Mr. Gary Wynn
City of Sanford
Building Department
P.O. Box 1778
Sanford, FL 32772-1778
Reference: Remodelina & Renovation of
Sanford Civic Center
Subject: Existing Electrical Service
Dear Mr. Wynn:
Concerning the existing electrical service, please find enclosed
a letter dated June 12, 1989, regarding the existing calculated
connected electrical load.
The existing electrical service is at its maximum capacity. The
total building connected load is approximately 200 KW (555 amps
at 208 volt, 3 phase). The existing incoming service conductors
are rated for 620 amps.
Since no additional electrical load is being added in this
remodeling phase and eventually the existing overhead electrical
service is to be changed to a new underground service, the
existing service entrance conductors are to remain and not change
as indicated on the contract documents for this remodeling phase.
If there are any questions concerning the above, please contact
Sincerely,
GAG. CONSULTING GZNEERS, INC.
enneth Rigby,
Principal/Electrrc al Engineer
KLR/sw
Attachment
cc: Jerry Claus - Schweizer, Inc.
Specializing In Innovative Engineering Design Services Since 1967.
i ®eeC Old
I
Ott COBS a street . 32z A
18 e58
rang
rgs`
o
da
5V`te oto s
AO 682 6g0
June 12, 1989
Mr. Doug Sangster
Schweizer Architects
55 E. Jackson Street
Orlando, FL 32801
Reference: Sanford Civic Center
W-
Subject: Existing Electrical Service Size
Dear Doug:
i
The existing overhead electrical service is 208Y/120 volt, 3
phase, 4 wire.
The electrical service consists of two main service disconnects
fusible). One main disconnect is rated 400 amp, fused at 300
amp, and serves the HVAC load and the other main disconnect is
rated 400 amp, fused at 300 amp, and serves lighting,
receptacle, and other equipment loads.
The incoming overhead electrical service conductors consist of
two parallel sets of (3) #350 MCM THW CU and 1#1/0 THW CU
neutral - (2) - 3" C. The service conductors are rated for 620
amps.
The electrical load breakdown is as follows:
400 Amp Disconnect for HVAC Load
Chiller - 75 HP
Fan - 10 HP
Well Pump - 5 HP
The total connected load is 90 HP (approximately 260 amps at 208
volt, 3 phase).
Specializing in Innovative Engineering Design Services since 1967.
I
Mr. Doug Sangster
Reference: Sanford Civic Center
j Subject: Existing Electrical Service Size !
o June 12, 1989 j
Page Two
400 Amp Disconnect for Buildina Load
Panel P4 Senior Citizen Center Remodeling) 30 KW
Panel P5 Senior Citizen Center Remodeling)
Existing Auditorium Lighting Load 13 W
Area
5
5
KW
KW
Equipment
Total 111 KW
The total connected load is 111 KW (approximately 308 amps at
208 volt, 3 phase). The actual demand will be less than 111 KW.
The incoming overhead electrical service conductors will be
upgraded to two parallel sets of 4#500 MCM THWN CU and the fuse
size in the disconnect serving the building load increased to
400 amp. This work is included in the Auditorium Relighting
project for which the design has recently been completed.
The electrical service will be required to be further upgraded
whenever the new stage lighting system is designed and
installed.
If there are any questions concerning the above, please contact
me..
Sincerely,
TOn'/n
co u t' engineers, inc.
f
St L .. Rig , P.E.
Principal/Electrical Engineer
KLR/sw
cc: ABCOM II, Inc.
eev
e
S' 'o tc®
ts ge S ee
t`ds32'
1A
118'a ;-'ob n95i
too
ONO ovtte S
June 12, 1989
Mr. Doug Sangster
Schweizer Architects
55 F. Jackson Street
Orlando, FL 32801
Reference: Sanford Civic Center
Subject: Existing Electrical Service Size
Dear Doug:
The existing overhead electrical service is (208Y/120 volt, 3
phase, 4 wire.
