HomeMy WebLinkAbout401 E Seminole Blvd Sanford Civic Center Correspondence Remodel Sanford Civic Centere J 111e erS5 MR mn consu1 1ng Mons Blvd f enter ' Om itland g275 p5t1a d,Florida 407, 660 660 $ 655FAX407- Y%" February 21, 1989 s Mr. Gary Wynn City of Sanford Building Department P.O. Box 1778 Sanford, FL 32772-1778 Reference: Remodelina & Renovation of Sanford Civic Center Subject: Existing Electrical Service Dear Mr. Wynn: Concerning the existing electrical service, please find enclosed a letter dated June 12, 1989, regarding the existing calculated connected electrical load. The existing electrical service is at its maximum capacity. The total building connected load is approximately 200 KW (555 amps at 208 volt, 3 phase). The existing incoming service conductors are rated for 620 amps. Since no additional electrical load is being added in this remodeling phase and eventually the existing overhead electrical service is to be changed to a new underground service, the existing service entrance conductors are to remain and not change as indicated on the contract documents for this remodeling phase. If there are any questions concerning the above, please contact Sincerely, GAG. CONSULTING GZNEERS, INC. enneth Rigby, Principal/Electrrc al Engineer KLR/sw Attachment cc: Jerry Claus - Schweizer, Inc. Specializing In Innovative Engineering Design Services Since 1967. i ®eeC Old I Ott COBS a street . 32z A 18 e58 rang rgs` o da 5V`te oto s AO 682 6g0 June 12, 1989 Mr. Doug Sangster Schweizer Architects 55 E. Jackson Street Orlando, FL 32801 Reference: Sanford Civic Center W- Subject: Existing Electrical Service Size Dear Doug: i The existing overhead electrical service is 208Y/120 volt, 3 phase, 4 wire. The electrical service consists of two main service disconnects fusible). One main disconnect is rated 400 amp, fused at 300 amp, and serves the HVAC load and the other main disconnect is rated 400 amp, fused at 300 amp, and serves lighting, receptacle, and other equipment loads. The incoming overhead electrical service conductors consist of two parallel sets of (3) #350 MCM THW CU and 1#1/0 THW CU neutral - (2) - 3" C. The service conductors are rated for 620 amps. The electrical load breakdown is as follows: 400 Amp Disconnect for HVAC Load Chiller - 75 HP Fan - 10 HP Well Pump - 5 HP The total connected load is 90 HP (approximately 260 amps at 208 volt, 3 phase). Specializing in Innovative Engineering Design Services since 1967. I Mr. Doug Sangster Reference: Sanford Civic Center j Subject: Existing Electrical Service Size ! o June 12, 1989 j Page Two 400 Amp Disconnect for Buildina Load Panel P4 Senior Citizen Center Remodeling) 30 KW Panel P5 Senior Citizen Center Remodeling) Existing Auditorium Lighting Load 13 W Area 5 5 KW KW Equipment Total 111 KW The total connected load is 111 KW (approximately 308 amps at 208 volt, 3 phase). The actual demand will be less than 111 KW. The incoming overhead electrical service conductors will be upgraded to two parallel sets of 4#500 MCM THWN CU and the fuse size in the disconnect serving the building load increased to 400 amp. This work is included in the Auditorium Relighting project for which the design has recently been completed. The electrical service will be required to be further upgraded whenever the new stage lighting system is designed and installed. If there are any questions concerning the above, please contact me.. Sincerely, TOn'/n co u t' engineers, inc. f St L .. Rig , P.E. Principal/Electrical Engineer KLR/sw cc: ABCOM II, Inc. eev e S' 'o tc® ts ge S ee t`ds32' 1A 118'a ;-'ob n95i too ONO ovtte S June 12, 1989 Mr. Doug Sangster Schweizer Architects 55 F. Jackson Street Orlando, FL 32801 Reference: Sanford Civic Center Subject: Existing Electrical Service Size Dear Doug: The existing overhead electrical service is (208Y/120 volt, 3 phase, 4 wire. The electrical service consists of two main service disconnects fusible). One main disconnect is rated 400 amp, fused at 300 amp, and serves the HVAC load and the other main disconnect is rated 400 amp, fused at 300 amp, and serves lighting, receptacle, and other equipment loads. The incoming overhead electrical service conductors consist of two parallel sets of (3) #350 MCM THW CU and 1#1/0 THW CU neutral `(2) 3" C. The service conductors are rated for 620 amps. elec.r1+:a1 load briak,down is as Tv11CVJ: - 400 Amp Disconnect for`HVAC.Load Chiller = 75 HP Fan -.10 HP Well Pump - 5 HP The total connected load is 90 HP (approximatelyt260_amps at 208 volt, 3 phase). Specializing in innovative Engineering Design Services since 1967. i Mr. Doug Sangster Reference: Sanford Civic Center Subject: Existing Electrical Service Size June 12, 1989 Page Two 400 Amp Disconnect for.Building Load Panel P4 (Senior Citizen Center Remodeling) - 