Plans Review Sheet
Date: 6/12/00 Business Address: 312 W. I" St. Oce. Ch. 27
Business Name: Federal Trust Bank Ph. (407) 645-1201
Contractor: Fla. Concepts (Dick Corbet) Ph. (727) 447-6776
Reviewed [ I Reviewed with comment [ X ] Rejected [ f
Reviewed by: H. A. "Pete" Tucker, Fire Protection Inspector
Comment: Alarm System components to be field verified as to location to be tied into
existing system, as per NFPA 72
1.1 Application — Interior remodel, 3,000 sf.
1.2 Mixed — N/A
1.3 Special Definitions — N/N
1.4 Classification of Occupancy — Business
1.5 Classification of Hazard of Contents — Ordinary
1.6 Minimum Construction — N/R
2.2 Means of Egress Components — O.K.
2.3 Capacity of Egress — O.K.
2.4 Number of Exits — O.K.
2.5 Arrangement of Egress — O.K.
2.6 Travel Distance — O.K.
2.7 Discharge from Exits — O.K.
2.8 Illumination of Means of Egress — O.K.; will field verify
2.9 Emergency Lighting — O.K.; will field verify
2.10 Marking of Means of Egress — O.K.
2.11 Special Features — O.K.
3.1 Protection of Vertical Openings — N/N
S 4�
3.2 Protection from Hazards — N/N
3.3 Interior Finish — Class "B"
3.4 Detection, Alarm and Communications Systems — see comments, (NFPA 72
3.5 Extinguishing Requirements —as per NFPA 10
3.6 Corridors -
- 4 Special Provisions
- 5 Building Services
5.1 Utilities
5.2 HVAC
5.3 Elevators, Escalators, Conveyors (4A-47)
5.4 Rubbish Chutes, Incinerators, and Laundry Chutes
Sanford City Code — Chapter 9
Fire Sprinklers: N/A to remodel
Monitoring: N/A to remodel
Other: NFPA 1
3-5.1 Fire Lanes — Required if building is more than 150' from street; exception:
building has fire sprinkler system.
3-6.1 Key Box — N/A to remodel
3-7.1 Bldg. Address Number Posted and Legible — Required; will field verify
r7 2 i
FtII
0 �
>
FW
ELICAL
_ECrR
FARM
AND AL
SYSTEM.- POWE R
-FIRE
E-2
."UGHIING, IF:1
SPE�.-,11FICA11ONS . . . E RIS EK D SC
IIIITE$
II
0 11 I Fill
F5 T 7 I T HF -E.,CLEANING AND .'EN5URE,�'THAT: Ols R jq�':OVLeRSE L; C -'A,T F TO 'F I NA L�� I �t,THE�, F:;5PON5(5IWTY'�*OF TH[;L �N IQ E; 'T I 0 N AL" 'IR ) 5 �:A R e M P0 N T A I N E Q 1 DUPING� CON AL H E, _:k� DOPTEC)�.E.0 (7:,R A C U5515 T H 5 N �6 �TA A 10 N A N 13 T R U Ce AN TCH. rA II NG'::;JW R I 50 I Q, T I Q K. - U NT Q AL' �AIR, PA j 'Al NTA[N NP A 4 NTR CTOR,WREf C> u C H 0 P A M 0 5. R, A Q I Z=PIEQ' 5 Y 0 WN A V t�,T,,T H E . F,e V IF 1.� 15 c TIP 's,u . 7rERM 'TO' :QWNER MAIN iINA7IQN Hl� B S - A N T 14 .4 L Y H A� -ACE F U D E A '�5 FOR CARE ��ANQ T I T He:,:,A EQ WMr.NT_�Q tR F PH R AND"LINSTRUC JR1, C P 5TfR U OT "ARE 4 6 Q 0 5 Q F T C Q N 1) I
