HomeMy WebLinkAbout312 W 1 St 01-683 Fire inspection Federal Trust BankSANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Airk Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772 407
302-2520 / FAX (407) 330-5677 Pager (
407) 918-0.395 aD
Plans
Review Sheet Date:
August 28, 2003 Business Address: 312 West First Street Occ. Ch. 38 Business Business
Name: Federal Trust Bank Ph. ( ) Contractor:
United Fire Protection Ph. (727) 945-1390 Fax.(
727) 727-505-5012 Reviewed [ ]
Reviewed with comment [ X ] Rejected [ ] Reviewed
by: Timothy Robles, Fire Protection Inspector/Plans Examiner 77-CComment:
Install F.M. 200 Instillation in Service Phone Room 1.
1 Application — Instillation of an ANSUL R-102 "3" Gallon fire system 1.
2 Nine flow points to be used 1.
3 System shall shut off gas and or electrical appliance 1.
4 "K" rated fire extinguisher required to be service and 25' from range 1.
5 Function dump test required
Al J'
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, FI. 32772
407 302-1022 / FAX (407) 330-5677
Pager (407) 444-3180
Plans Review Sheet
Date: 12/14/00 Business Address: 312 W. I" St. Occ. Ch. 27
First Floor
Business Name: Federal Trust Bank Ph. (407) 324-1881
Contractor: Fla. Concepts (Owen Hurd) Ph. (4070 330-0671
Reviewed [ ] Reviewed with comment [ X ] Rejected
Reviewed by: H. A. "Pete" Tucker, Fire Protection Inspector
Comment: Plans reviewed as Business Occupancy. FD reserves right to require applicable code
requirements if occupancy use changes. Need to add strobes and / or horns to existing alarm
system for bathrooms.
Application — Interior Renovation, Type V, 331 sq.ft.
1.1 Mixed — N/A
1.2 Special Definitions — N/N
1.3 Classification of Occupancy — Business
1.4 Classification of Hazard of Contents — Ordinary
1.5 Minimum Construction — N/R
2.2 Means of Egress Components O.K.
2.3 Capacity of Egress — O.K.
2.4 Number of Exits — O.K.
2.5 Arrangement of Egress — O.K.
2.6 Travel Distance — O.K.
2.7 Discharge from Exits — O.K.
2.8 Illumination of Means of Egress — O.K.; will field verify
2.9 Emergency Lighting — O.K.; will field verify
2.10 Marking of Means of Egress — O.K.
2.11 Special Features — O.K.
3.1 Protection of Vertical Openings — N/N
3.2 Protection from Hazards — N/N
1
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, Fl. 32771 / P. O. Box 1788, Sanford, Fl. 32772
407 302-1022 / FAX (407) 330-5677
Pager (407) 444-3180
3.3 Interior Finish — Class "C"
3.4 Detection, Alarm and Communications Systems — as per NFPA 72, see comments
15 Extinguishing Requirements — as per NFPA 10
3.6 Corridors — N/A
4 Special Provisions
5 Building Services
5.1 Utilities — as per LSC 7-1
5.2 H{VAC — as per LSC 7-2
5.3 Elevators, Escalators, Conveyors (4A-47) — N/A
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes - N/A
Sanford City Code — Chapter 9
Fire Sprinklers: N/A to renovation
Monitoring: N/A to renovation
Other: NFPA 1
3-5.1 Fire Lanes — N/A to renovation
3-6.1 Key Box — N/A to renovation
3-7.1 Bldg. Address Number Posted and Legible — N/A to renovation
2