30 KW ? Panel P5 (Senior Citizen Center Remodeling) - 58 KW 2 Existing Auditorium Lighting Load - 13 KW Dressing Area - 5 KW Kitchen Equipment - 5 KW Total 111 KW The total connected load is 111 KW (approximately :308 amps at 208 volt, 3 phase). The actual demand will be less than 111 KW. The incoming overhead electrical service conductors will be upgraded to two parallel sets of 4#500 MCM THWN CU and the fuse size in the disconnect serving the building load increased to 400 amp. This work is included in the Auditorium Relighting project for which the design has recently been completed. The electrical service will be required to be further upgraded whenever the new stage lighting system is designed and installed. If there are any questions concerning the above, please contact me. Sincerely, gx,d:on i ttirZical ers, inc. Engineer KLR/ s w cc: ABCOM II, Inc. r— Ts Inc ommons g vd Ma hand e 3277 5 DEC 2 7 1989 1055 d F jortdaMait1a660p0$$ 6554O716g0. e ; K FAX 407- December 21, 1989 Mr. John Lyons P.O. Box 396 Lake Monroe, FL 32747 RE: Sanford Civic Center Subject: Existing Electrical Service Dear John; Please, find enclosed letter regarding existing electrical service size for referenced project. Concerning the remodeling and renovation project, no additional load is being added to the existing electrical service. The renovation work includes upgrading the existing incoming electrical service conductors and increasing the fuse size in the main disconnect serving the'.building load. Based on the existing connected building load, the building load disconnect switch fuse size should be increased from 300 amp to 400 amp and the service entrance conductors increased accordingly. If there are any questions concerning the above, please contact me. Sincerely, coyffu,lt C inc. Kenneth L . Rigby,/P `- ngineerPrincipal/Electridal KLR/lm cc: Doug Sangster - Schweizer Architects Specializing In Innovative Engineering Design Services Since 1967. LiEC---,T` 9 TL 17= r WOO elo' Blost p Mr. Doug Sangster Schweizer Architects 55 E. Jackson Street' Orlando, FL 32801 Reference: Sanford Civic Center Subject; Existing Electrical Service Size Dear Doug: The existing overhead electrical service is 208Y/120 volt, 3 phase, 4 wire. The electrical service consists of two main service disconnects fusible). One main disconnect is rated 400 amp, fused at 300. amp,.and serves the HVAC load and the other main disconnect is rated 400 amp, fused at 300 amp, and serves lighting, receptacle, and other equipment loads. The incoming overhead electrical service conductors consist of two parallel sets of (3) #350 MCM THW CU and 1#1/0 THW CU neutral - (2) 311 C. The service conductors are rated for 620 amps. The electrical load breakdown is as follows: Chiller - 75 HP Fan - 10 HP HPwellPump The total connected load is 90 HP (approximately 260 amps at 208 volt, 3 phase). V. Specializing in innovative Engi neering Design Services since 1967. J Mr. Doug Sangster Reference: Sanford Civic Center subject: Existing Electrical Service Size June 12, 1989 Page Two Panel P4 (Senior Citizen Centex Remodeling) - 30 KW Panel P5 (Senior Citizen Center Remodeling) - 58 KW Existing Auditorium Lighting load - 13 KW Dressing Area - 5 KW Kitchen Equipment --• w Total ill KW The total connected load is Ill KW (approximately 308 amps at 20.8 volt, 3 phase). The actual demand will be less than Ill KW. The incoming overhead electrical service conductors will be upgraded to two parallel sets of 4#500 MGM THWN CU and the fusesizeinthedisconnectservingthebuildingloadincreasedto 4.00 amp. This work is included in the Auditorium Relighting project for which the design has recently been completed. The electrical service will be required to be further upgraded whenever the new stage lighting system is designed and installed. If there are any questions concerning the above, please contact me. Sincerely, W M eers, Base. E. Engineer KLR/8W cat ABCOM 11, Inc. A Wharton -Smith, Inc. General & Mechanical Contractors 750 County Road 15 / P.O. Box 396 / Lake Monroe, FL 32747 / 305/830-8393 DATE / • + • 9a TRANS NO. JOB NO. 940 RE 5gn74n:/ 6-1v1 c Cen Aer' GENTLEMEN: / Q SUBS: CONTRACT ITEM FILE NO. G?A FILE TITLE: ! f5%eMl %J VENDOR NAME WE ARE FORWARDING TO YOU: Estimates Proposals Reports Plans Prints Under separate cover via: Shop Drawings Samples Specifications Copy of letter Change order FOR PURPOSE CHECKED BELOW OUANT. DRAWING NUMBER DESCRIPTION For initial apprv'l Res. for apprv'l Appr. Appr'd as noted Fite Resub. . this quant. 