:T[QNE 0 R� DE Y FQR r N N, I -T 'r "' 'L L �L' � I , , , I � . I _ rN b, .� , 1; N C -' "AL ' M PROY EME NT 'NATLIRE- � ONTE T,5 RAL,,L�'rj K C U Q E M AN U F A T ' T H EL M A I N-T g. N A N C E 0 R 'A L L-�- "A e N I Q A R C; H T--'� P I- F 0, R T H, E:' r� R 10 IN E 5 A Q ST R I OR F OL R I N 7 F `TION N IR ON; ;,�BT!AR,T PL'-' OPE RA AN d, E M A 1 T'F: T T T 5 H fE T I 0 N,�� T Y P E-� C ON tVA I 141A 5LF_ H N N T 5 �v l5ee ..;j:�REpAREa' �T 'y IA N E UJL tq�(:j T F PEC f E, L CA E FI L T Q, R H jA� 1; L - P E R F Q. R A A A0 J5 M �IN L Ei N V e L�.' r E R I; 4) H -A N4 Qr N5. "T E R P.Q R A'U'(� T. A� C , Q I, 5 t 1 5) T, Y TTi R R O 6. 5, I�R ALL, H 5 H A EX A NE�� THE�-;�!:`ARJE ��7 O' -4 T I N G A, of� A'l 'T R A5 Ic 5 H V AG, U T R I 15 rz. F f U �5' H T FifA T; H I F I N I S,H �N K tt�, f� N_ 'T T< NO, W A L L ��,C_ 5j L5 TE DeTE,RMI� F, A R C HI T E C "AN T I N:,G A E A M IN F; 1, T! 10K R. E N 0 VA T I Q N5 7 9 E
,A N -C N Q 0 U15,, "A RE H:,, H e,' I M N, F, 0 �T 0 N T I VERIFYI '�:SAA V E 0 F Kc - Q R k :�UNIT$ _R 5S, H,E 1� 00., JAM
'AL L. K
IN ,U C E D '6 R-4` A' 0 0c I'A N7 A t--D R 4 T �, 0 5,e': 5 0 OR:,1NIFOR -TION AT H N Q, 'AT L- W O -T'Q 'C 'Rb OR A Sl N G.L
N O�, Q N EN RR M'Z) I1� , 0 N T H V W (UHe A P P R 0 V, R:,97HER, Q Al-IF.:,L, Il A T F; �l u Q & MATIQN:� T F �,,Q Is T� "I R NO �F RLOTECTI U.N 8 Fl�,R > /A N, IQ Q 4f '5 T� tr�F $0 T F 'T A f T, TH, fO N 17 A T1 N
MA 6 I TH W 5T . 0 7R A IW.. O N E� A L A 5 R OLI T H 15,,� N ACT r IQ
,,A C Ello" AM e T AH R'01�LED, E ��'A 9 TRACTOR'��5 nl� THE IV T U fl Q. R �T 0,7 T H T 5 H, A 4 - , Q - T HE FE R'r= C4�. ARI�A5,:,j0" T I-Y INC 0 t L IQ N -5 N [R F R CON _0 T R A-� TQ 10 N, Q N E M I� H. lq I- --T 0 N 01 T I t? N r IU. IitiIIIT AR F.4 F rz 5 P r `�'AN -TH r :A 9,jN 5 N 113 * 0 ,RDINA7 .6 L L " ?,�R "d Y,,' THER -',C T 'A PR p H E N wf�: Tx� T. I L � - I- 1.11 .1 WHICH PF-RFOR, N C E 'Q F- "'T IJOR K' R U CT eK T M5' "A K I KC ttt0 N
408,
F
No
y Jr
Ok
'KA,
1�4 ,,
r"A
WIX W,
07
'7 Vl�-,
io
yr
Yy V&
IN ll
IN
a
EF P -El%
I = NFU O -i.
,NGIN, A QT
1EXCEE skawavve sm—y-y" on-r-,
YOM' P90 -SINCF�C05T-��,DOE$K. OR
wools
J00 Rut
Soo
. . . . . . . . . . . . . . .
-00
yy
AW PA",,`,T 9
TIAWN&V WX W 020 rot.. J
D1000.fCJ fu�t IV V1J1I lHt 51It ANU FAMILIARIZE THEMSELVES WITH
EXISTING CONDITIONS AND SATISFY THEMSELVES AS TO THE NATURE AID
SCOPE OF WORK. THE SUBMISSION OF A BID WILL BE EVIDENCE THAT
SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR,
EQUIPMENT OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERI
WHICH COULD HAVE BEEN FORESEEN HAD AN EXAMINATION BEEN MADE,
WILL NOT BE ALLOWED.
ALL EXISTING CIRCUITS TO REMAIN SHALL BE RECONNECTED WHETHER
INDICATED OR NOT ON PROJECT DOCUMENTS.
NEW AND EXISTING CIRCUIT DESIGNATIONS MAY NOT REPRESENT ACTUAI
FIELD CONDITIONS. THEY ARE INTENDED FOR REFERENCE ONLY.
COORDINATE WITH OTHER TRADES FOR ITEMS IN THEIR SCOPE OF WORK
WHT('H wni II n RF(]I ITRF' r7I.r7r TDTr'AI %A/r)Dv (nTcr nKwC'rnrTCU l /nrr nnir��r.