The electrical service consists of two main service disconnects
fusible). One main disconnect is rated 400 amp, fused at 300
amp, and serves the HVAC load and the other main disconnect is
rated 400 amp, fused at 300 amp, and serves lighting,
receptacle, and other equipment loads.
The incoming overhead electrical service conductors consist of
two parallel sets of (3) #350 MCM THW CU and 1#1/0 THW CU
neutral `(2) 3" C. The service conductors are rated for 620
amps.
elec.r1+:a1 load briak,down is as Tv11CVJ: -
400 Amp Disconnect for`HVAC.Load
Chiller = 75 HP
Fan -.10 HP
Well Pump - 5 HP
The total connected load is 90 HP (approximatelyt260_amps at 208
volt, 3 phase).
Specializing in innovative Engineering Design Services since 1967.
i
Mr. Doug Sangster
Reference: Sanford Civic Center
Subject: Existing Electrical Service Size
June 12, 1989
Page Two
400 Amp Disconnect for.Building Load
Panel P4 (Senior Citizen Center Remodeling) - 30 KW ?
Panel P5 (Senior Citizen Center Remodeling) - 58 KW 2
Existing Auditorium Lighting Load - 13 KW
Dressing Area - 5 KW
Kitchen Equipment - 5 KW
Total 111 KW
The total connected load is 111 KW (approximately :308 amps at
208 volt, 3 phase). The actual demand will be less than 111 KW.
The incoming overhead electrical service conductors will be
upgraded to two parallel sets of 4#500 MCM THWN CU and the fuse
size in the disconnect serving the building load increased to
400 amp. This work is included in the Auditorium Relighting
project for which the design has recently been completed.
The electrical service will be required to be further upgraded
whenever the new stage lighting system is designed and
installed.
If there are any questions concerning the above, please contact
me.
Sincerely,
gx,d:on i
ttirZical
ers, inc.
Engineer
KLR/ s w
cc: ABCOM II, Inc.
r—
Ts Inc
ommons g vd
Ma hand e 3277 5 DEC 2 7 1989
1055 d F jortdaMait1a660p0$$
6554O716g0. e ; K
FAX 407-
December 21, 1989
Mr. John Lyons
P.O. Box 396
Lake Monroe, FL 32747
RE: Sanford Civic Center
Subject: Existing Electrical Service
Dear John;
Please, find enclosed letter regarding existing electrical
service size for referenced project.
Concerning the remodeling and renovation project, no additional
load is being added to the existing electrical service.
The renovation work includes upgrading the existing incoming
electrical service conductors and increasing the fuse size in
the main disconnect serving the'.building load.
Based on the existing connected building load, the building load
disconnect switch fuse size should be increased from 300 amp to
400 amp and the service entrance conductors increased
accordingly.
If there are any questions concerning the above, please contact
me.
Sincerely,
coyffu,lt
C
inc.
Kenneth L . Rigby,/P `-
ngineerPrincipal/Electridal
KLR/lm
cc: Doug Sangster - Schweizer Architects
Specializing In Innovative Engineering Design Services Since 1967.
LiEC---,T` 9 TL 17=
r
WOO
elo'
Blost
p
Mr. Doug Sangster
Schweizer Architects
55 E. Jackson Street'
Orlando, FL 32801
Reference: Sanford Civic Center
Subject; Existing Electrical Service Size
Dear Doug:
The existing overhead electrical service is 208Y/120 volt, 3
phase, 4 wire.
The electrical service consists of two main service disconnects
fusible). One main disconnect is rated 400 amp, fused at 300.
amp,.and serves the HVAC load and the other main disconnect is
rated 400 amp, fused at 300 amp, and serves lighting,
receptacle, and other equipment loads.
The incoming overhead electrical service conductors consist of
two parallel sets of (3) #350 MCM THW CU and 1#1/0 THW CU
neutral - (2) 311 C. The service conductors are rated for 620
amps.