2.89 G,24 Cor sv//icy L'n g c r' 2.2/• 89 G ecr Cons a/-,4irq engineer' Le REMARKS DISTRIBUTION: F I ELD 9.FILE BOOK OTHER BY .lohn Zyvn5Mfr L -- DEC-21-, ,_, TH_i 17: 20 I D: GRG DER' I EL 110: 407-660-1i_55 4 8 p june 12, 1989 Mr. Doug Sangster Schweizer Architocts 55 E. jaoknon Street Orlando, FL 32801 Reference: Sanford Civic Center 5ubjeot: Existing Electrical Service Giz® Dear Doug: The existing overhead electrical service is 208Y/120 volt, 3 phase, 4 wire. The electrical service consists of two main service disconnects fusible). One main disconnect is rated 400 amp, fused at 300 amp, and serves the HVAC load and the other main disconnect is rated 400 amp, fused at 30o amp, and serves Lighting, receptacle, and other equipment loads, The incoming overhead electrical service conductors consist of two parallel sets of (3) W350 MCM THW GU and 1#1/0 THW CU neutral - (2) - 3" C. The service conductors are rated for 620 amps. The electrical load breakdown is as follows: 400 Amy Disconnect for HV C Load Chiller - 75 HP Fan - 10 HP Well Pump - 5 HP The total connected load is 90 HP (approximately 260 amps at 206 volt, 3 phase). a Specializing In InnoveNve Engineering Design Services since 1987. '° DEC-21-' 89 THI 117: 21 I D: CRC-; i_0t V.-iJLI I I IG El lGR3 TEl hd0: 4t=t 7 -t ,r0-1 N 1 t_t5 F t_t4 t . Mx- Doug Sangster Reference: Sanford Civic center Subject: Existing Electrical Service Siza June 12, 1989 Page Two Panel P4 (Senior Citizen center Remodeling) _ 3ill'. 0KW Panel PS (Senior Citizen Centex Remodeling) KW Existing Auditorium Lighting Load _ _ 13 3KW Dressing Area 5 W Kitchen Equipment Y Total ill " The total connected load is Ill KW (approximately 308 amps at 208 volt, 3 phase). The actual demand will be less than Ill KW. The incoming overhead electrical service conductors will be upgraded to two parallel sets of 4#500 MCM THWN CU and the fuse sizeinthedisconnectservingthebuildingloadincreasedto400 amp. This work is included in the Auditorium Relighting project for which the design has recently been completed. The electrical service will be required to be further upgraded whenever the new stage lighting System is dosigned and installed. If there are any questions concerning the above, Please corLtact me. Sincerely, Miidth L. R1 Principal/Ele KLR/ Bw ineers, inn • P.E. ical Engineer cat ABCOM 11, Inc. ing endjneers5 OrSU1$' ons Blvd• C M 55 Ntadtand Ce 3275 cm 0 1 L Z 7 Maitland, 0088 a C407 g60660.1655FAXao December 21, 1989 Mr. John Lyons P.O. Box 396 Lake Monroe, FL 32747 RE: Sanford Civic Center Subject: Existing Electrical Service Dear John; Please, find enclosed letter regarding existing electrical service size for referenced project. Concerning the remodeling and renovation project, no additional load is being added to the existing electrical service. The renovation work includes upgrading the existing incoming electrical service conductors and increasing the fuse size in the main disconnect serving the building load. Based on the existing connected building load, the building load disconnect switch fuse size should be increased from 300 amp to 400 amp and the service entrance conductors increased accordingly. If there are any questions concerning the above, please contact me. Sincerely, C s, inc. Ke ineth - L . Rigby, P ELgineerPrincipal/Electri al KLR/lm cc: Doug Sangster - Schweizer Architects Specializing In Innovative Engineering Design Services Since 1967. e SCHWEIZER INCORPORATED ARCHITECTURE • ENGINEERING • PLANNING INTERIOR DESIGN August 2, 1989 Mr. Gary Wynn City of Sanford, Florida Building Department Post Office Box 1778 Sanford, Florida 32772-1778 RE: SANFORD CIVIC CENTER REMODELING AND RENOVATION Dear Sir, In order to minimize delays, Mr. Bill Simmons has asked that we go ahead and start the permitting even though a General Contractor has not yet been selected. Spaces 3a., 3b., and 24 on the attached form will be filled in by the General Contractor once one is selected. If you have any further questions or need to contact me for any reason concerning this application, please don't hesitate to call. Sincerely, Douglas Sangster Project Manager DSS/bjy:5 Enclosures cc: Mr. Tom Martin, Inspector File 55 EAST JACKSON STREET POST OFFICE BOX 1471 ORLANDO, FLORIDA 32802 TELEPHONE (407) 425-0922 SCHWEIZ R 0--'i , F) 0NC1FRi -AT E D August 2, 1989 Mr. Gary Wynn City of Sanford, Florida Building Department Post Office Box 1778 Sanford, Florida 32772-1778 RE:. SANFORD CIVIC CENTER REMODELING AND RENOVATION Dear Sir, In order to minimize delays, Mr. Bill Simmons has asked that we go ahead and start the permitting even though a General Contractor has not Yet been selected. Spaces 3a., 3b., and 24 on the attached form will be filled in by the General Contractor once one is selected. If you have any further questions or need to contact me for any reason concerning this application, please don't hesitate to call. Sincerely, Las DouglSangster Project Manager DSS/ bjy:5 ti Enclosures cc: ." Mr. Tom Jlar"i n-,., i.nsp.ecto.r File 1--, - Co-S-1 10--ic- 2(3) 471 rELEPHONE (407) '25 0922 a./89