HomeMy WebLinkAbout3767 S Orlando Ave 06-594 Electrical upgradeCITY OF SANFORD PLRMIT AI PL.ICATION
_ t
Job Address: .7, -7� 7
Description of Work:
Historic District:
e ,e lei e
Zoning:
R�ECE! V :LE,
Date: _ _ r//// 0;s-
NQT 12005
Value of Work: $ /,5, "cy, ac�'
Permit Type: Building Electrical // Mechanical—_ Plumbing _ Fire Sprinkler/Alarm Pool
Electrical: New Svt-viee — li of AMPS _ 2 0�0 Addition/Alteration _.,____ Change of Service Temporary Pole __
Mechanical: Residential - Non -Residential Replacetnent __- New (Duet Layout & Energy Cale, Required)
Plumbing/ New Commercial: # of Fixtures # of Water & Sewer Lines # of Gas Lines _ __
Plumbing/Nets, Residential: # of Water Closets _ Plumbing Repair — Residential or Commercial _
Occupancy Type: Residential Commercial fi" Industrial Total Square Footage.
Construction Type: # of Stories: # of Dwelling Units: Flood Zone: (FEtMA form required for other than X)
Parcel #:
Owners Name & Address:
s 7
Contractor Name & Address:
(Attach Proof of Ownership & Legal Description)
)I /
'F pf`o J.ye- _ Phone
State License Number:
Phone & Fax:
_1�� - _.
O l �! - 3 �� i Yl�' Contact Person: l3 - Phnne: G Gy
Bonding Company:
Address:
Mortgage Lender: .
Address--
Architect/Engineer:
Address:
5
!Tune:
Fax:
Application is hereby uradc to obtain a pcnnit to do the work and installations as indicated, l cettily that no work ur inslallaliou has conunenced prior to lho
issuance of a pcnnit and that all work will be pertonned to meet standards of all Taws regulating construction in thus jurisdiction. I understand that a separate
permit must be secured for ELECTRICAL WORK, PLUMBING, SIGNS, WELLS, POOLS, FURNACES, BOILERS, HEATERS, TANKS, and
AIR CON DIIONERS, ctc.
OWNER'S AFFIDAVIT: I certify that all of the horegoing information is accurate and that all work will be done in compliance with all applicable laws regulating
construction and zoning. WARNING'f0 OWNER: YOUR FAILURE TO RECORD A NOTICE, OF COMMENCEMENT MAY RESULT IN YOUR PAYING
TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT W1111 YOUR LENDER OR AN
ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT-.
NOTICE: In addition to the requirements of this permit, there may be additional restrictions applicable to this property that may be Ibund in the public records of
this county, and there may be additional permits required from other governmental entities such as water management districts, state agencies, or federal agencies.
Acceptance of pennit is verification that I will notify the owner of the property of the rcquhcm' tra' lorida Lico Law, FS 713.
Signature of Owner/Agent Date nature of Contractor/Agent Date
rA
lvrin_�t(C.nt
PrintOwner/Agcnt's Namc tactpdAgcn['s amc
Signature of -Notary -State of Florida Date Signature of Notary -State of Florida Date
N.>
4, DC:l]faR ESLANTON
N1Y 0.N• "rir' .;ION # DD '! 8t3491
Owner/Agent is _ Personally Known to Me or Contractor/Aent,(s Pcksgjl��ly,l rLy�)ydtaf9 `t %7
Produced ID T _ Productl J[��„1_�;�.,,� rW✓„ ^.�� `r� V��
APPLICATION APPROVED BY: Bldg: Zoning: Utilities: FD:
(Imti )Date) (Initial & Date) (Initial & Date) (Initial & Date)
Special Conditions:_._
16000 GENERAL ELECTRICAL REQUIREMENTS
A. THE COMPLETE ELECTRICAL INSTALLATION SHALL COMPLY WITH THE LATEST ADOPTED
EDITION OF THE FOLLOWING CODES & STANDARDS.
1. NFPA 70 NATIONAL ELECTRICAL CODE 2002 ED.
2. NFPA 90A STANDARD TO THE INSTALLATION OF AIR CONDITIONING AND VENTILATING
SYSTEMS.
3. NFPA 101 LIFE SAFETY CODE.
4. ANSI A117.1 ACCESSIBILITY CODE.
5. FLORIDA AMERICANS WITH DISABILITIES ACCESSIBILITY IMPLEMENTATION ACT AS
DESCRIBED IN ACCESSIBILITY REQUIREMENTS MANUAL, DEPARTMENT OF COMMUNITY
AFFAIRS.
6. AMERICANS WITH DISABILITIES ACT.
7. FLORIDA BUILDING CODE 2004.
8. FLORIDA FIRE PREVENTION CODE 2004 Ed.
B. 'FURNISH AND INSTALL' AND 'PROVIDE' ARE EQUIVALENT TERMS WHICH INDICATE MATERIAL
AND/OR EQUIPMENT SUPPLIED AND INSTALLED BY THIS CONTRACTOR. 'FURNISHED'
DENOTES MATERIAL OR EQUIPMENT SUPPLIED BUT NOT INSTALLED BY THIS CONTRACTOR.
'INSTALLED' DENOTES THE SETTING IN POSITION OR CONNECTION OF MATERIAL OR
EQUIPMENT BY THIS CONTRACTOR BUT SUPPLIED BY OTHERS.
C. IT IS THE REQUIREMENT OF THESE CONTRACT DOCUMENTS TO HAVE THE CONTRACTOR
PROVIDE SYSTEMS AND COMPONENTS THAT ARE FULLY COMPLETE AND OPERATIONAL AND
FULLY SUITABLE FOR THE INTENDED USE.