I ll
eyp
N
a�
c
4-J
C_
(a
c
co
I
0
0
0
Cu
0
Ln
Ln
IN
a
ro
ELECTRICAL SPECIFICATIONS
1. MATERIALS AND INSTALLATION, AS A MINIMUM, ARE TO CONFORM WITH THE LATEST EDITION
OF THE NATIONAL ELECTRIC CODE, THE LATEST EDITION OF N.F.P.A., AND THE LATEST EDITIONS
OF THE LOCAL CODES AND ORDINANCES, INCLUDING ALL AMENDMENTS TO THE N.E.C. EQUIPMENT,
WHERE APPLICABLE, WILL BE LISTED WITH THE UNDERWRITERS LABORATORIES, INC. QUALITY AND
WORKMANSHIP ESTABLISHED BY DRAWINGS AND SPECIFICATIONS ARE NOT TO BE REDUCED BY THE
ABOVE MENTIONED CODES.
2. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND t,
SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF WORK. THE SUBMISSION OF A BID WILL
BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT,
OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN
HAD AN EXAMINATION BEEN MADE, WILL NOT BE ALLOWED.
3. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST-CLASS
WORKMANLIKE MANNER. THE COMPLETED SYSTEM IS TO BE FULLY OPERABLE AND ACCEPTANCE OF
THIS SYSTEM BY THE ENGINEER/ARCHITECT MUST BE A CONDITION OF THE SUB CONTRACT.
4. ALL WORK TO BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE
PROGRESS OF CONSTRUCTION.
5. CONTRACTOR TO GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR PERIOD
OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE.
6. CORRECTION OF ANY DEFECTS TO BE COMPLETED WITHOUT ADDITIONAL CHARGE AND TO INCLUDE
REPLACEMENT OR REPAIR, OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN
DAMAGED THEREBY.
7. ALL REQUIRED INSURANCE TO BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY OF
PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
8. CONTRACTOR TO PAY FOR ALL PERMITS, FEES INSPECTIONS AND TESTINGS.
9. ELECTRICAL INSTALLATION TO MEET ALL STANDARD REQUIREMENTS OF LOCAL POWER AND
TELEPHONE COMPANIES. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL POWER AND
TELEPHONE COMPANIES PRIOR TO START OF CONSTRUCTION.
10. ALL WIRING SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED, MINIMUM WIRE SIZE SHALL
BE J12 AWG, EXCLUDING CONTROL WIRING. ALL CONDUCTORS SHALL BE COPPER WITH
THWN/THHN INSULATION. CONDUCTORS #10 AND SMALLER MAY BE SOLID; ALL THOSE #8
AND LARGER TO BE STRANDED.
11. ALL UNDERGROUND RACEWAYS SHALL BE MINIMUM 3/4% GALVANIZED RIGID STEEL CONDUIT OR
SCHEDULE 40 PVC. ALL OTHER RACEWAYS TO COMPLY WITH GOVERNING CODES. WHERE RIGID STEEL
IS USED, IT SHALL BE COMPLETELY COATED WITH AN ALKALI AND RUST RESISTANT BITUMASTIC
PAINT, KOPPER NO. 50, AND THREADS SHALL BE COATED WITH ZINC CHROMATE. RIGID STEEL
SHALL ALSO BE USED WHEN CONDUIT IS EXPOSED TO EXTERIOR ENVIRONMENT SUCH AS EXTERIOR
OF BUILDING OR WHERE IT IS EXPOSED AND SUBJECT TO DAMAGE, INSIDE OF BUILDING.
12. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS
IN WET OR DAMP LOCATIONS, AND BE OF SPECIAL CONSTRUCTION FOR OTHER CLASSIFIED AREAS.
ALL BOXES SHALL BE RECESSED (FLUSH) IN WALLS OR CEILINGS WHENEVER POSSIBLE,
13. DISCONNECT SWITCHES SHALL BE N.P. RATED, GENERAL DUTY, QUICK -MAKE; QUICK -BREAK TYPE.
ENCLOSURES SHALL BE AS REQUIRED BY N.E.C. AND LOCATION (WEATHERPROOF, EXPLOSION
PROOF, ETC.). ENGRAVED LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND
INSTALLED ON ALL DISCONNECT SWITCHES, CONTACTORS AND STARTERS.
13.1. ALL FUSES FOR SAFETY SWITCHES SHALL BE DUAL ELEMENT, CARTRIDGE TYPE. FUSES SHALL BE
THOSE MANUFACTURED BY EITHER BUSSMAN OR LITTLEFUSE. THE CONTRACTOR SHALL FURNISH
TO THE OWNER ONE SPARE FUSE FOR EACH SIZE AND TYPE OF FUSE INSTALLED. FUSES 600 AMPS
OR LESS SHALL BE CLASS RK1, TYPICAL UNLESS OTHERWISE NOTED. FUSES OVER 600 AMPS SHALL
BE CLASS L.