The electrical load breakdown is as follows:
Chiller - 75 HP
Fan - 10 HP
HPwellPump
The total connected load is 90 HP (approximately 260 amps at 208
volt, 3 phase).
V.
Specializing in innovative Engi neering Design Services since 1967.
J
Mr. Doug Sangster
Reference: Sanford Civic Center
subject: Existing Electrical Service Size
June 12, 1989
Page Two
Panel P4 (Senior Citizen Centex Remodeling) - 30 KW
Panel P5 (Senior Citizen Center Remodeling) - 58 KW
Existing Auditorium Lighting load - 13 KW
Dressing Area -
5 KW
Kitchen Equipment --•
w
Total ill KW
The total connected load is Ill KW (approximately 308 amps at
20.8 volt, 3 phase). The actual demand will be less than Ill KW.
The incoming overhead electrical service conductors will be
upgraded to two parallel sets of 4#500 MGM THWN CU and the fusesizeinthedisconnectservingthebuildingloadincreasedto
4.00 amp. This work is included in the Auditorium Relighting
project for which the design has recently been completed.
The electrical service will be required to be further upgraded
whenever the new stage lighting system is designed and
installed.
If there are any questions concerning the above, please contact
me.
Sincerely,
W M
eers, Base.
E.
Engineer
KLR/8W
cat ABCOM 11, Inc.
A
Wharton -Smith, Inc. General & Mechanical Contractors
750 County Road 15 / P.O. Box 396 / Lake Monroe, FL 32747 / 305/830-8393
DATE / • + • 9a
TRANS NO.
JOB NO. 940
RE 5gn74n:/ 6-1v1 c Cen Aer'
GENTLEMEN: /
Q
SUBS: CONTRACT ITEM FILE NO. G?A FILE TITLE: ! f5%eMl %J
VENDOR NAME
WE ARE FORWARDING TO YOU:
Estimates Proposals Reports
Plans Prints Under separate cover via:
Shop Drawings Samples Specifications
Copy of letter Change order
FOR PURPOSE CHECKED BELOW
OUANT. DRAWING NUMBER DESCRIPTION
For
initial
apprv'l
Res.
for
apprv'l
Appr.
Appr'd
as
noted
Fite
Resub. .
this
quant.
2.89 G,24 Cor sv//icy L'n g c r'
2.2/• 89 G ecr Cons a/-,4irq engineer' Le
REMARKS
DISTRIBUTION:
F I ELD 9.FILE BOOK OTHER
BY .lohn Zyvn5Mfr
L --
DEC-21-, ,_, TH_i 17: 20 I D: GRG DER' I EL 110: 407-660-1i_55
4
8
p
june 12, 1989
Mr. Doug Sangster
Schweizer Architocts
55 E. jaoknon Street
Orlando, FL 32801
Reference: Sanford Civic Center
5ubjeot: Existing Electrical Service Giz®
Dear Doug:
The existing overhead electrical service is 208Y/120 volt, 3
phase, 4 wire.
The electrical service consists of two main service disconnects
fusible). One main disconnect is rated 400 amp, fused at 300
amp, and serves the HVAC load and the other main disconnect is
rated 400 amp, fused at 30o amp, and serves Lighting,
receptacle, and other equipment loads,
The incoming overhead electrical service conductors consist of
two parallel sets of (3) W350 MCM THW GU and 1#1/0 THW CU
neutral - (2) - 3" C. The service conductors are rated for 620
amps.
The electrical load breakdown is as follows:
400 Amy Disconnect for HV C Load
Chiller - 75 HP
Fan - 10 HP
Well Pump - 5 HP
The total connected load is 90 HP (approximately 260 amps at 206
volt, 3 phase).
a
Specializing In InnoveNve Engineering Design Services since 1987. '°
DEC-21-' 89 THI 117: 21 I D: CRC-; i_0t V.-iJLI I I IG El lGR3 TEl hd0: 4t=t 7 -t ,r0-1 N 1 t_t5 F t_t4
t .