D. DRAWINGS ARE DIAGRAMMATIC AND SHOULD NOT BE SCALED TO DETERMINE EXACT
LOCATIONS. VERIFY ALL LOCATIONS AND REQUIREMENTS OF EQUIPMENT FURNISHED
AND/OR INSTALLED BY OTHERS BEFORE ROUGHING IN.
L ELECTRICAL SYSTEMS SHALL BE INSTALLED AS A COMPLETE INSTALLATION, INCIDENTAL
DETAILS NOT USUALLY SHOWN OR SPECIFIED, BUT NECESSARY FOR PROPER INSTALLATION
AND OPERATION SHALL BE INCLUDED IN THE WORK OF THIS CONTRACTOR.
F PREBID SURVEY
1. THIS CONTRACTOR SHALL SURVEY THE JOBSITE PRIOR TO SUBMITTING THEIR BID TO
DETERMINE THE FOLLOWING:
a- AREAS REQUIRING DEMOLITION, TEMPORARY POWER, RELOCATING, ETC, WHICH ARE
INADVERTENTLY NOT SHOWN ON THE DRAWINGS.
b. PROBLEMS WITH WORK SEQUENCE,
2. ANY UNUSAL CONDITIONS NOT SHOWN ON THE DRAWINGS SHALL BE REPORTED TO
THE ENGINEER PRIOR TO BIDDING,
G. ACCEPTABLE MANUFACTURERS: THE LISTING OF A MANUFACTURER AS "ACCEPTABLE" UNDER
ANY DIVISION 16 REQUIREMENTS DOES NOT IMPLYAUTOMATIC APPROVAL IT IS THE SOLE
RESPONSIBILITY OF THE CONTRACTOR TO ENSURE THAT ANY SUBMITTALS MADE ARE FOR
PRODUCTS THAT MEET OR EXCEED THE SPECIFICATIONS INCLUDED HERE.
H. UPON COMPLETION OF THE WORK, BUT BEFORE FINAL ACCEPTANCE OF THE SYSTEM AND
REQUEST FOR FINAL PAYMENT, FURNISH THE OWNER, FOR APPROVAL, OPERATION AND
MAINTENANCE MANUALS IN LOOSE-LEAF BINDERS. PROVIDE A MINIMUM OF 6 SETS.
I PROVIDE OWNER WITH A RECORD SET OF AS -BUILT DRAWINGS FROM A DESIGNATED MARKED -UP
SET OF BLUELINES.
J. PROVIDE TEMPORARY ELECTRICAL POWER TO JOBSITE FOR THE DURATION OF THE PROJECT.
K. SUBMIT SHOP DRAWINGS TO ARCHITECT FOR ALL ELECTRICAL ITEMS THE SHOP DRAWINGS
SHALL BE SUBMITTED COMPLETE FOR ALL ELECTRICAL ITEMS. INCOMPLETE SUBMITTALS WILL
BE RETURNED WITHOUT BEING REVIEWED OR THE CONTRACTOR SHALL AGREE TO PAY THE
ELECTRICAL ENGINEER DIRECTLYAT AN HOURLY RATE OF $95.00 TO REVIEW SUBSEQUENT
SUBMITTALS. SHOP DRAWING RE -SUBMITTALS DUE TO REJECTIONS FOR NOT SUBMITTING
THE SPECIFIED ITEMS ARE ALSO SUBJECT TO THE HOURLY REVIEW FEE.
L DIVISION 16 SUB -CONTRACTOR SHALL REVIEW DIVISION 15 SHOP DRAWINGS AND VERIFY
EQUIPMENT VOLTAGE, PHASE AND AMPS PRIOR TO ROUGH -IN OF ALL EQUIPMENT.
M ALL EQUIPMENT, DEVICES, ETC. FURNISHED BY ELECTRICAL CONTRACTOR SHALL BE U.L LISTED
(OR EQUIVALENT NATIONAL TESTING AGENCY) FOR ITS INTENDED PURPOSE. INFORM OWNER
THAT ALL OWNER FURNISHED EQUIPMENT, DEVICES, ETC. MUST ALSO HAVE A UL LISTING
(OR EQUIVALENT LISTING).
N. ALL ELECTRICAL COMPONENTS (CONDUIT, WIRE, FITTINGS, SUPPORTS, CIRCUIT BREAKERS,
LAMPS, ETC.) PROVIDED AND INSTALLED IN THIS PROJECT SHALL BE BRAND NEW. RE -USE
OF EXISTING COMPONENTS WILL NOT BE APPROVED.
16020 ELECTRICAL IDENTIFICATION
A. PROVIDE CABLE/CONDUCTOR IDENTIFICATION BANDS.
B. PROVIDE ENGRAVED PLASTIC LAMINATE SIGNS, WHITE LETTERING ON A BLACK BACKGROUND,
FOR EACH UNIT OF THE FOLLOWING CATEGORIES OF ELECTRICAL WORK SWITCHBOARDS,
MOTOR STARTERS, TRANSFORMERS, PANELBOARDS DISCONNECTS, AND JUNCTION BOXES
NAME PLATES SHALL IDENTIFY PANEL DESIGNATION (NAME), VOLTAGE, PHASE AND WIRE
CONFIGURATION.
C. UNDERGROUND CABLE/CONDUIT IDENTIFICATION PLASTIC LINE MARKERS SHALL BE PROVIDED
THE CONTINUOUS TRENCH LENGTH.
16040 ELECTRICAL DEMOLITION AND ALTERATIONS
A. ANY EXISTING CIRCUITS OR EQUIPMENT NOT SHOWN ON DRAWINGS AND WHICH ARE
LOGICALLY EXPECTED TO BE CONTINUED IN SERVICE SHALL BE RECONNECTED IN AN
APPROVED MANNER.
B. WIRING TO ELECTRICAL EQUIPMENT BEING DISCONNECTED SHALL BE REMOVED BACKTO
THEIR OVERCURRENT DEVICE OR BACK TO NEAREST ACTIVE JUNCTION BOX.