14. ALL GENERAL PURPOSE SWITCHES AND RECEPTACLES SHALL BE THE PRODUCT OF A SINGLE
MANUFACTURER. CATALOG NUMBERS LISTED ARE LEVITON: HOWEVER, COMPARABLE DEVICES BY
PASS & SEYMOUR, BRYANT, OR ARROW HART WILL BE ACCEPTED. COLOR OF DEVICES AND
PLATES SHALL BE DICTATED BY ARCHITECT/OWNER.
A. SWITCHES: LEVITON JCSB1-20I
B. RECEPTACLES: LEVITON #BR20-I
C. COVER PLATES: SMOOTH PLASTIC
NOTE: ALL OTHER REQUIRED DEVICES SHALL MATCH IN COLOR AND STYLE.
15. ALL RACEWAYS AND PIPES, SPACED IN OR Ti1ROUGH ANY CONCRETE SLAB, SHALL BE SPACED A
MINIMUM OF THREE TIMES THE DIAMETER OF THE LARGEST RACEWAY.
16. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE
CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL
SYSTEM, AND PROVIDE ALL NECESSARY DEVICES AND COMPONENTS FOR EQUIPMENT BE PLACED IN
PROPER WORKING ORDER.
17. A SEPARATE, GREEN TYPE THW COPPER GROUND CONDUCTOR SHALL BE RUN FROM GROUND LUG OF
EACH GROUNDED RECEPTACLE TO AN APPROVED CONNECTION INSIDE THE ENCLOSING STEEL OUTLET
BOX. DEVICE MOUNTING SCREWS SHALL NOT BE CONSIDERED AN APPROVED GROUND.
A SEPARATE GROUND CONDUCTOR SHALL BE INSTALLED IN EVERY CONDUIT AND RACEWAY AND
SECURELY BONDED IN AN APPROVED GROUNDING TERMINAL AT BOTH ENDS OF THE RUN. THE
GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE 250-95 OF THE N.E.C.
CONTRACTOR SHALL SIZE CONDUIT TO ACCOMMODATE ADDITIONAL CONDUCTOR.
18. LOAD DATA IS BASED ON INFORMATION GIVEN ENGINEER AT THE TIME OF DESIGN. VERIFY ALL
EQUIPMENT NAMEPLATE RATINGS BEFORE ORDERING.
19. CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD DATA AND PANEL SIZES. THE CONTRACTOR
IS TO PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB CONDITIONS.
20. FURNISH AND INSTALL DISCONNECT SWITCHES, WIRING, AND CONNECTIONS ON AIR CONDITIONING
SYSTEM AS SHOWN ON PLANS. ELECTRICAL CONTRACTOR SHALL VERIFY AND COORDINATE WITH
MECHANICAL CONTRACTOR REGARDING SUPPLY AND INSTALLATION OF ALL REQUIRED CONTROLS.
21. ALL FLUORESCENT AND H.I.D. LIGHTING FIXTURES SHALL BE FUSED, AS REQUIRED BY LOCAL
CODE ONLY.
22.TANDEM AND HALF -SPACE CIRCUIT BREAKERS SHALL NOT BE USED.
23. TYPEWRITTEN CIRCUIT INDEX SHALL BE AFFIXED TO INSIDE SURFACE OF EACH PANELBOARD
DOOR, CLEARLY INDICATING AREA AND TYPE OF LOAD SERVED BY EACH BRANCH CIRCUIT
PROTECTIVE DEVICE, INCLUDING SPARES. HAND PRINTED WILL NOT BE ACCEPTED.
24.ENGRAVED, LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND INSTALLED
ON ALL PANELS AND SWITCHGEAR. PLATES SHALL BE AFFIXED TO FRONT OF PANELS, INDICATING
PANEL NAME, VOLTAGE AND AMPERAGE.
25. ALL ELECTRICAL CONDUCTORS SHALL BE INSTALLED IN AN APPROVED RACEWAY, EMT, RIGID
GALVANIZED CONDUIT OF SCHEDULE 40 P.V.C. TYPE 'NM', 'MC', ELECTRICAL NON-METALLIC TUBING,
& FLEXIBLE METAL CONDUIT MAY BE USED FOR RESIDENTIAL TYPE BRANCH CIRCUITING. MAXIMUM
NUMBER OF 120 VOLT CIRCUITS ALLOWED IN A COMMON CONDUIT SHALL BE SIX (6). THE
CONTRACTOR SHALL STRICTLY CONFORM TO THE N.E.C. REQUIREMENTS OF DERATING FOR
CONDUCTOR AMPACITY AND CONDUIT FILL. ELECTRICAL CONTRACTOR SHALL VERIFY W/ LOCAL
AUTHORITIES PRIOR TO SUBMITTING BID.