Mx- Doug Sangster
Reference: Sanford Civic center
Subject: Existing Electrical Service Siza
June 12, 1989
Page Two
Panel P4 (Senior Citizen center Remodeling) _ 3ill'. 0KW
Panel
PS (Senior Citizen Centex Remodeling) KW Existing
Auditorium Lighting Load _ _ 13 3KW
Dressing
Area 5 W Kitchen
Equipment Y Total
ill " The
total connected load is Ill KW (approximately 308 amps at 208
volt, 3 phase). The actual demand will be less than Ill KW. The
incoming overhead electrical service conductors will be upgraded
to two parallel sets of 4#500 MCM THWN CU and the fuse sizeinthedisconnectservingthebuildingloadincreasedto400
amp. This work is included in the Auditorium Relighting project
for which the design has recently been completed. The
electrical service will be required to be further upgraded whenever
the new stage lighting System is dosigned and installed.
If
there are any questions concerning the above, Please corLtact me.
Sincerely,
Miidth
L. R1 Principal/Ele
KLR/ Bw
ineers, inn •
P.E.
ical Engineer
cat ABCOM
11, Inc.
ing endjneers5
OrSU1$' ons Blvd• C M
55 Ntadtand Ce 3275
cm
0 1 L Z 7
Maitland, 0088 a
C407 g60660.1655FAXao
December 21, 1989
Mr. John Lyons
P.O. Box 396
Lake Monroe, FL 32747
RE: Sanford Civic Center
Subject: Existing Electrical Service
Dear John;
Please, find enclosed letter regarding existing electrical
service size for referenced project.
Concerning the remodeling and renovation project, no additional
load is being added to the existing electrical service.
The renovation work includes upgrading the existing incoming
electrical service conductors and increasing the fuse size in
the main disconnect serving the building load.
Based on the existing connected building load, the building load
disconnect switch fuse size should be increased from 300 amp to
400 amp and the service entrance conductors increased
accordingly.
If there are any questions concerning the above, please contact
me.
Sincerely,
C
s, inc.
Ke ineth - L . Rigby, P ELgineerPrincipal/Electri al
KLR/lm
cc: Doug Sangster - Schweizer Architects
Specializing In Innovative Engineering Design Services Since 1967.
e
SCHWEIZER
INCORPORATED
ARCHITECTURE • ENGINEERING • PLANNING
INTERIOR DESIGN
August 2, 1989
Mr. Gary Wynn
City of Sanford, Florida
Building Department
Post Office Box 1778
Sanford, Florida 32772-1778
RE: SANFORD CIVIC CENTER REMODELING AND RENOVATION
Dear Sir,
In order to minimize delays, Mr. Bill Simmons has asked that we go ahead and
start the permitting even though a General Contractor has not yet been
selected. Spaces 3a., 3b., and 24 on the attached form will be filled in by
the General Contractor once one is selected. If you have any further
questions or need to contact me for any reason concerning this application,
please don't hesitate to call.
Sincerely,
Douglas Sangster
Project Manager
DSS/bjy:5
Enclosures
cc: Mr. Tom Martin, Inspector
File
55 EAST JACKSON STREET POST OFFICE BOX 1471 ORLANDO, FLORIDA 32802 TELEPHONE (407) 425-0922
SCHWEIZ R
0--'i , F) 0NC1FRi -AT E D August
2, 1989 Mr.
Gary Wynn City
of Sanford, Florida Building
Department Post
Office Box 1778 Sanford,
Florida 32772-1778 RE:.
SANFORD CIVIC CENTER REMODELING AND RENOVATION Dear
Sir, In
order to minimize delays, Mr. Bill Simmons has asked that we go ahead and start
the permitting even though a General Contractor has not Yet been selected.
Spaces 3a., 3b., and 24 on the attached form will be filled in by the
General Contractor once one is selected. If you have any further questions
or need to contact me for any reason concerning this application, please
don't hesitate to call. Sincerely,
Las
DouglSangster Project
Manager DSS/