C. CONTRACTOR SHALL PROVIDE SUPPORT FOR EXISTING CONDUIT IN REMODELED AREA THAT IS
TO REMAIN AND IS NOT PROPERLY SUPPORTED IN ACCORDANCE WITH N.E.C. REQUIREMENTS.
D. EXCEPT FOR CONDUIT, CONDUCTORS AND MISCELLANEOUS HARDWARE, ALL ELECTRICAL
EQUIPMENT SHALL REMAIN THE PROPERTY OF THE OWNER AND SHALL BE STORED OR
DISPOSED OF AS DIRECTED BY OWNER,
A. MINIMUM SIZE CONDUIT SHALL BE 112". DOES NOT APPLY TO MC CABLE.
B. CONDUIT SHALL BE MC CABLE, ELECTRICAL METALLIC TUBING, OR RIGID GALVANIZED STEEL
CONDUIT. SCHEDULE 40 PVC CONDUIT IS ALLOWED FOR CONDUITS IN/UNDER THE SLAB AND
UNDERGROUND.
C. ALL CONDUIT SHALL BE CONCEALED. CONDUIT SHALL BE EMT IN INTERIOR AREAS, AND
RIGID GALVANIZED STEEL CONDUIT IN EXTERIOR AREAS.
D. COORDINATE ROUTING (LOCATION) OF CONDUIT WITH HVAC DUCTWORK, PLUMBING PIPING
AND SPRINKLER PIPING.
E. SECURE CONDUIT IN PLACE WITH CORROSION -PROOF ALLOY STRAPS AT SPACINGS AS
REQUIRED BYN.E.C. CONDUIT SHALL BE SECURED TO BUILDING STRUCTURE.
F INSTALL FLEXIBLE STEEL CONDUIT NOT OVER 3' LONG TO MOTORS, TRANSFORMERS
AND EQUIPMENT SUBJECT TO VIBRATION.
G. INSTALL LIQUID -TIGHT FLEXIBLE CONDUIT NOT OVER 3' LONG WHERE SUBJECT TO
MOISTURE, DIRT OR FUMES.
H TYPE MC CABLE SHALL BE OF THE INTERLOCKING JACKET TYPE. CABLE SHALL BE SUPPORTED
AT NOT MORE THAN SIX-FOOT INTERVALS, AND ALL FITTINGS SHALL BE IDENTIFIED FOR USE
WITH SAID CABLE. MC CABLE SHALL NOT BE USED FOR SERVICE ENTRANCE OR IN EXPOSED
AREAS. MC CABLE MAYBE USED ABOVE DROP CEILINGS AND IN INTERIOR PARTITIONS.
1. CONTRACTOR SHALL MINIMIZE FLOOR SLAB PENETRATIONS.
J. ALL CONDUIT RUNS SHALL BE DESIGNED TO PRESENT A NEAT AND ORDERLY APPEARANCE,
RUNNING LINES PARALLEL WITH BUILDING STRUCTURE OR WALLS
K. ROOFTOP UNITS AND EXHAUST FANS ARE TO BE WIRED THROUGH THE ROOF CURBS OR
UTILIZE FACTORY -FABRICATED ROOF PIPING CURBS PITCH POCKETS ARE NOT ALLOWED.
L ROMEX CABLE IS NOT PERMITTED.
M. CONDUIT SHALL BE ROUTED PERPENDICULAR THROUGH RATED WALLS. PROVIDE PROPER
16120 WIRES, CABLES AND CONNECTORS
A. ALL CONDUCTORS SHALL BE COPPER WITH 600V 90°C THHN/THWN INSULATION.
B. USE SOLID CONDUCTOR, SINGLE CONDUCTOR, NO. 12 AWG MINIMUM FOR GENERAL USE
WIRING.
C. USE STRANDED CONDUCTOR, SINGLE CONDUCTOR NO. 12 AWG AND LARGER, FOR MOTORS
AND OTHER INSTALLATIONS WHERE VIBRATION IS GENERATED.
D. COLOR -CODING SHALL IDENTIFY THE SAME PHASE THROUGHOUT THE SYSTEM, FROM
SERVICE SWITCH OR TRANSFORMER THROUGH ALL BRANCH CIRCUITRY. ALL WIRING SHALL
BE COLOR -CODED AS FOLLOWS:
2081120 VOLT
PHASE A -BLACK
PHASE B-RED
PHASE C-BLUE
NEUTRAL -WHITE
E A STANDARD 500V MEGGER INSULATION TEST SHALL BE MADE AND RECORDED FOR ALL
RESULTS TO ENGINEER FOR REVIEW.
FEEDER CIRCUITS. PROVIDE COPY OF TEST
D
F. PROVIDE LUGS FOR FEEDER SIZES INDICATED ON DRAWINGS OR AS REQUIRED.
G. WIRE SIZE FOR 120V BRANCH CIRCUITS SHALL BE PER THE FOLLOWING LENGTH OF RUNS:
1. 0 TO 50 FT RUN FROM PANELBOARD TO FIRST OUTLET, NO. 12 AWG MINIMUM.
2. 51 TO 100 FT RUN., INCREASE ONE WIRE SIZE, LE. NO. 12 AWG BECOMES NO. 10
AWG TO FIRST OUTLET.
3. 101 TO 150 FT RUN: INCREASE TWO WIRE SIZES, I. E. NO. 12 AWG BECOMES NO. 8
AWG TO FIRST OUTLET.
4. 151 AND ABOVE. WIRING SHALL BE SIZED FOR 3% MAXIMUM VOLTAGE DROP.