25.1. CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS:
208V SYSTEM _MOV SYSTEM PHASE SEQUENCE
NEUTRAL - WHITE NEUTRAL - WHITE ABC, TOP TO BOTTOM
PHASE A - BLACK PHASE A - BROWN LEFT TO RIGHT, FRONT
PHASE B - RED PHASE B - ORANGE TO BACK
PHASE C - BLUE PHASE C - YELLOW
GRD.CON - GREEN GRD.CON - GREEN
26. CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING ALL CONDUIT PENETRATIONS MADE THROUGH
FIRE RATED WALLS, CEILINGS, SLABS, ETC. PENETRATION SEALS SHALL BE PER U.L. ASSEMBLY
STANDARDS.
27. CONTRACTOR SHALL PROVIDE SHOP DRAWING SUBMITTALS FOR LIGHT FIXTURES, SWITCHGEAR,
WIRING DEVICES, EMERGENCY GENERATOR/TRANSFER EQUIPMENT, AND ALL SYSTEMS (FIRE ALARM,
SECURITY, ETC.) PROVIDE TWO (2) COPIES, TEN (10) DAYS PRIOR TO BID DATE FOR ENGINEER'S
APPROVAL TO SUBMIT. ENGINEER'S APPROVAL OF THE PRIOR APPROVAL PACKAGE WILL BE
CONSIDERED PRELIMINARY. FINAL APPROVAL WILL BE CONTINGENT UPON REVIEW OF FINAL SHOP
DRAWINGS. ALL PROPOSED ALTERNATES MUST BE INDUSTRY STANDARD EQUALS TO THE ITEMS
SPECIFIED AS THE BASIS OF DESIGN; HOWEVER, IF THE ITEMS ARE NOT CONSIDERED EQUAL BY
THE ENGINEER, IT SHALL BE DISAPPROVED FOR FINAL SUBMITTAL. IF ELECTRICAL CONTRACTOR/
GENERAL CONTRACTOR DOES NOT SUBMIT SHOP DRAWINGS TO ELECTRICAL ENGINEER FOR ITEMS
LISTED ABOVE, ELECTRICAL ENGINEER WILL NOT BE RESPONSIBLE FOR ANY, AND OR OMISSIONS
OR ERRORS DUE TO SHOP DRAWINGS NOT SUBMITTED. SHOP DRAWINGS WILL ONLY BE REVIEWED
TWICE AS PART OF THIS CONTRACT. ADDITIONAL SHOP DRAWING REVIEWS SHALL BE INVOICED
AT 185.00 PER HOUR, BILLABLE TO THE SUB -CONTRACTOR, C.O.D.
28. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF CONTRACT DRAWINGS AT JOB SITE WITH
COLORED MARKINGS INDICATING PROGRESS OF WORK. THIS SET OF CONTRACT DRAWINGS IS TO
BE SEPARATE FROM AND IN ADDITION TO CONTRACTOR'S CONSTRUCTION SET. EVERY UNIT OF
EQUIPMENT, DEVICE, CONDUIT AND WIRE IS 'TO MARKED WHEN INSTALLED. USE SREEN TO
INDICATE INSTALLATION AS SHOWN ON DRAWINGS AND USE EM TO INDICATE FIELD CHANGES.
UPON COMPLETION OF WORK, THIS SET OF CONTRACT DRAWINGS IS TO BE TURNED OVER TO,
AND BECOME PROPERTY OF THE ARCHITECT.
29. THE OWNER RESERVES THE RIGHT TO REVISE THE DRAWING FROM TIME TO TIME TO INDICATE
CHANGES IN THE WORK. WHEN REVISED DRAWING ARE ISSUED, THE CONTRACTOR SHALL
EVALUATE THE CHANGES PROMPTLY. BEFORE INSTALLATION OF ANY ITEM OR PERFORMANCE OF
THE WORK INDICATED BY THE REVISED DRAWINGS, THE CONTRACTOR SHALL NOTIFY THE OWNER
IN WRITING THAT THE REVISED DRAWINGS INVOLVE AN ADDITION OR DEDUCTION OF A SPECIFIC
AMOUNT OF MONEY TO THE CONTRACT PRICE. THE CONTRACTOR SHALL NOT PROCEED WITH THE
REVISED WORK WITHOUT PRIOR WRITTEN APPROVAL BY THE OWNER OF THE COST OF THE REVISED
WORK.
