HomeMy WebLinkAbout196 Towne Center Cir - BC04-000148 (FIRE SPRINKLER PLAN) DOCUMENTS (A)PERMIT ADDRESS
CONTRACTOR
ADDRESS
0(� T
irl-�'i�`�
PHONE NUMBER
PROPERTY OWNER
ADDRESS
PHONE NUMBER
ELECTRICAL CONTRACTOR
MECHANICAL CONTRACTOR —
PLUMBING CONTRACTOR
MISCELLANEOUS CONTRACTOR
PERMIT NUMBER
MISCELLANEOUS CONTRACTOR
PERMIT NUMBER
FEE
FEE
SUBDIVISION
PERMIT # v r O DATE I k o (s �---`
PERMIT DESCRIPTION Ire-
PERMIT VALUATION G L (O d
SQUARE FOOTAGE
0
W
SANFORD FIRE DEPARTMENT
FIRE PREVENTION DIVISION
300 N. Park Ave., Sanford, FI. 32771 / P. O. Box 1788, Sanford, FI. 32772
(407302-2520 /FAX (407) 330-5677
Pager (407) 918-0395
Plans Review Sheet
Date: October 14, 2003 Business Address: 196 Towne Center Circle
Oce. Ch. #34 New Mercantile
Business Name: Factory Recreational Warehouse Ph. ( )
Contractor: Simplex Grinnell Ph. (407) 235-1100
Fax. (407)235-1150
Architect/Engineer: Ph.
Reviewed [ J Rejected [ ]
Reviewed by: Timothy Robles, Fire Protection Inspector/Plans Examiner
Comment: Plans reviewed as Mercantile Occupancy. Class "B" per L.S.C. FD reserves right to require
applicable code requirements if occupancy use changes. Sprinkler plans to be submitted for review, permitting,
and inspections.
Application —Existing Building Type IV
1.1 Fire Sprinkler Design: Wet Pipe Design criteria
1.2 Sales & Pre -Sales Areas: Ordinary Hazard group # 2 storage in height not to exceed 12' (ft)
1.3 Density for this area — 0.18 GPM/SQ FT 2500 sq ft, 250 p.s.i. for outside hose usage
1.4 Office Break Room: — Density -0.15 G.P.M./S. Q. FT
1.5 Operating area: 1, 500 sq. ft. Normal K factor W1155 degree heads chrome recess
• Two hour hydro required
• Provide fire sprinkler contractor at time of building finial
• 48 hour notice on all fire inspections
SYSTEM DEMAND @ BASE OF RI:
570.1 GPM @ 59.5#
STORE FRON
SCOPE OF WORK
SIMPLEX GRINNELL TO BEGIN @ EXISTING 4" GROOVED CAP
INSTALL NEW: '
4" SCH 10 CENTERFEED CROSSMAIN W/ THREADED WELDED OUTLETS
SCH 40 - B. LINES W/ CAST IRON BLACK FITTINGS
TOP BEAM CLAMP HANGERS W/ 6-0 ALL THD ROD
SPRINKLERS - QUICK RESPONSE 1/2" CHROME RECESS 155°
SPRINKLERS - NO CENTERLINE TILE
ALL DROPS 1 X 2-0 W/ 1 X 1/2 REDUCER
ALL DIMENSION CENTER TO CENTER
Steel I -Beam or
Bar Joist
Swivel Ring
Model 300 Michigan
Top Beam C -Clamp
or Equal
W / Lock Nut
All
Thread
Rod
3/8 X 6-0
Pipe
TYPICAL B. LINE HGR UN
Top Beam C -Clamp
IN LOCATION SUBJECT TO FREEZING CONDITIONS, IT IS THE OWNER'S RESPONSIBILITY TO SPRINKLERS
PROVIDE HEAT THROUGHOUT WET PIPE SPKR SYSTEMS AREAS AND ENCLOSURE FOR DRY DESCRIPTION TYPE ORIFICE TEMP FINISH
PIPE, DELUGE AND OTHER TYPE VALVES CONTROLLING WATER SUPPLIES TO SPRINKLE
RSYSTEMS
THIS DWG AND THE INFORMATION AND DESIGN APPLICATION HEREIN CONTAINED IS THE
PROPERTY OF SIMPLEX GRINNELL LP AND/OR ITS SUBSIDARIES AND IS LOANED UPON TY -FRB QUICK RESPONSE PENDENT SPRINKLER 1/2 155 CHROI
EXPRESS CONDITIONS THAT THE SAME BE RETURNED TO SGLP UPON REQUEST. ALL
INFORMATION HEREIN CONTAINED SHALL BE TREATED AS SECRET, AND CONFIFENTIAL; NO
REPRODUCTION OF THIS DWG OF ANY PART THEREOF SHALL BE MADE WITHOUT WRITTEN
CONSENT OF SGLP.
CANOPY I SYMBOL I QTY
SPRINKLER PLAN VIEW
1/4:= 1'-0
SYSTEM'TYPE
WET DRY DELUGE PREACTION
XXX
APPROVALS
CITY OF SANFORD
EDGARDO L, CORDOBA
MECHANICAL ENGINEER, P.E.
CERTIFICATE #57991
13649 TET,HERLINE TRAIL
ORLANDO FLORIDA 32837
SIMPLEX GRINNELL
TYCO FIRE AND SECURITY
3701 N. JOHN YOUNG PARKWAY
ORLANDO FLORIDA 32804
TELEPHONE NO: 407-235-1100
FAX NO: 407-235-1150
NOTES
TYPE SYSTEM,,- WET PIPE
TYPE OCCUPANCY - ORDINARY HAZARD GP -2
DENSITY .18 GPM/SQ.FT FOR 2500 SQ. FT + 250 HOSE
MAXIMUM SPRINKLER SPACING 120 SQ.FT
TYPE CONSTRUCTION - ACOUSTICAL TILE CLGS
GYPSUM WALL BOARD WALL W/ METAL STUDS
DESIGN, MATERIAL AND INSTALLATION PER NFPA-13 1999
EXISTING PIPE
NEW PIPE
0o HYDRAULIC CALC NODE POINT
ALL DIMENSIONS CENTER TO CENTER
CORRIDOR
RECREATIONAL FACTORY
SEMINOLE TOWN CENTER / 200 TOWN CTR CIRCLE
SANFORD FLORIDA
ADDITION TO EXISTING WET PIPE SYSTEM
7�
�r..i a � f
g
r y �
,i s�
r
PIANS REVIEWED
CITY OF SANFORD
WATER FLOW TEST STATIC PRESSURE RESIDUAL PRESSURE GPM FLOWING
CONDUCTED BY S/G AUG 2003 65# 55# 2420
n c .r 1 1�
7;;C
DRAWN BY: RAF
DATE: 10-7-03
SCALE: 1/4 = 1-0
DWG NO.: FP -1
I_. _ __... _ __..._