16130 BOXES
A. WALL OUTLET BOXES SHALL BE 4 INCH SQUARE WITH A TOTAL DEPTH OF LESS THAN
2-112" GALVANIZED PRESSED STEEL WITH PLASTER RINGS OR GANG COVER, OR SIZED
AS REQUIRED.
R WHERE MORE THAN TWO SWITCHES OR DEVICES ARE LOCATED AT ONE POINT, USE GANGED
BOXES AND COVERS.
C. ALL BOXES FOR ELECTRICAL EQUIPMENT SHALL HAVE COVERS.
D. DO NOT INSTALL BOXES BACK TO BACK OR THROUGH WALL OFFSET OUTLET BOXES ON
OPPOSITE SIDES OF WALL A MINIMUM OF 12 INCHES OR ON OPPOSITE SIDES OF STUD IN
PARTITION WALLS. WHERE BACK TO BACK BOXES CANNOT BE AVOIDED, PROVIDE GYPSUM
BOARD BETWEEN BOXES. PROVIDE PUTTY PADS ON ALL BOXES WHERE REQUIRED.
16140 WIRING DEVICES
A. WIRING DEVICES SHALL BE MANUFACTURED BY HUBBELL, BRYANT OR LFVITON.
B. RECEPTACLES SHALL BE HEAVY DUTY DUPLEX, 2 POLE, 3 WIRE, GROUNDING, 20 AMP,
125 VOLT, DESIGNED FOR SIDE AND BACK WIRING WITH NEMA CONFIGURATION 5-20R.
DESIGN SELECTION. HUBBELL CR-5362-L
C. RECEPTACLES NEXT TO DATA OUTLETS SHALL BE TVSS. DESIGN SELECTION:
HUBBELL 5360-ISA.
D. GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLES SHALL BE NEMA 5-20R AND EQUAL
TO HUBBELL GFR-5352-L
E. SWITCHES SHALL BE HEAVY DUTY SINGLE POLE AC QUIET SWITCHES, 20 AMPERES, EQUAL
TO HUBBELL CS- 1221-1, CS- 1223-1 (THREE-WAY), CS- 1224-1(FOUR-WAY).
F. PROVIDE SMOOTH NYLON COVERS FOR ALL DEVICES.
16155 MOTOR STARTERS
A. PROVIDE STARTER OF NEMA SIZE AND VOLTAGE RATING COMPATIBLE WITH MOTOR.
B. MANUFACTURERS SHALL BE G. E., SQUARED' OR SIEMENS.
C. AC FRACTIONAL HORSEPOWER MANUAL STARTERS, 2 POLE, SIZE AND RATING AS REQUIRED.
EQUIP WITH MANUALLY OPERATED TOGGLE -MECHANISMS, AND WITH ONE PIECE MELTING
ALLOY TYPE THERMAL UNITS, GREEN PILOT LIGHT, AND SWITCH CAPABLE OF BEING PAD-
LOCKED OFF. ENCLOSE STARTER IN NEMA TYPE 1 ENCLOSURE. SQUARE 'D' TYPE'P.
D. MANUAL MOTOR STARTING SWITCHES, 2 POLE, TOGGLE TYPE WITHOUT OVERLOAD
PROTECTION, SIZE AND RATING AS REQUIRED. NEMA 1 ENCLOSURE WITH SWITCH TOGGLE
GUARD WITH OFF LOCK -OUT FEATURE, SQUARED TYPE'K.
E MEGGER CHECK PHASE -TO -PHASE AND PHASE -TO -GROUND INSULATION LEVELS. DO NOT
MEGGER CHECK SOLID-STATE EQUIPMENT. TEST EACH MOTOR AND RECORD NAMEPLATE
DATA, OVERLOAD RELAY EQUIPMENT, PROTECTIVE RELAY SETTING, VOLTAGE AND CURRENT
PHASE READINGS AND DIRECTION OF ROTATION.
F. MAGNETIC COMBINATION NON -REVERSING STARTERS WITH CIRCUIT BREAKERS. EQUIP
STARTERS WITH BLOCK TYPE MANUAL RESET OVERLOAD RELAYS. PROVIDE ONE NORMALLY
OPEN AND TWO NORMALLY CLOSED AUXILIARY CONTACTS. PROVIDE MINIMUM 50VA CONTROL
VOLTAGE TRANSFORMER WITH VOLTAGE AS REQUIRED BUT NOT TO EXCEED 120V PROVIDE
ENCLOSURE IN SIZE AND NEMA RATING AS REQUIRED. EQUIP WITH PHASE FAILURE,
UNDERVOLTAGE, AND PHASE UNBALANCE RELAY PROTECTION. PROVIDE OPERATING HANDLE
FOR DISCONNECT SWITCH MECHANISM WITH INDICATION AND CONTROL OF SWITCH POSITION,
WITH ENCLOSURE DOOR EITHER OPENED OR CLOSED, AND CAPABLE OF BEING LOCKED IN
OFF POSITION, WITH A PADLOCK. SQUARED' CLASS 8539.
16160 PANELBOARDS
A. PANELBOARDS SHALL BE MANUFACTURED BY SQUARE 'D', GENERAL ELECTRIC, OR ITE SIEMENS.
B. PROVIDE LIGHTING AND APPLIANCE PANELBOARDS, AND POWER DISTRIBUTION PANELBOARDS
WITH DEAD FRONT COVERS, FULL SIZE NEUTRAL AVD BOLT -ON HEAVY DUTY, QUICK MAKE,
QUICK BREAK CIRCUIT BREAKERS. PANELBOARDS SHALL BE U.L. LISTED.
C. INSTALL PANELBOARDS SO TOP BREAKER IS NOT HIGHER THAN 6'-0" ABOVE FLOOR.
D. CONTRACTOR SHALL BALANCE PHASES IN PANELBOARD SO THAT LOAD IMBALANCE DOES NOT
EXCEED 10%.