30. IF ELECTRICAL CONTRACTOR HAS QUESTIONS, OR IN THEIR OPINION FINDS OMISSIONS OR
ERRORS ON ELECTRICAL DOCUMENTS, IT IS THEIR RESPONSIBILITY TO BRING THIS TO THE
ATTENTION OF THE ELECTRICAL ENGINEER/ARCHITECT/OWNER IMMEDIATELY. IF ELECTRICAL
CONTRACTOR PROCEEDS WITH Aa CHANGES TO THE CONTRACT DOCUMENTS WITHOUT WRITTEN
PRIOR APPROVAL FROM THE ELECTRICAL ENGINEER/ARCHITECT/OWNER WILL NOT BE COMPENSATED;
,
10 1
FLUSH MOUNTED PANEL "A" w/ ISOL. GROUND (EXISTING) MAIN BKR — 1
'120/208V,, 30, 4W. SQUARE-D TYPE "NQOD", 10,000 AIC (INTEGRATED) MAIN LUGS 225A
POLE
NO.
TRIP
AMP
BKR
POLE
WIRE
GND
WIRE
COND
SERVES
LOAD V.A.
POLE
NO.
TRIP
AMP
BKR
POLE
WIRE
GND
WIRE
COND
SERVES
A
B 0
C 0
1
20
1
2#12
1 ##12
1/2"
PLUGMOLU
1}5 75
18.0-
360r
/-600
`too;
q 2<LF)
360-
54CJ
360
_ J40
540
360
/1000
-840
,
-c524-0
`>
360
2
20
1
2#12
1 #12
1 /2"
QUAD RECEPTACLE
'
72C
.� J0C1
.�Fa �
<
500
1040->
<
3
20
1
2##12
1 ¢#12
1 /2"
ROOF TOP RECEPTACLE
4
20
1
2#12
1 #"1 2
1/2"
QUAD RECEPTACLE
c-
a
20
1
2##12
l�#12
/
1,2"
RECEPTACLES
C
� '
0
1
?
2#i2
1#12
1/2"
T C
F•ECEF Pr�CLE�
7
20
1
2##12
1#12
1/2"
RECEPTACLES `
8
20
1
2#12
1#12
1/2"
-rELLER
9
20
1
2#12
1 # 12
1 /2"
WORKROOM
10
20
1
2#12
1 #12
1/2"
BANK DISPLAY
1 I
20
1
2#12
1 #121
/2"
-rELEPt-1ON
j 12
2Q
1
2##12.
1360 :j#12
1/2"
WORKROOM
13
20
1
2#12
-1 #12
1/2"
REFRIGERA 1OR
14'
20
1
2#12
1 #12
1/2"
RECEPTACLES
15
20
1
2#12
2
1 #12
1, 2
' '„
PR.[id rER
16
20
1
2##12
1 ##12
1, 2"
LIGHTING
17
20
1
2#12
1 {#12
1/2"
COPIER
> 18
20
1
2#12
1 #12
1 /2"
LIGHTIt tG
19
21
23
.30
3
4,r'#1 U
1 #1 Q
1 /2"
SURGE SUPPRESSOR
20
100
3
3#3
1 #8
1 1 /4"
RJU-'I (HEA r)
22
;2 r
25
20
1 1
2#12
1#12
1/2"
SERVER
26
20
1
2#12
11/12
1/2"
LIGHrI11G
27
?_0
1
3#/12
2j 12
1 /2"
RECEPTS (f?PA 11h,115
28
20
1
3#12
2##12
1 /2"
� -�
RECEP 1a (RM 116,117,1'18)
29
20
1
RECEP r5 (RPr1 120,1211)
, 30
20
1
RECEPTS (RM 1 18)
-S4Q
540
31
20
1
3##12
2##12
1;�2"
RECEPTS (FOv1 103,112,113)
32
20
1
3#12
2#12
1/2 "
RECEPTS (COMP./WK. STA. 1,2)
540
54Q
3.3
20
1
RECEPTS (RN1 102,103,105)
34
20
1
RECEPTS (V.P. OPS/OPS MGR.)
360
35
20
1
3#12
2#12
1/2"
RECEPTS (TREAS./ACCTG. SUPV.)
