft) Toilet and 1 No visual task 1 None 0 1440 668 Total Watts for Zone 6 = 1440 Total Area for Zone 6 = 668 Total Watts = 19480 Total Area = 16375 Lighting criteria in 415.1.ABC have been met. CHECK v- 116. HVAC load sizing has been performed. (407.1.ABC.1) f 1-1-7.---D-u-ct-sizing--and--design-have--been-perf-o-r-m-d.-e(410_1_ABC_1_2)--- - - --- i---- i18. Testing and balancing will be performed. (410.1.ABC.4) 19. Operation/maintenance manual will be provided to owner.(102.1) A s CITY OF SANFO, RD r4 FIRE DEPARTMENT 1303 South French Avenue v Sanford, Florida 32771 407) 302-1091 (407) 302-1097 FAX ,, Plans Review Sheet Date: April 13, 1999 Business Address: 2 Red Cleveland Occ. Chap. 8 Business Name: Orlando Sanford Airport Ph. Contractor: Mark Construction Ph. 831-6275 Reviewed [ ] Reviewed with comment [ X ] Rejected [ Reviewed by: Bart Wright, Fire Protection Inspector Comment: Cover page errors: wrong edition of LSC (should be 1994); occupant load notes figure based on gross square footage (should be net square footage); wrong notation regarding sprinkler requirement (should note required and provided for existing system) f 1.1 Application — addition to an existing assembly airport passenger terminal 1.2 Mixed - N/A 1.3 Special Definitions - N/A 1.4 Classification of Occupancy - Ordinary Sub -classification: Class "A" > 1,000 1.5 Classification of Hazard of Contents - Ordinary 1.6 Minimum Construction — Applicant submitted type IV u.p. SBCCI; type 11(000) NFPA 1.7 Occupant Load — for addition only 3750 sq. ft.: 15 = 250 2.2 Means of Egress Components - O.K. 2.3 Capacity of Egress - O.K. 2.4 Number of Exits - O.K. 2.5 Arrangement of Egress - O.K. 2.6 Travel Distance - O.K. 2.7 Discharge from Exits - O.K. 2.8 Illumination of Means of Egress - O.K. 2.9 Emergency Lighting - O.K.; will field verify i 2.10 Marking of Means of Egress - O.K. for all uses; will field verify 2.11 Special Features -None noted 3.1 Protection of Vertical Openings —None noted 3.2 Protection from Hazards — N/A 3.3 Interior Finish - Class "B" 3.4 Detection, alarm and Communications Systems — N/R 3.5 Extinguishing Requirements — N/R 3.6 Corridors - N/A 4 Special Provisions - None noted 5 Building Services - No comment 5.1 Utilities 5.2 HVAC 5.3 Elevators, Escalators, Conveyors (4A-47) 5.4 Rubbish Chutes, Incinerators, and Laundry Chutes Sanford City Code - Chapter 9 Fire Sprinklers: Required and provided; see cover page note Monitoring: Required by a U.L. listed central station company Other: NFPA 1 3-5.1 Fire Lanes — N/A for addition 3-6.1 Key Box — N/A for addition 3-7.1 Bldg. Address Number Posted and Legible — N/A for addition DATE: January 8, .2001 TO: Building Official FROM: Utility Director f i RE: Wiginton Fire Sprinklers Inc. Plans Jerry's Restaurant - Sanford Airport Dan - I have reviewed the above referenced plans. The plans show a tie in to the city line to be done by Wiginton. The Utility Department needs to see details on this connection with appropriate materials. A City inspector needs to witness the tap. A minimum of forty-eight (48) hours notice is needed to schedule inspections. Thank You. PM/ap 0-