E. PANELBOARD SHALL INCLUDE COMPLETE TYPEWRITTEN DIRECTORY.
F. PROVIDE SPARE CONDUITS TO CEILING CAVITY FOR SPARES/SPACES IN RECESSED
PANELBOARDS. PROVIDE (1) 314"C. FOR EVERY 3 SPACES.
G. PROVIDE U. L LISTED BREAKERS FOR EXISTING PANELBOARDS TO MATCH MANUFACTURER
AND AIC RATING.
H. PROVIDE AFCI�ARC FAULT CIRCUIT INTERRUPTER) BREAKERS FOR ALL CIRCUITS SERVING
BEDROOMS 0 DWELLING UNITS PER N.E.C. 210.12.
L ALL BREAKERS SERVING MECHANICAL, REFRIGERATION, OR OTHER EQUIPMENT WHERE
REQUIRED, SHALL BE HACR RATED.
J. BREAKERS WITH HID LIGHTING LOADS SHALL BE HID RATED.
K. BREAKERS SERVING CIRCUITS UNDER KITCHEN HOODS SHALL BE SHUNT -TRIP TYPE,
16161 MOTOR CONTROL CENTERS
A. PROVIDE AS SHOWN ON POWER ONE -LINE DIAGRAM.
B. INCOMING: SERVICE TO MAIN DEVICE SHALL BE 20BY/12OV, 3 PHASE, 4 WIRE.
C. EQUIPMENT SHALL HAVE AN INTEGRATED AIC RATING MINIMUM OF 42KAIC.
D. PROVIDE ANYADDITIONAL REQUIREMENTS AS REQUIRED ON POWER ONE -LINE DIAGRAM.
E. DESIGN SELECTION: SIEMENS
16170 MOTOR AND CIRCUIT DISCONNECTS
A. DISCONNECT SWITCHES MAYBE GENERAL DUTY FOR 24OV,
B. PROVIDE RAIN -TIGHT HUBS FOR EXTERIOR DISCONNECTS.
C. PROVIDE CLASS R REJECTION FUSE CLIPS AND CLASS R FUSES.
D. FUSES SHALL BE MANUFACTURED BY BUSSMAN, LITTLE OR GOULD-SHOUWMUT.
E. SERVICE DISCONNECT SWITCH SHALL BE HEAVY DUTY TYPE.
16190 SUPPORTING DEVICES
SLEEVES AND FIRE SAFING/SEALANTS. A. LIGHTING FIXTURES SHALL BE SUPPORTED FROM BUILDING STRUCTURE AND NOT FROM
N. PROVIDE UL APPROVED FIRE SEALS FOR ALL FIRE RATED WALL AND FLOOR PENETRATIONS CEILING GRID. SECURE A MINIMUM OF TWO CORNERS (OPPOSITE) TO STRUCTURE ABOVE
16115 CONDUIT FITTINGS WITH CHAIN.
8. FASTEN CONDUIT TO STRUCTURAL PARTS OF BUILDING.
A. COMPRESSION TYPE OR SETSCREW TYPE SHALL BE UTILIZED. 16450 GROUNDING
B. PROVIDE PROPER EXPANSION FITTINGS WHEN CROSSING BUILDING EXPANSION LINES.
A. PROVIDE INSULATED GROUND CONDUCTORS IN ALL CONDUITS.
B. PROVIDE GROUNDING BUSHINGS FOR FEEDER CONDUITS.
C. SERVICE GROUND RESISTANCE SHALL BE MEASURED WITHOUT DEPENDING ON WATER PIPING
SYSTEM AND SHALL BE 25 OHMS OR LESS, IF GREATER THAN 25 OHMS, DRIVE ADDITIONAL
GROUND RODS TO OBTAIN REQUIRED RESISTANCE.
D. GROUND METAL LIGHTING POLES AS REQUIRED BY N.E.C.
ELECTRICAL SPECIFICATIONS
NOT TO SCALE
NEW CT CABINET
(SIZE AS REQUIRED
BY UTILITY COMPANY)
3R
SYMBOL DESCRIPTION.
POWER
MOUNTING
HEIGHT.' SYMBOL DESCRIPTION
DEMO. AND RENO. ABBREVIATIONS
On DUPLEX RECEPTACLE. 18" AFF
Ow DUPLEX RECEPTACLE, MOUNTED ABOVE COUNTER BACKSPLASH 6" ABOVE COUNTER
QUADRAPLEX (DOUBLE DUPLEX) RECEPTACLE 18" AFF
QUADRAPLEX (DOUBLE DUPLEX) RECEPTACLE, MTD. ABOVE COUNTER. 6" ABOVE COUNTER
gm DUPLEX GROUND FAULT CIRCUIT INTERRUPTED RECEPTACLE. 18" AFF
& DUPLEX GROUND FAULT CIRCUIT INTERRUPTED RECEPTACLE -MOUNTED 6" ABOVE COUNTER
ABOVE COUNTER BACKSPLASH.
® SPECIAL PURPOSE OUTLET, NEMA CONFIGURATION AS SHOWN.
0 JUNCTION BOX WITH BLANK PLATE; BRACKET INDICATES WALL MOUNTED.
rr PANELBOARD.
= RECESSED FLUSH -MOUNTED PANELBOARD, FRONT OF PANEL INDICATED
BY LONGER EDGES OF SYMBOL
Q METER SOCKET, PROVIDE PER UTILITY COMPANY REQUIREMENTS.
EQUIPMENT SYMBOLS
MOTOR AND CONNECTION. EQUIPMENT TYPE AS NOTED, REFER TO
MOTOR CONNECTION SCHED. COORDINATE WITH INSTALLED EQUIPMENT
a SAFETY DISCONNECT SWITCH-30A, 30, 48OV, NF, HD, NEMA 1, U.N.O.