36
-
1
-
-
-
SPACE ONLY
37
20
1
RECEPTS (WIRE/WK. STA. 1,2)
38
-
1
-
-
-
SPACE ONLY
39
1
-
-
SPACE ONLY
40
-
1
-
-
-
SPACE ONLY
_
41
-
1
-
-
-
SPACE ONLY
42
-
1
-
-
-
SPACE ONLY
\
CONNECTED V.A. PER PHASE
16280
14170
14320
rONNECTED AMPS PER PHASE
136
118
119
IG - ISOLATED GROUND CIRCUIT
ELECTRICAL LEGEND
rim F-1 FLUORESCENT LIGHT FIXTURE, LETTER INDICATES TYPE
QB INCANDESCENT OR HID LIGHT FIXTURE, LETTER INDICATES TYPE
FO C WALL BRACKET LIGHT FIXTURE, LETTER INDICATES TYPE
*0 EXIT LIGHT (ARROW INDICATES DIRECTION)
BATTERY POWERED EMERGENCY LIGHT
S. SINGLE POLE SWITCH, LOWER CASE LETTER INDICATES. LIGHT
CONTROLLED, MOUNT 48" A.F.F. U.O.N.
S2 DOUBLE POLE SWITCH, MOUNT 48" A.F.F. U.O.N.
S3 THREE-WAY SWITCH, MOUNT 48" A.F.F. U.O.N.
0 DIMMER SWITCH, WATTS AS NOTED, MOUNT 48" A.F.F. U.O.N.
S M MOTOR RATED SWITCH
DUPLEX RECEPTACLE, MOUNT 18" A.F.F. U.O.N.
DUPLEX RECEPTACLE, MOUNT ABOVE COUNTER HEIGHT U.O.N.
QUADRAPLEX RECEPTACLE, MOUNT 18" A.F.F. U.O.N.
@5 30A 10, 25OV. RECEPTACLE, AMPS AS NOTED, MOUNT 18" A.F.F. U.O.N.
Q FLOOR MOUNTED DUPLEX RECEPTACLE
JQ JUNCTION BOX (FLUSH MOUNT IN FINISHED AREAS U.O.N.)
DEVICE AS NOTED
LIGHTING OR POWER PANELBOARD
CONDUIT CONCEALED IN WALL OR ABOVE CEILING WITH 2 #12, 1 #12
E.G. CONDUCTORS IN 1/2" CONDUIT MIN. U.O.N.
® COMBINATION TELEPHONE/DATA OUTLET. PROVIDE 3/4" C. WITH
PULL -CORD STUBBED INTO CEILING SPACE WITH INSULATED
BUSHING. MOUNT 18" A.F.F. U.O.N.
ABBREVIATIONS
EG EQUIPMENT GROUND NIL NIGHT LIGHT
IG ISOLATED GROUND C/T CURRENT TRANSFORMER
WP WEATHERPROOF EX EXISTING DEVICE
EWH ELECTRIC WATER HEATER AFF ABOVE FINISH FLOOR
EWC ELECTRIC WATER COOLER AFG ABOVE FINISH GRADE
E/F-EF EXHAUST FAN U.O.N. UNLESS OTHERWISE NOTED
A/H-AHU AIR HANDLING UNIT N.T.S. NOT TO SCALE
ACC-CU CONDENSING UNIT EC EMPTY CONDUIT
RTU ROOF TOP UNIT
NOTE: MOUNTING HEIGHTS NOTED ARE TO CENTERLINE OF DEVICE SHOWN. U.O.N.
(NOT ALL SYMBOLS MAY BE USED FOR A PARTICULAR PROJECT) /
IG
IG
IG
IG
IG
IG
IG
FLUSH MOUNTED
120/208V., 30, 4W.
PANEL Opp" (EXISTING)
SQUARE 'D' TYPE "NQOD", 10,000 A.I.C. (INTEGRATED)
MAIN BKR —
MAIN LUGS 225A
POLE
NO.
TRIP
AMP
BKR
POLE
WIRE
GND
WIRE
COND
SERVES
LOAD V.A.
POLE
NO.
TRIP
AMP
BKR
POLE
WIRE
GND
WIRE
COND
SERVES
A 0
B 0
C 0
1
20
1
<
RECEPTS (LOUNGE/RM )
900
1000
<
720
-360
I��oU
>
900
.>
i`
1500
680
>
1120
900
-�_TC)
2
20
1
4##12
1##12
1/ 2"
REFRIGERATOR
3
20
1
RECEPTS HALL/RM
( )
4
20
1
MICROWAVE
1000
>
1540
154U
1 120-
i1>zo
`
' 780
-5h� -
<
2fJ
I
z##12
1##12
1/2"
FtECFr''rS (FZPA 114,115)
> °
20
1
COFFEE
7
20
1
RECEPTS (RM 120,121)
8
20
I
'�,�12
1 #12
1/2"
FAX
9
20
1
4#12
1 ##12
1/2"
LIGHTS (OPS MGR.,VP/WK. STA.)