IaM MOTOR STARTER.
COMBINATION MOTOR STARTER & NON -FUSED DISCONNECT SWITCH,
UNLESS NOTED OTHERWISE. "F" = FUSED; "NP' = NON -FUSED.
CONDUIT, RACEWAYAND WIRING
+ EACH CIRCUIT SHALL CONSIST OF PHASE, NEUTRAL AND GROUND CONDUCTORS.
FOR LIGHTING CIRCUITS PROVIDE REQUIRED SWITCH LEGS TO ACHIEVE SWITCHING
INDICATED ON PLANS, CONTRACTOR MAY COMBINE CIRCUITS INTO A COMMON
HOMERUN CONSISTING OF A MAXIMUM OF A COMMON NEUTRALIGROUND AND
(3) PHASE CONDUCTORS (A, 8 AND C PHASE). HOWEVER, A SEPARATE NEUTRAL
SHALL BE PROVIDED FOR ALL CIRCUITS SERVING COMPUTERS (DATA) CIRCUITS.
SERVICING DATA IS DEFINED AS ANY RECEPTACLE NEXT TO A DATA OUTLET OR
SPECIFICALLY SERVING A DATA PIECE OF EQUIPMENT.
HOME RUN TO PANEL, NUMBER OF ARROWS INDICATES NUMBER OF CIRCUITS.
ALL HOMERUNS SHALL BE # 10 AWG, 3/4"C., MINIMUM.
- - - INDICATES DEVICE(S) CONNECTED TO SAME CIRCUIT, BUT DIFFERENT SWITCHING
CONTROLS.
- -- I� GROUNDING CONDUCTOR.
--- - CONDUIT IN/UNDER SLAB.
---I CONDUIT CAP.
1 LT' AFF
6"-6" TO TOP
6"-6" TO TOP
<E> EXISTING TO REMAIN.
< K> EXISTING TO BE REMOVED.
< RD > REMOVE DEVICE ONLY, FOR CONNECTION OF NEW DEVICE IN SAME LOCATION.
<KL> EXISTING TO BE RELOCATED.
< N > NEW WORK - NOT USED WHERE WORK IS OBVIOUSLY NEW.
< N L> NEW LOCATION OF EXISTING TO BE RELOCATED.
<ND> NEW DEVICE, ETC. IN EXISTING DEVICE LOCATION.
SCREENED LINES INDICATE EXISTING EQUIPMENT TO REMAIN.
--DARK DARK LINES INDICATE NEW WORK
XX-LINES WITH X'S INDICATE EXISTING EQUIPMENT TO BE REMOVED.
GENERAL NOTES
(APPLIES TO ALL DIVISION 16000 DRAWINGS)
1. WHERE THE REQUIREMENTS OF ANOTHER DIVISION, SECTION, OR PART OF THE SPECIFICATIONS
EXCEED THE REQUIREMENTS OF THIS DIVISION, THOSE REQUIREMENTS SHALL GOVERN. ENGINEER
SHALL HAVE FINAL DECISION OF WHICH REQUIREMENT SHALL GOVERN.
2. ALL FLOOR, WALL AND ROOF PENETRATIONS SHALL MAINTAIN THE ENVIRONMENTAL AND FIRE
RATING OF THE STRUCTURE, ROOF PENETRATIONS SHALL BE COORDINATED WITH THE ROOFING
CONTRACTOR TO MAINTAIN THE ROOFING WARRANTY. PITCH POCKET ROOF PENETRATIONS ARE
NOT PERMITTED.
3. ALL MOUNTING HEIGHTS SHOWN SHALL BE TO CENTER LINE OF DEVICE BACKBOX FROM FINISHED FLOOR.
4. ALL COMMUNICATION CONDUIT SHALL HAVE WIDE SWEEPING BENDS.
5. ALL COMMUNICATION CONDUIT SHALL BE IDENTIFIED BYA DISTINCTIVE NUMBER AND LABELED AT
BOTH ENDS.
6. ALL CONDUIT IN SLAB/BELOW SLAB SHALL BE 314" MINIMUM.
7. ALL SYMBOLS PRESENTED MAY NOT NECESSARILY BE USED ON THESE DRAWINGS.
ABBREVIATIONS
A AMPS/AMPERAGE IUC IN -USE COVER
AFF ABOVE FINISHED FLOOR IWH INSTANTANEOUS WATER HEATER
AHJ AUTHORITY HAVING JURISDICTION KW KILOWATTS
AHU AIR HANDLER UNIT KVA KILO VOLTAMPERES
C./CDT. CONDUIT MH METAL HALIDE
C.B. CIRCUIT BREAKER MN . MOUNTING
CLG CEILING MCB MAIN CIRCUIT BREAKER
CU CONDENSING UNIT MLO MAIN LUGS ONLY
DISC DISCONNECT MMS MANUAL MOTOR STARTER
DN DOWN NEC NATIONAL ELECTRICAL CODE
EC ELECTRICAL CONTRACTOR NF NON -FUSED
EF EXHAUST FAN RGS RIGID GALVANIZED STEEL
EQPT EQUIPMENT RTU ROOF -TOP UNIT
EWC ELECTRIC WATER COOLER ST SHUNT TRIP
EWH ELECTRIC WATER HEATER SW SWITCH
FVNR FULL VOLTAGE NON REVERSING STARTER TTB TELEPHONE TERMINAL BACKBOARD
GC GENERAL CONTRACTOR TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR
GFI GROUND FAULT INTERRUPTOR UNO UNLESS NOTED OTHERWISE
GND./G. GROUND W WATTS
HPS HIGH PRESSURE SODIUM WP WEATHERPROOF (NEMA 3R)
HP HORSEPOWER V VOLTS
HRS HORSEPOWER RATED SWITCH XFMR TRANSFORMER
IG ISOLATED GROUND 0 PHASE
IMC INTERMEDIATE METAL CONDUIT Q DRAWING NOTE
SYMBOL LEGEND AND GENERAL NOTES
NOT TO SCALE
DRYER MOTORS
208V, 15HP, 30, 48.3FLA
(TYPICAL OF 4)
PANEL 'A' 6013
(REPLACE EXISTING LOADCENTER PANEL 'B' (-4#3, 1 #3G. -2"C. 50
PANEL 'D' PANEL 'L' WITH NEW PANELBOARD) (EXISTING)
DETAIL PANEL LOBE ROOM PANEL 225A MLO 400A MLO 3#4, 1#8G.-1
EXISTING FPL
M METER #6LL8543
UTILITY TRANSFORMER 3R (PROVIDE NEW
208/12OV, 30, 4W SERVICE METER SOCKET
16,469 SHORT CIRCUIT AMPS IF REQUIRED)
3R
UTILITY
PRIMARY
EXISTING UTILITY TRANSFORMERS ARE POLE MOUNTED.
CONTACT CHARLIE JOHNSON WITH FPL (407.328.1922) FOR
FURTHER COORDINATION ITEMS (EXISTING MAXIMUM KW
DEMAND FROM UTILITY WAS 96.0 KW OR 266 AMPS).
NOTE: ORIGINAL SERVICE WAS 600 AMPS FEEDING PANEL
A', PANEL 'B' AND 'MCC I'.
100
9013
NEW MOTOR CONTROL
CENTER 'MCC4'
N
20j
SERVICE #1
"'
i 4#500kcmil, 1#3G.-4"C.
NEW 400AMP, 30, 4W
PANEL 'S1'
2
o
42K AIC
SERVICE #2
SERVICE #3
100K AIC
190K AIC
10013
240V, 400AMP, 30, 4W
200/3
400-3
40013
HD FUSED DISCONNECT SWITCH
IN NEMA 3R ENCLOSURE
15013
4#500kcmil - 3 1/2"C.
(RE -USE 2 OF THE EXISTING
3 112" PVC CONDUITS IF
POSSIBLE)
40013
3Rl l I 3R _E_ .._..._ 3R
POWER ONE -LINE DIAGRAM
NOT TO SCALE
#310
5/8"x10'
GROUND ROD
10013 !
EXISTING MOTOR
DR CONTROL
CENTER 'MCC P
PANEL I S 1 '
VOLTS:
2081120
SERVICE 7l1 PANEL
SOURCE:
UTILITY
PHASE
30, 4W
BUS RATING:
400A MC8
KVA
AMPS
SINGLE PANEL
YES
CONN. LOAD:
111.0
308.11
GROUND BUS:
YES
UEMAND LOAD:
111.0
308.11
MOUNTING
SURFACE
LOADS
LOADS
DESCRIPTION.,
CKT.
NO,
KVA
A
KVA
B
KVA
C
VIPS/P01
VPSIPOtKVA
A
KVA
B
KVA
C
CKI.
NO.
DESCRIPTION:
PANEL'D
1
11.0
=
=
15013
13
5.0
=
=
2
SPARE LOADS
--------
3
1TO
=
----
----
5,0
=
4
__--_-
--------
5
11.0
r
5.0
6
PANEL'L'
7
6.0
10013
0.0
m
8
------
9
6.0
0.0
10
------
11
6.0
---
0.0
12
PANEL 'A'
13
15.0
r
20013
0.0
r
14
-------
15
15.0
r
0.0
16
-------
17
15.0
---
0.0
18
SPACE
19
0.0
0.0
20
SPACE
21
0.0
0.0
22
SPACE
23
0.0
r
0.0
24
3200
32.00
32.00
1
5.00
5.00
5.00
KVA CONNECTED
31.00
37.00
137.00
111.0
PANEL R
VOLTS:
2081120
EXTERIOR DETAIL PANEL
SOURCE:
PANEL'S 1'
PHASE:
30, 4W
BUS RATING:
P25A MI 0
KVA
AMPS
SINGLE PANEL:
YES
CONN. LOAD
.?3.0
91.60
GROUND BUS:
YES
DEMAND LOAD:
33.0
91.60
MOUNTING:
SURFACE
LOADS
LOADS
DESCRIPTION.
CKT
NO..
KVA
A
KVA
B
KVA
C
WPS/PU-'MPS/PPOII
KVA
A
KVA
8
KVA
C
CKT
NO -
DESCRIPTION:
VACUUM MOTOR
1
5.0
=
=
4513
0.0
=
=
2
SPACE
-------
3
5.0
=
I --
=
0.0
=
4
SPACE
-----
5
5.0
=
m
0.0
6
SPACE
VACUUM MOTOR
7
5.0
4513
0.0
m
8
SPACE
--------
9
5.0
0.0
10
SPACE
-------
I
r
5.0
=
0.0
12
SPACE
RECEPTACLES
13
1.0
2011
0.0
=
=
14
SPACE
LIGHTING
15
1.0
2011
0.0
m
16
SPACE
RECEPTACLES
17
1.0
2011
=
0.0
18
SPACE
SPARE
19
0.0
20/1
0.0
=
=
20
SPACE
SPARE
21
0.0
2011
m
0.0
m
22
SPACE
SPARE
23
0.0
2011
=
r
0.0
24
SPACE
SPACE
25
0.0
0.0
=
=
26
SPACE
SPACE
27
0.0
0.0
=
28
SPACE
SPACE
=
1 0.0
m
0.0
30
SPACE
11.00
11.00
11.00
000
0.00
0,00
KVA CONNECTED
11.00
11.00
11.00
1 33.01
PANEL V.