10
20
1
COPIER
11
20
1
LIGHTS (TREAS./ACCTG./COMP.)
r 12
20
1
3'12
��
i 12
�#
1 �
/`„
LIGHTS (HALL 1)
13
20
1
LIGHTS (FILES) `'
14
20
1
LIGHTS (RM '102.,103,106)
1400
14-5
15
20
1
i##12
1##12
/`
1, 2"
LIGHTS (FUTURE OFFICES)
16
20
1
3}#12
1##12
ii.2„
LIGHTS (RM '112,1 13,116)
17
20
1
2##12
1##12
1/2"
LIGHTS (RM 114,115,120,121)
18
20
1
LIGHTS (PM 117,118)
19
20
1
3##12
1 ##12
1 / 1"
LIGHTS (VAULT) {
20
20
1
3#12
1 #12
1/2"
RECEPTS (RN1 116,117, 118)
540 <
1900
21
20
1
LIGFITS (FILE/DEAD SrUR.)
22
20
1
RECEPTS (RM 118)
23
20
1
2j#12
1;#12
1/2"
VAULT RECEPTS
,24
20
i
2#t12
1 #12
1 j 2"
RECEPTS (RM '112,113,'114)
25
20
1
3#12
1#12
1/2"
RECEPTS (V.P. OPS/OPS MGR.)
26
20
1
3#12
1#12
1/2
RECEPTS (TREAS./ACCTG. SUPV.)
27
20
1
RECEPTS (COMP.)
20
1
RECEPTS MIS
( /WIRE)
108�
29
-
1
-
-
-
SPACE ONLY
N32
-
1
-
-
-
SPACE ONLY
_
31
-
1
-
-
-
SPACE ONLY
-
1
-
-
-
SPACE ONLY
_
33
-
1
-
-
-
SPACE ONLY
34
-
1
-
-
-
SPACE ONLY
_
35
-
1
-
-
-
SPACE ONLY
36
-
1
-
-
-
SPACE ONLY
_
37
-
1
-
-
-
SPACE ONLY
38
-
1
-
-
-
SPACE ONLY
_
39
-
1
-
-
-
SPACE ONLY
40
-
1
-
-
-
SPACE ONLY
_
41
-
1
-
-
-
SPACE ONLY
42
-
1
-
-
-
SPACE ONLY
CONNECTED V.A. PER PHASE
9755
10260
8840
J
CONNECTED AMPS PER PHASE
81
86
74
EXISTING 2500 AMP MAIN
SWITCHBOARD
r--------------------------------------------n
I I
r---------r----a----r------------ i 1
I I
PANEL
I I I I I I I I "f7"
I I I I I I I I I I I I I (EX.)
i I I L_J I I I I I I I 1
I I I L_J I I I I I I I
I I I I I I I I 1 I I I
I I L L 1 1 L L J J
1
j
L-------------------------
I
I
I
L-----------------Sj § - - - - - - -
PARTIAL O RISER DIAGRAM
N.T.S.
TOTAL CONNECTED LOAD (NEW):
6.1 KW @ 120/208V-30, 4W = 17 AMPS
1 1
EXISTING 200 AMP FEEDERS,;;
ca
PANEL
co
Cl X
61
(
TVSS
1
M r,
H 1ro1 & Associates, Inc..
TING ENGINEERS
�ray Street :Tampa, Florida 33609 _
el • ,+?8'13) 287-2719 Fax: (813) 287-5704 , 3 3 �
v
\'4
PLAPIS'
cay C;r
off rr"
-FINAL
MUST MEET FL,R1DA
ACCESSIBILITY CODES
MUST MEET FLORID
Y:I"
C
E:NLERGY CODES
ff
GRY of Sanford
Model Codes in effact:
Standard BUilding Code 1997 ed.
Standard PlUmbing Code 1997 ed.
Standard Mechanical Code 1997 ed.
National Electrical Code 1906 ed.
See City Code AMENDINIEN-rs
FL. Accessibility Codes 1997
FL. Energy Code 1997
SANFORD BUILOINO bgffr.
THESE PLANS ARE REVIRWE'O ANP 9�C*QiTIONALLY
ACCEPTED FOR Pewvirr, A rifflMIT ISSUED SHALL BE
CONSTRUED TO OC A LICENSE TO PROCEED WITH
THE WORK AND NOT AS AUTHORITY TO VIOLATE,
CANCEL, ALTER, OR '5ET ASIDE ANY OF THE
PROVISIONS OF THE: TECHNICAL CODES, NOR SHALL
ISSUANCE OF A PERMIT PREVENT THE BUILDING
DEPT FROM THEREAFTER REQUIRING A.CORREC-
-ViQ17J.QF-9RRQR5 ON THE PLANS, CONSTRUCTION
nR nTHER VIOLATIONS OF THE CODES.
Be
PERMIT