VOLTS:
2081120
NEWLURE ROOM PANEL
SOURCE:
PANEL'SP
PHASE:
30.4W
BUS RATING:
100A MLO
KVA
AMPS
SINGLE PANEL
YES
CONN. LOAD:
24.0
66.62
GROUND BUS:
YES
DEMAND LOAD:
24.0
66.62
MOUAIT1W
SURFACE
LOADS
IOADS
DESCRIPTION:
CKT
NO.
KVA
A
KVA
B
KVA
C
PS/Rol
YPS/pot
KVA
A
KVA
R
KVA
C
CKT
NO.
DESCRIPTION
LIGHTING
1
1,0
=
=
2011
0.0
=
r
2
SPACE
LIGHTING
3
m
TO
1 2011
0.0
m
4
SPACE
RECEPTACLES
5
=
=
1.0
2011
=
0.0
6
SPACE
RECEPTACLES
7
1.0
r
=
2011
0.0
m
m
8
SPACE
AIR COMPRESSOR (VERIFYACTUAL
REQUIREMENTS)
9
=
2.0
=
*13
0.0
10
SPACE
--------
11
m
m
2.0
0.0
12
SPACE
--------
13
2.0
r
=
-.--
0.0
r
14
SPACE
TIRE BALANCER (VEMFYACTUAL
REQUIREMENTS)
15
3.0
=
"l3
m
0.0
16
SPACE:
--------
17
3.0
---
0.0
18
SPACE
19
3.0
r
----
0.0
20
SPACE
SPARE
21
TO
2011
0.0
22
SPACE
SPARE
23
1.0
2011
0.0
24
SPACE
SPARE
25
1.0
27/1
0.0
26
SPACE
SPARE
27
1.0
2011
r
0.0
28
SPACE
SPARE
29
1.0
20/1
0.0
30
SPACE
8.00
8.00
8.00
0.00
0.00
0.00
KVA CONNECTED
8.00
8.00
8.00
24.0
POWER ONE -LINE DIAGRAM NOTES:
0
PROVIDE COMBINATION MOTOR STARTER AND DISCONNECTING MEANS, EITHER FUSED DISCONNECT OR
CIRCUIT BREAKER IS ACCEPTABLE.
OLUBE
ROOM PANEL INSTALLATION AND WIRING, INCLUDING FEEDER, SHALL BE INSTALLED /N ACCORDANCE
WITH N.E.C. 511. PROVIDE SEAL -OFF FITTINGS IN FEEDER CONDUIT IN ACCORDANCE WITH N.E.C. 511.
OPANEL
'B' HAS AN EXISTING CONNECTED LOAD OF 250 AMPS. THEREFORE, PANEL HAS SPARE CAPACITY IF
NEEDED FOR CONTRACTOR TO FIELD ADD ADDITIONAL BRANCH CIRCUITS, BUT SHALL NOT EXCEED 130 AMPS
COLD
MORE OF LOAD.
BUILDING WATER
STEEL PIPE
CONTRACTOR SHALL VERIFY SIZE OF NEW EQUIPMENT AND FIELD LAYOUT 3 NEW SERVICES AND CT CABINET
5/8° 04,\
ON EXTERIOR WALL AT LOCATION OF EXISTING 600 AMP SERVICE.
GROUNDD ROD
OPROVIDE
MAXIMUM LENGTH AT 104" FOR 104" TAP RULE. NOTE IT IS NECESSARY TO USE GROUND SIZE
INDICATED ABOVE TO COMPLY WITH M.E.C. 250.122)
OCONTRACTOR
SHALL PROVIDE OWNER WITH ADD ALTERNATIVE FOR TRANSIENT VOLTAGE SURGE SUPPRESORS
TO PROTECT EACH OF THESE.
AIZOJITE TuPL
T
INC.
A. C.E.
ELECTRICAL ENGINEER
517 SPRING VALLEY ROAD
ALTAMONTE SPRINGS, FL 32714
PHONE: (407) 339 - 3060
FAX: (407) 339 - 8121
E-MAIL: gsigle(9ace-mep.com
GREG SIDLE, P.E.
P.E. LICENSE NO: 48671
EBN # 8019/# 9682
000PYRIOHT ARCHITECTURAL CONSULTINOENOWERM, INC.
ALL RIGHTS RESERVED.
SEAL:
CLIENT:
uw
G
E
PROJECT:
U)
QC
C
O �
Z 4
y y
M
PANELBOARD SCHEDULES
NOT
TO SCALE 1wial
��� . DAl F DESCRIPTION
ht's
0104 i s 40 All)
CrWIA33 SNV'd
301AA0
ELECTRICAL LOAD
SUMMARY -
SVC. #3
N. E C
N.EC
N.E. C
CONNECTED
DEMAND
DEMAND
DESCRIPTION:
KW
FACTOR
KW
N.E.C. DEMAND KVA x 1000 = MINIMUM FEEDER AMPERAGE
SYSTEM VOLTAGE x SQ.RT(3)
141.4 x 1000= 393.0 AMPS
208 x 1.73
THEREFORE, 400 AMPS IS ADEQUATE FOR'MCC4'.
1. EXISTING MOTOR CONTROL CENTER'MCC 1'
28.8
1.0
28.8
2. NEW 'MCC4' WITH (4) 15HP MOTORS
90.1
1.25
112.6
TOTAL =
118.9
TOTAL =
141.4
JOB NUMBER:
25763
DATE:
NOV. 8, 2005
CAD FILE N 0 :
25763-EO01
SCALE:
AS NOTED
DRAWN:
K, SIGLE
CHECKED:
G. SIGLE
SHEET TITLE:
SYMBOLS, GENERAL NOTES, ELECTRICAL
SPECIFICATIONS, POWER ONE -LINE DIAGRAM,
PANELBOARD SCHEDULES, AND ELEC LOAD SUMM.
SHEET NO:
SHEET . OF
Emi